• Relay control output, without alarm, thermocouple input, light gray case: E5CSV-RKJ-W
• Relay control output, one alarm output, platinum resistance thermometer input, black case: E5CSV-R1P-W
4. Power Supply Voltage
Blank: 100 to 240 VAC
D:24 VAC/VDC
5. Case Color
Blank: Black
W:Light gray
1
E5CSV
Ordering Information
■ List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 100 to 240 VAC
SizeTypeControl
E5CSV
48 × 48mm
Terminal block ON/OFF or
modes
PID
AlarmsOutputsModel with
1RelayE5CSV-R1KJ-WE5CSV-R1P-W
Voltage (for driving SSR)E5CSV-Q1KJ-WE5CSV-Q1P-W
thermocouple
Model with platinum
resistance
thermometer
Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC
SizeTypeControl
E5CSV
48 × 48mm
Terminal block ON/OFF or
modes
PID
AlarmsOutputsModel with
thermocouple
1RelayE5CSV-R1KJD-W
Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC
Size
E5CSV
48 × 48mm
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).
TypeControl
Terminal block ON/OFF or
modes
PID
AlarmsOutputsModel with universal-
0RelayE5CSV-RT
Voltage (for driving SSR)E5CSV-QT
1RelayE5CSV-R1T
Voltage (for driving SSR)E5CSV-Q1T
2 (See note.)RelayE5CSV-R2T
Voltage (for driving SSR)E5CSV-Q2T
input (thermocouple
or platinum resistance
thermometer)
Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC
Size
E5CSV
48 × 48mm
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).
TypeControl
Terminal block ON/OFF or
modes
PID
AlarmsOutputsModel with universal-
0RelayE5CSV-RTD
Voltage (for driving SSR)E5CSV-QTD
1RelayE5CSV-R1TD
Voltage (for driving SSR)E5CSV-Q1TD
2 (See note.)RelayE5CSV-R2TD
Voltage (for driving SSR)E5CSV-Q2TD
input (thermocouple
or platinum resistance
thermometer)
■ Accessories (Order Separately)
Protective Cover
TypeModel
Hard Protective CoverY92A-48B
Terminal Cover
Model
E53-COV10
Terminal Cover
(For Controllers after the design change scheduled for October 2010)
Model
E53-COV17
Note: The E53-COV10 Terminal Cover cannot be mounted to
Controllers that are manufactured after the design change
scheduled for October 2010
Rubber Packing
Model
Y92S-29
Note: The Rubber Packing is provided with the Digital Controller.
2
Specifications
■ Ratings
Supply voltage100 to 240 VAC, 50/60 Hz
Operating voltage range85% to 110% of rated supply voltage
Power consumption100 to 240 VAC: 5 VA
Sensor inputThermocouple input type: K, J, L
Control
output
Control methodON/OFF or 2-PID (with auto-tuning)
Alarm outputSPST-NO, 250 VAC, 1A (resistive load)
Setting methodDigital setting using front panel keys
Indication method7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions• Setting change prohibit (key protection)
Ambient operating temperature−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C
Ambient operating humidity25% to 85%
Storage temperature−25 to 65°C (with no condensation or icing)
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
Relay outputSPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Proportional band (P)1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I)1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D)1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output rangeAbsolute-value alarm: Same as the control range
Control period2/20 s
Sampling period500 ms
Insulation resistance20 MΩ min. (at 500 VDC)
Dielectric strength2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration
resistance
Shock resistanceMalfunction
Life expectancyElectrical100,000 operations min. (relay output models)
WeightApprox. 120 g (Controller only)
Degree of protectionFront panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
Memory protectionEEPROM (non-volatile memory) (number of writes: 1,000,000)
EMCEMI Radiated: EN 55011 Group 1 Class A
Approved standardsUL 61010-1 (listing)
Conformed standardsEN 61326, EN 61010-1, IEC 61010-1
Note: 1. The following exceptions apply to thermocouples.
• U, L: ±2°C ±1 digit max.
• R: ±3°C ±1 digit max. at 200°C or less
2. The following exceptions apply to platinum resistance thermometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Malfunction
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Destruction
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Other thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Other: 0 to input setting range full scale (°C or °F)
Alarm hysteresis: 0.2°C or °F (fixed)
2
10 to 55 Hz, 20 m/s
2
min., 3 times each in 6 directions
100 m/s
2
300 m/s
min., 3 times each in 6 directions
EMI Conducted: EN 55011 Group 1 Class A
ESD Immunity: EN 61000-4-2: 4 kV contact discharge (level 2)
Radiated Electromagnetic Field Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage)
CSA C22.2 No.1010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
for 10 min each in X, Y, and Z directions
8 kV air discharge (level 3)
10 V/m (900 MHz pulse modulated)
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
• Using Thermocouple Sensors, Control Mode Switch 5: OFF
InputKJLTUNR
1,700
1,600
1,500
1,400
1,3001,300
Temperature
0
1
2
4
5
range
(selected
3
using switch)
9
8
7
6
(Default setting: 0)
Setting number
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
−100
−99−99−99−99−99−99
850850
400400
199.9199.9199.9
0.00.00.00
0123456789
Minimum setting unit 1°C0.1°C1°C0.1°C1°C0.1°C1°C
• Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
InputPt100JPt100
Temperature
0
1
2
4
5
range
(selected
3
using switch)
9
8
7
6
(Default setting: 0)
Minimum setting unit 1°C0.1°C1°C0.1°C1°C
Setting number
1,000
850
900
800
700
600
500
400
300
200
100
−100
0
199.9200199.9200
9999
0.0000.000
−99−99−99−99
500
400400
0123456789
1,700
The shaded value indicates the default
setting status.
The shaded value indicates the default
setting status.
4
External Connection Diagram
3
3
Voltage output
models
(See note 1.)
Relay output
models
Relay outputVoltage output
E5CSV
Alarm output
1
12 VDC,
21 mA
2
A
3
B
4
B
5
Platinum resistance
thermometer input
platinum resistance thermometer universal-input
Thermocouple/
11
2
2
3
4
5
Thermocouple
input
6
7
8
9
100 to 240 VAC, 50/60 Hz
(24 VAC/VDC)
(See note 2.)
10
Alarm output 2 (See note
Alarm output 1 (See note
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
3. The number of alarm outputs depends on the model.
Nomenclature
E5CSV Models with Terminal Blocks
Deviation indicators
Mode indicators
Mode Key
Lock Release Key
Output indicator
Temperature display
Alarm indicators
Up Key
Down Key
5
Dimensions
92A -48 B
Note: All units are in millimeters unless otherwise indicated.
■ Controller
E5CSV
E5CSV
48×48
E5CSV + Adapter for Flush Mounting
(Provided)
84
786
44.8×44.8
Note: Terminals cannot be removed.
Adapter for flush mounting
58
48
7.5
Note: 1. The recommended panel thickness is 1 to 4 mm.
Panel Cutout Dimensions
+0.6
45
0
+0.6
45
0
60 min.
Y92F-30 Adapter for flush mounting
Pane l
Tightening
screws
76.5
+0.6
45
0
L = (48×N−2.5)
Mounting side-by-side
(group mounting of N Controllers)
L
+1
0
2. Group mounting is possible in one direction only.
■ Accessories (Order Separately)
Hard Protective Cover
The Y92A-48B Protective Cover (hard type) is available for the following applications.
• To protect the set from dust and dirt.
• To prevent the panel from being accidentally touched causing displacement of set values.
• To provide effective protection against water droplets.
Terminal CoverRubber Packing
E53-COV10
E53-COV17
48
48.8
22
9.1
48
48.8
Y92S-29 (for DIN48 × 48)
Order the Rubber Packing separately if it becomes lost
or damaged. The Rubber Packing can be used to
achieve an IP66 degree of protection for models with
terminal blocks.
(Deterioration, shrinking, or hardening of the rubber
packing may occur depending on the operating
environment. Therefore, periodic replacement is
recommended to ensure the level of waterproofing
specified in NEMA4. The time for periodic replacement
depends on the operating environment. Be sure to
confirm this point at your site. Consider one year a
rough standard. OMRON shall not be liable for the level
of water resistance if the customer does not perform
periodic replacement.)
The Rubber Packing does not need to be attached if a
waterproof structure is not required.
°C
92A-48B
92A-48B
(For Controllers after the
design change scheduled
for October 2010)
22
9.1
6
Safety Precautions
Refer to Safety Precautions for All Temperature Controllers.
Refer to E5CS/E5CSV Operation for operating procedures.
E5CSV
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
7
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
•
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
•
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
•
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2010 All Right Reserved.
2010.8