Omron E5CN-Q2MT-500-AC100-240, E5CSVQ1TF, E5CSVR1TF Data Sheet

Temperature Controllers
E5CSV
Easy Setting Using DIP Switch and Simple Functions in DIN 48 × 48 mm-size Temperature Controllers
• Easy setting using DIP switch.
• Universal-input (thermocouple/platinum resistance thermometer) models also available.
• Clearly visible digital display with character height of 13.5 mm.
• Models available with black in addition to white cases.
• RoHS compliant.
Model Number Structure
CSM_E5CSV_DS_E_7_1
Refer to Safety Precautions for All Temperature Controllers.
Refer to E5CS/E5CSV Operation for operating procedures.
Model Number Legend
Models with Terminal Blocks
E5CSV-@@@@-@
1. Control Outputs
R: Relay Q: Voltage for driving SSR
2. Alarm Outputs
Blank: No alarm 1: 1 alarm 2: 2 alarms
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
1234 5
3. Input
KJ: Thermocouple P: Platinum resistance thermometer T: Thermocouple/platinum resistance
thermometer (universal-input)
Ordering Information when ordering.
Examples
Relay control output, without alarm, thermocouple input, light gray case: E5CSV-RKJ-W
Relay control output, one alarm output, platinum resistance thermometer input, black case: E5CSV-R1P-W
4. Power Supply Voltage
Blank: 100 to 240 VAC D: 24 VAC/VDC
5. Case Color
Blank: Black W: Light gray
1
E5CSV
Ordering Information
List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer, Power Supply Voltage: 100 to 240 VAC
Size Type Control
E5CSV 48 × 48mm
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with
1 Relay E5CSV-R1KJ-W E5CSV-R1P-W
Voltage (for driving SSR) E5CSV-Q1KJ-W E5CSV-Q1P-W
thermocouple
Model with platinum
resistance
thermometer
Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC
Size Type Control
E5CSV 48 × 48mm
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with
thermocouple
1 Relay E5CSV-R1KJD-W
Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC
Size
E5CSV 48 × 48mm
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).
Type Control
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with universal-
0Relay E5CSV-RT
Voltage (for driving SSR) E5CSV-QT
1Relay E5CSV-R1T
Voltage (for driving SSR) E5CSV-Q1T
2 (See note.) Relay E5CSV-R2T
Voltage (for driving SSR) E5CSV-Q2T
input (thermocouple
or platinum resistance
thermometer)
Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC
Size
E5CSV 48 × 48mm
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).
Type Control
Terminal block ON/OFF or
modes
PID
Alarms Outputs Model with universal-
0Relay E5CSV-RTD
Voltage (for driving SSR) E5CSV-QTD
1Relay E5CSV-R1TD
Voltage (for driving SSR) E5CSV-Q1TD
2 (See note.) Relay E5CSV-R2TD
Voltage (for driving SSR) E5CSV-Q2TD
input (thermocouple
or platinum resistance
thermometer)
Accessories (Order Separately)
Protective Cover
Type Model
Hard Protective Cover Y92A-48B
Terminal Cover
Model
E53-COV10
Terminal Cover
(For Controllers after the design change scheduled for October 2010)
Model
E53-COV17
Note: The E53-COV10 Terminal Cover cannot be mounted to
Controllers that are manufactured after the design change scheduled for October 2010
Rubber Packing
Model
Y92S-29
Note: The Rubber Packing is provided with the Digital Controller.
2
Specifications
Ratings
Supply voltage 100 to 240 VAC, 50/60 Hz
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 100 to 240 VAC: 5 VA
Sensor input Thermocouple input type: K, J, L
Control output
Control method ON/OFF or 2-PID (with auto-tuning)
Alarm output SPST-NO, 250 VAC, 1A (resistive load)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions Setting change prohibit (key protection)
Ambient operating temperature 10 to 55°C (with no condensation or icing); with 3-year guarantee: 10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature 25 to 65°C (with no condensation or icing)
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
Relay output SPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
2. Models for 24 VAC/DC can also be manufactured.
24 VAC, 50/60 Hz; 24 VDC
24 VAC: 3 VA, 24 VDC: 2 W
Platinum resistance thermometer input type: Pt100, JPt100 Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
Input shift
Temperature unit change (°C/°F)
Direct/reverse operation
Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models.
Control period switching
8-mode alarm output
Sensor error detection
E5CSV
Characteristics
Setting accuracy Thermocouple (See note 1.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Indication accuracy (ambient temperature of 23°C)
Influence of temperature R thermocouple inputs: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Influence of voltage
Hysteresis (for ON/OFF control) 0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
Proportional band (P) 1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range Absolute-value alarm: Same as the control range
Control period 2/20 s
Sampling period 500 ms
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration resistance
Shock resistance Malfunction
Life expectancy Electrical 100,000 operations min. (relay output models)
Weight Approx. 120 g (Controller only)
Degree of protection Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC EMI Radiated: EN 55011 Group 1 Class A
Approved standards UL 61010-1 (listing)
Conformed standards EN 61326, EN 61010-1, IEC 61010-1
Note: 1. The following exceptions apply to thermocouples.
U, L: ±2°C ±1 digit max.
R: ±3°C ±1 digit max. at 200°C or less
2. The following exceptions apply to platinum resistance thermometers. Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Malfunction
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Destruction
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Other thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Other: 0 to input setting range full scale (°C or °F) Alarm hysteresis: 0.2°C or °F (fixed)
2
10 to 55 Hz, 20 m/s
2
min., 3 times each in 6 directions
100 m/s
2
300 m/s
min., 3 times each in 6 directions
EMI Conducted: EN 55011 Group 1 Class A ESD Immunity: EN 61000-4-2: 4 kV contact discharge (level 2)
Radiated Electromagnetic Field Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2) Noise Immunity (First Transient Burst Noise): EN 61000-4-4 Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3) Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage)
CSA C22.2 No.1010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
for 10 min each in X, Y, and Z directions
8 kV air discharge (level 3)
10 V/m (900 MHz pulse modulated)
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
3
Temperature Range
Thermocouple Input Models
Input K J/L
9
8
7
6
2
4
5
range
3
(selected using switch)
Temperature
0
1
(Default setting: 2)
Setting number
1,000
900 800 700 600 500 400 300 200 100
0
300 300
200 200
0000000000
500 500
400 400
0123456789
Minimum setting unit 1°C1°C
Platinum Resistance Thermometer Input Models
9
8
7
6
2
4
5
range
3
(selected using switch)
Temperature
0
1
(Default setting: 3)
Minimum setting unit 1°C0.1°C1°C0.1°C1° C0.1°C
Setting number
Input JPt100/Pt100
500 400 300 200
50 50.0 80 99.9
100
100
0
0.0 0.0000000.0
50 20
0123456789
Universal-input (Thermocouple/Platinum Resistance Thermometer) Models
999
600
400 400
300 300
200 199.9
The shaded value indicates the default
setting status.
The shaded value indicates the default
setting status.
E5CSV
Using Thermocouple Sensors, Control Mode Switch 5: OFF
Input K J L T U N R
1,700 1,600 1,500 1,400
1,300 1,300
Temperature
0
1
2
4
5
range (selected
3
using switch)
9
8
7
6
(Default setting: 0)
Setting number
1,300 1,200 1,100 1,000
900 800 700 600 500 400 300 200 100
0
100
99 99 99 99 99 99
850 850
400 400
199.9 199.9 199.9
0.0 0.0 0.0 0
0123456789
Minimum setting unit 1°C0.1°C1°C0.1°C1°C0.1°C1°C
Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
Input Pt100 JPt100
Temperature
0
1
2
4
5
range (selected
3
using switch)
9
8
7
6
(Default setting: 0)
Minimum setting unit 1°C0.1°C1°C0.1°C1°C
Setting number
1,000
850
900 800 700 600 500 400 300 200 100
100
0
199.9 200 199.9 200 99 99
0.0000.000
99 99 99 99
500
400 400
0123456789
1,700
The shaded value indicates the default
setting status.
The shaded value indicates the default
setting status.
4
External Connection Diagram
3
3
Voltage output
models
(See note 1.)
Relay output
models
Relay outputVoltage output
E5CSV
Alarm output
1
12 VDC,
21 mA
2
A
3
B
4
B
5
Platinum resistance
thermometer input
platinum resistance thermometer universal-input
Thermocouple/
11
2
2
3
4
5
Thermocouple
input
6
7
8
9
100 to 240 VAC, 50/60 Hz (24 VAC/VDC) (See note 2.)
10
Alarm output 2 (See note
Alarm output 1 (See note
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
3. The number of alarm outputs depends on the model.
Nomenclature
E5CSV Models with Terminal Blocks
Deviation indicators
Mode indicators
Mode Key
Lock Release Key
Output indicator
Temperature display
Alarm indicators
Up Key
Down Key
5
Dimensions
92A -48 B
Note: All units are in millimeters unless otherwise indicated.
Controller
E5CSV
E5CSV
48×48
E5CSV + Adapter for Flush Mounting (Provided)
84
786
44.8×44.8
Note: Terminals cannot be removed.
Adapter for flush mounting
58
48
7.5
Note: 1. The recommended panel thickness is 1 to 4 mm.
Panel Cutout Dimensions
+0.6
45
0
+0.6
45
0
60 min.
Y92F-30 Adapter for flush mounting
Pane l
Tightening screws
76.5
+0.6
45
0
L = (48 × N2.5) Mounting side-by-side (group mounting of N Controllers)
L
+1
0
2. Group mounting is possible in one direction only.
Accessories (Order Separately)
Hard Protective Cover
The Y92A-48B Protective Cover (hard type) is available for the following applications.
To protect the set from dust and dirt.
To prevent the panel from being accidentally touched causing displacement of set values.
To provide effective protection against water droplets.
Terminal Cover Rubber Packing
E53-COV10
E53-COV17
48
48.8
22
9.1
48
48.8
Y92S-29 (for DIN48 × 48)
Order the Rubber Packing separately if it becomes lost or damaged. The Rubber Packing can be used to achieve an IP66 degree of protection for models with terminal blocks.
(Deterioration, shrinking, or hardening of the rubber packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in NEMA4. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Rubber Packing does not need to be attached if a waterproof structure is not required.
°C
92A-48B
92A-48B
(For Controllers after the design change scheduled for October 2010)
22
9.1
6
Safety Precautions
Refer to Safety Precautions for All Temperature Controllers. Refer to E5CS/E5CSV Operation for operating procedures.
E5CSV
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
7
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.