Panasonic CZ-256ESMC3, CZ-CFUNC2 Technical Data Manual

TECHNICAL DATA
Intelligent Controller
Intelligent Controller
Issued March 2017
Intelligent Controller
CZ-256ESMC3
Order No. SBPAC1703004CE
Communication Adaptor
Communication Adaptor
CZ-CFUNC2
The appearance and specifi cations of this unit and the contents of this Technical Data may be changed
without notice due to performance improvement or other reasons.
Commercial Air-Conditioner Business Unit
REFERENCE NO. TD831198-00

Table of Contents

Page
Safety Precautions 1
Note 2
Fault diagnosis 3
Various procedures 14
Display and settings for the communication adaptor board 14
― Communication adaptor microcomputer rewrite procedure 34 ― Intelligent Controller software update procedure 36 ― Replacement of SD card, and operation procedure at time of failure 37 ― Procedure for replacing touch panel LCD 41 ― Procedure when adding/removing a unit 44 ― Procedure when entering or leaving an area mid-period 45
Operating Instructions 46
Intelligent Controller 46
Installation Instructions 149
Intelligent Controller 149
― Communication adaptor 154
Intelligent Controller web settings 162
Advance check sheet 162
― Web setting 167 ― Outgoing email settings 173
Input of the admin number (password) 175

Safety Precautions

Before repair work, please read this “Safety Precautions” carefully and use the unit correctly.
The notes shown here are categorized as “
Warning” and “ Caution”, but since they all describe important contents on safety, be sure to observe them. The display and meaning are as follows.
This symbol refers to a hazard or
WARNING
CAUTION
Meaning of symbol
A “warning” or “caution” item.
Content that must not be done (prohibited item).
Content that must be done (mandatory item).
unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
2. Notes on products after repair
WARNING
Be sure to repair the unit with parts that
are described in the service parts list of the applicable model and use the appropriate tools. In addition, never modify the product. Doing so may cause electric shock, overheating or re.
When moving the unit, be sure to install it securely. Inadequate strength or incomplete installation may cause a fall, electric shock, overheating or re.
Do not damage or modify the power cord. Doing so may cause electric shock or re. Placing heavy objects on the power cord, heating it, or pulling it, may cause damage.
3. Inspection items after repair
After the repair work, make a test run to check
whether there is any error and explain the notes on use to the customer.
1. Notes on repair
WARNING
When performing disassembly repair, be sure to stop operation and switch off the earth leakage breaker. Failure to do so may cause electric shock. Be careful not to touch the charging unit when performing a repair or a circuit inspection that requires a power supply.
Switch off the earth leakage breaker of the unit before repair work. Failure to do so may cause electric shock.
Do not repair electrical parts with wet hands. Doing so may cause electric shock.
WARNING
Scratched or deteriorated power cords or lead wires must be replaced. Also, do not connect the power cord partway. Doing so may cause electric shock, overheating or re.
CAUTION
Check that product mounting positions, wiring conditions, and connection state such as soldering, crimp terminal, and so on are normal. Failure to do so may cause overheating, re or electric shock.
Do not spray detergent spray or water on the unit. Doing so may cause electric shock or re due to malfunction or electrical short circuit.
When disposing of this unit or other items, please take appropriate measures
such as collecting and erasing internal information to prevent leakage of
condential information.
1

Note

1. About noise malfunction
Since communication control is performed by pulse signal, it has the property that it is easily affected by external noise. In normal use, there is no problem since this is taken into consideration on the circuit, but please note that an inuence may occur depending on the installation state.
<Items that add high frequency noise to the signal line, causing error in the signal pulse and malfunction>
Places susceptible to noise Symptoms Measures
1. Area with strong radio waves in the
vicinity of a broadcasting station
2. Near to wireless station
3. Near to use of high-frequency sewing
machines or arc welding machines
4. Hospitals (such as X-ray rooms)
5. Near to plasma or liquid crystal
televisions
1. Stops in the middle of operation
2. The liquid crystal display ickers
Prevent noise from being received by
the signal wiring
· Keep away from source
· Adopt shielded wire
2

Fault diagnosis

Fault Diagnosis Table of Contents
1. Communication error related
1-1. [C06] error appears on [Alarm list] screen· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·4 1-2. [C17] or [Outdoor C17] error appears on [Alarm list] screen · · · · · · · · · · · · · · · · · · · · · · · 5 1-3. [C19] error appears on [Alarm list] screen· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·5 1-4. [Disc.] error appears on [Alarm list] screen · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·5
2. Screen display related
2-1. Touch panel LCD does not work (Screen operation is not possible) · · · · · · · · · · · · · · · ·6 2-2. Nothing is displayed on screen · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·· 6 2-3. No indoor unit is displayed on the screen, or the number of units is too small · · · · · · · · · · · · · · 7 2-4. Cannot enter the screen selected in the menu · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·7 2-5. Distribution ratio and usage are displayed as 0 · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 7 2-6. Pulse count does not enter properly · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8 2-7. Cumulative operation time (or distribution ratio) is counted even though the unit has not been operating · · · 9 2-8. Cannot back up or restore to USB memory device (button is greyed out and cannot be pressed) · · · · · · · · · 9 2-9. Intelligent Controller does not start · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10 2-10. [Config. change] appears on [Alarm list] screen · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 11 2-11. Room temperature display is in error ([I/D unit list] screen) · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · ·
11
3. Unit operation related
3-1. Schedule timer does not work properly · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 12 3-2. Unit does not stop (operate) even when Batch stop (startup) input is ON · · · · · · · · · · · · · · · · · · · · 12 3-3. External alarm (operation) output does not turn ON even though unit alarm is detected · · · 13 3-4.
Even if remote controller prohibition is set, function settings can be individually changed by the remote controller · ·13
ー 3
1. Communication error relatedFault diagnosis
Note》 The meaning of the symbols below are as follows.
· Adaptor Communication adaptor
· MAIN board MAIN board of communication adaptor
1. Communication error related
1-1. [C06] error appears on [Alarm list] screen
Detection method
1
If the Intelligent Controller cannot receive data from the communication adaptor board for a certain period of time or longer, or if in an error is detected in the received data.
Diagnosis of failure
2
1. Communication
adaptor
(Power supply
system)
2. Communication
adaptor
(Communication system)
3. Construction / settings related
4. Replace the communication adaptor board for which there is an alarm Or, replace the product main unit
1-1 Is anything displayed on the 7-segment LED (6) on the board? Yes 2-1
No 1-2
1-2 Is the power switch on the board ON? Yes 1-3
No Turn ON
1-3 Is there a disconnection or open circuit in a connector on the
board?
· CN 5 (white 6P)
1-4 (External adaptor only)
Is there a disconnection or open circuit in a connector on the
power supply board?
· CN1 (white 5P)
· CN2 (white 4P / 7P)
1-5 Has the fuse (F1) of the board burned out? Yes
2-1 Is there a disconnection, looseness, an open circuit, or a short
circuit in the wiring of 11P or 12P [ADAPT] (RS485) of the 20P terminal block CN2?
2-2 Is the wiring polarity of 11P, 12P “ADAPT” (RS485) of the 20P
terminal block CN2 correct? (+, -)
3-1 Did you change the adaptor address settings since the
Intelligent Controller started?
3-2 Are the “LINK connect Yes/No” settings correct?
(See the “Display and settings on the communication adaptor board” section)
3-3 Is jumper plug CN032 of the communication adaptor at the end
of the crossover wiring set to “B” (with terminating resistance)? * Built-in board of Intelligent Controller main body set to “B” (with
terminating resistance).
3-4
Is jumper plug CN032 of the communication board that's located not at the end of the crossover wiring set to “A” (with terminating resistance)?
3-5 Are there any of the following types of deciencies in the
construction of the communication adaptor control wiring?
· Power lines and bundled lines or running in parallel
· The total extension exceeds 1 km
· It is not crossover wiring (there is a branch point)
· Shielded wire is not used
· The shield is grounded on both sides or not grounded
Yes Correct
wiring
No 1-4
Yes Correct
wiring
No 1-5
Replace the
fuse
No 2-1
Yes Correct
wiring
No 2-2
Yes 3-1
No Correct
wiring
Yes Undo or
check conguration
No 3-2
Yes 3-3
No Modify
settings
Yes 3-4
No Set it to “B”
Yes 3-5
No Set it to “A”
Yes Reconstruct
properly
No 4
4
1. Communication error relatedFault diagnosis
1-2. [C17] or [Outdoor C17] error appears on [Alarm list] screen
Detection method
1
If the communication adaptor cannot receive data from the indoor or O/D unit for a certain period of time or longer, or if an error is detected in the received data.
Diagnosis of failure
2
1. Unit 1-1 Is there a unit that is turned off? Yes Turn on the
power
No 1-2
1-2 Is there looseness, a disconnection, an open circuit, or a short
circuit in the inter-unit control wiring connection?
1-3 Are there any of the following types of deciencies in the
construction of the inter-unit control wiring?
· Running in parallel with power lines
· Branch points exceed 16 places
· The total extension exceeds 1 km
· There is re-branching after branching
· There is a branch point with many branches (“star” or “octopus” conguration)
· The distance between one branch point and the next branch
point is 2 m or less
· Defective termination resistance settings (too low or too high)
· When shielded wire is used, the shield is grounded on both sides or not grounded
2. Intelligent Controller 2-1 Is there looseness, a disconnection, an open circuit, or a short-circuit in the wiring of 1, 2 (LINK1) or 4, 5 (LINK2) of the Intelligent Controller's 27P terminal board?
Yes Correct
wiring
No 1-3
Yes Reconstruct
properly
No 2-1
Yes Correct
wiring
No 3
3. Replace the communication adaptor board for which there is an alarm
Or, replace the product main unit
1-3. [C19] error appears on [Alarm list] screen
Detection method
1
When there are multiple adaptors with the same address in one communication adaptor control wiring system.
Diagnosis of failure
2
1. Communication
adaptor
2.
Communication
adaptor
control wiring
3. Replace the adaptor board for which there is an alarm Or, replace the product main unit
1-1 Is there more than one adaptor with the same address in one
communication adaptor control wiring system?
2-1 Are there any of the following types of deciencies in the
construction of the communication adaptor control wiring?
· Power lines and bundled lines or running in parallel
· The total extension exceeds 1 km
· It is not a crossover wiring (there is a branch point)
· Shielded wire is not used
· The shield is grounded on both sides or not grounded
* After correctly setting the adaptor address, perform [Check conguration] on the Intelligent
Controller screen, to conrm.
* [Check conguration] is displayed under [Settings] → [System settings].
Yes Modify
settings *
No 2-1
Yes Reconstruct
properly
No 3
1-4. [Disc.] error appears on [Alarm list] screen
Detection method
1
It is the same as for “1-1. [C06] error appears on [Alarm list] screen”. However, if an air conditioner is connected to the communication adaptor, a “Disc.” error is displayed on that air conditioner (Indoor unit, Outdoor unit).
Diagnosis of failure
2
Refer to “2 Diagnosis of failure” in 1-1.
ー 5
2. Screen display relatedFault diagnosis
2. Screen display related
2-1. Touch panel LCD does not work (Screen operation is not possible)
1. Intelligent Controller 1-1 Is [InitCom...] displayed? Yes Wait till it
disappears
No 1-2
1-2 Is the following displayed?
· Checking cong...
Wait...
· Updating cong... Wait...
· Calculating distribution...
· Please wait a moment now
1-3 Is it processing one of the following?
· Backup to USB memory device
· Restore from USB memory device
· Distribution calculation processing
Yes Wait till it
disappears
No 1-3
Yes Wait till
processing nishes
No 1-4
1-4 Restart the Intelligent Controller (turn the power off / on) and
wait for it to start up. Is the touch panel working at this time?
1-5 Replace touch panel LCD
Or, replace the product main unit
Yes
OK (END)
No 1-5
2-2. Nothing is displayed on screen
1. Intelligent Controller 1-1 Is the power indicator (green) on the front lit? Ye s 1-7
No 1-2
1-2 Is the main power supply ON? Yes 1-3
No Turn ON
1-3 Is power supplied to the power terminal board? Yes 1-4
No Connect the
power supply.
1-4 Is fuse F1 blown? Yes Replace the
power supply board.
No 1-5
1-5 Is there a disconnection or an open circuit of a connector on
the MAIN board?
· CN5 (white 6P)
· CN9 (white 2P)
1-6 Is anything displayed when the main power supply of the
Intelligent Controller is turned OFF once and then turned ON again?
1-7 Is anything displayed when you press somewhere on the
screen?
1-8 Remove the sheet metal cover on the LAN connector
(2 sides). At this time, is the SD memory card not installed or defective?
Yes
Correct wiring
No 1-6
Yes (END)
No 1-9
Yes (END)
No 1-8
Yes
Insert it correctly,
then turn ON the
power again
No 1-9
1-9 Replace Intelligent Controller
ー 6
2. Screen display relatedFault diagnosis
2-3. No indoor unit is displayed on the screen, or the number of units is too small
1. Intelligent
Controller
2-4. Cannot enter the screen selected in the menu
1. Intelligent
Controller
* When entering each menu on the Intelligent Controller, the PIN is set on the Settings → IntlgtCtrlr maintnce → Initialize screen.
2-5. Distribution ratio and usage are displayed as 0
If the distribution ratio is 0%, start from “1-1”. If distribution ratio is displayed, but usage is 0, start from “1-7”.
1. Intelligent
Controller
* 1 Diagnosed as item “2-6. Pulse count does not enter properly”.
Can you perform the basic settings for the indoor unit?
1-1
* For the basic settings of an indoor unit, select [I/D unit settings] from
[Settings] → [System settings], check the details of the setting, place a check in the [Register] eld and register with the [Register] button.
1-2 Is the [No-comm mode] setting set to [YES]?
* [No-comm mode] setting is displayed under [Settings] → [A/C
maintenance] → [A/C communication settings] → [Next].
Yes 1-2
No Register
Yes Set it to “NO”
Check conguration
No 1-3
1-3 Is the setting of [A/C conctn] set to [None
]
? Yes Correct the
setting to “ON”
No 1-4
1-4 Are you connecting 17 or more linked air conditioners? Yes Reduce to within
16 links
No 1-5
1-5 What happens when you perform [Check conguration]*?
[
Cong. has been chngd
Conrm conguration?] is displayed → [Begin cong
[
The conguration has not changed.] is displayed → Go to 1-6
1-6 Refer to the items
1-1. [C06] error appears on [Alarm list] screen”, “1-2. [C17] or [Outdoor
]
C17] error appears on [Alarm list] screen” and check all the same contents
* [Check conguration] is displayed under [Settings] → [System settings].
1-1 Are you registering an admin number (password)?
(Settings → System settings → Web user settings)*
Yes (END)
No
* For screens protected by the admin number (password), refer to
the Operating Instructions.
1-1 When performing time slot integration, is the displayed time slot
selection correct? (RglHour (RglHour 1 to 8) / OutOfHours / SpcfdDay / AllHours)
Yes 1-2
No Select the
correct time slot
1-2
When conrming the operation time of the indoor unit belonging to that area under [Oper./Status] → [Accumult/Distrib] → [I/D unit acc.]
Yes 1-3
1-4
No
screen, are all “0: 00”?
1-3 If the operation time is 0:00, the distribution ratio, charge, and usage are all displayed as 0.
(In the case of time distribution) (END)
1-4 Are the area distribution settings completed?
([Settings] → [System settings] → [Area group name settings] screen)
1-5 Are the distribution settings of the distribution group completed?
([Settings] → [System settings] → [Distribution group settings] screen)
1-6 In the case of an area consisting of all local adaptors, is the
capability value set?
Yes 1-5
No 1-7
Yes 1-6
No 1-7
Yes 1-8
No 1-7
([Settings] → [System settings] → [I/D unit settings] screen)
1-7 Set the contents of 1 - 4, 1 - 5, 1 - 6 correctly. (*)
If [0] is still displayed for usage, go to 1-8.
1-8 Is the count from the pulse meter on?
(Check the [Oper./Status] → [Accumult/Distrib] → [Pulse acc.]
Yes 1-9
No *1
screen)
1-9 Is the pulse unit quantity setting complete?
([Settings] → [System settings] → [Pulse meter settings] screen)
Yes
No Apply settings
*2
7
2. Screen display relatedFault diagnosis
2-6. Pulse count does not enter properly
1. Intelligent Controller 1-1 Is the distribution group correctly set on the [Settings] → [System Settings] → [Distribution group settings] screen?
1-2 Are you looking at the Cut off data display on the [Oper./
Status] → [Accumult/Distrib] → [Pulse acc.] screen? (Are the dates (e.g. 08/01 - 08/31) displayed in the upper right of the screen?)
1-3 When performing time slot totals calculation, is the displayed
time slot selection correct? (RglHour (RglHour 1 to 8) / OutOfHours / SpcfdDay / AllHours)
2. Communication
adaptor
3. Pulse meter 3-1 Is the wiring to the communication adaptor correct?
2-1 Is the wiring from the pulse meter correctly connected?
Is there a terminal mix-up, disconnection, open circuit, or short circuit?
(Pi1 to Pi3 of the 27P terminal board on the MAIN board) Pi1 (7, 8) Pi2 (7, 9) Pi3 (7, 10)
2-2 Remove all the wiring of the pulse meter from the terminal
board, and use a wire, scrap of lead wire, or other appropriate object to short-circuit the input parts (Pi1 to Pi3) of the terminal board several times while looking at the [Pulse acc.] screen of the Intelligent Controller. Does the number of pulses increase correctly? (It may take several minutes to update the display)
2-3 Replace MAIN board 2-4
If the distance between the pulse meter and the communication adaptor is 20 m or more, please use a relay. Even if the distance is within 20 m, please use a relay if you are concerned about the effect of noise.
Is there a terminal on the meter side with a disconnection, open circuit, short circuit or the like?
3-2 Is the signal line from the pulse meter denitely a no-voltage
a contact (relay contact)? * There is polarity in the case of open collector output.
(Number 7 is positive, numbers 8, 9, 10 are negative)
3-3 Remove the wiring from the terminal section, and short-
circuit the wires with each other several times while looking at the [Oper./Status] → [Accumult/Distrib] → [Pulse acc.] screen of the Intelligent Controller. Does the number of pulses increase correctly?
(It may take several minutes to update the display)
3-4 Is there a mistake in connecting the wattmeter and power
line, or the gas ow meter and fuel gas pipe?
3-5 Is the power amount or gas ow rate per pulse for this model
of pulse meter larger than necessary, or is the setting larger than necessary?
3-6 Investigate the main unit of the pulse meter
Yes 1-2
No Apply settings
Yes Look at the
“Current (calculating)” display
No 1-3
Yes 2-1
No Select the
correct time slot
Yes 2-2
No Correct wiring
Yes 3-1
No 2-3
2-4
Yes 3-2
No Correct wiring
Yes 3-3
No Correct wiring
Yes 3-4
No Go back to 2-1
Yes 3-5
No Reconstruct
them correctly
Yes 3-6
No Change meter
model, or modify settings
ー 8
2. Screen display relatedFault diagnosis
2-7.
Cumulative operation time (or distribution ratio) is counted even though the unit has not been operating
1. Intelligent Controller 1-1 Is the cumulative time zero? (Distribution ratio is counted) Yes *1
No 1-2
1-2 Did you not operate the unit but “forgot to stop it”? Yes (END)
No 1-3
1-3 Did the schedule timer or event control work?
(Remote controller, other centralised equipment, external input, and so on)
1-4 Is there evidence of forced operation of an indoor unit from a
PC or the like during repair service or maintenance?
1-5 When performing time slot integration, is the displayed
time slot selection correct? (RglHour (RglHour 1 to 8) / OutOfHours / SpcfdDay / AllHours)
1-6 (When using time slot distribution)
Are the timer settings and distribution specied day settings correct?
1-7 (When using time slot distribution)
Is an OFF timer set at the same time as or close to the
switching of the time slot?
Yes (END)
No 1-4
Yes (END)
No 1-5
Yes 1-6
No Select the
correct time slot
Yes 1-7
No Modify settings
Yes Modify settings
*2
No
* 1 In the Load Distribution mode, standby power is distributed even without operation. * 2 Avoid setting the OFF timer within about 10 minutes before the time slot switching time.
2-8. Cannot back up or restore to USB memory device (button is greyed out and cannot be pressed)
1. USB memory
device*
1-1 Is the USB memory device properly inserted in the specied
place?
1-2 Is backup or restoration also impossible with another USB
memory device?
1-3 Replace the Intelligent Controller.
* USB memory device specications Standard type (USB 2.0) Capacity: 4 GB or more Precautions for use
· Even if the USB memory device matches the above specications, operation is not guaranteed.
· USB memory device with encryption function (with security software) cannot be used.
Yes 1-2
No Insert it
Yes 1-3
No (END)
9
2. Screen display relatedFault diagnosis
2-9. Intelligent Controller does not start
1. Intelligent Controller does not start If “now loading ...”
OFF once and then turn it back ON again.
If the device does not start up even after turning on the power again, replace the SD card.
is displayed or the screen remains black 2 even with the power turned on, turn the power
1
1
2
10
2. Screen display relatedFault diagnosis
2-10. [Cong. change] appears on [Alarm list] screen
Detection method
1
This alarm is issued when the system conguration (such as number of adaptors, number of indoor units, and addresses) has changed or may have been changed, and unlike other alarm messages it does not indicate an error.
Diagnosis of failure
2
1. Unit side 1-1 Have you added or removed indoor unit or outdoor unit units? Ye s 2
No 1-2
1-2 Have you recongured the remote controller group? Yes 1-3
No 1-4
1-3 Is it a group spanning multiple areas? Yes 2
No 1-4
1-4 Did you change [Detailed Settings] of the remote controller? Yes 1-5
No 1-6
1-5
Is it one of the following items?
· Cap of indoor unit
· System address
· Indoor unit address
· ECONAVI Yes/No
· Presence of heater
· Group Main/Sub
· Indoor unit type
· Actual capacity of indoor unit
· Presence of VentOpen
Yes 2
No 1-6
1-6 Did you perform automatic address from the remote controller
or the outdoor unit?
1-7 Have you removed the remote controller and changed the
system to remote-less?
1-8 Although it does not fall under any of the above, does “Cong.
change” appear for no reason?
2 Perform Check Conguration. If the conguration has changed, perform Update Conguration. 3 Check whether the inter-unit control wiring has one of the following deciencies.
· Running in parallel with power lines
· Branch points exceed 16 places
· The total extension exceeds 1 km
· There is re-branching after branching
· There is a branch point with many branches (“star” or “octopus” conguration)
· The distance between one branch point and the next branch point is less than 2 m
· Defective termination resistance settings
· When shielded wire is used, the shield is grounded on both sides or not grounded
· More than 65 indoor units are connected in S-LINK If [Cong. change] still appears even when these changes are made, replace the MAIN board of the corresponding communication adaptor. If only an Intelligent Controller is used, replace the Intelligent Controller.
Yes 2
No 1-7
Yes 2
No 1-8
Yes 3
No (END)
2-11. Room temperature display is in error ([I/D unit list] screen)
1. Indoor unit side 1-1 Does it match the sensor temperature display on the remote controller?
When using remote control sensor: Sensor address 01 When using body sensor:
1-2 Is the centralised address set?
([Settings] → [System settings] → [Unit settings])
1-3 Is it only in error when heating? (OK except when heating) Yes *1
* 1 When using body sensor with heating, the room temperature after shifting may be displayed.
In this case, it does not match the sensor temperature display of the remote controller.
11
Sensor address 02
Yes Investigate
No 1-2
Yes 1-3
No Apply settings
No
thermistor
3. Unit operation related
3-1. The Schedule Timer does not work properly
3. Unit operation relatedFault diagnosis
1. Intelligent
Controller
1-1 Have you denitely set [Oper./Status] → [Set schedule]? Yes 1-2
No Apply settings
1-2 Is the timer selected for the indoor unit? Ye s 1-3
No Select
1-3 Is that day set as an area holiday or timer special day for that
indoor unit? * Area holidays and timer special days work with a dedicated timer
1-4 Is the current date / time setting correct? Yes 1-5
1-5 Did the following happen at the time of the timer?
· Power outage of indoor unit
· Power outage of Intelligent Controller
· Power outage of communication adaptor
· Communication error with air conditioner due to other causes
1-6 Is it set so that the units in one O/D unit system are in different
cooling / warming modes?
(Not allowed because of mismatch of heating and cooling)
1-7 Depending on the model, are the settings invalid?
(Example: Trying to set a cooling-only model to heating operation)
1-8 Are settings applied that change directly from cooling (dry) to
heating (or vice versa)?
1-9
Is the timer also used for other equipment (remote controller, Schedule Timer, etc.)?
1-10
Set a timer for [OFF] or [Fan] for one minute before (for example) switching the cooling / heating mode.
Yes (END)
No 1-4
No Correct the
settings
Yes (END)
No 1-6
Yes
Modify timer settings
No 1-7
Yes
Modify timer settings
No 1-8
Yes 1-10
No 1-9
Yes
Check setting conict.
No
3-2. Unit does not stop (operate) even when Batch stop (startup) input is ON
1. Intelligent Controller
or communication adaptor
1-1 Have you denitely set [System Settings] → [Event Control]? Yes 1-2
1-2 Is the connection of Batch stop (startup) input correct?
Intelligent Controller Communication Adaptor
27P terminal board 20P terminal board
20, 21 (DI1) 16, 17 (DI1) 20, 22 (DI2) 16, 18 (DI2) 20, 23 (DI3) 16, 19 (DI3)
Is there a mistake in the connection, or a disconnection or open circuit?
1-3 When the wiring of the Batch stop (startup) input signal is
removed from the terminal board and the Batch stop (startup) input part of the terminal board is short-circuited by using an appropriate wire, or broken piece of lead wire, does the unit turn OFF (ON) correctly?
1-4 Is the Batch stop (startup) input signal input with no voltage
“a” contact or a static signal?
1-5 On the [Settings] → [System Settings] → [I/D unit settings]
screen, 1 is there no check mark in the [Register] eld, or is
it 2 [Not managed]?
1-6 Replace MAIN board of communication adaptor connecting bulk input signal.
If only an Intelligent Controller is used, replace the Intelligent Controller.
No Modify settings
Yes 1-3
No Correct wiring
Yes 1-4
No 1-5
Yes Go back to 1-2
No Modify
Yes Modify settings
No 1-6
12
3. Unit operation relatedFault diagnosis
3-3 External alarm (operation) output does not turn ON even though unit alarm is detected
1. Intelligent Controller
or Communication Adaptor
1-1 Have you denitely set [System Settings] → [Event Control]? Yes 1-2
No Modify settings
1-2 Is the external output wiring properly connected?
Intelligent Controller Communication Adaptor
27P terminal board 20P terminal board
17, 18 (DO1) 13, 14 (DO1) 17, 19 (DO2) 13, 15 (DO2)
Is there disconnection, open circuit, or short circuit?
1-3 Is the load side (alarm device, etc.) properly connected?
(Contact rating: DC30 V, 0.5 A)
1-4 Is the “unit alarm” one of the following?
· Filter cleaning sign
· Engine oil Inspection Sign
· Remote control Inspection Sign
* In the case above, the external bulk warning is not output.
1-5 Replace MAIN board of communication adaptor connecting bulk output signal.
If only an Intelligent Controller is used, replace the Intelligent Controller.
Yes 1-3
No Correct wiring
Yes 1-4
No Modify
Yes (END)
No 1-5
3-4 Even if remote controller prohibition is set, function settings can be individually changed by
the remote controller
1. Intelligent Controller 1-1 Is the centralised address set?
(Conrm on the [Settings] → [System Settings] → [I/D unit settings] screen)
2. ON / OFF
Controller
2-1 The ON / OFF Controller main-sub changeover of the linked
ON / OFF Controller (ON / OFF CON) is OFF Is it set to (Main)?
2-2 Is the “centralised control main-sub changeover” of the
linked ON / OFF Controller (ON / OFF CON) set to OFF (Main)?
2-3
Replace the ON / OFF Controller
Yes 2-1
No Apply settings
Yes
Set it to ON (Sub)
No 2-2
Set it to ON
Yes
(Sub)
No 2-3
13

Various procedures

Display and settings for the communication adaptor board

Display and settings for the communication adaptor board
1. Overview
Communication adaptor board
1
It is possible to display/set using the four keys (HOME/UP/DOWN/SET), 6-digit 7-segment and 2 LEDs
•
(red/green).
7-segment numerical display LED
HOME key
UP/DOWN/SET keys
Terminating resistance
plug for communication
adaptor control wiring
Power supply
terminal strip
7-segment numerical display
2
Contents Display Contents Display Contents Display Contents Display
Power switch Signal terminal strip
ー 14
Various procedures
Display and settings for the communication adaptor board
2. Display immediately after power on
Immediately after turning on the power of the communication adaptor, all the segments light for 3 seconds,
•
then the microcomputer software version is displayed for 3 seconds, then the normal display is displayed.
Power on
(All segments lit: 3 seconds)
(Microcomputer software version display: 3 seconds)
Indication that air conditioner information is being collected is displayed.
Indication for air conditioner configuration
3. Air conditioner information collection in progress indication
(SCAN blinking) Air conditioner link number (X = 00 to 14)
In the following case, indication that air conditioner information is being collected is displayed.
•
1 When collecting information from the air conditioner immediately after turning on the power.
2 When checking configuration
15
Various procedures
Display and settings for the communication adaptor board
4. Indication for air conditioner conguration
While the indication for air conditioner configuration is displayed, information on the configurations of the indoor
•
unit linked system 1 and linked system 2 are alternately displayed for 10 seconds each.
If the touch switch on the adaptor board is not operated, the indication for air conditioner configuration is
•
normally displayed.
(Information on the indoor unit linked system 1: 10 seconds)
(Information on the indoor unit linked system 2: 10 seconds)
Content displayed during normal display
•
Example: When 2 outdoor units and 12 indoor units are connected to the air conditioner LINK 1, and 3 outdoor
units and 18 indoor units are connected to the air conditioner linked system 2
Number of connected indoor units: 12 units
Number of connected outdoor units: 2 units
Link address 0 (Linked system 1)
Number of connected indoor units: 18 units
Number of connected outdoor units: 3 units
Link address 1 (Linked system 2)
5. System OFF indication
While the system is OFF, the above is displayed.
•
The normal status is restored by restarting the power supply.
•
ー 16
(STOP blinking)
Air conditioner link number (X = 00 to 14)
Various procedures
Display and settings for the communication adaptor board
6. How to display the microcomputer version
There are two ways to display the microcomputer version.
Restart power supply of communication adaptor board
1
Restart the power switch of the communication adaptor (if it is built in to the Intelligent Controller, restart the
•
switch of the Intelligent Controller).
The microcomputer version is displayed for 3 seconds immediately after turning on the power (refer to
•
“2. Display immediately after power on”) .
Press the HOME and DOWN keys on the communication adaptor board simultaneously.
2
While the two keys are pressed, the microcomputer version is displayed.
17
Various procedures
Display and settings for the communication adaptor board
7. Advanced settings
It is possible to refer to and set detailed data using the four keys on the communication adaptor board.
Main menu Sub menu
00: Adaptor data display 01: Indoor unit data display (* 1) 02: Outdoor unit data display Connection outdoor unit address display 03: Error data display (alarm log) (* 1)
04: Adaptor data settings
05: Adaptor initial settings
06: Physical address settings and
check
07: (* 1)
01: Pulse count 1 02: Pulse count 2 03: Pulse count 3 04: Interval for regular communication 2 of air conditioner linked system 1 05: Interval for regular communication 2 of air conditioner linked system 2 06: Communication speed 07: Communication error detection interval 08: EEPROM initialisation 09: Software reset 10: No response settings 11: Delayed response settings 12: Outdoor unit maintenance data not required 13: Centralised address settings 01: Adaptor number 02: Address valid 03: Centralised equipment main-sub 04: Communication adaptor number of air conditioner linked system 1 05: Communication adaptor number of air conditioner linked system 2 06: Chattering cancel time 07: Local adaptor 08: Initial communication at power on 01: Physical address check / individual settings of air conditioner linked
system 1
02: Physical address check / individual settings of air conditioner linked
system 2
03: Clear the physical address of all indoor units of air conditioner linked
system 1
04: Clear the physical address of all indoor units of air conditioner linked
system 2
05: Automatic settings of physical address of all indoor units of air
conditioner linked system 1
06: Automatic settings of physical address of all indoor units of air
conditioner linked system 2
(* 1)
ー 18
(* 1) There are currently no items to display.
Various procedures
■ Main menu display
Press and hold the HOME key for 2 seconds or longer to display the menu display (level 0) screen.
•
In this status, the UP key or DOWN key can be pressed to select an item from the main menu.
On the main menu, 00 to 07 in the table below can be selected.
The main menu item number is displayed during and for 2 seconds after item change, and then the board
•
display content in the table below is displayed.
If an item (00 - 07) is selected and the SET key is pressed, the screen will shift to the detailed display screen
•
Display and settings for the communication adaptor board
for that item.
Main menu item
DOWN
UP
Board display content Overview
Adaptor data display (*1)
Indoor unit data display (*1)
Outdoor unit data display
Error data display (alarm log) (*1)
Adaptor data settings
Adaptor initial settings
Physical address settings and check
Date settings and display
(* 1) There are currently no items to display.
Even during detailed settings, if you press and hold the HOME key, it will return to the main menu selection.
•
(Content in the process of being set will be discarded.)
If there is no operation for 30 seconds, the unit returns to the indication for air conditioner configuration.
•
(Content in the process of being set will be discarded.)
ー 19
Various procedures
■ (02) Outdoor unit data display
This screen is not used normally; it is used when you want to add special specifications to a particular outdoor
•
unit model.
On the main menu screen, select (02: outdoor unit data display) and press the SET key to display the data of
•
the currently connected outdoor unit.
If there is no operation for 30 seconds, the unit returns to normal display.
Display and settings for the communication adaptor board
Air conditioner
link address
XX
DOWN
UP
YY
ZZ is an outdoor unit model. The factory setting of the communication adaptor is 0.
•
ZZ cannot be changed by communication adaptor board operation.
Outdoor unit No. Board display
Outdoor unit No. 1
Outdoor unit No. 2
Outdoor unit No. 30
Outdoor unit No. 1
Outdoor unit No. 2
Outdoor unit No. 30
An outdoor unit with a value between 80 and 82 registered can acquire maintenance data and send it to the
•
higher software.
ZZ Outdoor unit
80 81 82
0
T-type Eco-multi T-type W Eco-multi T-type 3WAY Outdoor units other than the above
20
Various procedures
■ (04) Adaptor data settings
This screen is for browsing and changing the internal data of the communication adaptor and is not
•
normally used.
If (04: Adaptor settings) is selected on the main menu and the SET key is pressed, a screen with current
•
detailed information on the communication adaptor is displayed.
If there is no operation for 30 seconds, the unit returns to normal display.
Use the UP and DOWN keys to browse/set necessary data from the following items.
•
Select a data number using the UP and DOWN keys to display the data.
Data display example
Display and settings for the communication adaptor board
The characters to the right of the point are the data.
Data number
Adaptor detailed data
•
number
DOWN
Data
1 Pulse count 1
2 Pulse count 2
3 Pulse count 3
Interval for regular
4
Interval for regular
5
6 Communication speed
7
8 EEPROM initialisation
Communication error
Item Display Remarks
communication 2
of air conditioner
linked system 1
communication 2
of air conditioner
linked system 2
detection
2345 times
2345 times
234 times
18 minutes
18 minutes
19200 BPS
10 minutes
UP
9 Reset
10 No response settings
11 Delayed response 20 msec
12
13
No maintenance data
required
Central address
settings
21
Various procedures
(04–01) Pulse count 1
(04–02) Pulse count 2
(04–03) Pulse count 3
Displays the current pulse count (P1, P2, P3).
•
If the pulse count value is changed, the distribution function of the Intelligent Controller will not operate properly.
•
[How to change]
1 Press and hold the SET key for at least 1 second and the pulse count value blinks.
2 Press the UP or DOWN key to change it to the pulse count value you want to set.
3 Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
Display and settings for the communication adaptor board
(Changeable range: 0 to 65535)
(04–04) Interval for regular communication 2 of air conditioner linked system 1
(04–05) Interval for regular communication 2 of air conditioner linked system 2
Displays the interval for the air conditioner regular communication 2.
•
At factory shipment, the interval for regular communication 2 is 18 minutes.
•
[How to change]
1 Press and hold the SET key for at least 1 second and the regular communication interval (minutes)
2 Press the UP or DOWN key to change it to the regular communication interval you want to set.
3 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
Air conditioner regular communication 2 is not performed when 0 minutes is set.
•
will blink.
(Changeable range: 0 to 99)
22
Various procedures
(04–06) Communication speed
Displays the communication speed of the communication adaptor control wiring.
•
The factory setting is 19,200 BPS.
•
The following BPS can be selected.
•
1 19200 BPS ... Intelligent Controller (Do not change from this setting)
2 9600 BPS ... AMY software
[How to change]
1 Press and hold the SET key for at least 1 second and the BPS value blinks.
2 Press the UP or DOWN key to display 19200 and 9600 alternately.
3 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
4 It becomes valid after power supply restart of the communication adaptor board.
Display and settings for the communication adaptor board
(04–07) Communication error detection interval
Displays the time (minutes) until judging that a communication error with the air conditioner has occurred.
•
The factory setting is 10 minutes.
•
It can be set in the range from 0 to 99 minutes.
•
If it is set to 0 minutes, communication error detection will not be performed.
•
23
Various procedures
(04–08) EEPROM initialisation
Use this to restore the EEPROM to the factory settings.
•
EEPROM initial values list
•
Pulse count 1 0
Pulse count 2 0
Pulse count 3 0
Address on air conditioner linked system 1 0x150
Address on air conditioner linked system 2 0x151
Address for air conditioner linked system 1 on communication adaptor control wiring
Address for air conditioner linked system 2 on communication adaptor control wiring
Presence/absence of air conditioner connection to indoor unit
or outdoor unit communication wire
Centralised equipment main-sub Air conditioner linked system 1: Main
Presence of local adaptor Air conditioner linked system 1: Yes
Check of air conditioner configuration at power on Air conditioner linked system 1: No
Response to RS485 Air conditioner linked system 1: Yes
Adaptor number 0
Pulse input chattering cancel time 100 msec
Communication speed of RS485 19200 BPS
Interval for air conditioner regular communication 2 Air conditioner linked system 1: 18 minutes
Time until air conditioner communication error detection 10 minutes
Reset count 0
Display and settings for the communication adaptor board
0x00
0x01
Air conditioner linked system 1: Yes Air conditioner linked system 2: Yes
Air conditioner linked system 2: Main
Air conditioner linked system 2: Yes
Air conditioner linked system 2: No
Air conditioner linked system 2: Yes
Air conditioner linked system 2: 18 minutes
[EEPROM initialisation method]
1 Press and hold the SET key for at least 1 second.
2 If all segments of the 7-segment numerical display light up, EEPROM initialisation is completed.
24
Various procedures
(04–09) Software reset
[Reset method]
1 Press and hold the SET key for at least 1 second.
2 Reset is completed if all segments of the 7-segment numerical display light up.
(04–10) No response settings
Sets whether to respond to request data from the communication adaptor control wiring.
•
[How to change]
1 Press and hold the SET key for at least 1 second and the setting value blinks.
Display and settings for the communication adaptor board
2 Press the UP or DOWN key to change the setting value in the order of 0 → 1 → 2 → 3 → 0 → · · ·.
Setting value HBS1 HBS2
0 (factory default)
1 2
3
3 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
4 Valid after power restart.
(04–11) Delayed response settings
Send response data xx milliseconds after receiving data from the communication adaptor control wiring.
•
(xx: factory default is 20 milliseconds)
Changing this setting may prevent communication with devices such as Intelligent Controller.
•
[How to change]
1 Press and hold the SET key for at least 1 second and the response delay time (milliseconds) will
Responds Responds Does not respond Does not respond
Responds Does not respond Responds Does not respond
blink.
2 Press the UP or DOWN key to change it to the delayed response time you want to set.
(Changeable range: 0 to 99)
3 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
25
Various procedures
(04–12) Outdoor unit maintenance data not required
Use to reduce communication load by not acquiring outdoor unit data.
•
At factory shipment, it is set to acquire outdoor unit data.
•
[How to change]
1 Press and hold the SET key for at least 1 second and the rightmost digit '0' flashes.
2 Press the UP or DOWN key and '0' and '1' are alternately displayed.
0 Acquire outdoor unit maintenance data.
1 Do not acquire outdoor unit maintenance data.
3 Press and hold the SET key. When the display changes from blinking to lit, the change is completed.
(04–13) Central address settings
Display and settings for the communication adaptor board
Use this when forcibly setting a central address to an indoor unit for which a central address is not set.
•
[Central address setting method]
1 Press and hold the SET key for at least 1 second.
2 If END is displayed on the 7-segment numerical display, the setting is completed.
(It is automatically set in order of indoor unit address in the range of 1 to 64)
* The central address of already set units is not changed.
Set unused central addresses in the order of address of unconfigured units.
ー 26
Various procedures
■ (05) Communication adaptor initial settings
Press the UP or DOWN key to select a function from the following options.
Display and settings for the communication adaptor board
Display Function
Adaptor number
Address valid
DOWN
UP
(05–01) Adaptor number
The factory default is 0.
•
It is the address on the communication adaptor control wiring.
•
Set it in the range of 0 to 15.
•
[How to change]
    1
Press and hold the SET key for at least 1 second and the adaptor number blinks.
Centralised equipment main-sub
Communication adaptor number of air conditioner linked system 1
Communication adaptor number of air conditioner linked system 2
Chattering cancel time
Local adaptor
Initial communication at power on
    2           3
Press the UP or DOWN key to display the adaptor number you want to set.
(Make sure not to duplicate addresses.)
Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
27
Various procedures
(05–02) Address valid
Set whether the air conditioner is connected to air conditioner linked systems 1 or 2.
•
Display and settings for the communication adaptor board
Address valid
0 (factory default)
1 2
3
[How to change]
1 Press and hold the SET key for at least 1 second and the address valid data blinks.
2 Press the UP or DOWN key to display the value you want to set.
(Select from 0 to 3 in the table above.)
3 Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
(05–03) Centralised device main-sub
Set main and sub of the centralised control.
•
Air conditioner linked systems 1 Air conditioner linked systems 2
Air conditioner connected
Air conditioner connected Air conditioner not connected Air conditioner not connected
Air conditioner connected
Air conditioner not connected
Air conditioner connected
Air conditioner not connected
Address valid
0 (factory default)
1 2
3
[How to change]
1 Press and hold the SET key for at least 1 second and the main/sub setting data of centralised control
blinks.
2 Press the UP or DOWN key to display the value you want to set.
(Select from 0 to 3 in the table above.)
3 Press and hold the SET key and when the display changes from blinking to lit, the change is
completed.
Air conditioner linked systems 1 Air conditioner linked systems 2
Main Main
Sub Sub
Main
Sub
Main
Sub
ー 28
Loading...
+ 149 hidden pages