Omron MX2, RX, LX User Manual

Page 1
:
inv
rer
o.
I17
01B
Page 2
Drive Programming
2
Table of Contents
1- Introduction ....................................................................................................................................... 5
1-1 Handling of this Instruction Manual ............................................................................................... 5
1-2 Safety Instruction .......................................................................................................................... 5
1-3 Preparation and System configuration .......................................................................................... 6
2- Specifications .................................................................................................................................... 7
3- Drive Programming Editor................................................................................................................ 8
3.1- Saving and loading programs ...................................................................................................... 9
3.2- Editor ............................................................................................................................................ 9
3.3- Toolbar ....................................................................................................................................... 10
3-3-1 Common Commands .......................................................................................................... 10
3-3-2 Commands for the Flowchart Editor .................................................................................... 11
3-3-3 Commands for the Text Editor ............................................................................................ 11
3.4- Shortcut Keys ............................................................................................................................. 12
3.5- Designer Area ............................................................................................................................ 12
3.6- Toolbox window ......................................................................................................................... 15
3.7- Block Parameters window.......................................................................................................... 16
3.8- Properties window ...................................................................................................................... 17
3.9- Output window ........................................................................................................................... 18
3.10- Creating a program with Flowchart Editor ............................................................................... 18
3.11- Creating a program with Text Editor ........................................................................................ 19
3.12- Run a program ......................................................................................................................... 19
3.13- Comments - Text Editor ........................................................................................................... 19
3.14- #Alias definition - Text Editor ................................................................................................... 20
3.15- #Region definition - Text Editor ............................................................................................... 21
3.16- Conversion from Flowchart to Text .......................................................................................... 21
3.17- Conversion from Text to Flowchart .......................................................................................... 21
3.18- Find & Replace function ........................................................................................................... 22
4- Drive Program structure ................................................................................................................. 23
4.1- Tasks .......................................................................................................................................... 23
4.2- Subroutines ................................................................................................................................ 24
5- Drive Programming user variables ................................................................................................ 25
5.1- Initial Data .................................................................................................................................. 25
U(00) to U(31) or User parameters ............................................................................................... 25
UL(00) to UL(07) or Internal User parameters .............................................................................. 25
5.2- Setting Variables ........................................................................................................................ 25
Set-Freq ........................................................................................................................................ 25
ACCEL .......................................................................................................................................... 25
DECEL .......................................................................................................................................... 26
5.3- Inverter Monitor Variables
FM ................................................................................................................................................. 26
Iout ................................................................................................................................................ 26
Dir.................................................................................................................................................. 26
PIB-FB .......................................................................................................................................... 26
F-CNV ........................................................................................................................................... 26
Tmon ............................................................................................................................................. 27
Vout ............................................................................................................................................... 27
Power ............................................................................................................................................ 27
Run-Time ...................................................................................................................................... 27
On-Time ........................................................................................................................................ 27
UMon(0) to UMon(2) ..................................................................................................................... 27
POS .............................................................................................................................................. 28
ERR-CNT ...................................................................................................................................... 28
ERR(1)-ERR(6) ............................................................................................................................. 28
DCV .............................................................................................................................................. 28
STATUS ........................................................................................................................................ 28
5.4- Terminal Variables ..................................................................................................................... 29
Page 3
Drive Programming
3
X(00)-X(11) ................................................................................................................................... 29
Xw ................................................................................................................................................. 29
Y(00)-Y(06) ................................................................................................................................... 29
Yw ................................................................................................................................................. 29
XA(0)-XA(2) .................................................................................................................................. 30
YA(0)-YA(2) .................................................................................................................................. 30
UB(00)-UB(07) .............................................................................................................................. 31
UBw .............................................................................................................................................. 31
TC(0)-TC(7) .................................................................................................................................. 31
TD(0)-TD(7) .................................................................................................................................. 31
TDw ............................................................................................................................................... 31
5.5- Digital input Functions ................................................................................................................ 32
5.6- Digital Output Functions ............................................................................................................. 34
6- Drive Programming Instructions ................................................................................................... 36
6.1- Control Commands .................................................................................................................... 36
Entry .............................................................................................................................................. 36
End ................................................................................................................................................ 36
Call ................................................................................................................................................ 36
Sub ................................................................................................................................................ 36
End Sub ........................................................................................................................................ 36
Go To ............................................................................................................................................ 38
On Trip .......................................................................................................................................... 39
If………. ........................................................................................................................................ 40
Ifs/ Else / End If ............................................................................................................................. 41
Select / Case / End Select ............................................................................................................ 42
For / Next ...................................................................................................................................... 43
While / Wend ................................................................................................................................. 44
Until / Loop .................................................................................................................................... 45
Wait ............................................................................................................................................... 46
6.2- Arithmetic and Logic Commands ............................................................................................... 47
= (Substitution) .............................................................................................................................. 47
Addition ......................................................................................................................................... 47
Subtraction .................................................................................................................................... 48
Multiplication ................................................................................................................................. 48
Division ......................................................................................................................................... 49
Mod ............................................................................................................................................... 49
Abs ................................................................................................................................................ 50
And ................................................................................................................................................ 51
Or. ................................................................................................................................................. 52
XOr ................................................................................................................................................ 53
Not ................................................................................................................................................ 54
Inc ................................................................................................................................................. 55
Dec ................................................................................................................................................ 56
6.3- Input/Output Control Commands ............................................................................................... 57
Var = X(i) ....................................................................................................................................... 57
Var = Xw ....................................................................................................................................... 58
Y(i) = value .................................................................................................................................... 59
Yw = value .................................................................................................................................... 60
func = value .................................................................................................................................. 61
Var = func...................................................................................................................................... 62
Var = UB(i) .................................................................................................................................... 63
Var = UBw ..................................................................................................................................... 64
UB(i) = value ................................................................................................................................. 65
UBw = value .................................................................................................................................. 66
6.4- Timer Control Commands .......................................................................................................... 67
Delay ............................................................................................................................................. 67
Timer Set ...................................................................................................................................... 68
Timer Off ....................................................................................................................................... 69
6.5- Parameter Control Commands .................................................................................................. 70
ChgParam ..................................................................................................................................... 70
MonParam .................................................................................................................................... 71
EepWrt .......................................................................................................................................... 72
Page 4
Drive Programming
4
RtcSet ........................................................................................................................................... 73
6.6- Inverter Control Commands ....................................................................................................... 74
Run-FW ......................................................................................................................................... 74
Run-RV ......................................................................................................................................... 74
Stop ............................................................................................................................................... 74
Set-Freq ........................................................................................................................................ 74
Trip ................................................................................................................................................ 76
Accel ............................................................................................................................................. 77
Decel ............................................................................................................................................. 77
7- Troubleshooting .............................................................................................................................. 78
8- Drive Programming Parameters – General Precautions ............................................................. 79
8.1- Parameters list affected by setting order ................................................................................... 79
8.2- Parameters list affected by Rated Current(%) ........................................................................... 79
8.3- Parameters list affected by PID enabled/disabled ..................................................................... 80
9- Insertion Points ( MX2 & RX ) ......................................................................................................... 81
9.1- ‘Frequency’ before ACC/DEC .................................................................................................... 81
9.2- ‘Frequency’ after ACC/DEC ....................................................................................................... 81
9.3- ‘Deviation’ before PID block ....................................................................................................... 81
Page 5
Drive Programming
5
1-Introduction
This Instruction Manual explains how to use the Drive Programming software for the Omron MX2/RX/LX Series Inverter. Be sure to read this Instruction Manual carefully before using Drive Programming, and keep it on hand for future reference.
1-1 Handling of this Instruction Manual
- The contents of this Instruction Manual are subject to change without prior notice.
- No part of this Instruction Manual may be reproduced in any form without the publisher’s permission.
- If you find any incorrect description, missing description or have a question concerning the contents of this Instruction Manual, please contact the publisher.
1-2 Safety Instruction
Be sure to read this Instruction Manual, Inverter Instruction Manual, and appended documents thoroughly before using Drive Programming and the inverter.
Before creating user programs for the inverter, also refer to the Inverter Instruction Manual and configuration software (CX-Drive) Instruction Manual for the necessary related Knowledge, and ensure you understand and follow all safety information, precautions, and operating and handling instructions for the correct use of the inverter.
Always use the inverter strictly within the range of specifications described in the Inverter Instruction Manual and correctly implement maintenance and inspection to prevent fault from occurring.
When using the inverter together with optional products, also read the manuals for those products. Note that this Instruction Manual and the manual for each optional product to be used should be delivered to the end user of the inverter.
In this instruction manual you can find WARNINGS along the instructions WARNING: Indicates that incorrect handling may cause hazardous situation, which may result in
serious personal injury or death.
Page 6
Drive Programming
6
1-3 Preparation and System configuration
To create user programs with Drive Programming function of the inverter, you must prepare the following devices and software:
(1) MX2, RX, LX inverter (2) Personal computer (PC) (Windows System)
-32-bit PC: Windows XP SP3, Windows Vista (any service pack) and Windows 7.
-64-bit PC: Windows Vista (any service pack) and Windows 7. (3) Optional programming software CX-Drive
· MX2 inverter: CX-Drive version 2.0x or higher.
· RX inverter: CX-Drive 2.3x or higher.
· LX inverter: CX-Drive 2.5x or higher. (4) Optional PC-inverter connection cable. For MX2 it is a USB cable, For RX/LX, the converter cable
USB to RJ-45 is required. Item codes:
- Item code name for MX2: AX-CUSBM002-E
- Item code name for RX/LX (2 option cables):
· 3G3AX-PCACN2, or
· USB CONVERTERCABLE
LX:
· Inverter port: Operator-connection port RJ-45. RX:
· Inverter port: Operator-connection port RJ-45. MX2:
· Inverter port: USB connector. The following figure shows the basic system configuration for programming.
Optional programming
software CX-Drive
Windows personal
computer
Optional PC-Inverter cable
MX2, RX or LX
Inverter
MX2: CX-Drive 2.0x or higher RX: CX-Drive 2.3x or higher LX: CX-Drive 2.5x or higher
- For MX2:
· AX-CUSBM002-E
- For RX/LX
(2 options):
· 3G3AX-PCACN2, or
· USB-CONVERTERCABLE
Install CX-Drive on your Windows personal computer, and connect the personal computer to the inverter (MX2, RX or LX) via the PC-inverter connection cable.
After completing these preparations, you can operate Drive Programming Editor to create a user program and download it to the inverter.
The table below lists the main functions of Drive Programming Editor.
Function Description
Programming Editor
Supports the input, editing, saving, reading, and printing of user programs
Compilation Compile and edit a user program Downloading and uploading
Downloads a user program to the inverter Uploads a user program from the inverter
Page 7
Drive Programming
7
2- Specifications
The table below lists the programming-related specifications of the Drive Programming function.
Item Specification
Language
specification
Programming language Flow Chart and Text language Input device
Windows personal computer (OS: Windows XP-SP3
,
Windows Vista, Windows 7) Max. program size 1024steps (The internal storage capacity of the inverter is 1024 steps or 6 Kilobytes.) Programming support function (programming software)
-Editing (on Windows) / - Display (on Windows)
-Program syntax check (on Windows)
-Downloading, uploading, and full clearance of program
Execution format
Execution by interpreter in an execution cycle of 2ms per instruction (possible subroutine call with nesting in up to 8 layers)
Input/output-related functions
External input
Contact Signal 24v open – collector input (using intelligent input terminals)
Program run signal input
RX: Assign to the PRG terminal / Always run MX2: Assign to the PRG terminal / Always run
Multifunction terminals
RX: Up to 8 terminals (X(00) to X(07)) MX2: Up to 8 terminals (X(00) to X(07))
General-purpose analog input
XA(0): 0 to 10V (O terminal) XA(1): 4 to 20mA (OI terminal) XA(2): 0 to 10V (O2 terminal) (Only RX)
External Output
General-purpose output terminal
RX: Up to 6 terminals (Y(00) to Y(05)) MX2: Up to 3 terminals (Y(00) to Y(02))
General-purpose analog output
YA (0): Assignable to the
EO
terminal (FM terminal for RX) YA (1): Assignable to the AM terminal YA (2): Assignable to the AMI terminal (Only RX)
Reserved Words
Instructions
(1) Program control instructions
-Loop (For) / - Unconditional branching (Goto) / -Time control (Wait)
-Conditional branching (If Then, Ifs Then Else, Select Case, Until, and While)
-Subroutine (call, sub) / - Others (Entry, End, Sub, End Sub, Inc, and Dec)
(2) Arithmetic instructions
-Arithmetic operation (+,-,*,/) / - Remainder (Mod) / -Substitution (=)
-Absolute value (Abs) / - Logic operation (Or, And, Xor, and Not)
(3) Input/Output control
-General-purpose input/output (bit input, word input, bit output, and word output)
- Reading of inverter input terminal. (4) Timer control: - Delay operation / -Timer control (5) Parameter control: - Rewriting of parameters by reselecting code on the operator’s display
Number of variables
User-defined variable U (00) to U (31) (32 variables) Internal user variable UL (00) to UL (07) (8 variables) Set frequency SET-Freq Acceleration time ACCEL Deceleration time DECEL
Monitoring variable
FM, Iout, Dir, PID-FB, F-CNV, Tmon, Vout, Power, RUN-Time, ON­Time, PlsCnt (Only RX), POS, STATUS, DCV, ERR CNT, ERR(1), ERR(2), ERR(3), ERR(4), ERR(5), and ERR(6)
Bit commands
FW, RV, CF1, CF2,CF3,CF4,JG,DB,SET,TCH,FRS,EXT,USP,CS,SFT, AT, RS, STA, STP, F/R, PID, PIDC, UP, DWN, UDC, OPE, SF1, SF2, SF3, SF4, SF5, SF6, SF7, OLR, TL, TRQ1-2, BOK, LAC, PCLR, ADD, F-TM, ATR, KHC, AHD, CP1-3, ORL, ORG, SPD, RS485, HLD, ROK, DISP.
Output Functions
RUN, FA1, FA2, OL, OD, AL, FA3, OTQ, UV, TRQ, RNT, ONT, THM, BRK, BER, ZS, DSE, POK, FA4, FA5, OL2, ODc, OIDc, FBV, NDc, LOG1, LOG2, LOG3, WAC, WAF, FR, OHF, LOC, IRDY, FWR, RVR, MJA, WCO, WCOI, FREF, REF, SETM, EDM.
General-purpose input contact
LX : X(00) to X(06) (7 contacts) RX : X (00) to X (07) (8 contacts) MX2 : X(00) to X(07) (8 contacts)
Extended IO option input contact
LX : X(07) to X(11) (3G3AX-EIO-E expansion card) RX : ----­MX2 : -----
General-purpose output contact
LX : Y(00) to Y(03) (4 contacts) RX :Y(00) to Y(05) (6 contacts) MX2 : Y(00) to Y(02) (3 contacts)
Extended output contact
LX: Y(04) to Y(06) (3G3AX-EIO-E expansion card)
MX2 & RX : ----­Internal user contact UB (00) to UB (7) (8 contacts) Internal timer contact TD (0) to TD (7) (8 counter contacts)
Internal timer counter TC (0) to TC (7) (8 counters) Inverter input/output Specification by code on the remote operator's display
User Monitor UMon(00) to UMon(02) (3 user monitors) User trip Makes the inverter trip (10 trips)
Page 8
Drive Programming
8
3- Drive Programming Editor
Drive Programming Editor allows the user to design drive programs in an intuitive way. CX-Drive provides a way to create drive programs, compile them, transfer them to and from the drive, start and stop their execution, and other related tasks. You can open this function by clicking on Drive Programming in the workspace of a drive which supports it, or selecting Program | Program Editor from the Drive menu, or with the CX-Drive toolbar
button
.
Please create a new CX-Drive File by clicking on the menu File | New. The New Drive window will appear (Image 1). Select the Drive Type and press OK button. Then it will appear on the Workspace (Image 2).
Image 1- New Drive window Image 2- CX-Drive Workspace
Making double-click to the Drive Programming option, the Drive Programming Editor will appear.
Page 9
Drive Programming
9
3-1 Saving and loading programs A drive program is automatically saved when the drive document which contains it is saved.
When a CX-Drive document is opened, the drive program which it contains, if any, is automatically loaded. You can display it by opening the Program Editor.
Alternatively, you can export a drive program, to save it independently of other drive information. To do so, use the Program | Export Program command in the Drive menu. Enter the name of the file to be used. The file will be saved with extension driveprogram.
A drive program can be imported with the Program | Import Program command in the Drive menu. 3-2 Editor The Program Editor is the main window of the Drive Programming function.
The window area consists of a toolbar with common commands, and a designer area where the program is displayed as a text.
Page 10
Drive Programming
10
3-3 Toolbar The Program Editor window contains the following commands:
3-3-1 Common Commands
Commands
Image
Description
New task (Flowchart)
It allows creating a new Flowchart task for the program, up to the maximum number of tasks allowed. Tasks are parts of the program which are executed independently of each other.
New Task (Text)
It allows creating a new Text task for the program, up to the maximum number of tasks allowed. Tasks are parts of the program which are executed independently of each other.
New Sub
routine
(Flowchart)
It allows creating a new Flowchart subroutine. A subroutine is a part of the program which is called from a task.
New Subroutine
(Text)
It allows creating a new Text subroutine. A subroutine is a part of the program which is called from a task.
Rename Current
Task/Subroutine
It allows to rename the current task/subroutine.
Delete Current Tab
It deletes the current Task or Subroutine.
Undo
It reverts the latest change.
Redo
It recovers the most recently undone change.
Transfer to Drive
It compiles the program and, if there are no errors, transfer it to the drive.
Transfer from Drive
It transfers the program from the drive to the Program Editor.
Start
It starts the program in the drive. CX-Drive will first compare it with the program currently being edited, to make sure that they are the same. If they differ, the program will not be started.
Stop
It stops the program in the drive. This action is done regardless of whether the program in the drive is the same that in the program designer.
Compile
It compiles the program which is currently being designed. Compile errors and warnings will be reported as tool tips in the blocks in the flowchart.
Password
It allows you to set, change or remove the program password.
Help
It displays the Drive Programming help.
Page 11
Drive Programming
11
3-3-2 Commands for the Flowchart Editor
Commands
Image
Description
Zoom in
It increases the zoom level.
Zoom out
It decreases the zoom level.
Zoom Reset
It restores the zoom to its initial value.
Select Mode
It allows the user to select one or more elements of the program, by click-and-drag with the mouse cursor. This mode is active by default.
Pan Mode
It allows the user to move the extent of the view. in any direction while keeping the same scale, by click-and-drag.
Horizontal Align Left
It aligns horizontally the left sides of the selected blocks.
Horizontal Align
Middle
It aligns horizontally the middles of the selected blocks.
Horizontal Align
Right
It aligns horizontally the right sides of the currently selected blocks.
Vertical Align Top
It aligns vertically the top sides of the selected blocks.
Vertical Align Middle
It aligns vertically the middles of the selected blocks.
Vertical Align Bottom
It aligns the bottom sides of the selected blocks.
Orientation
It selects a preferred orientation for connecting the blocks.
Auto-arrange
It arranges the elements of the flowchart automatically in the currently selected orientation.
Show contacts
It toggles display/hide of the contacts of the blocks, which are placeholders for the beginning and ending of arrow connections
Show
It allows you to select a display style of the program. (Text only, Icon Only, Icon and Text, or Name, Icon and Arguments).
3-3-3 Commands for the Text Editor
Commands
Image
Description
Find
It finds a text on the program code.
Replace
It replaces a text on the program code.
Increment
Indentation
It increases the indentation of the selected text.
Decrement
Indentation
It decreases the indentation of the selected text.
Format Selected Text
It applies the automatic formatting to the selected text.
Comment Selected
Text
It transforms the selected rows of text to comments.
Uncomment Selected
Text
It uncomments the selected rows of text.
Convert Text to
Flowchart
It converts current text Task/Subroutine to Flowchart
Convert whole
program to Flowchart
It converts whole program to Flowchart.
Convert Flowchart to
Text
It converts current Flowchart Task/Subroutine to text.
Convert whole
Program to Text
It converts whole program to Text.
Page 12
Drive Programming
12
3-4 Shortcut Keys The following Keyboard shortcuts can be applied to the designer area.
· Ctrl + X: Cut
· Ctrl + C: Copy
· Ctrl + V: Paste
· Ctrl + Z: Undo
· Ctrl + Y: Redo
· Ctrl + A: Select All
· Ctrl + F: Find function
· Ctrl + L: Lock
· Ctrl + P: Pin
· Ctrl + Space: Code Snippets
· Tab: Select Next
· Shift + Tab: Select Previous
· Arrow Keys: Move selected element
· Home, End, Page Up, Page Down: Navigate through the graph
· +: Zoom In
· -: Zoom Out
3-5 Designer Area The designer area will display the current design of the program.
This area may have different pages, organized in tabs. Each tab is either a Task or a Subroutine in Flowchart or Text. The designer is created with one default tab, which is a Text Task. When a program is compiled without error, an icon with a circled green arrow highlights the starting point of each Flow chart task.
With text editor, the output window will indicate if the program is compiled successfully.
Page 13
Drive Programming
13
For programs compiled with errors, a red icon with an exclamation mark identifies the erroneous blocks with Flowchart Editor. Placing the mouse on the error icon displays the compile error, which can also be seen in the Error List.
With Text Editor, in the output window will appear the errors of the program. The error will be showed with a red underline.
A Task or Subroutine may be deleted, or renamed, by right-clicking on the tab title.
Right-clicking on an area which is not an element of the flowchart displays a popup menu which allows you to Paste elements that you have previously copied, or to select all the elements.
Right-clicking on a Flowchart block element it shows a popup menu with more options
Page 14
Drive Programming
14
Right-clicking on a selected Text it shows a popup menu with more options
The available menu commands with Flowchart editor are described below.
Bring To Front places the element graphically in front of other elements.
Send To Back places the element graphically in back of other elements.
Pin fixes the element to its current position in the graph. It will not be moved in click-and-drag operations.
• Lock acts like Pin and, besides, sets the properties of the element as read-only.
• Cut deletes the element and saves it in the clipboard, for further pasting.
• Copy saves the element in the clipboard, for further pasting.
• Paste puts the contents previously copied in the clipboard into the design area. Note that after copying elements, you can also paste them to other contexts; for example, as images in a Microsoft Office application
.
The available menu commands with Text editor are described below.
Find looks for the selected text on the program code.
Replace exchange the selected text on the program code.
Cut deletes the element and saves it in the clipboard, for further pasting.
Copy saves the element in the clipboard, for further pasting.
Paste puts the contents previously copied in the clipboard into the design area. Note that after
copying text elements, you can also paste them to other contexts; for example, as text in a Microsoft Office application.
Go to Subroutine jumps to the selected text subroutine
Go to Label jumps to the selected text label.
Undo reverts the latest change.
Redo recovers the most recently undone change.
Help will show the CX-Drive help.
Page 15
Drive Programming
15
3-6 Toolbox window The Toolbox window allows you to add blocks to the Program Designer by drag and drop. It displays
the blocks supported for a particular drive, organized in categories. The Toolbox is displayed when Drive Programming is entered. You can also show or hide it by clicking
on Drive Programming | Toolbox in the View menu. The Toolbox is displayed by default docked at the rightmost side of CX-Drive. You can resize it as
needed to better display its elements. Also, you can toggle its docking by right clicking near the window’s edges.
You can also choose its displays style by right-clicking on it with the mouse. Three styles are available: Large Icons, Small Icons, and List. In any style, placing the mouse cursor on a block will show a short help text for it.
Click on any category title to display the blocks which belong to that category.
Page 16
Drive Programming
16
3-7 Block Parameters window The Block Parameters window allows the user to edit drive program parameters which act as variables
of the program. The parameters are organized in categories. Block parameters is displayed when Drive Programming is entered. You can also show or hide it by clicking on Drive Programming | Block Parameters in the View menu.
Block Parameters is displayed by default docked at the rightmost side of CX-Drive. You can resize it as needed to better display its elements. Also, you can toggle its docking by right clicking near the window’s edges.
To change the value of a block parameter, place the cursor at its row and click on the edition box to the right of its name. Enter the new value. CX-Drive will warn you if the value exceeds the valid range. At the lower part of the window, a help text for the block parameters is displayed.
Page 17
Drive Programming
17
3-8 Properties window The Properties window allows the user to edit the properties of the drive program block which is
currently selected in the Flowchart Program Editor. Properties are displayed when Drive Programming is entered. You can also show or hide it by clicking
on Drive Programming | Properties in the View menu. Properties are displayed by default docked at the rightmost side of CX-Drive. You can resize it as
needed to better display its elements. Also, you can toggle its docking by right clicking near the window’s edges.
To change one block command argument, place the cursor at its row and click on the edition box to the right of its name.
If the block argument has options, a second click of the mouse will unfold the available options for you to select.
If the block argument does not have options, clicking on its current value will enable you to change it by typing a new one. CX-Drive will warn you if the value exceeds the valid range.
If the block argument can have both an option and a custom value, clicking on the unfold sign at the right of the cell will unfold the available options, whereas clicking anywhere in the cell text, you will be able to edit it.
Page 18
Drive Programming
18
3-9 Output window It shows the compilation errors and warnings of the currently edited drive program after it is compiled.
Errors will prevent the program to be correctly compiled. Warnings will allow compilation, but advise customer of abnormal conditions.
· The Error(s) button toggles displaying error in the list.
· The
Warning(s) button toggles displaying warnings in the list.
· The
Message(s) button toggles displaying informative message in the list.
Messages in the list show the following information:
· Date: The date and time when the error was generated.
· Component: Identifies the element with an error.
· Description: The text of the error or warning message. The list is automatically cleared every time a Compile is done.
3-10 Creating a program with Flowchart Editor
Follow the steps described below to create a drive program.
1. Open the Program Editor. The Drive Programming auxiliary windows (Toolbox, Block Parameters, Properties and Error List) will be displayed automatically.
2. Select on the menu “New Tab” New Task (flowchart) or New Subroutine(flowchart).
3. Drag each block of the program from the Toolbox window to the Flowchart Program Editor.
4. After dragging a block, edit its properties by clicking on it and edit the arguments in the Properties window.
5. Connect the blocks accordingly.
6. Edit the drive program variables in the Block Parameters window.
7. You may now compile the program, transfer it to the drive, export it, etc. Alternatively, you can connect to a drive which has a program and transfer it, following the simple
steps described below.
1. Open the Program Editor. The auxiliary Drive Programming windows (Toolbox, Block Parameters and Properties) will be displayed automatically.
2. Click the Transfer from Drive button in the program Editor Toolbar. The program will be transferred from the drive and automatically displayed in the Program Editor designer area.
3. You may now edit the program, compile it, transfer it to the drive, export it, etc.
When a drive program is present, you can also transfer it from and to the drive with the Transfer to Drive and Transfer from Drive buttons of the CX-Drive toolbar. In this case, a message dialog will ask you whether to transfer the parameters, the program or both.
Page 19
Drive Programming
19
3-11 Creating a program with Text Editor
Follow the steps described below to create a drive program:
1. Open the program Editor. The Drive Programming auxiliary windows (Toolbox, Block Parameters, Properties and Error List) will be displayed automatically.
2. The three ways to edit the code are:
a. Manual typing b. Calling code snippets (Ctrl+Space) c. Drag & Drop commands from Toolbox window (like Flowchart Editor)
3. You may now compile the program, transfer it to the drive, export it, etc.
Note 1
: The Text editor is supported from CX-Drive version 2.50.
Note 2: Text and Flowchart Tasks/Subroutines can be used simultaneously within same program.
3-12 Run a program
After transferring the program to the device, you can run the program with the command or setting the next inverter parameters:
· MX2 and RX:
Parameter
Value
Description
A017 – Drive Programming Selection
0: Disabling
Drive Programming program will be stopped.
1: PRG terminal
Drive Programming program will run by digital input. Set terminal to PRG function.
2: Always
Drive Programming program will be always running.
· LX:
Parameter
Value
Description
F025 – Drive Programming function selection
0: Disable
Drive Programming program will be disabled.
1: Enable
Drive Programming program will be Enabled.
F026 – Drive Programming RUN trigger selection
0: TRM(‘PRG’ terminal)
Drive Programming program will run by terminal. Set terminal to PRG
function. 1: PARAM (setting F025=enable)
Drive Programming program will run if
F025 = enable
3-13 Comments – Text Editor
Only it is possible to add comments in a Text editor task or subroutine. To add a comment in a text line press the character “” follow by the comment. The comment will be showed in a green color format.
· Examples
Note
: if you convert a Text task or subroutine to Flowchart, the comments will be lost.
Page 20
Drive Programming
20
3-14 #Alias definition – Text Editor
Only it is possible to define an alias in a Text editor task and before the command ‘entry’. It’s not possible to define an alias in a subroutine.
Alias definitions are user-friendly names given to parameters, variables, commands and numerical constants. There are two kinds of alias definition:
· Local alias
: this alias definition only can be used in the current task and his subroutines, and not in the other tasks and subroutines that the program could have. This is the format for a local alias definition inside a task:
· Examples
· Global alias
: this alias definition can be used in all the tasks and subroutines. This is the
format for a global alias definition:
· Examples
Note 1: The alias will be lost converting a text task/subroutine to flowchart. CX-Drive will show a
message advising about this issue. Note 2: reserved words cannot be used like an alias. A compilation error will appear.
Page 21
Drive Programming
21
3-15 #Region definition – Text Editor
A Region definition can be only defined in a text task or subroutine. It is useful to define code regions to clarify the program source code.
· Examples
3-16 Conversion from Flowchart to Text
There are two options to convert from Flowchart program to text:
Command
Image
Description
Convert Flowchart to text
It converts current Flowchart Task/Subroutine to text.
Convert whole program to text
It converts whole program to text.
3-17 Conversion from Text to Flowchart
There are two option to convert from Text to Flowchart:
Command
Image Description
Convert Text to Flowchart
It converts current Flowchart Task/Subroutine to text.
Convert whole program to
Flowchart
It converts whole program to text.
Page 22
Drive Programming
22
3-18 Find & Replace function
Function only available in text mode. It allows look for an exchange code inside your text program. To use Find function press the
icon or the shortcut keys ‘Ctrl + F’.
To use Replace function press the
icon or the shortcut keys ‘Ctrl+F
Page 23
Drive Programming
23
4- Drive Program structure
The programming language is a Flowchart/Text language. The inverter can process five parallel tasks. The processing is as following diagram.
+ >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> Command Execution >>>>>>>>>>>>>>>>>>>>>>>>>>>> -
<<<<<<< Command Execution <<<<<<
Task 1
Task 2
Task 3
Task 4
Task 5
Elapsed time
line Code line Code line Code line Code line Code 1 Entry Entry Entry Entry Entry 2 [ms] 2
|
top
6
|
top
11
|
top
14
|
top
19
|
top
4 3 Process A 7 Process B 12 Process C 15 Process D 20 Process E 6 4 | 8 | 13
|
Goto top
16 | 21 | 8
5
|
Goto top
9 | 11
|
top
17 | 22 | 10
2
| top
10
| Goto top
12 Process C 18
| Goto top
23 | 12
3 Process A 6
| top
13
| Goto 11
14
| top
24
| Goto top
14 4 | 7 Process B 11
| top
15 Process D 19
| top
16 5
| Goto top
8 | 12 Process C 16 | 20 Process E 18
2
|
top
9 | 13
|
Goto top
17 | 21 | 20
3 Process A 10
| Goto top
11
| top
18
| Goto top
22 | 22
4 | 6
| top
12 Process C 14
| top
23 | 24
5
| Goto top
7 Process B 13
|Goto top
15 Process D 24
| Goto top
26 2
|
top
8 | 11
|
top
16 | 19
|
top
28 3 Process A 9 | 12 Process C 17 | 20 Process E 30
-
4 | 10
|
Goto top
13
|
Goto top
18
|
Goto top
21 | 32 [ms]
Inside each task, subroutines can be associated, but maximum nesting (call inside a subroutine call) is 8 level depth.
4-1 Tasks
When Drive Programming it’s open, an empty task appears by default:
.
With the right mouse click we can Delete Current Task or Rename Current Task.
Every task must begin with Entry and must finish with the End Control Commands.
Flowchart
Text
Page 24
Drive Programming
24
4-2 Subroutines
Subroutines are useful to organize your program into parts of code that you can reuse in other programs or in the same program. For insert a subroutine press the button
or and a new
subroutine will appear. Like on Tasks, you can delete or rename a subroutine. Every subroutine must begin with the Sub block, and end with the EndSub Control Command.
Flowchart
Text
The subroutine is executed via the call command with the subroutine name.
Flowchart
Text
It is only possible to call a subroutine that is associated with the task. To be used with other task, a copy of the subroutine is necessary on the task.
Page 25
Drive Programming
25
5- Drive Programming user variables 5-1 Initial Data U(00) to U(31) or User parameters
U(00) to
U(31)
Description Range of values Default Unit Data size Attribute
User variable 0 to 65535
Data
stored in P100 to P131
-
Unsigned
1-word
R/W
User variables are the general-purpose functions that can be used as unsigned 1-word. The data written from a drive program to the user-defined variables is not stored in the inverter’s EEPROM. The variables will restore the initial settings when the inverter power is turned off. The user-defined variables correspond to inverter parameters “P100” to “P131”. You can also change the settings of user-defined variables from the digital operator. The changes made from the digital operator will be stored in EEPROM. This is also possible to emulate from drive programming by using the EepWrt command.
The variables P129 to P131 (U(29) to U(31)) are saved at power down of the inverter automatically. This function may not work under heavy load (motor output current) or too small inverter (low capacity in DC bus). In case of trouble it is recommended to disable the inverter output to preserve the energy in the capacitors.
UL(00) to UL(07) or Internal User parameters.
UL(00)
UL(07)
Description Range of values Default Unit Data size Attribute
Internal user variable
31
2
to
1
231−
0 -
Signed 2-word
R/W
Internal user variables are the general-purpose functions that can be used as unsigned 2-word variables, for example, to temporarily store arithmetic operation results. The initial values can be set via the initial program data.
5-2 Setting Variables
Set-Freq
Description Range of values Default Unit Data size Attribute Output frequency setting
0 to 40000 0
0.01 Hz
Unsigned
1-word
R/W
When A001=7 (Freq. ref. from Drive Programming), it becomes the frequency set point of the inverter. Always reflects the reading of parameter F001, regardless the setting of A001. This variable is not stored in the inverter EEPROM. It will be restored to initial setting after power cycle. When the inverter receives an operation command (FW=1 or RV=1), it accelerates the motor up to the frequency that was set last.
ACCEL
Description Range of values Default Unit Data size Attribute Acceleration time setting
1 to 360000 Note 1
0.01 sec
Unsigned
2-word
R/W
This variable can be used to read and write the motor acceleration time in the inverter. It is enabled only when the setting of accel/decel time input selection (P031) is “03” (PRG). (Please note that it does not correspond to the setting of inverter parameter “F002”). The data written to this variable is not stored in the inverter’s EEPROM. It restores initial value after power cycle.
Note 1: By default (when the inverter power is turned on), the acceleration time follows the setting of the inverter parameter “F002”, “F202”, or “F302”. For details, refer to the Inverter Instruction Manual. Note 2: When a program writes a value to this variable, the value is reflected in the inverter in a 40-ms cycle, which conforms to the standard inverter specifications.
Page 26
Drive Programming
26
DECEL
Description Range of values Default Unit Data size Attribute Deceleration time setting
1 to 360000 Note 1
0.01 sec
Unsigned
2-word
R/W
This variable can be used to read and write the motor deceleration time in the inverter. The deceleration time setting using this variable is enabled only when the setting of accel/decel time input selection (P031) is “03” (PRG). (The setting of this variable does not correspond to the setting of inverter parameter “F003”). The data written to this variable is not stored in the inverter’s EEPROM. This variable will restore the initial setting when the inverter power is turned off.
Note 1: By default (when the inverter power is turned on), the deceleration time follows the deceleration (1) time setting “F003”, “F203” or “F303”. For details, refer to the Inverter Instruction Manual. Note 2: When a program writes a value to this variable, the value is reflected in the inverter in a 40-ms cycle, which conforms to the standard inverter specifications.
5-3 Inverter Monitor Variables (This units does not always corresponds with the display units)
FM
Description Range of values Default Unit Data size Attribute
(d001)
Output frequency monitor
0 to 40000 -
0.01
Hz
Unsigned
1-word
R
The data monitored with this variable corresponds to the data monitored by the output frequency monitor (d001). This variable is read-only.
Iout
Description Range of values Default Unit Data size Attribute
(d002) Output current monitor 0 to 9999 -
0.01% Unsigned
1-word
R
The data monitored with this variable corresponds to the data monitored by the output current monitor (d002). The monitored data indicates the ratio of present output current to rated current of the inverter. This variable is read-only. For details, refer to the Inverter Instruction Manual.
Dir
Description Range of values Default Unit Data size Attribute
(d003)
Rotation direction monitor
0: Stop 1: Normal rotation 2:Reverse rotation
- -
Unsigned
1-word
R
The data monitored with this variable corresponds to the data monitored by the rotation direction monitor (d003). This variable is read-only.
PID-FB
Description Range of values Default Unit Data size Attribute
(d004)
Process variable (PV), PID feedback monitoring
0 to 9990000 0
0.01% Unsigned
2-word
R
The data monitored with this variable corresponds to the data monitored by the process variable (PV), PID feedback monitor (d004). This variable is read-only.
F-CNV
Description Range of values Default Unit Data size Attribute
(d007)
Scaled output frequency monitor
0 to 3996000 - 0.01
Unsigned
2-word
R
The data monitored with this variable corresponds to the data monitored by the scaled output frequency monitor (d007). This variable is read-only.
Page 27
Drive Programming
27
T
mon
Description Range of values Default Unit Data size Attribute
(d012) Torque monitor -200 to 200 - %
Unsigned
1-word
R
The data monitored with this variable corresponds to the data monitored by the torque monitor (d012). This variable is read-only.
Vout
Description Range of values Default Unit Data size Attribute
(d013)
Output Voltage monitor
0 to 6000 - 0.1v
Unsigned
1-word
R
The data monitored with this variable corresponds to the data monitored by the output voltage monitor function (d013). This variable is read only.
Power
Description Range of values Default Unit Data size Attribute
(d014) Power monitor 0 to 9999 -
0.1 Kw
Unsigned
1-word
R
The data monitored whit this variable corresponds to the data monitored by the power monitor (d014). This variable is read only.
RUN
-
Time
Description Range of values Default Unit Data size Attribute
(d016) Run Time monitor 0 to 999999 - Hour
Unsigned
2-word
R
The data monitored with this variable corresponds to the data monitored by the cumulative operation RUN time monitor (d016). This variable is read only.
On-Time
Description Range of values Default Unit Data size Attribute
(d017)
Power-on time monitor
0 to 999999 - Hour
Unsigned
2-word
R
The data monitored with this variable corresponds to the data monitored by the cumulative power-on time monitor (d017). This variable is read-only.
UMon(0)
to
Umon(2)
Description Range of values Default Unit Data size Attribute
(d025
to
d027)
User Parameter monitor 0 to 2
- 2
31
to 2
31
-1 0 -
Signed 2-word
R/W
The data monitored with these variables corresponds to the data monitored on d025, d026 and d027. These are monitors available for the user Drive Programming application
Page 28
Drive Programming
28
POS
Description Range of values Default Unit Data size Attribute
(d030)
Current Position monitor
- (2
28
- 1) to 2
28
- 1
[- (2
30
- 1) to 2
30
- 1]
- 1
Signed
2-word
R
The data referenced with this variable corresponds to the data monitored by the current position monitor (d030). With RX when “03” (high-resolution absolute position control) has been selected for control pulse setting (P012), the range in brackets “[]” applies.
ERR
-
CNT
Description Range of values Default Unit Data size Attribute
(d080) Trip counter monitor 0 to 65535 -
Nº of times
Unsigned
1-word
R
The data monitored with this variable corresponds to the data monitored by the trip counter monitor (d080).
ERR(1)
-
ERR(6)
Description Range of values Default Unit Data size Attribute
(d081-
d086)
Trip monitor 1 to 6
0 to 127 - -
Unsigned
1-word
R
The data monitored with these variables correspond to the data monitored by trip monitors 1 to 6 (d081 to d086).
DCV
Description Range of values Default Unit Data size Attribute
(d102) DC voltage monitor 0 to 9999 -
0.1
Vdc
Unsigned
1-word
R
The data referenced with this variable corresponds to the data monitored by the DC voltage monitor (d102).
STATUS
Description Range of values Default Unit Data size Attribute
Inverter status monitor - - -
Unsigned
1-word
R
This variable can be used to reference inverter status information. The information is reflected with the following bit weights:
Bit 9
to 15
Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserve
Under
voltage
Reset
Over voltage suppression
Over current
suppression
Overload
suppression
Retry Reverse Trip Run
Page 29
Drive Programming
29
5-4 Terminal Variables Input/Output Control Instructions
X(00)
- X(11)
Description Range of Values Data Size Attribute
Input terminal 0 to 11
0: Off 1: On
bit R
See table below for each inverter function number:
Input
Inverter function number
MX2 RX LX
X(00) – MI1 56 56 49 X(01) – MI2 57 57 50 X(02) – MI3 58 58 51 X(03) – MI4 59 59 52 X(04) – MI5 60 60 53 X(05) – MI6 61 61 54 X(06) – MI7 62 62 55 X(07) – MI8 63 63 56
X(08) – MI9 -- -- 57 X(09) – MI10 -- -- 58 X(10) – MI11 -- -- 59 X(11) – MI12 -- -- 60
Xw
Description Range of Values Data Size Attribute
Input terminal (word) 0 to 65535
Unsigned
1-word
R
Instruction to access contact inputs by word. Each bit reflects one of the inputs.
Y(00)
- Y(06)
Description Range of Values Data Size Attribute
Output terminal 0 to 6
0: Off 1: On
bit R/W
See table below for each inverter function number:
Output
Inverter function number
MX2 RX LX
Y(00) – MO1 44 44 35 Y(01) – MO2 45 45 36 Y(02) – MO3 46 46 37 Y(03) – MO4 -- 47 38 Y(04) – MO5 -- 48 39 Y(05) – MO6 -- 49 40 Y(06) – MO7 -- -- 41
Yw
Description Range of Values Data Size Attribute
Output terminal (word) 0 to 65535
Unsigned
1-word
R/W
This variable can be used to change the digital output terminals in units of word. Each output is one bit.
Page 30
Drive Programming
30
XA(0)
XA(2)
Description Range of Values Data Size Attribute
XA(0)
General-purpose analog input (O terminal)
0 to 10000
Unsigned
1- word (0.01%)
R
XA(1)
General-
purpose analog input
(OI terminal)
XA(2)
General-purpose analog
input
(O2 terminal) only for RX and LX
These variables can be used to monitor the analog input to the O and OI and O2 terminals. Terminals [O]-[L], [OI]-[L], [O2]-[L]. Associated parameters (A011 to A015, A101 to A105, A111 to A114). XA(2) is only available for Rx and LX.
YA(0)
YA(2)
Description Range of Values Data Size Attribute
YA(0)
General-
purpose analog output
(EO terminal for MX2) (FM terminal for RX and LX)
0 to 10000
Unsigned
1-word
(0.01%)
R/W
YA(1)
General-
purpose analog output
(AM terminal)
YA(2)
General-
purpose analog output
(AMI terminal) only for RX and LX
With this variables we can monitor the analog outputs (any multifunction assigned to them), or write analog output if YA(0) to YA(2) are assigned to analog multifunction parameters (C027, C028 and C029). Value is reflected as a data range from 0% to 100.00%. YA(2) is only available for RX and LX.
Page 31
Drive Programming
31
UB(00)
– UB(07)
Description Range of Values Data Size Attribute
Internal user contact (bit access)
0: Off 1: On
bit R/W
These variables can be used as bit variable for the user.
UBw
Description Range of Values Data Size Attribute
Internal user contact (word access) 0 to 255
Unsigned
1-word
R/W
The bit variables reflected as single word.
TC(0)
- TC(7)
Description Range of Values Data Size Attribute Timer counters (0 to 7) (Unit: 10ms)
0 to
1
231−
Unsigned
2-word
R/W
The timer counters “TC(0)” to “TC(7)” operate as 31-bit-free-running timer counters. They start with the user program startup and are incremented in a 10-ms cycle.
When a timer-start instruction (timer set) or delay operation instruction (delay on or delay off) is executed, the timer counter corresponding to the instruction operates as the counter for output to a specified timer contact. In this case, the counter is cleared to zero when the instruction is executed, start counting, and then stops counting upon reaching the specified count. When a timer-stop instruction (timer off) is executed, the timer counter corresponding to the instruction is cleared to zero and operates as a 31-bi-free-running timer counter that is incremented in a 10-ms cycle.
TD(0)
- TD(7)
Description Range of Values Unit Attribute Timer contact output 0 – 7 (bit access)
0: Off 1: On
Unsigned
1-word
R
The data in timer contact output variables “TD(0)” to “TD(7)” change only when these variables are specified in the timer-start instruction (timer set) or delay operation instruction (delay on or delay off). A timer contact output variable is set to “0”(off) when the counter corresponding to the contact output is cleared to zero, the variable is set to “1”(on) when the counter stops counting (the timing action selected finish). While a timer counter variable “TC(k)” is being used for a free-running timer counter, timer contact output variable “TD(k)” corresponding to the timer counter variable retains its status.
TDw
Description Range of Values Unit Attribute
Timer contact output (word access) 0 to 255
Unsigned
1-word
R
It access to the timer counter outputs as word.
Page 32
Drive Programming
32
5-5 Digital input Functions
These variables correspond to the settings available for the digital multifunction input terminals. Setting the variable to 1 will simulate the function as if the terminal was closed in a digital input. It is interesting to note that the multifunction does not need to be configured in order to use the function.
E.g. FW := 1 will generate a RUN Forward command (as used in some examples). Please refer to the inverter user manual for details about the individual functions. Values: · 0: Off
· 1: On
Function
Description
MX2 RX LX Usage
Comment
FW Forward x x R/W C001-C009 = 00 RV Reverse x R/W C001-C009 = 01
CF1-CF4 Multi-speed 1-4 x R/W
C001-C009 = 02-
05 JG Jogging x R/W C001-C009 = 06 DB External Brake x R/W C001-C009 = 07 SET Second control R/W C001-C009 = 08 2CH 2nd acceleration/deceleration time x R/W C001-C009 = 09 FRS Free run R/W C001-C009 = 11 EXT External trip R/W C001-C009 = 12 USP Unattended start protection x R/W C001-C009 = 13 CS Change from commercial power x R/W C001-C009 = 14 SFT Software lock R/W C001-C009 = 15 AT Change of analog input x R/W C001-C009 = 16 SET3 3rd control x x R/W C001-C009 = 17 RS System reset R/W C001-C009 = 18 STA Start of 3 wires x R/W C001-C009 = 20 STP Stop of 3 wires x R/W C001-C009 = 21 F/R Forward/Reverse of 3 wires x R/W C001-C009 = 22 PID Switch PID x R/W C001-C009 = 23 PIDC Reset of PID integration x R/W C001-C009 = 24 CAS Control gain switching x x R/W C001-C009 = 26 UP Increasing speed from remote x R/W C001-C009 = 27 DWN Decreasing speed from remote x R/W C001-C009 = 28 UDC Clear data from remote operation x R/W C001-C009 = 29 OPE Change to operator x R/W C001-C009 = 31
SF1-SF7 Multi-speed bit 1-7 x R/W
C001-C009 = 32-
38 OLR Overload protection switch x R/W C001-C009 = 39 TL Torque Limit Enable x R/W C001-C009 = 40
TRQ1-2 Torque Limit Selection 1-2 x R/W
C001-C009 = 41-
42 PPI P/PI switching x x R/W C001-C009 = 43 BOK Brake Confirmation x R/W C001-C009 = 44 ORT Orientation x x R/W C001-C009 = 45 LAC LAD Cancel x R/W C001-C009 = 46 PCLR Clear Position Deviation x R/W C001-C009 = 47
STAT
Pulse train position command input permission
x x R/W C001-C009 = 48
ADD Add Setting Frequency x R/W C001-C009 = 50 F-TM Forced Terminal Block x R/W C001-C009 = 51 ATR Torque reference input permission x R/W C001-C009 = 52 KHC Integrated power clear x R/W C001-C009 = 53 SON Servo ON x x R/W C001-C009 = 54 FOC Preliminary excitation x x R/W C001-C009 = 55 X(00) – X(07)
Drive Programming (MI1-MI8)
x R/W
C001-C009 = 56-
63 AHD Analog command on hold x R/W C001-C009 = 65
CP1-3 Position command selection 1-3 x R/W
C001-C009 = 66-
68 ORL Origin return limit signal x R/W C001-C009 = 69 ORG Origin return start signal x R/W C001-C009 = 70
Page 33
Drive Programming
33
FOT Forward driving stop x x R/W C001-C009 = 71 ROT Reverse driving stop x x R/W C001-C009 = 72 SPD Speed/Position switching x R/W C001-C009 = 73 PCNT Pulse counter x x R/W C001-C009 = 74 PCC Pulse counter clear x x R/W C001-C009 = 75 GS1 GS1 input x x R/W C001-C009 = 77
Function
Description
MX2 RX LX Usage
Comment
GS2 GS2 input x x R/W C001-C009 = 78 RS485 Inverter communication start terminal x x R/W C001-C009 = 81 PRG Executing Drive Program x x R/W C001-C009 = 82
HLD
HOLD Acceleration / deceleration stopping
x x R/W C001-C009 = 83
ROK Operation OK signal x x R/W C001-C009 = 84 DISP Display limitation terminal x x R/W C001-C009 = 86 UP Upward RUN x x R/W C001-C009 = 00 DOWN Downward RUN x x R/W C001-C009 = 01 SPD1 Multi-speed 1 setting x x R/W C001-C009 = 02 SPD2 Multi-speed 2 setting x x R/W C001-C009 = 03 SPD3 Multi-speed 3 setting x x R/W C001-C009 = 04 OLR Change OL-level x x R/W C001-C009 = 32 TL Torque Limit enable x x R/W C001-C009 = 33 TRQ1 Change Torque Limit 1 x x R/W C001-C009 = 34 TRQ2 Change Torque Limit 2 x x R/W C001-C009 = 35 PCLR Clear the current position x x R/W C001-C009 = 40 KHC Kwh clear x x R/W C001-C009 = 46
X(00)-X(11) Drive Programming x x R/W
C001-C009 =49-
60 EMP Em-Power Operation x x R/W C001-C009 = 61 INS1 Inspection 1 x x R/W C001-C009 = 62 INS2 Inspection 2 x x R/W C001-C009 = 63 COK Contactor check signal x x R/W C001-C009 = 64 BOK Brake check signal x x R/W C001-C009 = 65
FP1-FP6 Floor position 1 to 6 x x R/W
C001-C009 = 66-
71 PAL Auto learning data latch trigger x x R/W C001-C009 = 72 TCL Torque bias latch trigger x x R/W C001-C009 = 73 LVS Leveling signal x x R/W C001-C009 = 74 NFS Near floor signal x x R/W C001-C009 = 75 PRG Program run x x R/W C001-C009 = 76 CMC Control Mode change x x R/W C001-C009 = 77
Note:The LX inverter functions are available for the digital multifunction input terminals P140-P144 (Multi-Input [Ex.IN1-5] 3G3AX-EIO-E: LX extra I/O board)
Page 34
Drive Programming
34
5-6 Digital Output Functions
These variables correspond to the settings available for the digital multifunction output terminals. The variable can read and used as it would be for an external device connected to the digital output configured for the function. It is interesting to note that digital outputs are not required to be assigned in order to use the function within the program (in other words, no waste of digital outputs required).
Fun
ction
Description
MX2 RX LX Usage
Comment
RUN Running R C021 - C026 = 00 FA1 Reaching constant speed R C021 - C026 = 01 FA2 Greater than setting frequency R C021 - C026 = 02 OL Overload preannounce R C021 - C026 = 03 OD PID deviation overrate x R C021 - C026 = 04 AL Trip signal R C021 - C026 = 05 FA3 Only the setting frequency R C021 - C026 = 06 OTQ Over torque/under torque R C021 - C026 = 07 IP Signal during m. power interruption x R C021 - C026 = 08 UV Under voltage signal R C021 - C026 = 09 TRQ Torque limitation signal R C021 - C026 = 10 RNT RUN time over R C021 - C026 = 11 ONT ON time over R C021 - C026 = 12 THM Thermal warning R C021 - C026 = 13 ZS 0 Hz detection signal x x R C021 - C026 = 14 POK Positioning complete x x R C021 - C026 = 16 FA4 Set frequency overreached 2 x x R C021 - C026 = 17 FA5 Set frequency reached 2 x x R C021 - C026 = 18 BRK Brake open x R C021 - C026 = 19 BER Brake error x R C021 - C026 = 20 ZS Zero speed signal x R C021 - C026 = 21 DSE Speed deviation overrate x R C021 - C026 = 22 POK Positioning operation complete x R C021 - C026 = 23 FA4 Greater than setting frequency 2 x R C021 - C026 = 24 FA5 Only the setting frequency 2 x R C021 - C026 = 25 OL2 Overload preannounce 2 x R C021 - C026 = 26 ODc Analog O break detection x R C021 - C026 = 27 OIDc Analog OI break detection x R C021 - C026 = 28 O2Dc Analog 2 disconnection detection x x R C021 - C026 = 29 WAC Capacitor life warning x X R C021 - C026 = 30 FBV PID feedback comparison x R C021 - C026 = 31 NDc Communication break detection x R C021 - C026 = 32 LOG1 Result of logic operation 1 x R C021 - C026 = 33 LOG 2 Result of logic operation 2 x R C021 - C026 = 34 LOG 3 Result of logic operation 3 x R C021 - C026 = 35 LOG 4 Result of logic operation 4 x x R C021 - C026 = 36 LOG 5 Result of logic operation 5 x x R C021 - C026 = 37 LOG 6 Result of logic operation 6 x x R C021 - C026 = 38 WAC Condenser life-span preannounce x R C021 - C026 = 39 WAF Fan life-span preannounce x R C021 - C026 = 40 FR Start contact signal x R C021 - C026 = 41 OHF Cooling fan over heat preannounce x R C021 - C026 = 42 LOC Low electricity signal x R C021 - C026 = 43 Y(00) Drive Programming (MO1) x R C021 - C026 = 44 Y(01) Drive Programming (MO2) x R C021 - C026 = 45 Y(02) Drive Programming (MO3) x R C021 - C026 = 46 Y(03) Drive Programming (MO4) x x R C021 - C026 = 47 Y(04) Drive Programming (MO5) x x R C021 - C026 = 48 Y(05) Drive Programming (MO6) x x R C021 - C026 = 49 IRDY Operation setup complete x R C021 - C026 = 50 FWR Forward running signal x R C021 - C026 = 51 RVR Reverse running signal x R C021 - C026 = 52 MJA Serious failure signal x R C021 - C026 = 53 WCO Window comparator O x R C021 - C026 = 54 WCOI Window comparator OI x R C021 - C026 = 55 WCO2 Window comparator O2 x x R C021 - C026 = 56 MPS Magnet pole position search x x R C021 - C026 = 57
Page 35
Drive Programming
35
Function
Description
MX2 RX LX Usage
Comment
FREF Command frequency sel. mode x x R C021 - C026 = 58 REF Command operation mode x x R C021 - C026 = 59 SETM Setting motor x x R C021 - C026 = 60 EDM STO operation monitor signal x x R C021 - C026 = 62 IRDY Inverter ready x x R C021 - C026 = 44 FWR Forward rotation x x R C021 - C026 = 45 RVR Reverse rotation x x R C021 - C026 = 46 MJA Major failure X x R C021 - C026 = 47 OL2 Overload advance signal 2 x x R C021 - C026 = 19 TH-C Thermal warning (CTL) x x R C021 - C026 = 20 NDc Network disconnection x x R C021 - C026 = 23 WAF Cooling-fan speed drop x x R C021 - C026 = 31 FR Starting contact signal x x R C021 - C026 = 32 OHF Heat sink overheat warning x x R C021 - C026 = 33 LOC Low-current indication signal x x R C021 - C026 = 34 Y(00) Drive Programming (MO1) x x R C021 - C026 = 35 Y(01) Drive Programming (MO2) x x R C021 - C026 = 36 Y(02) Drive Programming (MO3) x x R C021 - C026 = 37 Y(03) Drive Programming (MO4) x x R C021 - C026 = 38 Y(04) Drive Programming (MO5) x x R C021 - C026 = 39 Y(05) Drive Programming (MO6) x x R C021 - C026 = 40 Y(06) Drive Programming (MO7) x x R C021 - C026 = 41 CON Contactor control signal x x R C021 - C026 = 51 BRK Brake Control signal x x R C021 - C026 = 52 UPS UPS protect direction search status x x R C021 - C026 = 54 UPD UPS protect direction x x R C021 - C026 = 55 GMON Gate suppress monitor x x R C021 - C026 = 56 SEQ SEQ error x x R C021 - C026 = 58
Note:The LX inverter functions are available for the digital multifunction output terminals P145-P147 (Multi-Output [Ex.OUT1-3] 3G3AX-EIO-E: LX extra I/O board)
Page 36
Drive Programming
36
6- Drive Programming Instructions 6-1 Control Commands
Entry
Command
Description
Arguments
It indicates the beginning of the task. ---
Format
---
Note
: It is compulsory to have Entry at the begging of each task.
End
Command
Description
Arguments
It indicates the end of the task. ---
Format
---
Note
: It is compulsory to have End at the end of each task.
Call Command
Description
Arguments
It jumps to a subroutine
• Subroutine: Subroutines are identified by a name or alias defined by the user.
Format
call <subroutine>
Note
: After the execution of the subroutine ends, the next instruction line after the call is executed.
Sub Command
Description
Arguments
It indicates the beginning of the subroutine.
---
Fo
rmat
--- Note
: It is compulsory to have
Sub
at the beginning of each subroutine.
End Sub
Command
Description
Arguments
It indicates the end of a subroutine. ---
Format
---
Note
: It is compulsory to have
End Sub
at the end of each subroutine.
Page 37
Drive Programming
37
Example
Flowchart
Main
Main:RunFW
Main:RunRV
Text
Main Main:RunFW Main:RunRV
A forward and reverse run at 60Hz is repeated continuously between two limits X(01) and X(02).
Page 38
Drive Programming
38
Go To
Command
Description
Arguments
Use this instruction to branch processing unconditionally to the step labeled with label name.
• Label: A name that is used to identify a particular function block in the task.
Format
GoTo <label>
Note
: The instruction must also be connected to the next program block you want to be executed. This
is necessary to make clear the flow of the program.
Example
Flowchart
Text
Change parameter P100 in order to test the GoTo function with this sample. When P100=1, P101 starts counting. When P100<>1 stops counting.
Page 39
Drive Programming
39
On Trip
Command
Description
Arguments
This instruction makes conditional branching in case a trip in the inverter occurs.
• Label: A name that is used to identify a particular function block in the task.
Format
On Trip goto <label>
Note
: The
On Trip
instruction works as a trigger arming. The instruction is executed once, if any trip
occurs the program jumps immediately to the designated label, then the On trip trigger is disarmed.
Example
Flowchart
Text
When the digital input is set to ON value, then P100 parameter is incrementing every second. If a trip is generated (like by external trip input) then P103 increments count. And then goes to the beginning of the task.
Page 40
Drive Programming
40
If
Command
Description
Arguments
Jump to a label when a condition is satisfied.
Condition
: A comparison between two variables or constant with the format<Left hand value><Comparison><Right Hand Value>
-Left hand value: any variable or constant(range -128 to 127)
-Comparison
: =, <, >, <=, >=, <>
-Right hand value: any variable or constant(range -128 to 127)
Label: A name that is used to identify a particular function block in the task.
Format
If <condition> GoTo <label>
Example
Flowchart
Text
Change parameter P100 in order to test the GoTo function with this sample. When P100 = 1, P101 starts counting. When P100<>1 stops counting.
Page 41
Drive Programming
41
Ifs/ Else / End If
Command
Description
Arguments
This instruction executes different portion of code based on a condition. When the condition is met, this instruction executes <instruction set 1>. When the condition is not met, this instruction executes <instruction set 2>.
Condition
: A comparison between two variables or constant with the format <Left hand Value><Comparison><Right hand Value>
-Left hand value: any variable or constant (range -128 to 127)
-Comparison
: =, <, >, <=, >=, <>
-Right hand value: any variable or constant (range -128 to 127)
Instruction set 1: One or more instructions, until Else instruction. It can contain nested instructions (up to 8 levels)
Instruction set 2: One or more instructions, until End If instruction. It can contain nested instructions (up to 8 levels)
Format
Ifs <condition> Then <instruction set 1> Else <instruction set 2> Endif
Example
Flowchart
Text
The example changes the value of P103 based on the value of parameter P100 and P101. If P100 is bigger than P101 then P103=10. If not P103=20.
Page 42
Drive Programming
42
Select / Case / End Select
Command
Description
Arguments
This instruction allows multiple program sections to be executed depending on a variable value. For a particular CASE section it Executes <instruction set n> when <conditional variable> matches <conditional value n> If <conditional variable> doesn’t match any of the CASE section the <instruction set if no other> (Case Else) is executed. This instruction is convenient when multiple choices have to be done from parameter value. It makes simple some if/then structures. This instruction is recommended to organize program by using subroutine calls as instruction set.
Conditional variable: the instruction select variable.
Conditional value x: variable value.
Instruction set x: One or more instructions, until next case or end select. It can contain nested instructions (up to 8 levels).
Format
Select <conditional variable> Case <conditional value 1> <instruction set 1> Case <conditional value 2> <instruction set 2> … Case Else <instruction set if no other> End select
Example
Flowchart
Text
The P101 parameter is set to 100, 200, 300 or 500 depending on the value of the P100 parameter (1, 2, 3 or any other, respectively).
Page 43
Drive Programming
43
For / Next
Command
Description
Arguments
Executes <instruction set> repeatedly until <variable> reaches <end value>. Each cycle <incremental value> is added to <variable>.
Variable
: any variable
Start value: Initial value, it is the value assigned to the variable in the first loop. (Constant value from -128 to 127)
End value: Value that exits the loop. (Constant value from -128 to 127)
Incremental value: The variable will be incremented by this value each loop. (Constant value from -128 to 127)
Instruction set: One or more instructions, until Next instruction. It can contain nested instructions (up to 8 levels)
Format
For <variable><start value><end value><incremental value> <instruction set> Next
Example
Flowchart
Text
This example make the variable U(00) P(100) count from 1 to 8 each second.
Page 44
Drive Programming
44
While / Wend
Command
Descri
ption
Arguments
Executes <instruction set> while a condition is met.
Condition
: A comparison between two variables or constants with the format <Left hand value><Comparison><Right Hand Value>
- Left hand value: any variable or constant (range -128 to 127).
- Comparison
: =, <, >, <=, >=, <>
- Right hand value: any variable or constant (range -128 to 127).
Instruction set: One or more instructions, until Wend instruction. It can contain nested instructions (up to 8 levels)
Format
While <condition> <instruction set> Wend
Example
Flowchart
Text
The code will increment P101 parameter every second while the digital input X(00) is closed (while­wend loop). If it is open, P101 is not increased (GoTo-label loop loop; the while – wend portion is
not executed). Digital input has to be configured in the multifunction input.
Page 45
Drive Programming
45
Until / Loop
Command
Desc
ription
Arguments
Executes <instruction set> until a <condition> is met.
Condition
: A comparison between two variables or constants with the format <Left hand value><Comparison><Right Hand Value>
-Left hand value: any variable or constant (range -128 to 127)
-Comparison: =,<,>,<=,>=,<>
-Right hand value: any variable or constant (range -128 to 127)
Instruction set: One or more instructions, until Loop instruction. It can contain nested instructions (up to 8 levels)
Format
Until <condition> <instruction set> Loop
Example
Flowchart
Text
This code will increment while the digital input is closed. If it is open, then it will stay in the until-loop portion. The check of the input is every second because of this structure. Digital input has to be configured in the multifunction input.
Page 46
Drive Programming
46
Wait
Command
Description
Arguments
This instruction makes the program wait for a number of seconds or until a condition is met.
Value
: any variable or constant (time in
10 x ms).
Condition: A comparison between two variables or constant with the format <Left hand value><Comparison><Right Hand Value>
-Wait Time value from 0 to 32767 * 10ms
-Left hand value: any variable or constant (range -128 to 127)
-Comparison: =, <, >, <=, >=, <>.
-Right hand value: any variable or constant (range -128 to 127)
Format
Wait <value> or <condition> NOTE: WaitTime is not accurate way to measure time, please use internal timers or external Real Time Clock in LCD for accurate time measurement.
Example Wait Time: wait during a time period.
Flowchart
Text
The P100 parameter is increased every second.
Example Wait condition: wait for condition.
Flowchart
Text
The program waits until the digital input is closed (you need to set one of the multifunction inputs for this), and then P100 parameter is increased.
Page 47
Drive Programming
47
6-2 Arithmetic and Logic Commands
= (Substitution)
Command
Des
cription
Arguments
Assigns <value> to <result>.
Result: any variable.
Value: any variable or constant (range -2147483648 to 2147483647).
Format
<result> = <value>
Warning
: Drive programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P100 and P101 parameters are set to 200.
+ (Addition)
Command
Description
Arguments
Adds <value 1> and <value 2>.
Result
: any variable.
Value 1: any variable or constant (range
-128 to 127)
Value 2: any variable or constant (range
-2147483648 to 2147483647).
Format
<result> = <value 1> + <value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P102 parameter calculation result is 700.
Page 48
Drive Programming
48
- (Subtraction)
Command
Description
Arguments
Subtracts <value 2> from <value 1>.
Result
: any variable.
Value 1: any variable or constant (range
-128 to 127).
Value 2: any variable or constant (range
-2147483648 to 2147483647).
Format
<result>= <value 1> - <value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P102 parameter calculation result is 300.
*(Multiplication)
Command
Description
Arguments
Multiplies <value 1> by <value 2>.
Result
: any variable.
Value 1: any variable or constant (range
-128 to 127).
Value 2: any variable or constant (range
-2147483648 to 2147483647).
Format
<result> = <value 1> * <value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowcha
rt Text
The P102 parameter is set to 1000.
Page 49
Drive Programming
49
/(Division)
Command
Description
Arguments
Divides <value 1> by <value 2>.
Result
: any variable.
Value 1: any variable or constant (range
-128 to 127)
Value 2: any variable or constant (range
-2147483648 to 2147483647).
Format
<result> = <value 1> / <value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P102 parameter calculation result is 250.
% (Mod)
Command
Description
Arguments
Remainder of division.
Result
: Any variable.
Value 1: any variable or constant (range
-128 to 127).
Value 2: any variable or constant (range
-2147483648 to 2147483647)
Format
<result> = <value 1> Mod <value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P102 parameter calculation result is 0.
Page 50
Drive Programming
50
Abs
Command
Description
Arguments
Absolute value.
Result: any variable.
Value: any variable or constant (range -2147483648 to 2147483647).
Format
<result> = Abs <value>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The UL(01) variable is set to 200.
Page 51
Drive Programming
51
And
Command
Description
Arguments
And (logical product).
Value 1
Value 2
Result
0 0 0 0 1 0 1 0 0 1 1 1
Result: any variable.
Value 1: any variable or constant (range
-128 to 127).
Value 2: any variable or constant (range -2147483648 to 2147483647).
Format
<result> = <value 1> And <Value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The initial P104 parameter calculation result is 4, as 6 in binary format is 00000110 and 12 in binary format is 00001100, so the result of the and operation is 00000100 that is 4 in decimal format If P102 and P103 are changed by the user, then P104 will recalculate accordingly.
Page 52
Drive Programming
52
Or
Command
Description
Arguments
Or (logical addition).
Value 1
Value 2
Result
0 0 0 0 1 1 1 0 1 1 1 1
Result: any variable.
Value 1: any variable or constant (range -128 to 127).
Value 2: any variable or constant (range -2147483648 to 2147483647).
Format
<result> = <value 1> Or <value 2>
Warn
ing
: Drive programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The initial P104 parameter calculation result is 14, as 6 in binary format is 00000110 and 12 in binary format is 00001100, so the result of the operation is 00001110 that is 14 in decimal format. If P102 and P103 are changed by the user, then P104 will recalculate accordingly.
Page 53
Drive Programming
53
XOr
Command
Description
Arguments
XOr(exclusive-or)
Value 1
Value 2
Result
0 0 0 0 1 1 1 0 1 1 1 0
Result: any variable.
Value 1: any variable or constant (range -128 to 127).
Value 2: any variable or constant (range -2147483648 to 2147483647).
Format
<result>= <value 1> XOr <value 2>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The initial P104 parameter calculation result is 10, as 6 in binary format is 00000110 and 12 in binary format is 00001100, so the result of the XOr operation is 00001010 that is 10 in decimal format. If P102 and P103 are changed by the user, then P104 will recalculate accordingly.
Page 54
Drive Programming
54
Not
Command
Description
Arguments
Not (negation)
Value 1
Result
0 1 1 0
Result
: any variable, except variables
with bit data size (Note 1)
Value: any variable or constant, except variables with bit data size (Note 1) (range -2147483648 to 2147483647).
Format
<result> = Not<value>
Note:
Unexpected result will be obtained with instructions like UB(1) = Not UB(0). Please use XOr command to negate variables with bit data size in Drive Programming as shown on the next examples:
· Example 1: UB(1) = UB(0) Xor 1
· Example 2: UB(2) = X(00) Xor 1
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The initial P104 parameter calculation result is 65523, as 12 in binary format is 0000000000001100, so the result of the not operation is 1111111111110011 that is 65523 in decimal format. If P103 is changed by the user, then P104 will recalculate accordingly.
Page 55
Drive Programming
55
Inc
Command
Description
Arguments
Increments a value by 1.
Value: any variable.
Format
Inc<value>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P102 parameter is incremented by 1 every second.
Page 56
Drive Programming
56
Dec
Command
Description
Arguments
Decrements a value by 1.
Value: any variable.
Format
Dec<value>
Warning
: Drive Programming does not control overflow/underflow. The application should take care.
Example
Flowchart
Text
The P102 parameter is decremented by 1 every second.
Page 57
Drive Programming
57
6-3 Input/Output Control Commands
For memory optimization, use Input/Output Control Commands (4 bytes) instead of the Equal Arithmetic Command “=” (8 bytes).
Var = X(i)
Command
Description
Arguments
Instruction to access contact inputs. Reflects the state of the input.
Variable: any variable (the value of the variable will be 0 or 1).
i: Number of the contact input (range 0 to 11).
Format
<variable>=X(i)
Note
: The inputs have to be assigned to digital multifunction input (by the multifunction 56 to 63).
X(02) is not necessarily input 2 (depends where MF 58 is). X(00) = MI1
X(01) = MI2 X(02) = MI3 X(03) = MI4 X(04) = MI5 X(05) = MI6 X(06) = MI7 X(07) = MI8 X(08) = MI9 X(09) = MI10 X(10) = MI11 X(11) = MI12 Note
: more details in chapter 5-4 Terminal Variables.
Example
Flowchart
Text
The state of the input terminal X(01) is monitored on the d025 parameter
.
Page 58
Drive Programming
58
Var = Xw
Command
Description
Arguments
Instruction to access contact inputs by word. Each bit reflects one of the inputs.
Variable: any variable.
Format
<variable> = Xw
Note
: The inputs have to be assigned to digital multifunction input (by the multifunction 56 to 63 for
MX2 and RX or 49 to 60 on LX) Xw = 1 bit 0
Xw = 2 bit 1 Xw = 4 bit 2 Xw = 8 bit 3 Xw = 16 bit 4 Xw = 32 bit 5 Xw = 64 bit 6 Xw = 128 bit 7 (only for RX and LX) Xw = 256 bit 8 (only for LX with extension I/O) Xw = 512 bit 9 (only for LX with extension I/O) Xw = 1024 bit 10 (only for LX with extension I/O) Xw = 2048 bit 11 (only for LX with extension I/O)
Example
Flowchart
Text
This example acquires the state of the X(02) - X(05) input terminals and outputs it to Y(00) -Y(03) output terminals. To cut X(00) - X(01), the U(00) value is divided by 4. To cut X(06) - X(07), the U(00) value is masked by 15.
Page 59
Drive Programming
59
Y(i) = va
lue
Command
Description
Arguments
Instruction to access digital outputs.
i: Number of the contact output (range 0 to 6)
Value: any variable or constant.
For
mat
Y(i)=<value>
Note
: The inputs have to be assigned to digital multifunction output (by the multifunction 44 to 49 for MX2 and RX and 35 to 41 for LX). Y(00) = MO1 Y(01) = MO2 Y(02) = MO3 Y(03) = MO4 Y(04) = MO5 Y(05) = MO6 Y(06) = MO7 Note
: more details in chapter 5-4 Terminal Variables
Example
Flowchart
Text
To test this example, initialize the user variables with the following value: U(00) = 1000, U(01) = 2000, U(02) = 3000. Y(00) – Y(01) are sequentially turned on every 10Hz step of the output frequency.
Page 60
Drive Programming
60
Yw = value
Command
Description
Arguments
Instruction to access digital outputs by word. Each bit reflects one of the outputs.
Value: any variable or constant
Format
Yw = <value>
Note
: The inputs have to be assigned to digital multifunction input (by the multifunction 44 to 49 for MX2 and RX, 35 to 41 for LX). Yw = 1 bit 0 Yw = 2 bit 1 Yw = 4 bit 2 Yw = 8 bit 3 (only if expanded I/O board used) Yw = 16 bit 4 (only if expanded I/O board used) Yw = 32 bit 5 (only if expanded I/O board used, and enough outputs) Yw = 64 bit 6 (only if expanded I/O board for LX is used)
Example
Flowchart
Text
This example acquires the state of the X(02)-X(05) input terminals and outputs it to Y(00)-Y(03) output terminals. To cut X(00) – X(01), the U(00) value is divided by 4. To cut X(06) – X(07), the U(00) value is masked by 15.
Page 61
Drive Programming
61
func = value
Command
Description
Arguments
Assigns the value of a variable to a command of a terminal input.
Function: any function of input terminal.
Value: any variable or constant.
Format
<function> = <value>
Example
Flowchart
Text
A forward and reverse run at 60Hz is repeated continuously.
Page 62
Drive Programming
62
Var = func
Command
Description
Arguments
A terminal output status is assigned to a variable.
Variable: any variable.
Function: any function of output terminal.
Format
<variable>=<function>
Example
Flowchart
Text
The value of P100 is set to “1” if the ZS (zero speed signal) is on, otherwise is set to “0”.
Page 63
Drive Programming
63
Var = UB(i)
Command
Description
Arguments
Assigns the value of an internal user contact to a variable.
Variable: any variable (value of the variable will be 0 or 1).
i: Number of the user contact (range 0 to 7)
Format
<variable> = UB(i)
Example
Flowchart
Text
The internal user contacts are cleared on the loop’s 1
st
instruction. The status of the X(00) – X(02) input terminals are stored in the UB(0) – UB(2) internal user contacts and monitored on the d025 parameter. Finally, the status of the X(02) input terminal is set tot the Y(00) output terminal.
Page 64
Drive Programming
64
Va
r = UBw
Command
Description
Arguments
Assigns the value of the internal user contact as word (all together) to a word variable. .
Variable: any variable.
Format
<variable> = UBw
Note
: UBw = 1 bit 0 UBw = 2 bit 1 UBw = 4 bit 2 UBw = 8 bit 3 UBw = 16 bit 4 UBw = 32 bit 5 UBw = 64 bit 6 UBw = 128 bit 7
Example
Flowchart
Text
The internal user contacts are cleared on the loop’s 1st instruction. The status of the X(00) – X(02) input terminals are stored in the UB(0) – UB(2) internal user contacts and monitored on the d025 parameter. Finally the status of the X(02) input terminal is set to the Y(00) output terminal.
Page 65
Drive Programming
65
UB(i) = value
Command
Description
Arguments
Assigns a value to an internal user contact control.
i: Number of the user contact (range 0 to 7).
Value: any variable or constant.
Format
UB(i) = <value>
Example
Flowchart
Text
The internal user contacts are cleared on the loop’s 1st instruction. The status of the X(00)-X(02) input terminals are stored in the UB(0)-UB(2) internal user contacts and monitored on the d025 parameter. Finally, the status of the X(02) input terminal is set to the Y(00) output terminal.
Page 66
Drive Programming
66
UBw = value
Command
Description
Arguments
Assigns a value to the internal user contact controls. Instruction to access internal user contact by word.
Value: any variable or constant.
Format
UBw = <value>
Note
: UBw = 1 bit 0 UBw = 2 bit 1 UBw = 4 bit 2 UBw = 8 bit 3 UBw = 16 bit 4 UBw = 32 bit 5 UBw = 64 bit 6 UBw = 128 bit 7
Example
Flowchart
Text
The internal user contacts are cleared on the loop’s 1st instruction. The status of the X(00)-X(02) input terminals are stored in the UB(0)-UB(2) internal user contacts and monitored on the d025 parameter. Finally, the status of the X(02) input terminal is set to the Y(00) output terminal.
Page 67
Drive Programming
67
6-4 Timer Control Commands
Delay
Command
Description
Arguments
This instruction sets the count of the timer in <value 2> and starts the timer counter. When the timer output “TD (K)” is turned on/off, <value 1> is turned on/off. It is important to note, that meantime counting proceeds, the <value 1> remains unchanged from original value.
Value 1: any variable.
Value 2: any variable or constant (time in 10 x ms)
K: number of timer.
Format
Delay on/off <value 1>TD(k)<value 2>
Timing chart
Example
Flowchart
Text
Sample program that activates/deactivates the FW instruction with Delay On/Delay Off instruction.
Page 68
Drive Programming
68
Timer Set
Command
Description
Arguments
Sets <value> in the timer and starts the counter. The timer starts from 0 and increments until <value>. Associated timer contact reflects status (“1” = finish timing)
Value: any variable or constant (time in 10 x ms)
K: number of timer (range 0 to 7)
Format
Timer set TD(k) <value>
Note
: Timer value can be check in variable TC(k). Completion of timer can be checked in variable TD(k) (when it becomes “1”).
Timing chart
Example
Flowchart
Text
This program will set the timer TD(0) to an increasing value each timer execution, taking longer time on each loop.
Page 69
Drive Programming
69
Timer Off
Command
Description
Arguments
Clears the timer counter (up counter) to zero, and starts it in free-running mode.
k: number of timer (range 0 to 7)
Format
Timer off TD(k)
Timing chart
Example
Flowchart
Text
This example uses a fixed timer execution. But it is cancelled when digital input X(01) is OFF.
Page 70
Drive Programming
70
6-5 Parameter Control Commands
ChgParam
Command
Description
Arguments
Changes the parameter’s inverter setting specified by display code to a value. Any inverter parameter can be changed.
Parameter: parameter code (Fxxx, Axxx, bXXX, Cxxx, Hxxx, Pxxx)
Value: any variable or constant.
Format
ChgParam <parameter><value>
Note
: The same rules to parameter writing from operator panel or communications apply: Some parameters can not be written in certain mode of inverter (e.g. some parameters can not be changed during RUN condition). This instruction does not fix the parameter in EEPROM (EepWrt to be used for this purpose)
Example
Flowchart
Text
The F002 (acceleration time setting 1) value is increased by 1 every second.
Page 71
Drive Programming
71
MonParam
Command
Description
Arguments
Assigns the inverter’s parameter content specified by display code to a variable.
Parameter: parameter code (Fxxx, Axxx, bxxx, Cxxx, dxxx, Hxxx, Pxxx).
Variable: any variable
Format
MonParam<parameter><variable>
Example
Flowchart
Text
The value of the F001 parameter (output frequency setting) is monitored on the d025 parameter (user parameter monitor).
Page 72
Drive Programming
72
EepWrt
Command
Description
Arguments
The command allows write into EEPROM the next ChgParam executed just after this command. (if two ChgParam follows an EepWrt, only for the first one will be saved).
---
Format
EepWrt
Note
: Limitation of EepWrt:
-If this command is executed in more than one task, ChgParam is executed in the sequence it is detected. For the second invocation of the command, a waiting time of typically 10 ms will occur before each ChgParam is executed. For example, when ChgParam is detected in task 1,2 and 3 at the same time, and the one in task 1 is executed at first, is necessary to wait 10 ms for task 2 and 20 ms for task 3. But when Eepwrt is not executed, ChgParam doesn’t need this waiting time.
Example: (only F002 is stored in EEPROM)
Flowchart
Text
On executing the program, only F002 parameter is saved permanently from U(02). After power off and on again, F003 will have the old value. The initial values of the U(02) and U(03) variables can be set on the program variables list or the P102, P103 parameters.
Page 73
Drive Programming
73
RtcSet
Command
Description
Arguments
This statement sets 6 bytes data of time to a variable. This data corresponds with year, month, day, day of week, hour and minute. The variable value in hexadecimal corresponds to the year, month, day, day of a week, hour and minute (in decimal). RtcSet on: updates the 6 bytes data continuously. RtcSet off: updates the 6 bytes data only once.
User variable: any user or internal user variable (U(xx) or UL(xx)).
Format
RtcSet on/off <user variable>
Note
:
RtcSet on U(<k>): It will set U(<k>) with 2 bytes for year and 2 bytes for month, U(<k+1>) with 2 bytes for Month’s day and 2 bytes for week’s day(00 for Sunday, 06 for Saturday), and U(<k+2>) with 2 bytes for hour and 2 bytes for minutes.
RtcSet on UL(<k>): It will set UL(<k>) with 2 bytes for year, 2 bytes for month, 2 bytes for month’s day and 2 bytes for week’s day (00 for Sunday, 06 for Saturday), and UL(<k+1>) with 2 bytes for hour, 2 bytes for minutes and 4 bytes of padding(0000).
• If the watch LCD operator is not attached, RtcSet instruction sets 000000000000h
Example
Flowchart
Text
After executing the program (with the watch LCD operator attached), the hexadecimal value of the first 2 bytes of U(00) will correspond with the current year and the hexadecimal value of the last 2 bytes of U(00) will correspond to the current month.
I.e. if the example program runs on July 5
th
(Monday) of 2010 at 02:29 P.M., then U(00), U(01) and
U(02) will display the following values:
Parameter…
…display in decimal
format…
Which converted to
hexadecimal format
results in…
…which means
U(00) 4103 1007
‘10’ for 2010
‘07’ for July
U(01) 1281 0501
‘05 for 5
th
day of month
‘01’ for Monday
U(02) 5161 1429
‘14’ for 2 p.m.
‘29’ for 29 minutes
Page 74
Drive Programming
74
6-6 Inverter Control Commands
Run FW
Command
Description
Arguments
Makes the inverter run the motor in forward direction (starts the inverter output). This command is a shortcut of the func = value command.
---
Format
FW = 1 for RX and MX2 or UP =1 for LX
Note
: The instruction is available since CX-Drive v2.10.
Run RV
Command
Description
Arguments
Makes the inverter run the motor in reverse direction (starts the inverter output). This command is a shortcut of the func = value command.
---
Format
RV = 1 for RX and MX2 or DOWN=1 for LX
Note
: This instruction is available since CX-Drive v2.10.
Stop
Command
Description
Arguments
Makes the inverter decelerate and stop the motor (stop the inverter output).
---
Format
Stop
Set Freq
Command
Description
Arguments
It sets the frequency of the inverter. This command is a shortcut of the ‘=’ command. Units: 0.01Hz.
Value: any variable or constant (range from 0 to 40000).
Format
Set-Freq = <value>
Note
: This instruction is available since CX-Drive v2.10.
Page 75
Drive Programming
75
Example
Flowchart
Text
This program will run the motor in forward direction at 10Hz if general input contact Xw is 1. If general input contact Xw is 2, it will run in reverse direction at 15Hz. For other values the motor will stop.
Page 76
Drive Programming
76
Trip
Command
Description
Arguments
This instruction makes inverter trip.
Value: any variable or constant (range 0 to 9).
Format
Trip<value>
Example
Flowchart
Text
This sample program will throw a user trip on the inverter when digital input X(01) is set to ON.
Page 77
Drive Programming
77
Accel
Command
Description
Arguments
It sets the acceleration time of the inverter. This command is a shortcut of the ‘=’ command. Units: 10 ms.
Value: any variable or constant (range from 1 to 360000).
Format
Accel =<value>
Note:
Parameters P031 for MX2 and RX or A053 on LX must be set to value 3 (Drive programming)
for the command to become effective.
Decel
Command
Description
Arguments
It sets the deceleration time of the inverter. This command is a shortcut of the ‘=’ command. Units: 10ms
Value: any variable or constant (range from 1 to 360000).
Format
Decel = <value>
Note
: Parameters P031 for MX2 and RX or A053 on LX must be set to value 3 (Drive programming) for the command to become effective
Example
Flowchart
Text
This sample program will set the Acceleration to 10 seconds and deceleration to 20 seconds if digital input X(00) is set to ON.
Page 78
Drive Programming
78
7- Drive Programming specific trips and Troubleshooting
The table below shows how to handle the specific errors to Drive Programming function. For details on other errors in the inverter, refer to the inverter instruction manual.
Factor
code
Error (causing
inverter trip)
Possible cause Checking method Corrective action
E43 Invalid instruction
The PRG terminal was turned on without a program downloaded to the inverter.
By uploading the program, you can check if really a program is in the inverter or not.
Recreate the program, and then download it to the inverter
E44 Nesting count error
Subroutines are nested in more than eight layers.
Read the program to check the number of nesting layers (some times difficult to recognize)…
Correct the program so that the number of layers will be eight or less.
For-Next loop statements are nested in more than eight layers. If statements are nested in more than eight layers.
E45 Instruction error 1
The jump destination of a GoTo instruction is a next instruction to end a for or other loop.
Check whether each GoTo instruction jumps to an instruction that ends a loop.
Correct the jump destinations of GoTo instructions. As general recommendation, never jump a Goto out of the current level it is.
The variable “U(ii)” referenced via another variable is not found.
Check the numerical value specified in “U(ii)”.
Correct the value of variable “U(ii)” or limit the range of values of
variable “U(ii)”. An arithmetic instruction caused:
-Overflow,
-underflow, or
-division by zero
Check the program for the instruction causing overflow, underflow, or division by zero (not in early MX2 firmware).
Correct the program so
that no arithmetic
instruction causes
overflow, underflow, or
division by zero. A ChgParam instruction
caused:
- reference to a non existing parameter.
-writing of a value out of the setting range
-change of a parameter value (during inverter operation) that cannot be updated during inverter operation, or Change of a parameter value of which updating is restricted by software lock (when software lock is enabled).
-Check the parameters and the values to be written.
-If the error has occurred during inverter operation, check whether the parameter in question can be updated during inverter operation.
-Check the setting of software lock selection (b031).
-Correct the parameters
or the values to be
written to parameters so
that they will be within
the setting range.
-Disable software lock.
-If the parameter to be
updated is the one that
cannot be updated
during inverter
operation, change the
setting of software lock
selection (b031) to “10”
to switch to the mode
enabling parameter
updating during inverter
operation.
E50 to E59
User trip 0 to 9 These trips are generated
from the user application. The cause is determined by the Drive Programming logic
Check with the drive program documentation to recognize the trip conditions
Check the drive
program documentation
to recognize
countermeasures
Page 79
Drive Programming
79
8- Drive Programming Parameters – General Precautions 8-1 Parameters list affected by setting order
Parameter
Description
A003 Base frequency setting A004 Maximum frequency setting A203 Base frequency setting, 2nd motor A204 Maximum frequency setting, 2nd motor B015 Free setting, electronic thermal frequency (1) B017 Free setting, electronic thermal frequency (2) B019 Free setting, electronic thermal frequency (3) B049 Dual Rating Selection B050 Controlled deceleration on power loss B051 DC bus voltage trigger level of control deceleration B052 Over-voltage threshold of control deceleration B060 Maximum-limit level of window comparators O B061 Minimum-limit level of window comparators O B062 Hysteresis width of windows comparators O B063 Maximum-limit level of window comparators OI B064 Minimum-limit level of window comparators OI B065 Hysteresis width of window comparator (OI) B079 Watt-hour display gain setting B082 Start frequency adjustment B100 Free setting V/f freq. (1) B102 Free setting V/f freq. (2) B104 Free setting V/f freq. (3) B106 Free setting V/f freq. (4) B108 Free setting V/f freq. (5) B110 Free setting V/f freq. (6) B112 Free setting V/f freq. (7) P070 Low-speed zero-return frequency
Note: this parameter list only affect MX2 and RX.
8-2 Parameters list affected by Rated Current (%)
Param
eter Description
B012 Level of electronic thermal setting B016 Free setting, electronic thermal current (1) B018 Free setting, electronic thermal current (2) B020 Free setting, electronic thermal current (3) B022 Overload restriction level setting B025 Overload restriction level 2 setting B028 Current level of active freq. matching restart setting B126 Brake release current setting B212 Level of electronic thermal setting, 2nd motor B222 Overload restriction operation mode, 2nd motor C030 Digital current monitor reference value C039 Low load detection level C041 Overload level setting C111 Overload setting (2) C241 Overload level setting, 2nd motor
Note: this parameter list affect MX2. RX and LX.
Page 80
Drive Programming
80
8-3 Parameters list affected by PID enabled/disabled
Parameter
Description
A011 Pot./O-L input active range start frequency A012 Pot./O-L input active range end frequency A020 Multi-speed 0 setting A021 Multi-speed 1 setting A022 Multi-speed 2 setting A023 Multi-speed 3 setting A024 Multi-speed 4 setting A025 Multi-speed 5 setting A026 Multi-speed 6 setting A027 Multi-speed 7 setting A028 Multi-speed 8 setting A029 Multi-speed 9 setting A030 Multi-speed 10 setting A031 Multi-speed 11 setting A032 Multi-speed 12 setting A033 Multi-speed 13 setting A034 Multi-speed 14 setting A035 Multi-speed 15 setting A101 [OI] input active Range start frequency A102 [OI] input active Range end frequency A145 ADD frequency A220 Multi-speed 0 setting, 2nd motor F001 Output frequency setting
These parameters are affected by A071 / A075. Note
: this parameter list only affect MX2 and RX.
Page 81
Drive Programming
81
9 Insertion Point ( MX2 & RX )
The Gain/Bias can be applied to any reference
9-1 ‘Frequency’ before ACC/DEC
Para
meter
Description
Range
A901 Insertion Point 0: Disable; 1: Enable A902 Insertion Point ‘Frequency’ before ACC/Dec Gain 0 to 1000% A903 Insertion Point ‘Frequency’ before ACC/DEC Bias -100 to +100%
9-2 ‘Frequency’ after ACC/DEC
Parameter
Description
Range
A901 Insertion Point 0: Disable; 1: Enable A904 Insertion Point ‘Frequency’ after ACC/Dec Gain 0 to 1000% A905 Insertion Point ‘Frequency’ after ACC/DEC Bias -100 to +100%
9-3 ‘Deviation’ before PID block
Parameter
Description
Range
A901 Insertion Point 0: Disable; 1: Enable A906 Insertion Point ‘Deviation’ before PID block Gain 0 to 1000% A907 Insertion Point ‘Deviation’ before PID block Bias -100 to +100%
Page 82
Note: Specications subject to change without notice.
Austria Tel: +43 (0) 2236 377 800 www.industrial.omron.at
Belgium Tel: +32 (0) 2 466 24 80 www.industrial.omron.be
Czech Republic Tel: +420 234 602 602 www.industrial.omron.cz
Denmark Tel: +45 43 44 00 11 www.industrial.omron.dk
Finland Tel: +358 (0) 207 464 200 www.industrial.omron.
France Tel: +33 (0) 1 56 63 70 00 www.industrial.omron.fr
Germany Tel: +49 (0) 2173 680 00 www.industrial.omron.de
Hungary Tel: +36 (0) 1 399 30 50 www.industrial.omron.hu
Italy Tel: +39 02 32 681 www.industrial.omron.it
Middle East & Africa Tel: +31 (0) 23 568 11 00 www.industrial.omron.eu
Netherlands Tel: +31 (0) 23 568 11 00 www.industrial.omron.nl
Norway Tel: +47 (0) 22 65 75 00 www.industrial.omron.no
Poland Tel: +48 (0) 22 645 78 60 www.industrial.omron.com.pl
Portugal Tel: +351 21 942 94 00 www.industrial.omron.pt
Russia Tel: +7 495 648 94 50 www.industrial.omron.ru
Spain Tel: +34 913 777 900 www.industrial.omron.es
Sweden Tel: +46 (0) 8 632 35 00 www.industrial.omron.se
Switzerland Tel: +41 41 748 13 13 www.industrial.omron.ch
Turkey Tel: +90 (0) 216 474 00 40 www.industrial.omron.com.tr
United Kingdom Tel: +44 (0) 870 752 08 61 www.industrial.omron.co.uk
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands.
Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.industrial.omron.eu
B
Loading...