Panasonic CS-W50BTP, CU-V50BBP8, CU-W50BBP8 Service Manual

1 SERVICE INFORMATION 3 2 FEATURES
4
3 SPECIFICATION (HEAT PUMP TYPE )
9
4 SPECIFICATION (COOLING ONLY TYPE )
10
5 TECHNICAL DRAWING
11
13
7 OPERATING INSTRUCTION
25
8 REFRIGERATION CYCLE
27
9 OPERATION RANGE
28
10 PIPE LENGTH
29
11 OPERATING CHARACTERISTIC
31
12 FAN PERFORMANCE
32
© 2002 Matsushita Industrial Corporation. Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.
CS-W50BTP CU-V50BBP8 CS-W50BTP CU-W50BBP8
13 SAFETY DEVICE 33 14 COMPONE NT SPECIFICATION
34
15 CAPACITY AND POWER CONSUMPTION
35
16 DISCHARG E AND SUCTION PRESSURE
38
17 REACHING DISTANCE
39
18 SOUND DATA
40
19 TWIN AND TRIPLE
42
20 WIRING MISTAKE PREVENTI ON
47
21 T EST OPERATION AND SELF DIAGNOSIS
48
22 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH
52
23 GROUP CONTROL
53
24 TROUBLESHOOTING
54
AIR CONDITIONER
CONTENTS
Page Page
ORDER NO. MAC0210059C2
25 EMERGEN CY OPERATIO N 59 26 CONTROL
60
27 WIRED REMOTE CONTROL INSTALLATION MANUAL
70
28 WIRELESS REMOTE CONTROL INSTALLATION MANUAL
75
29 INSTALLATION (INDOOR UNIT)
82
30 INSTALLATION (OUTDOOR UNIT)
92
31 REPLACEM E NT PARTS
104
2
1 SERVICE INFORMATION
Caution:
O
Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
O
Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
Notice of Address setting for NEW Ceiling / NEW Outdoor Unit.
The new Ceiling / new Outdoor models are possible to have address setting for twin / triple control or group control automatically when main power supply is switched on.
(Manual address setting is also possible by using DSW1 switch on the indoor unit P.C. board.) However,
this address setting is
only possible when proper wiring connection is made and indoor unit must be of original unit
.
1.1. Example of trouble during test operation
If the below phenomenon is found during test operation, wrong address setting is possible. Therefore, please inspect the address setting.
1. LCD display of the wired remote control is not illuminated although the main power supply switch is ‘on’.
2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated. (But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control OFF/ON button is ‘on’.) (For normal operation, the outdoor unit will only start its operation after 3 to 5 minutes upon pressing the OFF/ON button.)
3. P.C. board had memorized wrong setting information. a. If main power supply is switched on with the wrong connection. b. When changing the connection or combination of units due to re-installation etc.
• •
When changing the system from twin to triple (triple to twin).
• •
When changing the system from group control to normal one to one system.
• •
When making the replacement of units of master and slave etc.
1.2. Caution during test operation
Do not touch the remote control button and do not change any wirings for one minute when the main power supply switch is ‘on’. (Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When the main power supply switch is ‘on’, the P.C. board will automatically memorize the connecting system. Consequently, when initial power supply is ‘on’, there mustn’t be any interchanging of units even of the same type and same capacity unit.
Therefore, connection of the unit to another system is prohibited.
3
2.1. New design
2.1.1. Gentle curved styling
• •
The base has gentle curves which express a functional beauty. It spreads the air quietly over a wide area.
2.2. Such quietness!
2.2.1. Several new mechanism add up to low 49 dB noise (W50BT - High Fan Speed)
1. Delta throat fan
A delta throat (projection) has been attached to the fan outlet to suppress the generation of vortexes. This helps maintain air flow speed even at lower fan speeds and is effective in reducing noise.
2. Reflux orifice
The orifice at the intake port is equipped with an air flow guide which minimizes the flow disturbances which occur at the orifice and inside the impeller.
This reduces pressure losses inside the casing and also helps reduce noise.
3. Adoption of wing-shaped vanes
• •
The vanes of the fan have been changed to “aerodynamic” shaped vanes, so that the air flow more smoothly over the vane surfaces and noise is thus suppressed.
• •
Side filters have been adopted in the pipe partitions. These allow the air intake space to be increased and also further reduce noise.
2.2.2. Automatic swinging louvre
• •
The horizontal air flow angle is a wide 100 degrees (manual). The louvre can swing automatically (through 70 degrees vertically) using the remote control. This increases the area of comfortable air flow and warms the air even to floor level.
2.2.3. Newly-shaped louvre
• •
The newly-shaped louvre and air outlet effectively distribute the air flow. During cooling, this stops warm air from collecting near the louvre, and prevents freezing.
2 FEATURES
4
2.3. Easy installation
2.3.1. Easy suspension
• •
A suspension bolt fixing bracket with 4-point support is attached to the main unit, which increases the space available for installation.
2.3.2. Two installation methods : standard and wall
• •
In addition to the standard (1) ceiling installation, a wall (2) installation method (using a wall-hanging bracket) is available for cases where the ceiling is too high for the main unit to be suspended.
2.4. Piping
2.4.1. 3-direction pipe lead-out
• •
The refrigerant piping can lead out in one of three directions (right, rear-right and top-right), and the drain pipe direction can be selected from four directions (right, rear-right, left and rear-left).
2.5. Easy maintenance
2.5.1. Long life filter (standard equipment)
• •
In general office environments, cleaning (maintenance) is not required until after approximately 2,500 hours of operation, thus reducing maintenance work.
• •
For optimum comfort, it is recommended to clean the air filter every 1-1/2 months.
2.5.2. Maintenance is possible from underneath the unit.
• •
If the bottom panel is detached, the drain pan can then be removed and installed from underneath the unit, and inspection and servicing of component such as the control panel also becomes easier.
2.6. Auto fan mode (indoor unit)
• •
Auto fan mode is added besides high, medium and low. It automatically adjusts the fan speed according to the indoor unit’s temperature.
2.7. Hot start system (heat pump
models)
2.8. Automatic changeover
function (heat pump models)
• •
The unit automatically switches between cooling and heating in accordance with operating load in order to maintain a comfortable indoor temperature.
5
2.9.1. Product features
• •
Low-noise design improves comfort in surrounding areas
1. The noise-suppressing winglet fan is a result of new research into vane design theory. The unique curved shape suppresses the generation of vortexes, thus reducing air flow noise.
2. The adoption of double-orifice rings reduces air passage resistance.
3. Strengthening of the noise insulation materials in the compressor and the sealing-in of mechanical noise allows vibration noise to be greatly enclosed and suppressed.
4. The heat exchanger has an L-shaped design to allow air to flow more smoothly.
5. Noise is automatically reduced further during night-time operation with lower outdoor air temperatures.
2.10. Greatly improved workability increases system renewal capability
• •
Pipes that are one size larger can also be connected for renewal.
− −
If renewing the system, existing refrigerant pipes can be utilized so that only the indoor and outdoor units need to be replaced.
− −
For example, liquid and gas pipes from 10 years ago can be connected to current pipes with the same size or one size larger. Effective utilization of materials reduces working time and trouble. (Adaptor sockets are not supplied.)
2.9. Low-noise outdoor units
6
• •
Additional refrigerant charging unnecessary for 30 m
− −
All models do not require any additional charging of refrigerant for 30 m of pipe length. This makes installation much easier.
• •
Drain water dripping-prevention structure
− −
The base of the outdoor unit is provided with a single drain hole in order to prevent drain water from leaking out of the unit. By connecting a drain elbow and a discharge pipe, water leakages can be prevented even when the unit is installed to a wall.
• •
Save space design allows units to be installed side-by­side continuously
− −
Servicing after installation can be carried out by removing the front covers.
• •
Long pipe design for refrigerant pipes
− −
Maximum piping length of 50m for all models.
• •
Internal pipe connection
− −
Pipes are connected inside the units (inside the side covers), making the final appearance more attractive.
− −
Pipes can be diverted outward in any of four directions (forward, right, down, rear).
− −
Small liquid pipe diameters of 9.52mm for 50BB models, making installation work much easier.
• •
Centralized draining method
− −
Even when multiple outdoor units are installed to a wall, the drain outlets can be concentrated into a single drain pipe. This makes installation easier and also improves appearance.
2.11. A brand-new control method using the latest in technology
• •
Easier power supply wiring connection Power supply wiring and other wiring tasks can be carried out more easily.
− −
Twin non-polar wires used to connect indoor and outdoor units.
− −
Adoption of connection error prevention circuits for drive wires and signal wires. If a connection error is made, the relay does not operate and current does not flow to the circuit boards.
• •
Twin and Triple operation
− −
Simultaneous air conditioning of wide spaces and corners is possible. Indoor units of different horsepowers can even be used in combination.
− −
Master unit and slave-units can be set automatically in twin and triple systems. No address setting is necessary.
− −
Multiple indoor units can be operated simultaneously with a single remote control. Note that individual operation is not possible.
• •
Separate indoor/outdoor unit power supplies
The power supply can be connected to (1) just the outdoor units, or (2) to both the indoor and outdoor units.
• •
Easy test operation
Test operation can be carried out for both indoor and outdoor units.
• •
Automatic setting initialization function
(Remote control and Indoor unit) In accordance with the indoor and outdoor units connected and the connection methods, conditions such as the connection configuration (twin or triple format) and remote­control functions such as automatic louvre operation and cooling or heating mode are automatically detected and set instantly.
7
2.12. Wired Remote Control
• •
The new design includes an easily-visible red pilot lamp. The power can be turned on and off at a single touch, without opening the cover.
• •
Has a built-in thermistor, allowing indoor temperature detection in accordance with indoor conditions by switching with main unit thermistor.
• •
Twin non-polar wires make installation work easy. (10 m cable supplied as accessory.)
2.13. Wireless Remote Control
• •
New design with compact size. (Operation range within approximately 8 m.)
• •
Built-in timer with ON/OFF timer setting (within 24 hours)
Wired Wireless
Heat Pump CZ-RD51P CZ-RL51P
Cooling CZ-RD51P CZ-RL01P
NOTE: Both of the above remote control is packed separately from the indoor unit.
2.14. Group Control Equipment
8
3 SPECIFICATION (HEAT PUMP TYPE )
CS-W50BTP / CU-W50BBP8
ITEM / MODEL Indoor Unit Outdoor unit
Main Body CS-W50BTP CU-W50BBP8
Remote CZ-RD51P (Wired)
Control CZ-RL51P (Wireless)
Cooling Capacity kW 14.0
BTU/h 47,700
Heating Capacity kW 16.0
BTU/h 54,600 Refrigerant Charge-less m 30 Standard Air Volume for High Speed m3/min 35
cfm 1236
Outside Dimension (H x W x D) mm 250 x 1600 x 700 1220 x 1100 x 320
inch 9-27/32 x 62-31/32 x 27-9/16 48-1/24 x 43-5/16 x 12-19/32
Net Weight kg 47 115
lbs 104 254
Piping Connection
Refrigerant Gas mm (inch) O.D Ø 19.05 (3/4) Flared Type
Liquid mm (inch) O.D Ø 9.52 (3/8) Flared Type
Drain mm O.D Ø 20 I.D Ø 20 x 1
Compressor Type, Number of Set - Hermetic-1 (Scroll), 1
Starting Method - Direct on-line starting Motor Type - 2-pole 3-phase induction motor
Rated Output kW - 4.10
Fan Type, Number of Set Sirocco fan Propeller fan
Motor Type 4-pole single phase induction motor 6-pole single phase induction motor
Rated Output kW 0.14 0.055 x 2 Air-heat Exchanger Slit-fin type X-Louvre-fin type Refrigerant Control Cool Capillary tube -
Heat - Capillary tube Refrigerant Oil (Charged) litre - MMMAPOE Refrigerant (Charged) kg - R407C (4.4)
(oz) (155)
Running Adjustment
Control Switch Wireless or Wired Remote Control ­Room Temperature Thermostat (Main Body) -
Safety Devices Internal protector for compressor, Internal thermostat for fan motor,
Crankcase heater, High and heating pressure switch, Current transformer
Noise Level dB (A) Hi 49 Lo 45 Cooling 56, Heating 58
Power level dB Cooling : Hi 66 Lo 62
Heating : Hi 66 Lo 62
Cooling 69, Heating 71
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F D.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50Hz)
ITEM / MODEL CS-W50BTP, CU-W50BBP8
Condition by JIS B 8615 Volts V 380 400 415 Phase 3N 3N 3N Power Consumpti on kW Cool 5.35 5.35 5.35
Heat 5.45 5.45 5.45
Running Current A Cool 9.2 9.2 9.2
Heat 9.2 9.2 9.2 Starting Current A 69 69 69 Power Factor % Cool 88 84 81
Heat 90 86 82 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz
9
4 SPECIFICATION (COOLING ONLY TYPE )
CS-W50BTP / CU-V50BBP8
ITEM / MODEL Indoor Unit Outdoor unit
Main Body CS-W50BTP CU-V50BBP8
Remote CZ-RD51P (Wired)
Control CZ-RL01P (Wireless)
Cooling Capacity kW 14.0
BTU/h 47,700 Refrigerant Charge-less m 30 Standard Air Volume for High Speed m3/min 35
cfm 1236
Outside Dimension (H x W x D) mm 250 x 1600 x 700 1220 x 1100 x 320
inch 9-27/32 x 62-31/32 x 27-9/16 48-1/24 x 43-5/16 x 12-19/32
Net Weight kg 47 112
lbs 104 247
Piping Connection
Refrigerant Gas mm (inch) O.D Ø 19.05 (3/4) Flared Type
Liquid mm (inch) O.D Ø 9.52 (3/8) Flared Type
Drain mm O.D Ø 20 I.D Ø 20 x 1
Compressor Type, Number of Set - Hermetic-1 (Scroll), 1
Starting Method - Direct on-line starting Motor Type - 2-pole 3-phase induction motor
Rated Output kW - 4.10
Fan Type, Number of Set Sirocco fan Propeller fan
Motor Type 4-pole single phase induction motor 6-pole single phase induction motor
Rated Output kW 0.14 0.055 x 2 Air-heat Exchanger Slit-fin type X-Louvre-fin type Refrigerant Control Capillary tube Capillary tube Refrigerant Oil (Charged) litre - MMMAPOE Refrigerant (Charged) kg - R407C (4.4)
(oz) (155)
Running Adjustment
Control Switch Wireless or Wired Remote Control ­Room Temperature Thermostat (Main Body) -
Safety Devices Internal protector for compressor, Internal thermostat for fan motor,
Crankcase heater, High pressure switch, Current transformer
Noise Level dB (A) Hi 49 Lo 45 56
Power level dB Hi 66 Lo 62 69
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
ELECTRICAL DATA (50Hz)
ITEM / MODEL CS-W50BTP, CU-V50BBP8
Condition by JIS B 8615 Volts V 380 400 415 Phase 3N 3N 3N Power Consumpti on kW Cool 5.35 5.35 5.35 Running Current A Cool 9.2 9.2 9.2 Starting Current A 69 69 69 Power Factor % Cool 88 84 81 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3N~380V, 400V, 415V 50Hz
10
5 TECHNICAL DRAWING
11
12
6 CIRCUIT DIAGRAM
13
14
15
16
17
18
19
20
21
22
23
24
7 OPERATING INSTRUCTION
7.1. Wired Remote Control (OPTIONAL PARTS)
NOTES:
• •
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
• •
The illustration above is for explanatory purposes only. The appearance will be different during actual operation.
• •
Do not operate the remote control with wet hands. Otherwise, electric shock or malfunction may occur.
• •
Do not press the remote control buttons with sharp object as this may damage the remote control.
• •
Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same button once more to cancel the operation.
• •
When the power resumed after power failure, the unit will restart automatically with all the previous settings preserved by the memory function. (Auto restart function)
25
7.2. Wireless Remote Control (OPTIONAL PARTS)
NOTES:
• •
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
• •
The illustration above is for explanatory purpose only. The appearance will be different during actual operation.
• •
If using the wireless remote control in conjunction with the wired remote control, the settings made from the wireless remote control will appear on the wired remote control display (except when making timer settings).
• •
Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same button once more to cancel the operation.
• •
When the power resumed after power failure, the unit will restart automatically with all previous settings preserved by the memory function. (Auto restart function)
26
8 REFRIGERATION CYCLE
CS-W50BTP/CU-W50BBP8
CS-W50BTP/CU-V50BBP8
27
9 OPERATION RANGE
Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.
Power Supply
MODEL Unit Main Power Applicable Voltage
CU- Phase, Volts Hz Max Min
V50BBP8 3N~380 50 418 342
W50BBP8 3N~400 50 440 360
3N~415 50 457 374
Indoor and Outdoor Temperature
• •
Cooling only type Model 50Hz CU-V50BBP8
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Max Min Max Min
Cooling 50 32/23 21/15 43/- -5/-
• •
Heat pump type Model 50Hz CU-W50BBP8
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Max Min Max Min
Cooling 50 32/23 21/15 43/- -5/-
Heating 50 27/- 16/- 24/18 -10/-
28
10 PIPE LENGTH
QQQQ
CORRECTION OF COOLING CAPACITY AND HEATING CAPACITIES
Correction of cooling and heating capacities according to the connecting pipe length. The data of cooling capacities (marked on the name plate) are based on 7.5 meters connecting pipe and horizontal installation. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
29
Attention
QQQQ
REFRIGERANT ADDITIONAL CHARGE
1.
Piping installation by standard piping
• •
At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m. (Refer to the following table)
But when the piping length exceeds 30m, additional charge is required according to the following table.
Example: CU-V50BBP8
In case of 50m long pipe (one way), the amount of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g
Q
Cooling only type
Model Name Standard piping specification
Liquid piping (dia.mm) Gas piping (dia.mm) Gas charge- less length
(m)
Additional gas volume (g/m)
CU-V50BBP8 9.52 19.05 30 50 Model Name Existing piping specification (Larger piping)
Liquid piping (dia.mm) Gas piping (dia.mm) Gas charge- less length
(m)
Addition gas volume (g/m)
CU-V50BBP8 12.7 19.05 7 100
Q
Heat pump type
Model Name Standard piping specification
Liquid piping (dia.mm) Gas piping (dia.mm) Gas charge- less
length (m)
Additional gas volume (g/m)
CU-W50BBP8 9.52 19.05 30 50
Model Name Existing piping specification (Larger piping)
Liquid piping (dia.mm) Gas piping (dia.mm) Gas charge- less length
(m)
Addition gas volume (g/m)
CU-W50BBP8 12.7 19.05 17 100
2.
Piping installation by existing piping
The above models change the liquid pipe size of the previous series. It is to use the existing piping by adjusting the refrigerant gas volume.
Please do correct piping installation referring to the above table.
• •
Please do not decrease the gas piping size. (It causes the breakdown of the compressor).
• •
The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping specification.
30