Omron E5CN-C2MT-500, E5CN-Y2MT-500, E5CN-R2MTD-500, E5CN-Q2MTD-500, E5CN-C2MTD-500 Datasheet

...
Basic-type Digital Temperature Controller E5CN/E5CN-U 1
Basic-type Digital Temperature Controller
E5CN/E5CN-U
(48 x 48 mm)
New 48 x 48-mm Basic Temperature Controller with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function.
Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%) Pt input: ±0.2% of PV (previous models: ±0.5%) Analog input: ±0.2% FS (previous models: ±0.5%)
New E5CN-U Models (Plug-in Models) with analog inputs and
current outputs.
A PV/SV-status display function can be set to alternate between
displaying the PV or SV and the status of the Temperature Controller (auto/manual, RUN/STOP and alarms).
Preventive maintenance for relays using a Control Output ON/OFF Counter.
Main I/O Functions
48 × 48-mm
E5CN
48 × 48-mm
E5CN-U
Refer to Safety Precautions on page 18.
Event Inputs
• None
• Two
Sensor Inputs
• Universal thermocouple/Pt inputs (Models with temperature inputs)
• Analog current/voltage inputs (Models with analog inputs)
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period and control update
• 250 ms
Control Output 1
• Relay output
• Voltage output (for driving SSR)
• Current output
• Long-life relay output (hybrid)
Control Output 2
• None
• Voltage output (for driving SSR)
2 Auxiliary Outputs
2 line Display: PV and SV
4-digit, 11 segment display
E5CN
• Auto/manual switching
• Temperature Controller status display
Simple program function
• Control output ON/OFF count alarm
• PV change rate alarm
• Models optional with RS-485 communications
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)
2 Basic-type Digital Temperature Controller E5CN/E5CN-U
Lineup
Note: All models can be used for Heating, Cooling and Heating & Cooling control
Model Number Structure
Model Number Legend
Controllers
1. Control Output 1
R: Relay output Q: Voltage output (for driving SSR) C: Current output Y: Long-life relay output (hybrid) ✽1
2. Auxiliary Outputs ✽2
2: Two outputs
3. Option
M: Option Unit can be mounted.
4. Input Type
T: Universal thermocouple/platinum resistance thermometer L: Analog current/voltage input
5. Power Supply Voltage
Blank: 100 to 240 VAC D: 24 VAC/VDC
6. Case Color
Blank: Black W: Silver (contact your local sales for more information)
7. Terminal Cover
-500: With terminal cover
Option Units
1. Applicable Controller
CN: E5CN
2. Function 1
Blank: None Q: Control output 2 (voltage for driving SSR) P: Power supply for sensor
3. Function 2
Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection
(For 3-phase heater applications, 2x CT) B: Two event inputs 03: RS-485 communications H03: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + RS-485 communications
HB: Heater burnout/SSR failure/Heater overcurrent detection
(CT1) + Two event inputs HH03: Heater burnout/SSR failure/Heater overcurrent detection
(For 3-phase heater applications, 2x CT)
4. Version
N2: Applicable only to models produced after January 2008
(Box marked with N6)
Note: Not all combinations of function 1 and function 2 specifications are possible for Option Units (E53-CN@@N2). 1. Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is connected because a triac is used for
switching the circuit. For details, check the conditions in Ratings.
2. Auxiliary outputs are contact outputs that can be used to output alarms, control or results of logic operations.
Plug-in
Terminal block
E5CN
Basic Type
Analog input
Temperature input
2 control outputs
1 control output
2 control outputs
1 control output
2 auxiliary outputs
2 auxiliary outputs
2 auxiliary outputs
2 auxiliary outputs
Analog input
Temperature input
1 control output
1 control output
2 auxiliary outputs
2 auxiliary outputs
1 2 3 4 5 6 7
E5CN-@2M@@-@-500
1 2 3
4
E53-CN@@N2
Basic-type Digital Temperature Controller E5CN/E5CN-U 3
Ordering Information
Controllers with Terminal Blocks
Note: add power supply voltage to model to complete ordering code (ie. E5CN-R2MT-500 AC100-240 or E5CN-R2MTD-500 AC/DC24)
Option Units
One of the following Option Units can be mounted to provide the E5CN with additional functions.
Note: Option Units cannot be used for plug-in models.
These Option Units are applicable only to models produced after January 2008 (Box marked with N6).
Size Case color
Power supply
voltage
Input type Auxiliary outputs Control output 1 Model
1/16 DIN 48 × 48 × 78 (W × H × D)
Black
100 to 240 VAC
Thermocouple or Resistance thermometer
2
Relay output E5CN-R2MT-500
Voltage output (for driving SSR) E5CN-Q2MT-500
Current output E5CN-C2MT-500
Long-life relay output (hybrid) E5CN-Y2MT-500
24 VAC/VDC
Thermocouple or Resistance thermometer
2
Relay output E5CN-R2MTD-500
Voltage output (for driving SSR) E5CN-Q2MTD-500
Current output E5CN-C2MTD-500
100 to 240 VAC
Analog (current/voltage)
2
Relay output E5CN-R2ML-500
Voltage output (for driving SSR) E5CN-Q2ML-500
Current output E5CN-C2ML-500
Long-life relay output (hybrid) E5CN-Y2ML-500
24 VAC/VDC
Analog (current/voltage)
2
Relay output E5CN-R2MLD-500
Voltage output (for driving SSR) E5CN-Q2MLD-500
Current output E5CN-C2MLD-500
Functions Model
Event inputs E53-CNBN2
Event inputs
Control output 2 (Voltage for driving SSR)
E53-CNQBN2
Event inputs
Heater burnout/SSR failure/Heater overcurrent detection
E53-CNHBN2
Event inputs
External power supply for ES1B
E53-CNPBN2
Communications RS-485
E53-CN03N2
Communications RS-485
Control output 2 (Voltage for driving SSR)
E53-CNQ03N2
Communications RS-485
Heater burnout/SSR failure/Heater overcurrent detection
E53-CNH03N2
Communications RS-485
3-phase heater burnout/SSR failure/ Heater overcurrent detection
E53-CNHH03N2
Communications RS-485
External power supply for ES1B
E53-CNP03N2
Heater burnout/SSR failure/Heater overcurrent detection
Control output 2 (Voltage for driving SSR)
E53-CNQHN2
3-phase heater burnout/SSR failure/ Heater overcurrent detection
Control output 2 (Voltage for driving SSR)
E53-CNQHHN2
Heater burnout/SSR failure/Heater overcurrent detection
External power supply for ES1B
E53-CNPHN2
4 Basic-type Digital Temperature Controller E5CN/E5CN-U
Model Number Structure
Model Number Legend (Plug-in-type Controllers)
1. Output Type
R: Relay output Q: Voltage output (for driving SSR) C: Current output
2. Number of Alarms
2: Two alarms
3. Input Type
T: Universal thermocouple/platinum resistance thermometer L: Analog Input
4. Plug-in type
U: Plug-in type
Ordering Information
Plug-in-type Controllers
Note: add power supply voltage to model to complete ordering code. (ie. E5CN-R2TU AC100-240 or E5CN-R2TDU AC/DC24)
1 2 3 4
E5CN-@2@U
Size Case color Power supply voltage Input type Auxiliary outputs Control output 1 Model
1/16 DIN Black
100 to 240 VAC
Thermocouple or resistance thermometer
2
Relay output E5CN-R2TU
Voltage output (for driving SSR) E5CN-Q2TU
Current output E5CN-C2TU
Analog (current/voltage)
2
Relay output E5CN-R2LU
Voltage output (for driving SSR) E5CN-Q2LU
Current output E5CN-C2LU
24 VAC/VDC
Thermocouple or resistance thermometer
2
Relay output E5CN-R2TDU
Voltage output (for driving SSR) E5CN-Q2TDU
Current output E5CN-C2TDU
Basic-type Digital Temperature Controller E5CN/E5CN-U 5
Accessories (Order Separately)
USB-Serial Conversion Cable
Terminal Cover
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Note: The Waterproof Packing is included with the Controller only for
models with terminal blocks.
Current Transformers (CTs)
Adapter
Note: Use this Adapter when the panel has been previously prepared
for the E5B@ (72x72 mm panel cut-out).
Sockets (for Plug-in Models)
CX-Thermo Support Software
Model
E58-CIFQ1
Connectable models Terminal block models
Model E53-COV17
Model
Y92S-29
Hole diameter Model
5.8 dia. E54-CT1
12.0 dia. E54-CT3
Connectable models Model
Terminal block models Y92F-45
Type Model
Front-connecting Socket P2CF-11
Front-connecting Socket with Finger Protection P2CF-11-E
Back-connecting Socket P3GA-11
Terminal Cover for Back-connecting socket with Finger Protection
Y92A-48G
Model
EST2-2C-MV4
6 Basic-type Digital Temperature Controller E5CN/E5CN-U
Specifications
Ratings
Power supply voltage
No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consump­tion
E5CN
100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA)
E5CN-U
100 to 240 VAC: 6 VA (max.) 24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W)
Sensor input
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70° C, 60 to 120°C, 115 to 165° C, or 140 to 260°C Voltage input: 0 to 50 mV
Models with analog inputs
Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Control outputs
Relay output
E5CN
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
E5CN-U
SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
Voltage output (for driving SSR)
E5CN E5CN-U
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
Current output E5CN 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000
Long-life relay output
E5CN
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max. (250 VAC, 60 Hz)
Auxiliary outputs
Number of outputs 2
Output specifica­tions
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
Event inputs
Number of inputs 2
External contact input specifica­tions
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided
Setting method Digital setting using front panel keys
Indication method
11-segment digital display and individual indicators (7-segment display emulation also possible) Character height: PV: 11 mm, SV: 6.5 mm
Multi SP
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial communications.
Bank switching Not supported
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple program, automatic cooling coefficient adjustment
Ambient operating temperature 10 to 55° C (with no condensation or icing), for 3-year warranty: 10 to 50° C
Ambient operating humidity 25% to 85% Storage temperature 25 to 65° C (with no condensation or icing)
Basic-type Digital Temperature Controller E5CN/E5CN-U 7
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal Inputs)
Models with Analog Inputs
Shaded settings are the default settings.
Input Typ e
Platinum resistance
thermometer
Thermocouple
Infrared temperature
sensor
Analog
input
Name Pt100 JPt100 K J T E L U N R S B W
PL
II
10 to 70° C
60 to
120
° C
115
to
165
°C
140
to
260
° C
0 to
50 mV
Temperature range (°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100.0
200.0
2300
Usable in the following ranges by scaling:
1999 to 9999 or
199.9 to
999.9
1800
1700 1700
1300 1300 1300
850 850 850
600
500.0 500.0 500.0
400.0 400 400.0 400 400.0
260
120 165
100.0 100.0 90
100
0.0 0.0 00 00 0 0 0 0
20.0 −100 −20.0 100
200 −199.9 199.9 200 200 −199.9 −200 200 −199.9 −200
Setting number
01234
5 6 7 8 9 10 11 12 13 14 15 16 17 18 24 25 19 20 21 22 23
Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Input Type Current Voltage
Input specification 4 to 20mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Setting range
Usable in the following ranges by scaling:
1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999
Setting number 01234