Panasonic CZ-PXXXHR2U installation

INSTALLATION INSTRUCTIONS
Solenoid Valve Kit
For 3WAY VRF System
IMPORTANT! Please Read Before Starting
This solenoid Valve kit must be installed by the sales dealer or installer. This information is provided for use only by authorized persons.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
This solenoid Valve kit shall be installed in accordance with National Wiring Regulations.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING When Wiring
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are
used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Connect all wiring tightly. Loose wiring
may cause overheating at connection points and a possible fire hazard. Provide a power outlet to be used exclu-
sively for each unit.
practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
CZ-PXXXHR2U
(Single type)
Provide a power outlet exclusively for each unit, and full disconnection means having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring rules. To prevent possible hazards from
insulation failure, the unit must be grounded. This equipment is strongly recommended
to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
When Transporting
Be careful when picking up and moving the units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges on the solenoid valve kit can cut your fingers.
When Installing…
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
…In a Room
●●Properly insulate any tubing run inside a
room to prevent “sweating” that can cause dripping and water damage to walls and floors. The solenoid valve kit produces some refrigerant noise. If it is to be installed in a quiet place such as a hospital, library or hotel, it is strongly recommended that the solenoid valve kit be installed in the ceiling of a corridor, etc. apart from the room.
Keep the fire alarm and
CAUTION
the air outlet at least
4.9 ft (1.5 m) away from the unit.
85464369881000 CV6233327044
When Connecting Refrigerant Tubing
Pay particular attention to refrigerant leakages.
CAUTION
When performing piping work, do not mix air except for specified refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high tension inside the refrigerant cycle.
If the refrigerant comes in contact with a flame, it produces a toxic gas.
Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury, etc.
Ventilate the room immediately, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of toxic gas.
Keep all tubing runs as short as possible except the tubing between solenoid valve kit and indoor unit. It is strongly recommended that the solenoid valve kit be installed in the ceiling of a corridor, etc. apart from the room.
Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
Do not leak refrigerant while piping work for an installation or re-installation, and while repairing refrigeration parts. Handle liquid refrigerant carefully as it may cause frostbite.
WARNING
This product must not be
modified or disassembled under any circumstances. Modified or disassembled unit may cause fire, electric shock or injury.
Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.
In case of malfunction of this appliance, do not repair by yourself. Contact the sales dealer or service dealer for repair.
CAUTION
●●Ventilate any enclosed areas when
installing or testing the refrigeration system. Leaked refrigerant gas, on contact with fire or heat, can produce dangerous toxic gas. Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
Others
CAUTION
Do not sit or step on the unit, you may fall down accidentally.
When Servicing
Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that no metal chips or bits of wiring have been left inside the unit.
2
1. Accessories
Part Name
Figure Q'ty
Remarks
Washer
Suspension hook
Tapping screw ( L=15/32" (12 mm))
Tapping screw ( L=5/16" (8 mm))
Wire holder
3-Way connect wire ( L=6.2ft (1.9m))
Solenoid Valve Relay Kit
Clamper
For suspension bolts
2
Used to suspend the Solenoid Valve Kit
1
For suspension hook
4
For Solenoid Valve Relay Kit
4
For Solenoid Valve Relay Kit wiring
1
1
1
For electrical wiring
4
2. Positioning for Installation
The solenoid valve kit produces some refrigerant noise. If it is to be installed in a quiet place such as a hospital, library or hotel, it is strongly recommended that the solenoid valve kit be installed in the ceiling of a corridor, etc. apart from the room.
Room
Strongly
Indoor unit
recommended installation
Corridor
NOTE
After the power is turned on, the sound of the solenoid valve coil may sometimes occur. Note that this is not a fault. The sound level will gradually become small at the time of starting operation.
Room
Solenoid valve kit
Indoor unit
Avoid
Room
Corridor
Indoor unit
Room
Indoor unit
Solenoid valve kit
×
3