Can be used to power individual appliances plugged directly into the generator’s outlets, or as a back-up
connection to a building’s power supply (via a professionally installed UL-approved transfer switch.
WARNING
READ and UNDERSTAND this manual completely before using the generator! Failure to properly set up,
operate, and maintain this generator could result in serious injury or death from carbon monoxide poisoning,
electric shock, fire/explosion, or burns. In particular, be aware of the following hazards:
Generators give off carbon monoxide, a poisonous gas that can kill you. You CANNOT smell it, see it, or taste it.
• ONLY run generator OUTDOORS and AWAY from building air intakes. NEVER run generator inside any enclosed or
semi-enclosed spaces, including homes, basements, garages, sheds , boxes , RVs, boats or pick-up truck beds. These
spaces can trap poisonous gases, EVEN if you run a fan or open windows.
• Install carbon monoxide alarms inside nearby structures/buildin gs (bat t er y -o perat ed , or plug-in with battery backup).
Electric shock / Electrocution
• High voltage electricity from generator can kill. DO NOT operate in wet locations. Be sure generator is properly
grounded. Use only UL-listed, outdoor-rated grounded extension cords of proper size.
• NEVER plug the generator directly into a wall outlet. ANY connection to a building’s electrical system MUST
ISOLATE THE GENERATOR FROM UTILITY POWER via a UL-approved transfer switch installed by a licensed
electrician. Otherwise, back feed from the generator into the power grid could kill utility workers.
• DO NOT overload generator (per rated capacity), and OPERATE ONLY in an area with adequate cooling ventilation so
engine does not overheat. Exhaust can be extremely hot. Keep muffler at least 7’ from all combustible objects.
• All fuels are flammable. Never fuel a running or hot engine. Never pump fuel directly into generator at gas station – use
approved container to transfer fuel. Ensure there are no fuel leaks, and keep sources of sparks and flames away.
• ALWAYS keep a fire extinguisher rated “ABC” nearby.
CO Poisoning
Fire / Explosion
STOP!
CHOOSE THE RIGHT GENERATOR FOR YOUR NEEDS. See the “Power load Planning & Management” section
of this manual to determine your power load requirements and then compare to the generator’s rated capacity.
INSPECT COMPONENTS: Closely inspect to make sure no components are missing or damaged. See the “Unpacking
& Delivery Inspection” section for instructions on whom to contact to report missing or damaged parts.
ARRANGE FOR PROFESSIONAL INSTALLATION of a transfer switch if you will be connecting the generator
to your building’s electrical system. See the “Installation/Initial Set-Up” section for more information about this
requirement.
Any Questions, Comments, Problems, or Parts Orders
Call NorthStar Product Support 1-800-270-0810
Hazard Signal Word Definitions
2
Table of Contents
Hazard Signal Word Definitions .................................................................................................2
About Your Generator .................................................................................................................4
Thank you for purchasing your NorthStar portable generator!
This engine-driven, portable generator is designed to provide up to 8000 Watts of
electrical power (6600 watts continuous, 8000 watts surge).It can supply power:
1. As a portable power source. You can plug appliances directly into the generator’s
electrical outlets.
2. As a back-up, standby power source for a building. A licensed electrician can connect
the generator to your building’s electrical system via the installation of an UL-approved transfer switch. (See the “Installation & Initial Set-up” section of this manual to learn
more about specific requirements and precautions relating to wiring the generator to your
building’s electrical system.)
You must select a generator adequately sized for your power needs. You need to
determine the power needs of all the appliances/tools you wish to power at the same time and
choose a generator rated to provide at least that power level. See the “Power Load Planning &
Management” section of this manual to determine your specific power load requirements and
then compare them to this generator’s rated capacity. You must not overload the generator.
Overloading will cause damage to the generator and attached electrical devices, and may also
result in fire
Be sure to read about site selection and grounding requirements for running this
generator. More detailed information can be found in the “Installation & Initial Set-up, Steps
5 & 6” of this manual.
This generator is too heavy for one person to lift without mechanical assistance. An
optional wheel kit is available from NorthStar and is recommended if you will be moving the
generator unassisted. Other optional accessories available from NorthStar include a vi nyl
cover for storage, UL-approved transfer switches, and extension cords.
Contact NorthStar Product Support at 1-800-270-0810 with questions about optional
accessories or to order.
Read this Manual
About Your Generator
Improper use or maintenance of this generator can result in serious injury or death from
carbon monoxide poisoning, electric shock/electrocution, fire/explosion, or burns.
Read this manual completely before using the generator and follow all instructions and
safety rules.
You must follow all instructions and safety precautions presented throughout this manual. A
summary of important safety information can be found at the end of the manual. Keep this
manual for reference and review.
Proper preparation, operation, and maintenance will result in operator safety, as well as best
performance and long life of the generator. For detailed engine operation and maintenance
information, always refer to the engine Owner’s Manual furnished with the generator.
WARNING
4
About Your Generator (cont’d)
NorthStar is constantly improving its products. The specifications outlined herein are subject
to change without prior notice or obligation. The purchaser and/or user shall assume liability
for any modification and/or alterations of this equipment from original design and
manufacture.
Before using, the user shall determine the suitability of this product for its intended use and
assumes liability therein.
Contact NorthStar Product Support at 1-800-270-0810 for any questions about the
appropriate use of this generator.
Warranty Registration
Please fill out and submit the warranty registration card so that we have your contact
information for any future product literature or replacement parts you may need.
ATTENTION:
All Rental Companies and Private Owners who loan this
All persons to whom you rent/loan this generator must have access to and read this manual.
Keep this owner’s manual with the generator at all times and advise all persons who will
operate the machine to read it. You must also provide personal instruction on how to safely
operate the generator and remain available to answer any questions a renter/borrower might
have.
equipment to others!
5
Specifications
SPECIFICATIONS
Item Number 165920
Maximum Output 8000 Watts (W)
Continuous Output 6600 Watts (W)
Voltage 120 / 240 Volt (V)
Phase Single phase (4-wire)
Frequency 56.5 - 63.3 Hertz (Hz)
Power Factor 1.0 p.f.
Engine 13 HP Honda GX390
Engine Speed 3390 - 3798 RPM
Fuel Type Unleaded gasoline
Fuel Capacity 6.5 gallons (24.6 L)
Oil Capacity 1.16 US quarts (1.1 L)
Starting Method Electric Start / Recoil
120 V Receptacle (2) 20 Amp (A) duplex GFCI (NEMA 5-20R)
1) contain caustic acid, 2) emit explosive gases, 3) can cause electric shock
ALWAYS use eye protection. Caustic acid and explosive gases can cause blindness or severe burns.
NO smoking, sparks, or flames.
NEVER touch both battery terminals at the same time with your hand or any non-insulated tools.
FLUSH immediately with water if battery acid contacts eyes, skin, or clothing.
CONNECT cables in correct sequence: FIRST RED to POSITIVE terminal, then BLACK to NEGATIVE
terminal. When disconnecting, DISCONNECT BLACK cable first, then RED.
NEVER charge a visibly damaged or frozen battery. ALWAYS read and follow charger instructions.
IF GENERATOR IS TO BE STORED LONGER THAN 2 MONTHS,
charge battery with a trickle charger that is rated for 3 amps maximum.
A charged battery ensures reliable engine starting.
PN 779396
• Commercial-grade electric start engine
• Extend run 6.5 gallon fuel tank
• Maintenance-free brushless alternator design
• Smooth running focus mount isolation system
Always make sure safety labels are in place and in good condition. If a safety label is
missing or not legible, order new labels or unsafe operation could result.
To order replacement safety labels, call NorthStar Product Support at 1-800-270-0810.
1 Air Cleaner 11 Gas Cap with Gauge
2 Oil Drain Plug 12 6.5 Gallon Gas Tank
3 Full Power Switch 13 Super Silent Muffler
4 Voltmeter 14 Generator Head
5 Idle Control On/Off Switch 15 Battery Box
6 Hour Meter 16 Vibration Isolation Mount
7 Main Line Circuit Breaker 30A 17 Recoil
8 50A Circuit Breaker 18 Fuel Shut-Off Valve
9 30A Circuit Breaker 19 Choke Lever
Refer to your Honda engine manual for air cleaner care.
Refer to your Honda engine manual for oil change
recommendations.
The switch reconnects the two generator windings from
parallel (120V only) to series (120/240V).
• 120V Only
any combination of 120 volt receptacles. The 120/240V
30A locking device receptacle is 120V only at this time.
• 120/240V
However, only half the power or 3300 watts (27.5A), can
be used at any one 120V receptacle. 120V output can
total 6600 watts.
Voltmeter needle should be in green area during all generator
load conditions.
This feature senses the load on the generator. With no load
on the generator the engine speed drops to idle. This saves
fuel and lengthens engine life. When a load is applied, the
engine speed returns to 3600 - 3780 RPMs. Turning the
switch off disables the sensing device and the generator will
run at 3600 - 3750 RPM whether or not a load is applied.
Note: When the engine is idling, it is normal for the
voltmeter needle to be in the red range.
Allows for better maintenance scheduling of generator.
30 amp (A) magnetic 2-pole main circuit breaker to protect
against electrical overloads.
50 amp (A) push-to-reset circuit breaker
30 amp (A) push-to-reset circuit breaker
20 amp (A) push-to-reset circuit breaker
The gas cap is extra large, creating a large hole for
refueling. You can monitor the fuel level without removing
the cap by using the fuel level indicator built into the gas
cap.
Large tank allows for extended run capabilities. ALWAYS
allow room for gasoline expansion by not filling the gas tank
completely full.
4 dB less than Honda’s standard muffler.
The electricity producing part of the generator.
The battery box provides protection for the battery and will
accept a standard lawn tractor size battery (Group U1-7).
The engine requires a 12-volts battery, with a minimum
rating of 18Ah (Amp-Hour). See battery section for sizing.
The engine and generator are mounted on rubber cylinders
that absorb most of the engine vibration. This feature
eliminates the tendency of the machine to “walk” which is
common in engine powered equipment.
Grasp firmly when starting engine. Consult engine manual
for further instruction.
The engine is equipped with an ON-OFF valve located on
the left side of the recoil. ALWAYS keep this valve closed
when the generator is not in use.
Used during cold starts. Refer to the starting/stopping
instructions and the Honda engine manual for usage.
The engine key is located on the engine. Always locate this
switch and be familiar with its location before operating the
generator.
: Allows all 6600 watts (55A) to be used in
: Allows all 6600 watts to be used for 240V.
9
Power Load Planning & Management
WARNING
NEVER exceed the rated wattage capacity of your generator.
OVERLOADING may cause SERIOUS DAMAGE to the generator and
Your generator MUST BE SIZED PROPERLY to provide both the running and starting (surge)
wattage of the devices you will be powering. Before using your generator, determine the running
and starting wattage requirements of all the electrical devices you will be poweringsimultaneously.
The sum of the running and starting wattages of the devices being powered must not exceed the
continuous output rating of your generator. (The continuous output rating of your generator is listed
in the “Specifications” section of this manual.) Note that:
• Devices without electric motors such as light bulbs, radios, and televisions have the same
• Devices with electric motors such as refrigerators, compressors, and hand tools typically
The running and starting wattage requirements are often listed on a device’s nameplate. If wattage
is not given on the device’s nameplate, the wattage may be calculated by multiplying the nameplate
voltage by nameplate amperage, Watts = Volts X Amps.
If only the running voltage is given on the nameplate for a device with an electric motor, the starting
wattage can be approximated to be three to five times the running wattage.
Estimates for the running wattage requirements for common devices are listed in Table 1 below.
Guidance for starting wattages is provided in the table’s footnotes.
Table 1
Device
Air conditioner (12.000 BTU) 1700 (a,b) Jet pump 800 (a)
Battery charger (20 Amp) 500 Lawn mower 1200
Belt sander (3”) 1000 Light bulb (100 Watt) 100
Chain saw 1200 Microwave oven 700
Circular saw (6½”) 2000 (a,b) Milk cooler 1100 (a)
Coffee maker 1800 (a,b) Oil burner on furnace 300
Compressor (1 HP) 1400 (a,b) Oil-fired space heater (140,000 Btu) 400
Compressor (3/4 HP) 1800 (a) Oil-fired space heater (85,000 Btu) 225
Compressor (1/2 HP) 1400 (a) Oil-fired space heater (30,000 Btu) 150
Curling iron 700 Oven 4500
Dishwasher 1200 Paint sprayer, Airless (1/3 HP) 600 (a)
Edge trimmer 500 Paint sprayer, Airless (handheld) 150
Electric nail gun 1200 Radio 200
Electric range (1 element) 1500 Refrigerator 600 (b)
Electric skillet 1250 Slow cooker 200
attached electrical devices, and may result in fire.
running and starting wattage.
require a starting wattage that is 3 to 5 times greater than the running wattage.
Example conversion to watts:
120 Volts X 5 Amps = 600 Watts
Running
Watts Device
Running
Watts
10
Power Load Planning & Management (cont’d)
Device
Running
Watts Device
Running
Watts
Furnace fan (1/3 HP) 1200 (a) Submersible pump (1-1/2 HP) 2800 (a)
Freezer 800 (b) Submersible pump (1 HP) 2000 (a)
Hair dryer 1200 Submersible pump (1/2 HP) 1500 (a)
Hand drill (1”) 1100 Sump pump 600 (a)
Hand drill (1/2”) 875 Table saw 2000 (a)
Hand drill (3/8”) 500 Television 500
Hand drill (1/4”) 250 Toaster 1000
Hedge trimmer 450 Vacuum cleaner 250
Home computer 150 VCR 70
Impact wrench 500 Water Heater 3000
Weed trimmer 500
(a) Hard-starting motors require 3-5 times the rated running watts
(b) For extremely hard to start loads such as air conditioners and air compressors, consult the equipment dealer to
determine maximum wattage
To calculate the running and starting wattage requirements for the devices you will be
powering, follow these steps:
1. Make a list of all electrical devices you will be powering at the same time with the generator.
2. List the greater of the running or starting wattage next to each device as obtained from the
devices’ nameplate or Table 1. If only the running wattage for a device with an electric
motor is known, the starting wattage can be estimated to be at least 3 times the running
wattage.
3. Add the wattages for all devices on your list. This total must be lower than the continuous
output rating of your generator.
Example:
Device to be Powered
Light Bulb 75 W
Refrigerator – 18 Cu. Ft. 1600 W
Microwave 700 W
Window AC 1800 W
Sump pump (1/3 hp) 2100 W
Total 6275W
Greater of Starting/Running
Wattage
In this example, the generator must have a continuous output of at least 6275 W in order to
power all of the devices simultaneously.
STAGGERING LOADS
You can increase the number of devices your generator can power by staggering the load on the
generator. For example, you could alternately power your refrigerator and air conditioner for
limited periods of time -- powering only one of the devices at a time and never powering both at the
same time.
11
Installation / Initial Set-Up
There are a number of important steps required to set up your generator for initial use. These steps
are:
Steps for Installation / Initial Set-Up
1. Unpacking & delivery inspection.
2. Planning the power load to stay within the generator’s rated
capacity.
3. Setting up generator for the type of power generation you need:
a. portable power source, or
b. connected to a building as a back-up power source.
You should inspect the generator immediately after you receive delivery.
See the “Machine Component Identification” section of this manual for a
• If you have missing components, contact Product Support at 1-800-270-0810.
• If you have damaged components, contact the freight company that delivered the unit and file a
Plan your power load so that you do not exceed the generator’s rated capacity.
See the “Power Load Planning & Management” section of this manual to review how to plan and
manage power loads for the generator.
diagram of the generator and its components.
claim.
2. Planning the Power Load
12
Installation / Initial Set-Up
3. Set-up either as a BUILDING BACK-UP or PORTABLE Power Source
This generator is designed to provide up to 8000Wof electrical power. It can supply electricity in
two ways:
1. As a back-up, standby power source for a building. For this application, you must arrange
for a licensed electrician to connect the generator to your building’s electrical system via the
installation of an UL-approved transfer switch
accordance with building electrical code and guidelines supplied by your power company.
2. As a portable power source. You can plug appliances or tools directly into the generator’s
electrical outlets.
Specific requirements for each are given below.
Note: Regardless of whether you use your generator as a back-up power source connected to a
building or as a portable power source, you must not overload the generator. Overloading
may cause serious damage to the generator and attached electrical devices.
Using as a
Back-up Power
Source for a
Building
Contact a licensed electrician to install an UL-approved transfer switch if
you want to use your generator as a back-up power source for a building.
What does a transfer switch do? It:
a) Safely connects the generator to your building’s electrical system by
isolating your generator from your utility company’s power lines,
AND
b) Connects your generator to a critical subset of your building’s circuits
that are needed for emergency power needs.
If your generator will be connected to your building’s electrical system, it
MUST ALWAYS be isolated from the utility power grid with a UL-approved transfer switch installed by a licensed electrician in compliance with all
applicable building and electrical codes, and in accordance with guidelines
supplied by your power company.
DANGER:
A transfer switch must be installed in order to isolate your
generator from the utility power grid. If your generator is
NOT properly isolated from the utility system, serious
hazards will arise:
♦ When your generator is running, it’s output will back feed
into the utility power line and transformer that are
normally used to provide you with power. The
transformer will step up the current to the normal line
voltage. An unsuspecting utility line worker working on
what he thinks is a deactivated line could be electrocuted.
♦ If your generator is connected (running or not) when
utility power is restored, your generator will be destroyed.
It could also explode or cause fire.
In addition to isolating your generator from the utility system, the transfer
switch connects your generator to a limited set of circuits in your building
that have been chosen as critical to operate during a power outage.
. The transfer switch must be installed in
13
Y
A
NEMA
R
N
R
N
R
N
Using as a
Portable Power
Source
Installation / Initial Set-Up
The generator cannot power your entire home -- you must work with the
installing electrician to determine which devices/appliances you wish to
power during an outage. The electrician can help you determine which
circuits and devices can be powered simultaneously without overloading the
generator.
(See the previous section of this manual entitled “Power Load Planning &
Management” for more information on load application and selection.)
When using the generator as a portable power source, you can plug
electric devices and appliances directly into the generator’s electrical
outlets.
There are four different kinds of electrical outlets on the generator:
1. One 120 Volt, 50 Amp straight-blade receptacle (NEMA 5-50R
receptacle compatible with NEMA 5-50P mating plug)
2. One 120/240 Volt, 30 Amp locking receptacle (NEMA L14-30R
locking receptacle compatible with L14-30P mating plug)
3. One 120 Volt, 30 Amp locking receptacle (NEMA L5-30R receptacle
compatible with NEMA L5-30P mating plug)
4. Two 120 Volt, 20 Amp, duplex GFCI-protected straight-blade
receptacles (NEMA 5-20R duplex receptacles compatible with
NEMA 5-20P or 5-15P mating plugs) – with a single, shared trip
Note: This generator is equipped with a Full Power Switch that allows you
light and reset button.
to switch between 120V only or 120/240V power at the outlets. See
the “Machine Component Identification” section of this manual for
more information about the use of the Full Power Switch.
IDLE CON TR OL
DJUSTABLE IDLE
DELA
HOUR METER
RECEPTACLES
2X
EMA
FULL POWER
SWITCH
L14-30
EMA
L5-30
G
H
Y
H
N
X
120V
EMA
5-50
5-20R
(See more technical detail about these receptacles and their associated
circuit breakers in the “Machine Component Identification” section of this
manual.)
14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.