Mitsubishi Electric MS-A18VD-K1, MS-A18VD-K2, MS-A24VD-K1, MS-A18VD, MS-A30VD-K2 Service Manual

...
SPLIT-TYPE AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Models
Revision C:
• Another type of the electronic control P.C. board (TYPE 2) has been added to the original one (TYPE 1). They are both com­patible with MS-A18/24/30VD- .
Please void OB400, REVISED EDITION-B.
K
No. OB400
REVISED EDITION-C
MS-A18VD­MS-A18VD­MS-A24VD­MS-A24VD­MS-A30VD­MS-A30VD-
MS-A18VD MS-A24VD MS-A30VD
K1
K2
K1
K2
K1
K2
Outdoor unit service manual
MU-A·VD Series (OB401)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. OUTLINES AND DIMENSIONS·························6
5. WIRING DIAGRAM ············································7
6. REFRIGERANT SYSTEM DIAGRAM················9
7. SERVICE FUNCTIONS ····································10
9. DISASSEMBLY INSTRUCTIONS ····················21
10. PARTS LIST······················································23
11. RoHS PARTS LIST···········································26
NOTE:
• This service manual describes technical data of the indoor units.
• RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
TM
Indoor unit:Unit size:W1,015mmoH320mmoD190mm W1,100mmoH325mmoD258mm Electricity receiving unit: Indoor unit Outdoor unit Rated voltage : 220/240V 220-230-240V
Frequency New Model Old Model
MS-18NV -
KB
w
: change
MS-A18VD -
K1
50Hz
MS-18UV -
P1
MS-18RV -
R1
w w w
w w
w
Indoor unit:Unit size:W1,015mmoH320mmoD190mm W1,100mmoH325mmoD258mm Electricity receiving unit: Indoor unit Outdoor unit Rated voltage : 220/240V 220-230-240V
Frequency New Model Old Model
MS-24NV -
K1
MS-A24VD -
K1
50Hz
MS-24UV - P1MS-24RV -
R1
w w w
w w
w
Indoor unit:Unit size:W1,100mmoH325mmoD227mm W1,100mmoH325mmoD258mm Rated voltage : 220/240V 220-230-240V
Frequency New Model Old Model
MS-30SV - K1MS-30SV -
P1
MS-A30VD -
K1
50Hz
w w
w
Use the specified refrigerant only
OB400C
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
• MS-A18VD- , MS-A24VD- and MS-A30VD- have been added.
K2K2K2
Revision B:
• Remote controller model “KM04B” has been added. There are two remote controller models for “ ” and “ ”. (KP0B, KM04B) You can use the remote controller model “KP0B” and “KM04B”. The remote controller model “KM04B” is supplied as service parts for “ ” and “ ”.
K2K1
K2K1
Revision C:
• Another type of the electronic control P.C. board (TYPE 2) has been added to the original one (TYPE 1). They are both com-
patible with MS-A18/24/30VD- .
K
TECHNICAL CHANGES1
MS-A18VD - MS-A18VD ­MS-A24VD - MS-A24VD ­MS-A30VD - MS-A30VD -
1. Fan guard has been added.
2. Fan speed has been changed.
K2K1
K2K1
K2K1
3. Wiring diagram has been changed.
4. FUSE (F12) has been removed. (MS-A18/24VD- )
5. “8-5.C Check of indoor electronic control P.C. board” has been changed.
K2
2
2
OB400C
PART NAMES AND FUNCTIONS
INDOOR UNIT
MS-A18VD MS-A24VD MS-A30VD
Air cleaning filter (White bellows type)
Front Panel
Catechin air filter
Vertical vanes
Horizontal vane
Operation section
(When the grille is opened)
Emergency operation switch
Grille
Air inlet
Remote control
receiving section
Remote controller
Display section
Operation indicator lamp
Remote control
receiving section
3
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
WIDE VANE
LONG
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET CLOCK
FAN
Open the front lid.
Signal transmitting section
Operation display section
OPERATE/ STOP
(ON/ OFF)button
TEMPERATURE buttons
Indication of remote controller model is on back.
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE button
(Horizontal vane button)
CLOCK SET button
LONG button
WIDE VANE button
(Vertical vane button)
Installation plate Installation plate fixing screw 4 x 25 mm Remote controller holder Fixing screw for 3 3.5 x 16 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping) Air cleaning filter Pipe cover
1 2 3 4 5 6 7 8 9
1 7 1 2 2 1 1 2
ACCESSORIES
OB400C
REMOTE CONTROLLER
MS-A18VD MS-A24VD MS-A30VD
4
3
Indoor model
Function
Power supply
Air flow
(High/Med./Low) Running current Power input Auxiliary heater Power factor Fan motor current Model Winding resistance(at 20:) Dimensions WOHOD Weight Air direction Sound level
(High/Med./Low)
Fan speed
(High/Med./Low) Fan speed regulator Thermistor RT11(at 25:) Thermistor RT12(at 25:) Thermistor RT13(at 25:) Remote controller model
Electrical
data
Fan
motor
Special
remarks
Capacity
Cooling
Single phase
220-230-240V, 50Hz
1,100O325O258
16
5
3 10 10
KP0B / KM04B
0.33-0.34-0.35 67-69-75
92-88-89
0.33-0.34-0.35
RC4V40-AA WHT-BLK 138.2 RED-BLK 159.0
774/660/552
0.30-0.30-0.31 60-60-64
91-87-86
0.30-0.30-0.31
RC4V32-AA WHT-BLK 293.0 RED-BLK 146.0
42/37/33
K /h
A
W
A(kW)
%
A
"
mm
kg
dB
rpm
k" k" k"
972/828/684
45/41/37
1,220/1,070/910 1,280/1,130/970
1,220/1,070/910 1,280/1,130/9701,010/880/760 1,070/920/780
10
MS-A18VD - K1 MS-A18VD - K2 MS-A24VD - K1 MS-A24VD - K2 MS-A30VD - K1 MS-A30VD - K2
OB400C
SPECIFICATION
NOTE:Test conditions are based on ISO 5151.
Cooling : Indoor Dry-bulb temperature 27: Wet-bulb temperature 19:
Indoor-Outdoor piping length : 5 m
Outdoor Dry-bulb temperature 35: Wet-bulb temperature 24:
5
OUTLINES AND DIMENSIONS4
OB400C
MS-A18VD MS-A24VD MS-A30VD
INDOOR UNIT
Unit: mm
325
56
58
1100
791
19
1068
253
Installation plate
98
47
98 173414.5 414.5
Wall hole [75
Air in
258
Air out
5
Installation plate
Indoor unit
173
Liquid line [ 6.35-0.5m Gas line [ 12-0.43m
{
Insulation [ 50 O.D
Liquid line [ 9.52-0.5m Gas line [ 16-0.43m
{
Insulation [ 50 O.D
Drain hose [16 (Connected part O.D)
Insulation [28
2.5
[ 32 I.D
for MS-A18VD for MS-A24VD
[ 32 I.D
for MS-A30VD
255.547
7.5
315
162
Wireless remote controller
6
5
OB400C
WIRING DIAGRAM
MS-A18VD - MS-A24VD -
K1K1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
220-230-240V~
220-230-240V~
SYMBOL
C11
F11
F12
HIC1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(3.15A) THERMAL FUSE (93:) DC/DC CONVERTER INDOOR FAN MOTOR(INNER PROTECTOR)
MF
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
MS-A18VD - MS-A24VD -
TB
2
WHT
N
BLU
L
BRN
NAME
F12
GRN/YLW
MV2
CN 151
MV2
BLU
1
BLU
2
15
MV1
SYMBOL
NR11 RT11 RT12
K2K2
MV1 MV2
CN201
3 2
BLU
1
CN
102
CN
ELECTRONIC CONTROL P.C. BOARD
101
33
DISPLAY P.C. BOARD
RECEIVER P.C. BOARD
NAME NAME HORIZONTAL VANE MOTOR VERTICAL VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR
HIC1
3
52C/ X11
4
F11
REMOTE CONTROLLER
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
220-230-240V~
220-230-240V~
TB
2
WHT
N
BLU
L
BRN
CN 151
CN
102
CN201
3 2 1
CN
ELECTRONIC CONTROL P.C. BOARD
101
HIC1
3
X11
4
F11
NR11
SR141
NR11
SR141
C11
CN211
SYMBOL
SR141
TB
52C/X11
CN
112
CN
111
CN 121
1
C11
3 4
CN211
CN
112
CN
111
CN 121
3
1 3 4
RT12 RT11
BLK GRY YLW BRN WHT RED
MF
SOLID STATE RELAY TERMINAL BLOCK COMPRESSOR CONTACTOR
RT12 RT11
3
BLK GRY YLW BRN WHT RED
MF
GRN/YLW
MV2
SYMBOL
C11 F11
HIC1
MV1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(T3.15AL250V) DC/DC CONVERTER INDOOR FAN MOTOR(INNER PROTECTOR)
MF
HORIZONTAL VANE MOTOR
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
MV2
15
MV1
DISPLAY P.C. BOARD
SYMBOL
MV2
NR11
RT11
RT12
SR141
33
RECEIVER P.C. BOARD
REMOTE CONTROLLER
NAME NAME VERTICAL VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR SOLID STATE RELAY
7
SYMBOL
TB
X11
TERMINAL BLOCK CONTACTOR
MS-A30VD
OB400C
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220-230-240V~
3
N
2
TB
RED BLU BRN
CN
151
CN
102
CN201
3 2 1
TAB12
HIC1
NR11
F11
CN
ELECTRONIC CONTROL P.C. BOARD
101
SR141
C11
4 3 2 1
CN112
CN
121
1 3 4
CN211
CN
111
RT13
RT12
3
BLK GRY YLW BRN WHT RED
RT11
MF
MV2
15
MV1
DISPLAY P.C. BOARD
SYMBOL
MV2 NR11 RT11 RT12 RT13
33
RECEIVER P.C. BOARD
REMOTE CONTROLLER
NAME NAME VERTICAL V ANE MOT OR V ARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
GRN/YLW
MV2
SYMBOL
C11 F11
HIC1
MV1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE (T3.15AL250V) DC/DC CONVERTER INDOOR FAN MOTOR (INNER PROTECTOR)
MF
HORIZONT AL VANE MOT OR
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL
SR141
TB
SOLID STATE RELAY TERMINAL BLOCK
8
6
Indoor heat exchanger
Flared connection
RT11 Room temperature thermistor
Distributor
Flared connection
Refrigerant pipe [12.7 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12
Strainer
#50
OB400C
REFRIGERANT SYSTEM DIAGRAM
MS-A18VD
INDOOR UNIT
Unit : mm
MS-A24VD
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Strainer
#50
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
MS-A30VD
INDOOR UNIT
Indoor heat exchanger
Indoor coil thermistor RT13 (sub)
Room temperature thermistor RT11
Strainer
Indoor coil thermistor RT12 (main)
#50
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant flow in cooling
9
7
OB400C
SERVICE FUNCTIONS
MS-A18VD MS-A24VD MS-A30VD
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 8-6.) Set time : 1-minute 1-second
Set time : 3-minute 3-second
It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit of JPG and JPS.
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
Remote controller model : KP0B
Remote controller model : KM04B
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J1
J2
NOTE : For modification, take out the
batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish modification, put back the batteries then press the RESET button.
J1
J2
10
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
Table 1
OB400C
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
7-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically. However if the unit is operated in “I FEEL CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature.
How to disable “AUTO RESTART FUNCTION”
1Turn off the main power for the unit. 2Pull out the indoor electronic control P.C. board and the display P.C. board.(Refer to 9-1.2.) 3Solder the Jumper wire or the RESISTOR 220" to the RESISTOR JR07 on the indoor electronic control P.C.board.
(Refer to 8-6.)
Operation
1If the main power has been cut, the operation settings remain. 2After the power is restored, the unit automatically resumes the same operation as the memory has recorded.
However, it takes the compressor at least 3 minutes to get started.
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
11
TROUBLESHOOTING8
Lead wiring
<Incorrect>
Housing point
<Correct>
RESET button
Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.
OB400C
MS-A18VD MS-A24VD MS-A30VD
8-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirm­ing the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work.
2) Before servicing that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discolouration.
4) When troubleshooting, refer to 8-2. and 8-3.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally. 1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press the RESET button with a thin instrument,
and then use the remote controller.
NOTE: 1. If the RESET button is not pressed, the remote controller may not operate correctly.
2. Do not use the leaking batteries.
12
Start
Indoor unit operates. Outdoor unit does not operate.
Indoor unit does not receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation. w
Indoor unit operates when EMERGENCY OPERATION switch is pressed.
Indoor unit does not operate when EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to 8-6. "Test point diagram and voltage".
Refer to "Check of outdoor unit".
Refer to 8-5. B "Check of remote controller and receiver P.C. board".
MS-A30VD
Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring
2-time flash Cause: Indoor unit
• T roub le of room temp­ erature/ indoor coil thermistor
3-time flash Cause: Indoor unit
• T roub le of indoor fan motor
MU-A30VD
6-time flash Cause: Outdoor unit
• T roub le of thermistor in outdoor unit
MU-A30VD
7-time flash Cause: Outdoor unit
• T roub le of outdoor control system
Refer to 8-5. D "How to check mis-wiring (When outdoor unit does not work)".
Check room temperature thermistor and indoor coil thermis­tor. Refer to 8-6. "Test point diagram and voltage".
Refer to 8-5. A "Check of indoor fan motor".
Refer to "Check of outdoor thermistor".
Replace the deicer P.C. board.
MU-A30VD
10-time flash Cause: Outdoor unit
• T roub le of low discharge temperature protection
Refer to "Check of LEV".
4-time flash Cause: Indoor unit
• T roub le of indoor control system
Replace the indoor electronic control P.C. board.
1. Check indoor / outdoor connecting wire.
2. Check of outdoor fuse.
(MU-A18/A24VD
)
3. Refer to 8-5. C "Check of indoor electronic control P.C. board".
MU-A24VD-
K2
MU-A30VD
Outdoor unit does not stop even if indoor unit stop.
Indoor unit operates. Outdoor unit does not operate normally.
MU-A30VD
Outdoor unit repeats start and stop.
Refer to outdoor unit service manual. "Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.w
MU-A30VD
Outdoor unit does not operate even in Test Run operation. w
Refer to "Check of outdoor unit".
Refer to "Check of solenoid valve coil".
8-2. Instruction of troubleshooting
OB400C
13
No.
1
2
4
5
6
SymptomIndication Condition
Remedy
0.5-second ON
0.5-second OFF
Mis-Wiring
Outdoor thermistors
Outdoor control system
Indoor coil thermistor
3 minutes after power supply turns ON, when serial signal is not received.
<Thermistor short> Thermistors are abnormal when they short after compressor start-up. <Thermistor open> Thermistors are abnormal when they open after compressor start-up. However, discharge temperature thermistor is abnormal when open circuit is detected more than 10 minutes after compressor start-up.
Nonvolatile memory data cannot be read properly on deicer P.C. board.
• Shortage of refrigerant
• Replace the deicer P.C. board. Refer to "Check of outdoor
thermistor". Refer to outdoor unit service manual.
• Replace the deicer P.C. board.
Refer to outdoor unit service manual.
• Refer to 8-5. D "How to check mis-wiring ".
3
Indoor fan
motor.
7
Low discharge temperature protection
Discharge temperature has been 50: or less for 20 minutes.
Abnormal
point
Outdoor unit does not operate.
Room tempera­ture thermistor
2-time flash
2.5-second OFF
Detect Indoor coil/room temperature thermistor short or open circuit every 8 seconds during operation.
• Refer to the characteristics of indoor coil thermistor, sub indoor coil thermistor,
and room temperature thermistor on 8-6.
3-time flash
2.5-second OFF
Indoor fan motor repeats 12 seconds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping.
Rotational frequency feedback signal is not emitting during 12-second indoor fan operation.
• Refer to 8-5. A "Check of
indoor fan motor".
4-time flash
2.5-second OFF
Indoor control system
Nonvolatile memory data cannot be read properly on indoor electronic control P.C. board.
Outdoor unit does not operate.
Outdoor unit does not operate.
• Replace the indoor electronic
control P.C. board.
6-time flash
2.5-second OFF
• Refer to "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
Refer to outdoor unit service manual.
Outdoor unit does not operate.
Outdoor unit does not operate.
Outdoor unit does not operate.
MS-A30VD
MU-A30VD
MU-A30VD
MU-A30VD
7-time flash
2.5-second OFF
10-time flash
2.5-second OFF
Operation Indicator
Lighted
Not lighted
OB400C
8-3. Troubleshooting check table
• Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with the OPERATION INDICATOR lamp flashing.
· Flashing of the OPERATION INDICATOR lamp (the left-hand side lamp) indicates possible abnormalities.
· The OPERATION INDICATOR lamp (the left-hand side lamp) is lighting during
normal operation.
14
8-4. Trouble criterion of main parts
MAIN
AUX.
BLK
REDWHT
ORN
BLUYLW
RED
PNK
ROTOR
282 ~ 306 "
Normal
Color of lead wire
WHT - BLK BLK - RED
MS-A18VD
Normal
282 ~ 304 "
MS-A24/30VD
132 ~ 144 "
141 ~ 152 " 152 ~ 166 "
Color of lead wire
BRN - YLW YLW - GRY
Normal
4.5 ~ 5.5 V
(When fan revolved one time)
0V5V0V
(Approx.)
OB400C
MS-A18VD MS-A24VD MS-A30VD
Part name
Room temperature thermistor
(RT11) Indoor coil thermistor (RT12(main), RT13(sub))
Indoor fan motor (MF)
INNER PROTECTOR 135i 5: OPEN
86i15: CLOSE
Horizontal vane motor(MV1) Vertical vane motor(MV2)
Check method and criterion
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C) Refer to 8-6. “Test point diagram and voltage”, “Indoor electronic control P.C. board”, for the chart of thermistor.
Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)
Motor part
Measure the voltage Power ON.
Sensor part
Measure the resistance between the RED terminals and other ones. (Winding temperature10°C ~ 30°C)
Figure
15
PP
:INNER PROTECTOR
8-5. Troubleshooting flow
OB400C
When OPERATION INDICATOR lamp flashes 3-time. Indoor fan motor does not operate.
AA
Check of indoor fan motor
Turn OFF the power supply. Check connector CN211 visually.
No
Reconnect the lead wires.
Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board. Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4.
Are lead wires connected?
Is resistance 0 (short circuit) or (open circuit)?
Yes
Yes ( 0 or ∞ )
Repair the indoor fan motor.
Is soldered point of the connector
correctly soldered?
Yes
Turn ON the power supply. Stop it if the unit operate. Insert screwdriver into air outlet to rotate indoor fan motor slowly for 1
No
(others)
revolution or over, and measure voltage No.2(+) and No.3(-) on CN121.
No
Does voltage repeat 0 VDC and 5 VDC?
Replace the indoor electronic control P.C. board.
No
Resolder it.
Yes
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
BB
Check of remote controller and receiver P.C. board
w Check if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the remote con­troller visible?
Yes
No (not clear)
Replace the batteries (Refer to 8-1.4.).
Remove batteries, then set them back and press the RESET button. Check if the unit operates with remote con­troller.
Does the unit operate with remote controller?
Yes
OK
Measure the voltage between receiver P.C. board connector CN301 No.1
the remote controller button is pressed (Refer to 8-6.).
No
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
Is the voltage approximately 4 VDC?
No (5V or 0 VDC)
Replace the receiver P.C.board.
16
No
Yes
(+)
and No.3
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
(-)
when
Replace the indoor electronic control P.C. board
Indoor electronic control P.C. board
Varistor (NR11)
Indoor electronic control P.C. board
Fuse (F11)
Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
Replace the fuse.
Is fuse(F11) blown?
Replace the fan motor.
Is the winding resistance of fan motor 0 "?
Is the winding resistance of vane motor 0 "?
No
Yes
Replace the vane motor.
No
Yes
Yes
Is varistor(NR11) burnt?
Replace the varistor.
No
Yes
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
No
Does the unit operate with the remote controller? Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?
Yes
No
Turn OFF the power supply.
Turn OFF the power supply.
Replace the indoor electronic control P.C. board.
Measure the resistance between CN201 1 on the indoor electronic control P.C. board and
N
on the terminal block with a tester.
Is resistance
approximately 0"?
Replace the fuse (F12).
No
Yes
()
CN201
1 2
L
N
F12
Terminal block
2
MS-A18/24VD - K1
1
2
3
MS-A18/24VD -
K2
MS-A30VD
The unit does not operate with the remote controller.
OB400C
Also, the OPERATION INDICATOR lamp does not light up by pressing the EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board
C
17
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
OB400C
Outdoor unit does not operate.
How to check mis-wiring
D
• Turn ON the power supply.
• Press EMERGENCY OPERATION switch once.
When the unit has mis-wiring, in 3 minutes, OPERATION INDICATOR lamp on indoor unit flash on and off at 0.5 second intervals. w
Make them sure.
1. Turn OFF the power supply and disconnect only terminal block 3 of indoor/ outdoor connecting wire on indoor side.
2. Short-circuit terminal block N-3 by lead wire.
3. Turn ON the power supply and press EMERGENCY OPERATION switch once.
Yes
Is this mis-wiring, poor contact, or wire disconnection?
Is there 1V DC detected between both ends of PS132 on the indoor electronic control P.C. board ? However, the stylus of a tester would be between 0 and 20V.
• Turn OFF the power supply.
• Disconnect the lead wire that terminal block N-3 is short-circuited.
Connect ON indoor/ outdoor connecting wire.
MS-A30VD
Start
No
Yes
w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self-check to be displayed in 3 seconds.
No
Replace the indoor electronic control P.C. board.
Turn ON the power supply.
Is there 220-230-240V AC between L-N on the outdoor terminal block?
Is there 5V DC between J101 + -J401 - ?
When EMERGENCY OPERATION is operated, is there 10V DC between both ends of R601 on the deicer P.C. board? However the stylus of a tester would be between 5 ~10V.
Replace the deicer P.C. board.
Yes
Yes
Yes
Refer to outdoor unit service manual .
No
Check the outdoor power supply and connection of wiring.
No
Replace the deicer P.C. board.
Make the wiring between CN730
No
on the deicer P.C. board and outdoor terminal block correct.
18
8-6. Test point diagram and voltage
Indoor coil thermistor (RT12 (main), RT13 (sub)) Room temperature thermistor (RT11)
Temperature (:)
Resistance (k")
OB400C
MS-A18VD MS-A24VD MS-A30VD
Indoor electronic control P.C.board
TYPE 1
Fuse (F11) T3.5AL250V
PS132
MS-A30VD
w There are 2 types of electronic control P.C. boards
(TYPE1/TYPE2). They are both compatible with MS-A18/24/30VD.
Varistor (NR11)
Fan motor power supply
220-230-240 VAC(CN211)
Power supply input
}
220-230-240 VAC
5 VDC
}
+
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12 (main))
MS-A30VD
Indoor coil thermistor (RT13 (sub))
CN121
Receiver P.C. board
CN301
To disable “Auto restart function”, solder the Jumper wire or the Resistor 220" to the Resistor JR07. (Refer to 7-3.)
+
}
12 VDC
Vane motor power supply
(CN151)
Emergency operation switch
Timer short mode point (JPS, JPG) (Refer to 7-1.)
19
+
}
}
Resistance (k
)
+
{
Fan motor power supply (CN211)
Fuse (F11) T3.15AL250V
220-230-240 V AC
5 VDC
Indoor coil thermistor (RT12 (main))
MS-A30VD
Indoor coil thermistor (RT13 (sub))
Timer short mode point (JPS, JPG) (Refer to 7-1.)
Emergency operation switch
CN121
Room temperature thermistor (RT11)
PS132
MS-A30VD
To disable “Auto restart function”, solder jumper wire to JR07. (Refer to 7-3.)
Vane motor power supply (CN151)
12 VDC
Indoor coil thermistor (RT12 (main), RT13 (sub))
Room temperature thermistor (RT11)
Power supply input
MS-A18VD MS-A24VD MS-A30VD
OB400C
Indoor electronic control P.C.board
TYPE 2
Receiver P.C. board
CN301
20
9
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
OB400C
DISASSEMBLY INSTRUCTIONS
9-1. MS-A18VD MS-A24VD MS-A30VD
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
1. Removing the front panel
(1) Remove the screws caps of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board, the receiver P.C. board and the display P.C. board
(1) Remove the front panel. (Refer to 1.) (2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Remove the screw of the V.A. clamp.
Remove the V.A. clamp. (4) Remove the screw of the terminal block. (5) Remove the screw of the ground wire. (6) Disconnect all the connectors and all the lead wires on the
electronic control P.C. board. (7) Remove the R.L holder. (8) Remove the electronic control P.C. board. (9) Open the R.L holder, remove the receiver P.C. board and
the display P.C. board.
Photo 1
Photo 2
Screws of the ground wire
Screw of the terminal block
PHOTOS
Front panel
Screws
R.L holder
Receiver P.C. board
Fan motor connectors
Vane motor connector
Indoor electronic control P.C.board
Screw of the electrical cover
Screw of the V.A. clamp
21
OPERATING PROCEDURE PHOTOS
OB400C
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1.) (2) Remove the electrical cover. (Refer to 2.) (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic
control P.C. board. (5) Remove the screw of ground wire. (6) Remove the fan motor lead wire and indoor coil thermistor
from the electrical box. (7) Remove the lead wire of vane motor from the bottom of
electrical box. (8) Remove the screw fixing the electrical box, remove the
electrical box.
4. Removing the vane motor
(1) Remove the front panel. (Refer to 1.) (2) Remove the electrical cover. (Refer to 2.) (3) Remove the lead wire of vane motor.(Refer to 3.) (4) Remove the R.L. holder. (5) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly.
(6) Remove the screws of the vane motor, disconnect the con-
nector.
(7) Remove the vane motor.
Photo 5
Screws of the vane motor
Photo 3
Photo 4
Screws of the ground wire
Vane motors
Screw of the electrical cover
Screw of the electrical box
Screws of the vane motor
Vane motor
5. Removing the line flow fan and the indoor fan motor
(1) Remove the front panel. (Refer to 1.) (2) Remove the electrical box. (Refer to 3.) (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly. (4) Remove the water cut. (5) Slide the hole cover, remove the hole cover. (6) Remove the hexagon socket set screw from the line flow
fan. (7) Remove the fan motor after removing screws, which fasten
the motor, but be careful not to drop it because of its heavy
weight. (8) Remove the screws fixing the left side of the heat
exchanger. (9) Lifting the left side of the heat exchanger.
10
) Remove the line flow fan.
(
Photo 8
Hole cover
Photo 6
Screws fixing the left side of the heat exchanger
Photo 7
Indoor coil thermistor
Water cut
Screws fixing the fan motor
22
PARTS LIST (non-RoHS compliant)10
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
1 2 3 4 5 6 7 8 9
10
E02 527 970 E02 685 234 E02 888 000 E02 408 142 E02 685 067 E02 888 010 E02 685 975 E02 534 100
E02 888 007
INSTALLATION PLATE BOX FRONT PANEL ASSEMBLY CATCH SCREW CAP GRILLE CORNER BOX RIGHT CATECHIN AIR FILTER AIR CLEANING FILTER LAMP PANEL
Including No.4,5,6 4PCS/SET 3PCS/SET
1PCE/SET MAC-1700FT
Q'ty/unit
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
MS-A30
VD-
K2
MS-A30
VD-
K1
MS-A24
VD-
K2
MS-A24
VD-
K1
MS-A18
VD-
K2
MS-A18
VD-
K1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
12
13
E02 817 620 E02 947 620 E02 890 620 E02 179 667 E02 138 666
E02 A16 666
E02 151 667 E02 527 667
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION(GAS) UNION(GAS) UNION(GAS) UNION(LIQUID) UNION(LIQUID)
{12.7 {15.88 {15.88 {6.35 {9.52
OB400C
MS-A18VD MS-A24VD MS-A30VD
10-1. INDOOR UNIT STRUCTURAL PARTS
1 2
3
4
CATCH
5
SCREW
CAP
7
6
8
10-1. INDOOR UNIT STRUCTURAL PARTS
Part number that is circled is not shown in the illustration.
10-2. INDOOR UNIT HEAT EXCHANGER
11
9 (See 10-5.)
12
13
10-2. INDOOR UNIT HEAT EXCHANGER
23
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
1 2 3 4
5 6
7 8 9
10 11 12
13 14 15
16
17 18
19
20
21 22 23
E02 527 302 E02 408 509 E02 001 504 E02 408 702 E02 527 235 E02 996 235 E02 685 040 E02 685 041 E02 A49 382 E02 817 385 E02 527 034 E02 817 300 E02 527 300 E02 448 303 E02 408 303 E02 528 329 E02 527 468 E02 946 452 E02 A14 452 E02 947 452 E02 A15 452 E02 948 452 E02 A16 452 E02 527 308 E02 817 333 E02 527 333 E02 888 375 E02 814 375 E02 408 311 E02 947 311 E02 527 311 E02 528 034 E02 529 034 E02 408 381
LINE FLOW FAN BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE NOZZLE VANE UPPER VANE LOWER FUSE VARISTOR VANE CRANK SET INDOOR FAN MOTOR ASSEMBLY INDOOR FAN MOTOR ASSEMBLY VERTICAL VANE MOTOR HORIZONTAL VANE MOTOR DISPLAY P.C. BOARD RECEIVER P.C. BOARD ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ROOM TEMPERATURE THERMISTOR MOTOR BAND MOTOR BAND TERMINAL BLOCK TERMINAL BLOCK INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR VANE MOTOR SUPPORT SET (RIGHT) VANE MOTOR SUPPORT SET (LEFT) THERMAL FUSE
F11
NR11
MF
MF MV2 MV1
RT11
TB
TB
RT12 RT12
RT12, RT13
F12
Q'ty/unit
1 1 1 1 1
1 1 1 1 1
1 2 1 1 1
1
1
1 1
1
1 1 1
1 1 1 1 1
1 1 1 1 1
1 2 1 1 1
1
1
1
1
1 1 1
1 1 1 1 1
1 1 1 1 1 1
2 1 1 1 1
1 1
1
1
1 1 1
1 1 1 1
1 1 1 1 1 1
1 2 1 1 1
1
1
1 1
1
1 1
1 1 1 1
1 1 1 1 1 1
1 2 1 1 1
1 1
1
1
1 1 1
1 1 1 1
1 1 1 1 1 1 1
2 1 1 1
1
1 1
1
1
1 1
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
T3.15AL250V
RIGHT&LEFT UP&DOWN
RC4V32­Including RUBBER MOUNT
RC4V40­Including RUBBER MOUNT
MS-A30
VD-
K2
MS-A30
VD-
K1
MS-A24
VD-
K2
MS-A24
VD-
K1
MS-A18
VD-
K2
MS-A18
VD-
K1
w1 Refer to 8-6.
PARTS LIST (non-RoHS compliant)
OB400C
MS-A18VD MS-A24VD MS-A30VD 10-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
1
2
3
4
5
6
7
10-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
12
10
8
20
11
9
13
24
18
17
14
19
15
16
Air cleaning filter (White bellows type)
Model
Part No.
MAC-1700FT
MS-A18VD -
K1
MS-A18VD - K2 MS-A24VD - K1 MS-A24VD - K2 MS-A30VD - K1 MS-A30VD - K2
1 2
E02 527 426 E02 527 083
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
1 1
KM04B
1 1
1 1
1 1
1 1
1 1
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
MS-A30
VD-
K2
MS-A30
VD-
K1
MS-A24
VD-
K2
MS-A24
VD-
K1
MS-A18
VD-
K2
MS-A18
VD-
K1
PARTS LIST (non-RoHS compliant)
OB400C
MS-A18VD MS-A24VD MS-A30VD
10-4. ACCESSORY AND REMOTE CONTROLLER
1 2
10-4. ACCESSORY AND REMOTE CONTROLLER
10-5. AIR CLEANING FILTER
Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
25
RoHS PARTS LIST (RoHS compliant)11
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
1 2 3 4 5 6 7 8 9
10
RoHS
G G G G G G G G G G
E12 527 970 E12 685 234 E12 888 000 E12 408 142 E12 685 067 E12 888 010 E12 685 975 E12 534 100
E12 888 007
INSTALLATION PLATE BOX FRONT PANEL ASSEMBLY CATCH SCREW CAP GRILLE CORNER BOX RIGHT CATECHIN AIR FILTER AIR CLEANING FILTER LAMP PANEL
Including No.4,5,6 4PCS/SET 3PCS/SET
1PCE/SET MAC-1700FT
Q'ty/unit
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
1 1 1 4 3 1 1 2 2 1
MS-A30
VD-
K2
MS-A30
VD-
K1
MS-A24
VD-
K2
MS-A24
VD-
K1
MS-A18
VD-
K2
MS-A18
VD-
K1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
11
12
13
E12 817 620 E12 947 620 E12 890 620 E12 179 667 E12 138 666
E12 A16 666
E12 151 667 E12 527 667
G G G G G G G G
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION(GAS) UNION(GAS) UNION(GAS) UNION(LIQUID) UNION(LIQUID)
{12.7 {15.88 {15.88 {6.35 {9.52
OB400C
MS-A18VD MS-A24VD MS-A30VD
11-1. INDOOR UNIT STRUCTURAL PARTS
1 2 3
4
CATCH
5
SCREW CAP
7
6
8
11-1. INDOOR UNIT STRUCTURAL PARTS
Part number that is circled is not shown in the illustration.
11-2. INDOOR UNIT HEAT EXCHANGER
11
9 (See 11-5.)
12
13
11-2. INDOOR UNIT HEAT EXCHANGER
26
RoHS PARTS LIST (RoHS compliant)
OB400C
MS-A18VD MS-A24VD MS-A30VD 11-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
1
2
20
19
3
4
12
11
5
18
6
17
10
7
13
15
8
14
16
9
11-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
K2
1 1 1 1
1 1 1 1 1 1 1
2 1 1 1
1
1 1
1
1
1 1
Q'ty/unit
MS-A24
K1
VD-
1 1 1 1 1
1 1 1 1 1
1 2 1 1 1
1
1
1 1
1
1 1 1
MS-A24
K2
VD-
1 1 1 1
1 1 1 1 1 1
1 2 1 1 1
1
1
1 1
1
1 1
No. Part No.
RoHS
1 2 3 4
5 6
7 8 9
10 11 12
13
14 15
16
17 18
19
20
21 22 23
E12 527 302
G
E12 408 509
G
E12 001 504
G
E12 408 702
G
E12 527 235
G
E12 996 235
G
E12 685 040
G
E12 685 041
G
E12 A49 382
G
E12 817 385
G
E12 527 034
G
E12 817 300
G
E12 527 300
G
E12 448 303
G
E12 408 303
G
E12 528 329
G
E12 527 468
G
E12 946 452
G
E12 A14 452
G
E12 947 452
G
E12 A15 452
G G
E12 948 452
G
E12 A16 452
G
E12 527 308
G
E12 817 333
G
E12 527 333
G
E12 888 375
G
E12 814 375
G
E12 408 311
G
E12 947 311
G
E12 527 311
G
E12 528 034
G
E12 529 034
G
E12 408 381
w1 Refer to 8-6.
Symbol
Part name
in Wiring
Diagram
LINE FLOW FAN BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE NOZZLE VANE UPPER VANE LOWER FUSE VARISTOR
F11
NR11 VANE CRANK SET INDOOR FAN MOTOR ASSEMBLY INDOOR FAN MOTOR ASSEMBLY VERTICAL VANE MOTOR HORIZONTAL VANE MOTOR
MF
MF MV2 MV1
DISPLAY P.C. BOARD RECEIVER P.C. BOARD ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ELECTRONIC CONTROL P.C. BOARD w1 ROOM TEMPERATURE THERMISTOR
RT11 MOTOR BAND MOTOR BAND TERMINAL BLOCK TERMINAL BLOCK INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR INDOOR COIL THERMISTOR
TB
TB RT12 RT12
RT12, RT13 VANE MOTOR SUPPORT SET (RIGHT) VANE MOTOR SUPPORT SET (LEFT) THERMAL FUSE
F12
MS-A18
K1
VD-
1 1 1 1 1
1 1 1 1 1 1
2 1 1 1 1
1 1
1
1
1 1 1
MS-A18
VD-
MS-A30
K1
VD-
1 1 1 1 1
1 1 1 1 1
1 2 1 1 1
1
1
1
1
1 1 1
MS-A30
K2
VD-
1 1 1 1
1 1 1
T3.15AL250V
1 1 1
RC4V32­Including RUBBER MOUNT
RC4V40-
1
Including RUBBER MOUNT
RIGHT&LEFT
2
UP&DOWN
1 1 1
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART Including No.15
AUTO RESTART
1
Including No.15
1
1
1
1 1 1
Remarks
27
Air cleaning filter (White bellows type)
Model
Part No.
MAC-1700FT
MS-A18VD -
K1
MS-A18VD - K2 MS-A24VD - K1 MS-A24VD - K2 MS-A30VD - K1 MS-A30VD - K2
1 2
E12 527 426 E12 527 083
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
1 1
KM04B
1 1
1 1
1 1
1 1
1
1
No.
G G
RoHS
Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
MS-A30
VD-
K2
MS-A30
VD-
K1
MS-A24
VD-
K2
MS-A24
VD-
K1
MS-A18
VD-
K2
MS-A18
VD-
K1
RoHS PARTS LIST (RoHS compliant)
MS-A18VD MS-A24VD MS-A30VD
11-4. ACCESSORY AND REMOTE CONTROLLER
1 2
11-4. ACCESSORY AND REMOTE CONTROLLER
11-5. AIR CLEANING FILTER
Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Aug. 2011. No.OB400 REVISED EDITION-C Distributed in May 2006. No.OB400 REVISED EDITION-B 6 Distributed in Nov. 2005. No.OB400 REVISED EDITION-A 6 Distributed in Mar. 2005. No.OB400 106
Made in Japan
New publication, effective Aug. 2011 Specifications subject to change without notice.
Loading...