• Single-pole and double-pole models are applicable to operating
coils with ratings of 100/110 VAC, 110/120 VAC, 200/220 VAC,
220/240 VAC, or 100/110 VDC).
• Three-pole and four-pole models are applicable to operating
coils with ratings of 100/110 VAC, 200/220 VAC, or 100/110
VDC).
AC6 V214.1 mA183 mA12.2 Ω0.04 H0.08 H80% max. 30% min. 110%1.0 to 1.2 VA
12 V106.5 mA91 mA46 Ω0.17 H0.33 H
24 V53.8 mA46 mA180 Ω0.69 H1.30 H
50 V25.7 mA22 mA788 Ω3.22 H5.66 H
100/110 V11.7/12.9 mA10/11 mA3,750 Ω14.54 H24.6 H0.9 to 1 VA
110/120 V9.9/10.8 mA8.4/9.2 mA4,430 Ω19.20 H32.1 H
200/220 V6.2/6.8 mA5.3/5.8 mA12,950 Ω54.75 H94.07 H
220/240 V4.8/5.3 mA4.2/4.6 mA18,790 Ω83.50 H136.40 H
DC6 V150 mA40 Ω0.16 H0.33 H10% min.0.9 W
12 V75 mA160 Ω0.73 H1.37 H
24 V36.9 mA650 Ω3.20 H5.72 H
48 V18.5 mA2,600 Ω10.6 H21.0 H
100/110 V9.1/10 mA11,000 Ω45.6 H86.2 H
Note: See notes on the bottom of next page.
Coil inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consum.
(approx.)
(60 Hz)
(60 Hz)
A-32General-purpose Relay LY
Three-pole Relays
Rated voltage Rated currentCoil
resistance
50 Hz60 HzArm. OFFArm. ON% of rated voltage
AC6 V310 mA270 mA6.7 Ω0.03 H0.05 H80% max. 30% min. 110%1.6 to 2.0 VA
12 V159 mA134 mA24 Ω0.12 H0.21 H
24 V80 mA67 mA100 Ω0.44 H0.79 H
50 V38 mA33 mA410 Ω2.24 H3.87 H
100/110 V14.1/16 mA12.4/13.7 mA2,300 Ω10.5 H18.5 H
200/220 V9.0/10.0 mA7.7/8.5 mA8,650 Ω34.8 H59.5 H
DC6 V234 mA25.7 Ω0.11 H0.21 H10% min.1.4 W
12 V112 mA107 Ω0.45 H0.98 H
24 V58.6 mA410 Ω1.89 H3.87 H
48 V28.2 mA1,700 Ω8.53 H13.9 H
100/110 V12.7/13 mA8,500 Ω29.6 H54.3 H
Note: See notes under next table.
Coil inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consum.
(approx)
(60 Hz)
Four-pole Relays
Relays
Electromechanical
Rated voltage Rated currentCoil
50 Hz60 HzArm. OFFArm. ON% of rated voltage
AC6 V386 mA330 mA5 Ω0.02 H0.04 H80% max. 30% min. 110%1.95 to
12 V199 mA170 mA20 Ω0.10 H0.17 H
24 V93.6 mA80 mA78 Ω0.38 H0.67 H
50 V46.8 mA40 mA350 Ω1.74 H2.88 H
100/110 V22.5/25.5 mA19/21.8 mA1,600 Ω10.5 H17.3 H
200/220 V11.5/13.1 mA9.8/11.2 mA6,700 Ω33.1 H57.9 H
DC6 V240 mA25 Ω0.09 H0.21 H10% min.1.5 W
12 V120 mA100 Ω0.39 H0.84 H
24 V69 mA350 Ω1.41 H2.91 H
48 V30 mA1,600 Ω6.39 H13.6 H
100/110 V15/15.9 mA6,900 Ω32 H63.7 H
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for rated currents and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperatures of 23°C.
3. AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power consumption drop was measured for the above data. When driving transistors, check leakage current and connect a bleeder re-
sistor if required.
resistance
Coil inductance
(reference value)
Must
operate
voltage
Must
release
voltage
Max.
voltage
Power
consum.
(approx)
2.5 VA
(60 Hz)
General-purpose RelayLYA-33
■ Contact Ratings
RelaySingle contactBifurcated contacts
1-pole2-, 3- or 4-pole2-pole
LoadResistive load
Rated load110 VAC 15 A
Rated carry
current
Max.
switching
voltage
Max.
switching
current
Max.
switching
power
Failure rate
(reference
value)*
*Note: P level: λ60 = 0.1 x 10-6/operation, reference value
(cosφ = 1)
24 VDC 15 A
15 A10 A7 A
250 VAC
125 VDC
15 A10 A7 A
1,700 VA
360 W
100 mA, 5 VDC 100 mA, 5 VDC 10 mA, 5 VDC
Inductive load
(cosφ=0.4,
L/R=7 ms)
110 VAC 10 A
24 VDC 7 A
1,100 VA
170 W
Resistive load
(cosφ = 1)
110 VAC 10 A
24 VDC 10 A
250 VAC
125 VDC
1,100 VA
240 W
Inductive load
(cosφ=0.4,
L/R=7 ms)
110 VAC 7.5 A
24 VDC 5 A
825 VA
120 W
Resistive load
(cosφ = 1)
110 VAC 5A
24 VDC 5 A
250 VAC
125 VDC
550 VA
120 W
110 VAC 4 A
24 VDC 4A
440 VA
100 W
■ Characteristics
ItemAll except Relays with bifurcated contactsRelays with bifurcated contacts
Contact resistance50 mΩ max.
Operate time25 ms max.
Release time25 ms max.
Max. operating frequencyMechanical:18,000 operations/hr
Insulation resistance100 MΩ min. (at 500 VDC)
Dielectric strength1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
Vibration resistanceDestruction:10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Shock resistance
EnduranceMechanical: AC: 50,000,000 operations min. (at 18,000 operations/hr)
Ambient temperature*Operating:
Ambient humidityOperating: 5% to 85%
WeightSingle- and double-pole: approx. 40 g, three-pole: approx. 50 g, four-pole: approx. 70 g
Note: 1. The values given above are initial values.
2. The upper limit of 40°C for some Relays is because of the relationship between diode junction temperature and the element used.
Electrical:1,800 operations/hr (under rated load)
2,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
Malfunction:10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Destruction:1,000 m/s
Malfunction:200 m/s
DC: 1,00,000,000 operations min. (at 18,000 operations/hr)
Electrical:Single-, three-, and four-pole: 200,000 operations min. (at 1,800 operations/hr
under rated load)
Double-pole: 500,000 operations min. (at 1,800 operations/hr under rated load)
Single- and double-pole standard, bifurcated-contact Relays: –25°C to 55°C (with no icing)
(–25°C to 70°C if carry current is 4 A or less)
All other Relays: –25°C to 40°C (with no icing) (–25°C to 55°C if carry current is 4 A or less)
2
2
Inductive load
(cosφ=0.4,
L/R=7 ms)
A-34General-purpose Relay LY
■ Endurance Under Real Loads (reference only)
LY 1
Rated voltageLoad typeConditionsOperating frequencyElectrical life
100 VACAC motor400 W, 100 VAC single-phase with 35-A in-
AC lamp300 W, 100 VAC with 51-A inrush current,
Capacitor
(2,000 µF)
AC solenoid50 VA with 2.5-A inrush current, 0.25-A
rush current, 7-A current flow
3-A current flow
500 W, 100 VAC with 78-A inrush current,
5-A current flow
24 VDC with 50-A inrush current, 1-A cur-
rent flow
current flow
100 VA with 5-A inrush current, 0.5-A cur-
rent flow
LY 2
Rated voltageLoad typeConditionsOperating frequencyElectrical life
100 VACAC motor200 W, 100 VAC single-phase with 25-A in-
AC lamp300 W, 100 VAC with 51-A inrush current,
Capacitor
(2,000 µF)
AC solenoid50 VA with 2.5-A inrush current, 0.25-A
rush current, 5-A current flow
3-A current flow
24 VDC with 50-A inrush current, 1-A cur-
rent flow
24 VDC with 20-A inrush current, 1-A cur-
rent flow
current flow
100 VA with 5-A inrush current, 0.5-A cur-
rent flow
ON for 10 s, OFF for 50 s50,000 operations
ON for 5 s, OFF for 55 s100,000 operations
25,000 operations
ON for 1 s, OFF for 6 s100,000 operations
ON for 1 s, OFF for 2 s1,500,000 operations
800,000 operations
ON for 10 s, OFF for 50 s200,000 operations
ON for 5 s, OFF for 55 s80,000 operations
ON for 1 s, OFF for 15 s10,000 operations
150,000 operations
ON for 1 s, OFF for 2 s1,000,000 operations
500,000 operations
Relays
Electromechanical
LY 4
Rated voltageLoad typeConditionsOperating frequencyElectrical life
100 VACAC motor200 W, 200 VAC triple-phase with 5-A in-
AC lamp300 W, 100 VAC with 51-A inrush current,
Capacitor
(2,000 µF)
AC solenoid50 VA with 2.5-A inrush current, 0.25-A
rush current, 1-A current flow
750 W, 200 VAC triple-phase with 18-A in-
rush current, 3.5 A current flow
3-A current flow
24 VDC with 50-A inrush current, 1-A cur-
rent flow
24 VDC with 20-A inrush current, 1-A cur-
rent flow
current flow
100 VA with 5-A inrush current, 0.5-A cur-
rent flow
ON for 10 s, OFF for 50 s500,000 operations
70,000 operations
ON for 5 s, OFF for 55 s50,000 operations
ON for 1 s, OFF for 15 s5,000 operations
ON for 1 s, OFF for 2 s200,000 operations
ON for 1 s, OFF for 2 s1,000,000 operations
500,000 operations
General-purpose RelayLYA-35
Loading...
+ 9 hidden pages