Mitsubishi PUH-4VKSA.UK Service Manual

Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
OUTDOOR UNIT
TECHNICAL & SERVICE MANUAL
Outdoor unit [Model names] [Service Ref.]
PUH-4VKSA PUH-4VKSA.UK
1999
No.OC184
CONTENTS
1. PART NAMES AND FUNCTIONS·····················2
2. SPECIFICATIONS·············································2
3. DATA··································································3
4. OUTLINES AND DIMENSIONS························4
5. WIRING DIAGRAM ···········································5
REFRIGERANT SYSTEM DIAGRAM
7. DISASSEMBLY PROCEDURE ·························7
8. PARTS LIST······················································9
9. OPTIONAL PARTS··························Back cover
The Slim Line. From Mitsubishi Electric.
··················6
Page 2
1 PART NAMES AND FUNCTIONS
PUH-4VKSA.UK
Air intake
Air outlet
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Input Running current Starting current
Model Motor output Starter type Protection devices Cranckcase heater
Fan(drive) o No. Fan motor output Airflow
Charge Oil (Model)
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
OUTDOOR UNIT
REFRIGERANT
PIPING
kW
A A
kW
kW
CMM
dB(A) mm(in) mm(in) mm(in) kg(lbs)
kg(lbs)
CC mm(in) mm(in)
3.52
16.3 79
PUH-4VKSA.UK
Single, 50Hz, 220~240V
Munsell 5Y 7/1
Capillary tube
Hermetic
NH56VNDT
2.7
Line start
Internal thermostat, thermal switch, Hp switch
38
Plate fin coil
Propeller (direct) o2
0.065+0.065 95
Reverse cycle
54
870(34-1/4)
295+24 (11-5/8 add 1)
1258(49-1/4)
94(207)
R-22
4.2(9.2)
1600 (MS-32)
9.52 (3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor :27¡C(80¡F)DB. 19¡C(66¡F)WB Outdoor :35¡C(95¡F)DB. 24¡C(75¡F)WB Heating : Indoor :20¡C(68¡F)DB. Outdoor :7¡C(45¡F)DB. 6¡C(43¡F)WB Refigerant piping length (one way) :5m (16ft)
2. Guaranteed operating range
3. Above values are as follows. Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz
Indoor 32¡C DB, 23¡C WB 21¡C DB, 15¡C WB
27¡C DB 20¡C DB
Outdoor
43¡C DB
-5¡C DB
24¡C DB, 18¡C WB
-5¡C DB, -6¡C WB
Upper limit Lower limit Upper limit Lower limit
Cooling
Heating
CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR UP TO 30m PIPING LENGTH AT SHIPMENT.
The unique refrigerant circuit and a large accumulator always control the optimal refrigerant level regardless of the length (50m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems. Therefore, it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps to speed up the installation work.
2 SPECIFICATIONS
2
Page 3
3 DATA
Service Ref.
5m 10m 15m 20m 25m
Refrigerant pipimg length (one way)
30m 35m 40m 45m 50m
3.5PUH-4VKSA.UK 3.6 3.8 3.9 4.1 4.2 4.4 4.5 4.6 4.8
Outdoor unit PUH-4VKSA.UK
NH56VNDTCompressor Model
0.64
1.55 —
U-V
(R-C)
Winding
Resistance
(')
at 20-C
U-W
(R-C)
W-V
1. REFILLING REFRIGERANT CHARGE (R-22 : kg)
2. COMPRESSOR TECHNICAL DATA
3
Page 4
150 10
1000For 10 units or less
300
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
Outdoor Unit-Necessary surrounding clearance
The upper side must be open.
Handle
for moving
138
95
Rear piping hole
23
33
Rear fresh
air intake
Side air intake
7 24(1)295(11-5/8)
Outlet guide
installation hole
302
Air intake
Air intake
Air outlet
870(34-1/4)
185
(7-9/32)
185
(7-9/32)
500(19-11/16)
330(13)
362(14-1/4)
1715
39.5 27.5
Terminal block for
indoor and outdoor
unit connection
Terminal block for power line
and Ground terminal
300
10
10
10
Note:Allow adequate
upper clearance
100
500
500
Service space
Handle for moving
52461
585
83 524
345
382
403
959
1258(49-1/2)
40 60524
Service panel
Handle
for moving
Refrigerant-pipe flared
connection [19.05 3/4F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,
drainage and wiring)
R20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
52
57
12
R6
104
39
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12o23 Oval holes
(standard bolt M10)
Front opening
4 OUTLINES AND DIMENSIONS
PUH-4VKSA·UK Unit : mm (inch)
4
Page 5
5 WIRING DIAGRAM
DISCHARGE PIPE THERMOSTAT26C
LED(CHECK,SERVICE)
LD1-LD8<O.B>
FUSE(6A)F<O.B>
FAN CONTROLLERFC<O.B>
COMPRESSOR CAPACITOR C2
C1 FAN MOTOR CAPACITOR
CRANKCASE HEATERHC
CONNECTOR(TRANSFORMER)
CN4T<O.B>
WIRES INDOOR/OUTDOOR)
CONNECTOR(CONNECTINGCN3<O.B>
NAMESYMBOL
EARTH
CRANKCASE HEATER RELAYX11<O.B>
OUTDOOR COIL THERMISTORTH
TERMINAL BLOCKTB1,3
TRANSFORMERT
SELECT SWITCH(CHECK,SERVICE)
SW1 • 2 • 3<O.B>
SOLENOID COIL(BYPASS VALVE)21R
OUTDOOR CONTROLLER BOARD
O.B
MF
MC
FAN MOTOR
COMPRESSOR
NAMESYMBOL
HIGH PRESSURE RELAYX16
PROTECT HIGH PRESSURE SWITCH
63H2
CONTROL HIGH PRESSURE SWITCH
63H1
COMPRESSOR CONTACTOR52C
4-WAY VALVE SOLENOID COIL21S4
SURGE ABSORBERZNR<O.B>
SOLENOID COIL RELAYX14<O.B>
SOLENOID COIL RELAY
COMPRESSOR RELAY
X13<O.B>
X12<O.B>
NAMESYMBOL
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
TB3
BRN
ORN
YLW
3
2
1
LED
O.B
LD8
LD7
LD6
LD5
LD4
LD3
LD2THLD1
CN2
12
ON
OFF
SW3
SW2
SW1
CN3
1
2
3
1234
CN4
X11X12X13X14
X11X12X13X14
220V
230V
240V
RED
ORN
YLW
T
AC12.3V
AC
12.3V
BRN
BRN
RED
RED
4
123
CN4T
4
POWER SUPPLY
~
(1PHASE)
220
-
240V 50Hz
N
L
TB1
RED
BLU
RED
BLU
GRN/YLW
RED
C2
S
C
R
RED
WHT
BLK
MC
52C
T3/6
T1/2
L3/5
L1/1
2
6
8
7
GRY
GRY
63H2
X16
X16
GRY
A2
52C
A1
GRY
GRY
HC
WHT
WHT
BLU
BLU
RED
RED
WHT
WHT
F
ZNR
CH52C21S4TRFSV
21R
21 S4
26C
5
1
VLT
VLT
X16
63H2
BLU
BLUBLU
63H1
BLK
BLK
YLW
YLW
BRN
BRN
RST
26C
63H1
51CM
5
MF2
RED
C1
ORN
RED
BLU
WHT
ORN
BLU
WHT
F. C
MF1
1
2
4
3
MF
BRN
C1
YLW
BRN
BLU
WHT
YLW
BLU
WHT
MF
1
2
4
3
26C Overheat protection
63H2 functions
(when both No.1 and No.2 of SW3 are "OFF")
Check Display (flashing)
TH overheat protection Defective input
Pipe sensor short/open
Compressor indoor command
Crankcase heater ON
Bypass valve ON
4-way valve ON
Outdoor fan ON
Compressor ON
63H1 ON
Heating indoor command
Output Display (light)
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
LED No.
Main functions of LED
The output display (light) remains during operation
in flashing mode. Pressing the switch again returns
How to use SW1 and SW2
but pressing SW2 displays the past check contents
to output display(light).
stored on the microcomputer.
Pressing SW1 erases the past check contents
NOTE: If the operation of the protection device stops to function, then check the display flashes.
Since the indoor and outdoor connecting wires have polarity,make sure to connect the same terminal numbers(1,2,3)for indoor and outdoor units.
Since LD8 lights when normal power is turned "ON", check the power supply with the ON or OFF LD8. w Since the outdoor transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connections according to the following procedure.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
CAUTIONS FOR POWER SUPPLY WIRING
Connect the lead wires according to the colour indication of the sticker on the compressor terminal.
CAUTION FOR SERVICING
RED WHITE
220V
YELLOW
240V
w When Power Supply is 220V
230V
ORANGE
PUH-4VKSA·UK
5
Page 6
6 REFRIGERANT SYSTEM DIAGRAM
Indoor unit
Outdoor unit
Indoor heat exchanger
Thermistor (TH2)
Strainer
Flexible tube
Service port (check)
Accumulator
Ball valve
Strainer
Compressor
Refrigerant pipe (option)
19.05A({3/4") (with heat insulator)
Refrigerant pipe (option)
9.52A({3/8") (with heat insulator)
Ball valve (with service port)
Strainer
Bypass valve
Restrictor valve
4-way valve
Oil separator
Service port
High pressure Control switch
Protective high pressure switch
Outdoor heat exchanger
Thermistor TH3
W1(O.D.3.2OI.D.2.0-R820)O2pcs
Distributor with strainer
Restrictor valve
Capillary tube
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Thermal switch (Discharge)
Capillary tube W1
PUH-4VKSA·UK
Unit : mm
6
Page 7
7 DISASSEMBLY PROCEDURE
PUH-4VKSA·UK
OPERATING PROCEDURE PHOTOS
1. Removing the electrical parts
(1)
Remove the 3 screws at the front and 2 screws at the rear of the top panel.
(2)
Remove the top panel.
(3)
Remove the screw from the panel cover. Unhook the catches from the side panel and pull the panel cover toward you to remove.
(4)
Remove the screw from the service panel. Pull down the service panel to unhook the catches. Pull the service panel toward you to remove.
Photo 1
Screws
Panel cover
Photo 2
2. Removing the fan motors
(1)
Remove the 3 screws and the front panel. Open the panel to a 45-degree angle and lift it to remove. The panel is hooked by 3 catches on the left side.
(2)
Remove the propeller nuts and the propellers.
(3)
Remove the 3 screws each and the fan motors. Disconnect the lead connectors.
Screws
Photo 3
Motor support
Terminal block
Separator support plate
High pressure switch
Propeller nut
Propeller
7
Valve bed
Page 8
OPERATING PROCEDURE PHOTOS
3. Removing the heat exchanger and the compressor NOTE :When removing the panels, move them up and down
to unhook catches.
(1)
Remove the rear panel set screws : 2 screws at the
front, 1 screw on the side, and 3 screws at the rear.
(2)
Remove the valve bed.
(3)
Open the rear panel rearward to remove.
(4)
Remove the 4 screws of the right side panel and remove it.
(5)
Remove the 3 screws of the rear guard and remove it.
(6)
Remove the 4screws of the separator support plate and remove it.
(7)
Remove the 2 screws of the motor support and remove it.
(8)
Remove the 5 screws of the valve bed. Lift the valve bed to unhook the catches on both sides.
(9)
Remove the electrical parts box.
)
(
Disconnect the connectors of the high-pressure
10
switch, crankcase heater, shell thermo, and fan motor.
(11)
Remove the 2 screws of the separator and remove it.
(12)
Remove the 2 screws of the heat exchanger and
remove it.
(13)
Detach the brazed points of the pipe.
(14)
Remove the 3 nuts of the compressor and remove it.
(15)
Detach the welded points of the suction pipe and
discharge pipe.
Photo 4
Screws
Screws
Photo 5
Heat exchanger
Photo 6
8
Charge plug
Ball valve
Compressor
Accumulator
Page 9
8 PARTS LIST
STRUCTURAL PARTS PUH-4VKSA·UK
12
10
13
1
14
96
7
3
2
4
3
4
No.
Part No.
1
S70 020 641
2
S70 004 668
3
S70 001 675
4
S70 A00 655
5
S70 004 661
6
S70 040 662
7
S70 040 682
8
S70 020 658
9
S70 040 698
10
S70 050 130
11
S70 001 686 12 13 14
11
Q'ty/set
Part name
TOP PANEL FRONT PANEL FAN GUARD PANEL HANDLE SERVICE PANEL SIDE PANEL REAR PANEL PANEL COVER REAR GUARD MOTOR SUPPORT
BASE – – –
F.ST SCREW
MOTOR PLATE
LABEL(MITSUBISHI)
Specification
PUH-4
VKSA.UK
1 1 2 3 1 1 1 1 1 1 1
13
1 1
5
Remarks
(Z004M203H10) (BG00G231G01) (BC79G510H01)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Price
Amount
8
9
Page 10
FUNCTIONAL PARTS PUH-4VKSA·UK
30
29
6 5 3 7 9 8
32
1
23 33
2
1
24
18
13
31
30
17 15
2
34 27
11
14
10
22
19 25 26 21 20
28
10
Page 11
No.
Part No.
Part name
Specification
Remarks
Unit
Amount
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
PUH-4
Price
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
FAN MOTOR PROPELLER OUTDOOR CONTROLLER BOARD D.P ASSY TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER FAN MOTOR CAPACITOR COMPRESSOR CONTACTOR SOLENOID VALVE SOLENOID COIL CAPILLARY TUBE RESTRICTOR VALVE STRAINER 4-WAY VALVE DISCHARGE PIPE THERMOSTAT STRAINER CHARGE PLUG CHARGE PLUG BALL VALVE BALL VALVE OIL SEPARATOR ACCUMULATOR OUTDOOR COIL THERMISTOR COMPRESSOR CRANKCASE HEATER CONTROL HIGH PRESSURE SWITCH PROTECT HIGH PRESSURE SWITCH OUTDOOR HEAT EXCHANGER NUT CAPILLARY TUBE HIGH PRESSURE RELAY COMPRESSOR CAPACITOR 4WAY COIL
VKSA.UK
2 2 1 1 1 1 1 2 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1
S70 040 763 S70 001 115 S70 A04 315 S70 A01 529 S70 509 716 S70 516 716 S70 106 799 S70 39J 255 S70 956 708 S70 272 428 S70 106 242 S70 A00 425 S70 993 418 S70 42L 450 S70 260 403 S70 A02 201 S70 A11 450 S70 943 413 S70 A01 413 S70 670 411 S70 943 410 S70 A14 490 S70 A12 440 S70 A00 202 S70 610 300 S70 A02 236 S70 A00 208 S70 A04 208 S70 012 408 S70 30L 097 S07 113 425 S70 737 215 S70 040 723 S70 A00 242
O.B
TB1 TB3
T
C1
52C
21R
26C
TH
MC
HC 63H1 63H2
X16
C2
PN6V60-UA
3P(L,N,;) 3P(1,2,3)
4+ 440V S-N35
{3.2O{2.0O820mm
3/4" 3/8"
NH-56VNDT 240V 38W
M8
{2.5O{0.6O1000A
LY-2F 230V 10A 60
+ 450V
OFF ON
2.55MPa 2.1MPa OFF ON
3.3MPa 2.1MPa
MF
Part numbers that are circled are not shown in the figure.
11
Page 12
9 OPTIONAL PARTS
538
537
5247
524
72
7
{6
4 holes
7
7
AIR OUTLET GUIDE
This guide is for changing the outdoor unit air discharge direction. For PUH-4/5/6 type, 2 sets of PAC-292SG are needed.
Part No.
Applied Service
PAC-292SG(1 pc/set PUH-1.6~6K(S)A type
)
© Copyright 1999 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Issued in Mar.1999 No.OC184 242 New publication, effective Mar.1999 Printed in Japan. Specifications subject to change without notice.