Mitsubishi Electric MS-A18VD-K1, MS-A18VD-K2, MS-A24VD-K1, MS-A18VD, MS-A30VD-K2 Service Manual

...
SPLIT-TYPE AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Models
Revision C:
• Another type of the electronic control P.C. board (TYPE 2) has been added to the original one (TYPE 1). They are both com­patible with MS-A18/24/30VD- .
Please void OB400, REVISED EDITION-B.
K
No. OB400
REVISED EDITION-C
MS-A18VD­MS-A18VD­MS-A24VD­MS-A24VD­MS-A30VD­MS-A30VD-
MS-A18VD MS-A24VD MS-A30VD
K1
K2
K1
K2
K1
K2
Outdoor unit service manual
MU-A·VD Series (OB401)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. OUTLINES AND DIMENSIONS·························6
5. WIRING DIAGRAM ············································7
6. REFRIGERANT SYSTEM DIAGRAM················9
7. SERVICE FUNCTIONS ····································10
9. DISASSEMBLY INSTRUCTIONS ····················21
10. PARTS LIST······················································23
11. RoHS PARTS LIST···········································26
NOTE:
• This service manual describes technical data of the indoor units.
• RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
TM
Indoor unit:Unit size:W1,015mmoH320mmoD190mm W1,100mmoH325mmoD258mm Electricity receiving unit: Indoor unit Outdoor unit Rated voltage : 220/240V 220-230-240V
Frequency New Model Old Model
MS-18NV -
KB
w
: change
MS-A18VD -
K1
50Hz
MS-18UV -
P1
MS-18RV -
R1
w w w
w w
w
Indoor unit:Unit size:W1,015mmoH320mmoD190mm W1,100mmoH325mmoD258mm Electricity receiving unit: Indoor unit Outdoor unit Rated voltage : 220/240V 220-230-240V
Frequency New Model Old Model
MS-24NV -
K1
MS-A24VD -
K1
50Hz
MS-24UV - P1MS-24RV -
R1
w w w
w w
w
Indoor unit:Unit size:W1,100mmoH325mmoD227mm W1,100mmoH325mmoD258mm Rated voltage : 220/240V 220-230-240V
Frequency New Model Old Model
MS-30SV - K1MS-30SV -
P1
MS-A30VD -
K1
50Hz
w w
w
Use the specified refrigerant only
OB400C
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• MS-A18VD- , MS-A24VD- and MS-A30VD- have been added.
K2K2K2
Revision B:
• Remote controller model “KM04B” has been added. There are two remote controller models for “ ” and “ ”. (KP0B, KM04B) You can use the remote controller model “KP0B” and “KM04B”. The remote controller model “KM04B” is supplied as service parts for “ ” and “ ”.
K2K1
K2K1
Revision C:
• Another type of the electronic control P.C. board (TYPE 2) has been added to the original one (TYPE 1). They are both com-
patible with MS-A18/24/30VD- .
K
TECHNICAL CHANGES1
MS-A18VD - MS-A18VD ­MS-A24VD - MS-A24VD ­MS-A30VD - MS-A30VD -
1. Fan guard has been added.
2. Fan speed has been changed.
K2K1
K2K1
K2K1
3. Wiring diagram has been changed.
4. FUSE (F12) has been removed. (MS-A18/24VD- )
5. “8-5.C Check of indoor electronic control P.C. board” has been changed.
K2
2
2
OB400C
PART NAMES AND FUNCTIONS
INDOOR UNIT
MS-A18VD MS-A24VD MS-A30VD
Air cleaning filter (White bellows type)
Front Panel
Catechin air filter
Vertical vanes
Horizontal vane
Operation section
(When the grille is opened)
Emergency operation switch
Grille
Air inlet
Remote control
receiving section
Remote controller
Display section
Operation indicator lamp
Remote control
receiving section
3
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
WIDE VANE
LONG
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET CLOCK
FAN
Open the front lid.
Signal transmitting section
Operation display section
OPERATE/ STOP
(ON/ OFF)button
TEMPERATURE buttons
Indication of remote controller model is on back.
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE button
(Horizontal vane button)
CLOCK SET button
LONG button
WIDE VANE button
(Vertical vane button)
Installation plate Installation plate fixing screw 4 x 25 mm Remote controller holder Fixing screw for 3 3.5 x 16 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping) Air cleaning filter Pipe cover
1 2 3 4 5 6 7 8 9
1 7 1 2 2 1 1 2
ACCESSORIES
OB400C
REMOTE CONTROLLER
MS-A18VD MS-A24VD MS-A30VD
4
3
Indoor model
Function
Power supply
Air flow
(High/Med./Low) Running current Power input Auxiliary heater Power factor Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level
(High/Med./Low)
Fan speed
(High/Med./Low) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Thermistor RT13(at 25:) Remote controller model
Electrical
data
Fan
motor
Special
remarks
Capacity
Cooling
Single phase
220-230-240V, 50Hz
1,100O325O258
16
5
3 10 10
KP0B / KM04B
0.33-0.34-0.35 67-69-75
92-88-89
0.33-0.34-0.35
RC4V40-AA WHT-BLK 138.2 RED-BLK 159.0
774/660/552
0.30-0.30-0.31 60-60-64
91-87-86
0.30-0.30-0.31
RC4V32-AA WHT-BLK 293.0 RED-BLK 146.0
42/37/33
K /h
A
W
A(kW)
%
A
"
mm
kg
dB
rpm
k" k" k"
972/828/684
45/41/37
1,220/1,070/910 1,280/1,130/970
1,220/1,070/910 1,280/1,130/9701,010/880/760 1,070/920/780
10
MS-A18VD - K1 MS-A18VD - K2 MS-A24VD - K1 MS-A24VD - K2 MS-A30VD - K1 MS-A30VD - K2
OB400C
SPECIFICATION
NOTE:Test conditions are based on ISO 5151.
Cooling : Indoor Dry-bulb temperature 27: Wet-bulb temperature 19:
Indoor-Outdoor piping length : 5 m
Outdoor Dry-bulb temperature 35: Wet-bulb temperature 24:
5
OUTLINES AND DIMENSIONS4
OB400C
MS-A18VD MS-A24VD MS-A30VD
INDOOR UNIT
Unit: mm
325
56
58
1100
791
19
1068
253
Installation plate
98
47
98 173414.5 414.5
Wall hole [75
Air in
258
Air out
5
Installation plate
Indoor unit
173
Liquid line [ 6.35-0.5m Gas line [ 12-0.43m
{
Insulation [ 50 O.D
Liquid line [ 9.52-0.5m Gas line [ 16-0.43m
{
Insulation [ 50 O.D
Drain hose [16 (Connected part O.D)
Insulation [28
2.5
[ 32 I.D
for MS-A18VD for MS-A24VD
[ 32 I.D
for MS-A30VD
255.547
7.5
315
162
Wireless remote controller
6
5
OB400C
WIRING DIAGRAM
MS-A18VD - MS-A24VD -
K1K1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
220-230-240V~
220-230-240V~
SYMBOL
C11
F11
F12
HIC1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(3.15A) THERMAL FUSE (93:) DC/DC CONVERTER INDOOR FAN MOTOR(INNER PROTECTOR)
MF
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
MS-A18VD - MS-A24VD -
TB
2
WHT
N
BLU
L
BRN
NAME
F12
GRN/YLW
MV2
CN 151
MV2
BLU
1
BLU
2
15
MV1
SYMBOL
NR11 RT11 RT12
K2K2
MV1 MV2
CN201
3 2
BLU
1
CN
102
CN
ELECTRONIC CONTROL P.C. BOARD
101
33
DISPLAY P.C. BOARD
RECEIVER P.C. BOARD
NAME NAME HORIZONTAL VANE MOTOR VERTICAL VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR
HIC1
3
52C/ X11
4
F11
REMOTE CONTROLLER
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
220-230-240V~
220-230-240V~
TB
2
WHT
N
BLU
L
BRN
CN 151
CN
102
CN201
3 2 1
CN
ELECTRONIC CONTROL P.C. BOARD
101
HIC1
3
X11
4
F11
NR11
SR141
NR11
SR141
C11
CN211
SYMBOL
SR141
TB
52C/X11
CN
112
CN
111
CN 121
1
C11
3 4
CN211
CN
112
CN
111
CN 121
3
1 3 4
RT12 RT11
BLK GRY YLW BRN WHT RED
MF
SOLID STATE RELAY TERMINAL BLOCK COMPRESSOR CONTACTOR
RT12 RT11
3
BLK GRY YLW BRN WHT RED
MF
GRN/YLW
MV2
SYMBOL
C11 F11
HIC1
MV1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(T3.15AL250V) DC/DC CONVERTER INDOOR FAN MOTOR(INNER PROTECTOR)
MF
HORIZONTAL VANE MOTOR
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
MV2
15
MV1
DISPLAY P.C. BOARD
SYMBOL
MV2
NR11
RT11
RT12
SR141
33
RECEIVER P.C. BOARD
REMOTE CONTROLLER
NAME NAME VERTICAL VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR SOLID STATE RELAY
7
SYMBOL
TB
X11
TERMINAL BLOCK CONTACTOR
MS-A30VD
OB400C
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220-230-240V~
3
N
2
TB
RED BLU BRN
CN
151
CN
102
CN201
3 2 1
TAB12
HIC1
NR11
F11
CN
ELECTRONIC CONTROL P.C. BOARD
101
SR141
C11
4 3 2 1
CN112
CN
121
1 3 4
CN211
CN
111
RT13
RT12
3
BLK GRY YLW BRN WHT RED
RT11
MF
MV2
15
MV1
DISPLAY P.C. BOARD
SYMBOL
MV2 NR11 RT11 RT12 RT13
33
RECEIVER P.C. BOARD
REMOTE CONTROLLER
NAME NAME VERTICAL V ANE MOT OR V ARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
GRN/YLW
MV2
SYMBOL
C11 F11
HIC1
MV1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE (T3.15AL250V) DC/DC CONVERTER INDOOR FAN MOTOR (INNER PROTECTOR)
MF
HORIZONT AL VANE MOT OR
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL
SR141
TB
SOLID STATE RELAY TERMINAL BLOCK
8
6
Indoor heat exchanger
Flared connection
RT11 Room temperature thermistor
Distributor
Flared connection
Refrigerant pipe [12.7 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12
Strainer
#50
OB400C
REFRIGERANT SYSTEM DIAGRAM
MS-A18VD
INDOOR UNIT
Unit : mm
MS-A24VD
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Strainer
#50
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
MS-A30VD
INDOOR UNIT
Indoor heat exchanger
Indoor coil thermistor RT13 (sub)
Room temperature thermistor RT11
Strainer
Indoor coil thermistor RT12 (main)
#50
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant flow in cooling
9