CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR MAXIMUM PIPING LENGTH AT SHIPMENT.
The unique refrigerant circuit and a large accumulator always control the optimal refrigerant level regardless of the length
(30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems.
Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps
to speed up the installation time.
39.5 27.5
Terminal block for indoor and outdoor unit connection
Terminal block for power line
Handle for moving
77
524
339
282
297
444
650 (25-5/8)
4060524
Service panel
Ground terminal
Refrigerant-pipe flared
connection
[15.88 3/8F
Refrigerant-pipe flared
connection
[9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,drainage
and wiring)
R
20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
42
45
12
R6
104
33
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12✕23 Oval holes
(standard bolt M10)
Handle for moving
PUH-1.6VKA2/PUH-2VKA
2
Unit : mm (inch)
5
Page 6
PUH-2.5VKA
10010
1000For 10 units or less
200
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
The upper side must be open.
Outdoor Unit-Necessary surrounding clearance
200
10
10
10
Note:Allow adequate
upper clearance
150
500
500
Service space
Front opening
138
95
Rear piping hole
23
33
Rear fresh
air intake
Side air intake
724(1)295(11-5/8)
Outlet guide
installation hole
302
Air intake
Air intake
Air outlet
870(34-1/4)
185
(7-9/32)
185
(7-9/32)
500(19-11/16)
330(13)
362(14-1/4)
1715
39.5 27.5
Terminal block for indoor and outdoor unit connection
Terminal block for power line
Handle for moving
179524
441
337
352
403
553
850(33-7/16)
4060524
Service panel
Ground
terminal
Refrigerant-pipe flared
connection [15.88 5/8F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,drainage
and wiring)
R
20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
42
45
12
R6
104
33
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12✕23 Oval holes
(standard bolt M10)
Handle for moving
2
PUH-3VKA2/PUH-3YKA
2
Unit : mm (inch)
6
Page 7
PUH-4YKSA
300
Outdoor Unit-Necessary surrounding clearance
3
Note:Allow adequate
upper clearance
10
Front opening
10
1715
185
(7-9/32)
100
500
Service space
500
10
Terminal block for
indoor and outdoor
unit connection
362(14-1/4)
330(13)
39.5 27.5
Terminal block for power line
Ground
terminal
Service panel
Handle
for moving
Refrigerant-pipe flared
1258(49-1/2)
959
4553
Knock out holes for
60
connection [19.05 3/4F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
403
382
power line 2-[27
120
(refrigerant,drainage
and wiring)
104
R20
20
R
Knock out hole
for right piping
(refrigerant,
57
52
Bottom
39
Unit : mm (inch)
Standard bolt length
25 max.
80
65
Front right piping holes-
17
R6
drainage and wiring)
piping hole
2-U-shaped
notched
holes
detail figures
12
Air intake
500(19-11/16)
185
(7-9/32)
Air intake
300
1000For 10 units or less
The upper side must be open.
870(34-1/4)
302
Air outlet
Outlet guide
724(1)295(11-5/8)
installation hole
Side air intake
52461
585
Handle for moving
Rear fresh
air intake
345
2-12✕23 Oval holes
(standard bolt M10)
83524
4060524
Drain hole
33
23
Drain hole
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
15010
Handle
for moving
Rear piping hole
95
138
7
Page 8
PUH-5YKSA3/PUH-6YKSA
15010
1000For 10 units or less
300
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
Outdoor Unit-Necessary surrounding clearance
The upper side must be open.
Handle
for moving
138
95
Rear piping hole
23
33
Rear fresh
air intake
Side air intake
724(1)345(13-9/16)
Outlet guide
installation hole
352
Air intake
Air intake
Air outlet
970(38-3/16)
185
(7-9/32)
185
(7-9/32)
600(23-5/8)
380(14-31/32)
412(16-1/4)
1715
39.5 27.5
Terminal block for
indoor and outdoor
unit connection
Terminal block for power line
300
10
10
10
Note:Allow adequate
upper clearance
150
500
500
Service space
Handle for moving
52461
585
83524
345
382
403
959
1258(49-1/2)
9060524
Service panel
Ground
terminal
Handle
for moving
Refrigerant-pipe flared
connection [19.05 3/4F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,
drainage and wiring)
R
20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
52
57
12
R6
104
39
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12✕23 Oval holes
(standard bolt M10)
Front opening
2
Unit : mm (inch)
8
Page 9
5WIRING DIAGRAM
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
SW1
SW2
SW2
21
OFF
ON
O.B
3
2 CN3
CN4T
1
4321
CN4
4321
4
T
YLW
ORN
BRN
FROOM INDOOR UNIT
CONNECTING WIRES
12V DC (polar)
2
1
TB1
L
N
3
TB3
LED
BRN 12.3V AC
RED 12.3V AC
RED
ORN
YLW
220V
230V
240V
POWER SUPPLY
~/N(1phase)
220-240V 50Hz
GRY/YLW
BLK
REDR
T
UWBLU
WHT
BLURED
BLK
RED
52C
C2
MC
R
S
C
21R
RED
RED
RED
RED
SV
✕14
21
S4
21S4
✕13
WHT
WHT
WHT
BRN
BRN
YLW
YLW
YLW
YLW
BLU
WHT
WHT
TRF
52C
GRY
GRY
GRY
GRY
52C
✕12
CHZNR R/1 S/2 T/3
BLU BLU
BLU
✕11
A
S
B
HC
RT
CN2
✕14 ✕13 ✕12 ✕11
4
3
2
1
MF
F
63H1
63H1
FC
26C
MF2
63H2
51CM
MF1
S
BLU
RED
ORN
WHT
RED
ORN
C1
PUH-1.6VKA
SYMBOL
HC
C1
C2
FC<O.B
F<O.B
21S4
21R
LD1~LD8
CRANKCASE HEATER
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6A
R.V.COIL
B.V.COIL
CHECK,SERVICE LED
2
NAME
)
SYMBOL
MC
MF
O.B
SW1·2·3<O.B
T
TB1,3
RT
X11<O.B
COMPRESSOR (INNER THERMOSTAT)
NAME
OUTDOOR FAN MOTOR (
INNER THERMOSTAT)
OUTDOOR CONTROLLER BOARD
>
CHECK,SERVICE SELECTOR
TRANSFORMER
TERMINAL BLOCK
OUTDOOR COIL THERMISTOR
(
0˚C/15kΩ,25˚C/5.4kΩ
>
HC RELAY
)
SYMBOL
X12<O.B
X13<O.B
X14<O.B
ZNR<O.B
52C
63H1
>
COMPRESSOR RELAY
>
21S4 RELAY
>
21R RELAY
>
VARISTER
CONTACTOR
HIGH PRESSURE SWITCH
NAME
Main functions of LED
LED No.
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
NOTE : If the operation stops and the protection device is functioning, the check display will flash.
How to use SW1 and 2
●
Pressing erases the past check contents loaded on the microcomputer.
●
The output display (light) remains lit during operation, but pressing displays the past check contents by a flashing mode.
Pressing the switch again returns it to output display (light).
CAUTION FOR SERVICING
●
The connector marked s turns the compressor ON and OFF during servicing.
The compressor stops when the white connector is disconnected. See fig.1.
CAUTIONS FOR POWER SUPPLY WIRING
●
Since LD8 lights when normal power is turned ”ON”, check the power supply with the ON or OFF LD8.
❈
Since the indoor transformer (T) is connected with 240V power, using 220V or 230V power will require a wiring connection change. See fig.2.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires have polarity, be sure to connect the same terminal numbers (1,2,3) for the indoor and outdoor units.
If the operation stops to function of the protection device, the check
display flashes.
How to use SW1 and 2
●
●
SW1
Pressing erases the past check contents loaded on the microcomputer.
The output display (light) remains during operation but pressing displays the
past check contents in flushing mode.
Pressing the switch again returns to output display (light).
SW2
10
Page 11
PUH-3VKA
SYMBOL
CN3(O.B
CN4T(O.B
HC
C1
C2
FC(O.B
F(O.B
LD1-LD8
)
CONNECTING WIRES
INDOOR/OUTDOOR CONNECTOR
)
TRANSFORMER CONNECTOR
CRANKCASE HEATER
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
)
FAN CONTROLLER
)
FUSE(6,3A
CHECK,SERVICE LED
2
NAME
)
SYMBOL
MC
MF
O.B
21R
SW1·2·3(O.B
T
TB1,3
RT
X11(O.B
)
COMPRESSOR (INNER THERMOSTAT)
NAME
OUTDOOR FAN MOTOR (INNER THERMOSTAT)
OUTDOOR CONTROLLER BOARD
BYPASS VALVE SOLENOID COIL
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR POWER SUPPLY WIRING
●
Since LD8 lights when normal power is furned ”ON”, check the power supply with the ON or OFF LD8.
❈
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used,
change the wiring connection in the following procedure.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
❈When power supply is 220V
REDWHITE
220V
ORANGE
YELLOW
230V
240V
11
Page 12
PUH-3YKA
L1L2L3
Power line reconnection procedure
In case of reverse rotation
Unit side
wiring
Outdoor unit
terminal
Field wiring
Change thie side
charge 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
123
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
SW1
SW2
SW3
OFF
ON
21
3
2
1
CN3
CN2
4321
4321
CN4T
CN4
BRN
BLK
RED
WHT
BLU
WHT
WHT
RED
RED
RED
ORN
220V
BRN
RED
RED
AC
12.3V
AC12.3V
YLW
230V
240V
T
3
BRN
2
ORN
1
YLW
TB3
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
O.B.
LED
RT
21R
SVTRF
RED
RED
21S4
GRY
GRY
BRN
BRN
ORN
ORN
YLW
YLW
52C
52C
WHT
WHT
CH
4
21
S4
A1
A2
HC
✕14✕13
✕14 ✕13 ✕12 ✕11
✕12✕11
ZNR
F
RST 5
63H126C51C
96
95
3
4
2
1
MF
WHT
BLU
WHT
BLU
REDRED
ORN
ORN
C1
63H1
26C
51C
F.C.
MF1
MF2
T1/2
L1/1
L3/5
T3/6
BLU
WHT
RED
TB1
BLK
WHT
BLU
51C52C
MC
U
W
V
GRN/YLW
L1
L2
L3
N
POWER SUPPLY
3N~
380/220-415/240V 50Hz
T2/4
L1/1
L3/5
L2/3
SYMBOL
CN3<O.B
CN4T<O.B
C
FC<O.B
F<O.B
HC
LD1-LD8
MC
>
CONNECTING WIRES
INDOOR/OUTDOOR CONNECTOR
>
TRANSFORMER CONNECTOR
FAN MOTOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6.3A
CRANKCASE HEATER
CHECK,SERVICE LED
COMPRESSOR
2
NAME
)
SYMBOL
MF
O.B
SW1·2·3<O.B
T
TB1,3
RT
X11<O.B
X12<O.B
X13<O.B
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
❈When power supply is 220V
ORANGE
YELLOW
REDWHITE
220V
230V
240V
Page 13
PUH-4YKSA
SYMBOL
CN3<O.B
CN4T<O.B
C1,2
FC<O.B
F<O.B
HC
LD1-LD8
MC
>
CONNECTING WIRES
INDOOR/OUTDOOR CONNECTOR
>
TRANSFORMER CONNECTOR
FAN MOTOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6,3A
CRANKCASE HEATER
CHECK,SERVICE LED
COMPRESSOR
3
NAME
)
SYMBOL
MF1,2
O.B
SW1·2·3(O.B
T
TB1,3
RT
X11(O.B
X12(O.B
X13(O.B
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Unit side
wiring
Field wiring
Change thie side
Power line reconnection procedure
In case of reverse rotation
L1L2L3
charge 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
123
and 2.)
❈When power supply is 220V
REDWHITE
220V
ORANGE
YELLOW
230V
240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Outdoor unit
terminal
13
Page 14
PUH-5YKSA
SYMBOL
MC
MF1,2
C1,2
RT
HC
49C
52C
21S4
21R
COMPRESSOR
OUTDOOR FAN MOTOR (INNER THERMOSTAT)
FAN MOTOR CAPACITOR
OUTDOOR COIL THERMISTOR
CRANKCASE HEATER
INTERNAL THERMOSTAT FOR MC
CONTACTOR
4-WAY VALVE SOLENOID COIL
BYPASS VALVE SOLENOID COIL
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
●
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnection procedure
In case of reverse rotation
Unit side
wiring
Field wiring
Change thie side
L1L2L3
123
❈When power supply is 220V
REDWHITE
ORANGE
YELLOW
charge 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
220V
230V
240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
14
Outdoor unit
terminal
Page 15
PUH-6YKSA
SYMBOL
MC
MF1,2
C1,2
RT
HC
49C
52C
21S4
21R
T
COMPRESSOR
OUTDOOR FAN MOTOR (INNER THERMOSTAT)
FAN MOTOR CAPACITOR
OUTDOOR COIL THERMISTOR
CRANKCASE HEATER
INTERNAL THERMOSTAT FOR MC
CONTACTOR
4-WAY VALVE SOLENOID COIL
BYPASS VALVE SOLENOID COIL
TRANSFORMER
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
●
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnection procedure
In case of reverse rotation
Unit side
wiring
Field wiring
Change thie side
L1L2L3
123
❈When power supply is 220V
REDWHITE
ORANGE
YELLOW
charge 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
220V
230V
240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Outdoor unit
terminal
15
Page 16
Indoor unit
Outdoor unit
Indoor
heat
exchanger
Thermistor
TH2
Strainer
Flexible tube
Service
port
Accumulator
Ball valve
Strainer
Compressor
Refrigerant pipe
(option)
19.05A({3/4")
(with heat insulator)
Refrigerant pipe
(option)
9.52A({3/8")
(with heat insulator)
Ball valve
(with service port)
Strainer
Bypass
valve
Restrictor
valve
4-way valve
Oil
separator
Service
port
High pressure
control switch
Outdoor heat exchanger
Thermistor
RT
Capillary tube
PUH-5
....
(O.D.4.0✕I.D.2.4-R840)✕2
PUH-6
....
(O.D.4.0✕I.D.2.4-R1200)✕2
Distributor
with
strainer
Restrictor valve
Capillary
tube
Flared
connection
THERMAL
SWITCH
Capillary tube
6REFRIGERANT SYSTEM DIAGRAM
Indoor unit
Outdoor unit
Indoor
heat
exchanger
Indoor coil
thermistor
(TH2)
Strainer
Flexible tube
Service
port
(check)
Accumulator
Ball valve
Strainer
Compressor
Refrigerant pipe
(option)
19.05A({3/4")
(with heat insulator)
Refrigerant pipe
(option)
9.52A({3/8")
(with heat insulator)
Ball valve
(with service port)
Strainer
Bypass
valve
Restrictor
valve
4-way valve
Oil separator
Service
port
High pressure
control switch
Outdoor heat exchanger
Outdoor coil
thermistor
(RT)
Capillary
tube
(O.D.3.2✕I.D.2.0-R820)✕2pcs
Distributor
with
strainer
Restrictor
valve
Capillary
tube
Flared
connection
Refrigerant flow in cooling
Refrigerant flow in heating
Remove the 5 screws and the top panel. (3 screws in
front and 2 screws in rear
(2)
Remove the screw of the cover panel. To remove the
cover panel, pull it toward you and unhook the catches
from the side panel.
(3)
Remove the screw of the service panel. To remove the
service panel, pull it down toward you and unhook the
catches on the both sides.
)
2
Photo 1
Screws
Top panel
Service panel
Panel cover
Front panel
Photo 2
Outdoor controller
board
TransformerCapacitor
Contactor
2. Removing the fan motor
(1)
Remove the 3 screws of the front panel. Open the
front panel to a 45-degree angle. Then lift it and
unhook the 3 catches to remove.
(2)
Remove the propeller nut and the propeller.
(3)
Remove the 3 screws and the fan motor.
Disconnect the lead connectors.
Photo 3
Propeller
Motor support
Overcurrent
relay
Terminal blockScrews
Separator support plate
High-pressure control
switch
Lead
connectors
Valve bed
Propeller nutCrankcase heater
17
Page 18
OPERATING PROCEDUREPHOTOS
3. Removing the heat exchanger and the compressor
(1)
Remove the rear panel (2 screws in front, 1 screw on
the side, 3 screws in the rear). Remove the valve bed,
and open the rear panel to the rear to remove.
NOTE :
All panels are fixed by catches, and must be removed by
shifting up and down.
(2)
Remove the 4 screws of the right side panel and
remove it.
(3)
Remove the 3 screws of the rear guard and remove it.
(4)
Remove the 4 screws of the separator support plate
and remove it.
(5)
Remove the 2 screws of the motor support and
remove it.
(6)
Remove the 5 screws of the valve bed.
The valve bed is fixed by the catches on the right and
left sides.
Lift it to remove.
(7)
Remove the electrical parts box.
Disconnect the connectors from the high pressure
switch, crank case heater, shell thermo, and fan motor
lead.
(8)
Remove the 2 screws of the separator and remove it.
(9)
Remove the 2 screws of the heat exchanger and
remove it.
Detach the welded point of pipe.
)
(
Remove the 3 nuts of the compressor and remove it.
10
Detach the welded points of the compressor suction
pipe and discharge pipe.
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE
(5✕10)
Q,ty/set
PUH-1.6
VKA,VKA
1,VKA2
Remarks
(Drawing No.)
1
13
1
1
3
1
1
2
1
1
1
1
1
(ZOO4M203H10)
(DG79R130H01)
(BG00B020G47)
STRUCTURAL PARTS
PUH-1.6VKA
PUH-1.6VKA1
PUH-1.6VKA2
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE