Mitsubishi MS-18RV-E1, MS-24RV-E1, MS-30RV-E1, MU-18RV-E1, MU-24RV-E1 Service Manual

...
SPLIT-TYPE AIR CONDITIONERS
SERVICE MANUAL
Wireless type Models
No. OB271
MS-18RV ­MS-24RV ­MS-30RV -
MS-18RV ­MS-24RV -
E1 E1
(WH)
(WH)
(WH)
· MU-18RV -
· MU-24RV -
· MU-30RV -
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································6
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS·······················10
6. WIRING DIAGRAM ··········································13
7. REFRIGERANT SYSTEM DIAGRAM··············17
8. PERFORMANCE CURVES······························20
9. MICROPROCESSOR CONTROL ····················34
10. SERVICE FUNCTIONS·····································45
12. DISASSEMBLY INSTRUCTIONS·····················61
13. PARTS LIST······················································69
14. OPTIONAL PARTS ······················BACK COVER
E1E1
E1E1
E1E1
1
TECHNICAL CHANGES
MS-18NV - MS-18RV ­MS-24NV - MS-24RV -
1. Remote controller has been changed.
• SLEEP MODE function has removed.
• ECONO COOL operation has added.
• SWING button is removed, but SWING MODE function is available by VANE CONTROLbutton.
MS-30RV -
New model
E1
MU-18NV - MU-18RV ­MU-24NV - MU-24RV -
1. Outdoor model name has changed.
MU-30RV -
New model
E1
E1E4
E1E2
E1E4
E1E2
2
2
Remote control receiving section
Air cleaning filter(option)
Deodorizing filter(option)
Front panel
Grille
(When the grille is open)
Operation Indicator
PART NAMES AND FUNCTIONS
INDOOR UNIT
MS-18RV ­MS-24RV -
MS-18RV ­MS-24RV -
E1
E1
E1 E1
MS-18RV ­MS-24RV -
MS-30RV -
E1 E1
E1
MS-30RV -
OUTDOOR UNIT
MU-18RV ­MU-24RV -
E1
E1
E1
MS-30RV -
MU-30RV -
E1
E1
3
ACCESSORIES
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller mouting hardware Fixing screw for 3 o 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 7 1 2 2 1 1
1 6 1 2 2 1 1
MS-18RV­MS-24RV-
E1
MS-30RV-
E1
E1
Indoor unit
REMOTE CONTROLLER
MS-18RV ­MS-24RV -
E1
E1
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
Open the front lid.
ON/OFF
ON/OFF
TOO
WARM
CLOCK
TOO
WARM
PM
AM
TOO
COOL
PM
AM
TOO
COOL
TEMPERATURE buttons
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
4
FAN
I FEEL
COOL
VANE
DRY
FAN
MODE
ECONO COOL
RESET
CLOCK
STOP
START
HR.
MIN.
OFF-TIMER button
ON-TIMER button
HR. button
VANE CONTROL button
MIN. button
(TIME SET button)
CLOCK SET button
REMOTE CONTROLLER
MS-30RV -
E1
Signal transmitting section
Operation display section
OPERATE/ STOP
(ON/ OFF)button
Open the front lid.
ON/OFF
TOO
WARM
PM
AM
TOO
COOL
TEMPERATURE buttons
VANE button
(Horizontal vane button)
OPERATION SELECT button
ECONO COOL button
WIDE VANE button
(Vertical vane button)
RESET button
TOO
ON/OFF
WARM
COOL
DRY
WIDE VANE
FAN
VANE
LONG
RESET CLOCK
I FEEL
FAN
MODE
ECONO COOL
5
CLOCK
PM
AM
TOO
COOL
STOP
START
HR.
MIN.
FAN SPEED CONTROL button
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
LONG button
3
Indoor model
Function
Power supply
Capacity Dehumidification Air flow(High) Power outlet Running current Power input Auxiliary heater Power factor Starting current Fan motor current
Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (High) Fan speed (High) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Outdoor model Air flow Compressor motor current Fan motor current Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High) Fan speed regulator Refrigerant filling capacity(R22) Refrigerating oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A
"
mm
kg
dB
rpm
k" k"
K /h
A A
W
"
"
mm
kg
dB
rpm
kg cc
Cooling
Single phase
220-240V, 50Hz
WHT-BLK 183.8 BLK-RED 250.5 1,015O320O190
14
5
3 10 10
850o605o290
900 (MS32N1)
MS-24RV -
E1
6.4
3.4
816
25
12.9-12.6
2,780-2,900
98-96
59
0.29
2.30-2.21
RA4V27-EE
45
1,260
MU-24RV -
E1
2,286-2,358
12.06-11.76
0.55
NH-47VMDT
2,200 C-R 0.96 C-S 2.07
RA6V60-AC
WHT-BLK 81.1 BLK-RED 102.2
BLK-YLW 92.2
61 53
860-886
2
2.15
MS-18RV -
E1
5.1
2.5
756
15
9.1
1,910-2,010
95-92 51-55
0.25
2.67-2.54
RA4V27-EF
42
1,180
MU-18RV -
E1
2,340-2,400
8.46
0.39
PH-33VPET
1,500 C-R 1.08 C-S 2.18
RA6V50-OG
WHT-BLK 116.4
BLK-RED 111.0
48 52
830-860
1
1.05
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Capacity
Cooling
Single phase
220-240V, 50Hz
WHT-BLK 183.8
BLK-RED 250.5 1,015O320O190
14
5
3 10 10
850o605o290
1,200 (MS32N1)
SPECIFICATION
NOTE:Test conditions are based on JIS C 9612.
Cooling : Indoor DB 27°C / WB 19°C
Outdoor DB 35°C / WB (24°C)
6
Indoor model
Function
Power supply
Capacity Dehumidification
Capacity
Air flow(High) Power outlet Running current Power input Auxiliary heater
Electrical
data
Power factor Starting current Fan motor current
Coefficient of performance(C.O.P)
Model Winding
Fan
motor
resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (High) Fan speed (High) Fan speed regulator
Special
remarks
Thermistor RT11(at25:) Thermistor RT12(at25:) Thermistor RT13(at25:) Outdoor model
Capacity
Air flow Compressor motor current Fan motor current
Electrical
data
Model Output Winding
Compressor
resistance(at20:) Model Winding
Fan
motor
resistance(at20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High) Fan speed regulator Refrigerant filling
Special
remarks
capacity(R22) Refrigerating oil (Model) Thermistor RT62(at25:) Thermistor RT63(at0:)
kW
R/h
K /h
A A
W
A(kW)
%
A A
"
mm
kg
dB
rpm
k" k" k"
K /h
A A
W
"
"
mm
kg
dB
rpm
kg
cc k" k"
E1
MS-30RV -
Cooling
Single phase
220-240V, 50Hz
8.4
4.5 960
25
15.7-15.8
3,380-3,520
— 98-93 82-84
0.33-0.35
2.49-2.39
RC4V40-AA
WHT-BLK 138.2
BLK-RED 159.0 1,100O325O227
16
5
47
1,280
3 10 10 10
E1
MU-30RV -
2,880-3,000
14.81-14.87
0.56-0.58
NH-56VNHT
2,700 C-R 0.66 C-S 1.58
RA6V75-AA
WHT-BLK 62.8 BLK-YLW 55.9
YLW-RED 26.0
870o850o295
78 55
790-820
2
2.40
1,200 (MS32N1)
231.44
33.18
NOTE:Test conditions are based on JIS C 9612.
Cooling : Indoor DB 27°C / WB 19°C
Outdoor DB 35°C / WB (24°C)
7
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
42
SPL(dB(A)) LINE
NOTCH
High
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
45
SPL(dB(A)) LINE
NOTCH
High
NOISE CRITERIA CURVES
MS-18RV -
E1
MS-24RV -
E1
MU-18RV -
E1
NOTCH
High
SPL(dB(A)) LINE
52
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MU-24RV -
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
8
E1
NOTCH
High
SPL(dB(A)) LINE
53
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-20
BAND CENTER FREQUENCIES, Hz
MS-30RV -
E1
NOTCH
High
SPL(dB(A)) LINE
47
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
NC-20
BAND CENTER FREQUENCIES, Hz
MU-30RV -
E1
NOTCH
High
SPL(dB(A)) LINE
55
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
9
5
[9.52(MU-24RV)
[6.35(MU18RV)
Drainage hole {16.2
Drainage 3holes {33
Air in
Air in
Air out
355
248
605
29220
290
157
100
310
345
90
35
350 20
30
74
183
500 850
161
Service panel
Liquid refrigerant
pipe joint
Gas refrigerant
pipe joint
Refrigerant pipe
(flared) {15.88
Refrigerant pipe
(flared)
30°
35°
50
OUTLINES AND DIMENSIONS
MS-18RV ­MS-24RV -
E1
E1
INDOOR UNIT
320
58
162
995
1015
19
19077550
Power supply cord Lead to right 2m Lead to left 1m
150 648 217
60
40
Installation plate
Air in
4holes 11o20
450 450
Air out
Indoor unit
352438
5190
Installation plate
Liquid line [8-0.5m Gas line [12-0.43m
{
Insulation [50 O.D
[28 I.D
Drain hose [16 Insulation [28
Unit : mm
20
254
3 297
Wall hole [75
Wireless remote controller
MU-18RV ­MU-24RV -
OUTDOOR UNIT
E1
E1
10
REQUIRED SPACE
100mm or more
500mm or more
100mm or more
100mm or more
350mm or more
MS-30RV -
E1
Unit: mm
INDOOR UNIT
325
56
58
1100
791
19
1068
253
Installation plate
98 173
47
98 173414.5 414.5
Air in
Air out
Indoor unit
Wall hole [ 75
5225
Installation plate
Liquid line [ 9.52-0.5m Gas line [ 19-0.43m
{
Insulation [ 50 O.D
Drain hose [ 16 (Connected part O.D)
Insulation [ 28
7.5315
255.547
2.5
[ 32 I.D
162
Wireless remote controller
11
100 10
1000For 10 units or less
200
Outdoor Unit-Necessary surrounding clearance (Concentrated installation)
The upper side must be open.
Outdoor Unit-Necessary surrounding clearance
200
10
10
10
Note:Allow adequate upper clearance
150
500
500
Service space
Front opening
R20
R20
25 max.
Standard bolt length
65
Front right piping holes­detail figures
80
17
12
R6
23
33
Side air intake
724295
Outlet guide installation hole
302
Air intake
Air intake
Air outlet
870
185 185
500
330
362
1715
39.5 27.5
Terminal block for indoor and outdoor unit connection
Terminal block for power line
Handle for moving
179 524
441
445
450
468
553
850
40 60524
Service panel
Refrigerant-pipe flared connection [15.88
Refrigerant-pipe flared connection [9.52
Knock out hole for front piping
(refrigerant,drainage and wiring)
42
45
104
33
Bottom piping hole
2-U-shaped notched holes
Drain hole [33
Drain hole [33
2-12o23 Oval holes (standard bolt M10)
Handle for moving
A
Handle for moving
138
95
Rear piping hole
Rear fresh air intake
A
Knock out hole for right piping
(refrigerant,drainage and wiring)
60
120
4553
Knock out holes for power line 2-[27
MU-30RV -
E1
OUTDOOR UNIT
Unit: mm
12
6
WIRING DIAGRAM
MS-18RV -
INDOOR UNIT
TO OUTDOOR UNIT
CONNECTING
220-240V~
POWER SUPPLY CORD ~/N 220-240V 50Hz
PE
CIRCUIT BREAKER
SYMBOL
C11
DSAR
F11 F12
HIC1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
E1
MODEL WIRING DIAGRAM
TB
L
GRN/YLW
INDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A) THERMAL FUSE(93°C) DC / DC CONVERTER
BRN
2
N
BLU
NAME
BRN
F12
WHT
BLU
BRN
DSAR
BLU BLU
GRN/YLW
2 1
CN
LD1
102
SYMBOL
IC141
MF MV
NR11
RT11
4
52C
3
F11
ELECTRONIC CONTROL P.C. BOARD
REMOTE CONTROLLER
BLU
CN
151
MV
DISPLAY P.C. BOARD
CN201
3 1
CN 101
5
RECEIVER P.C. BOARD
33
NAME NAME HYBRID IC INDOOR FAN MOTOR(INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR
HIC1
TRANS
IC141
NR11
SYMBOL
RT12
TB
52C
CN 112
3
CN 121
CN211
4
C11
2 1
CN 111
RT12
BRN YLW GRY WHT RED BLK
RT11
MF
INDOOR COIL THERMISTOR TERMINAL BLOCK CONTACTOR
VG79B019H01
MU-18RV -
OUTDOOR UNIT
SYMBOL
C1 C2
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
E1
MODEL WIRING DIAGRAM
TB
2
220-240V~
FROM
INDOOR UNIT
CONNECTING
NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR
N
GRN/YLW
SYMBOL
F
MC
WHT
WHT
BLU
F
C2
RED ORN WHT BLU
1 2 3 4
RED ORN WHT BLK
NAME NAME FUSE(2A) COMPRESSOR(INNER PROTECTOR)
C1
RED
MF
SYMBOL
MF
TB
C
MC
S
BLK
R
OUTDOOR FAN MOTOR(INNER PROTECTOR) TERMINAL BLOCK
SG79J002H01
13
MS-24RV -
E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
220-240V~
220-240V~
POWER SUPPLY CORD ~/N 220-240V 50Hz
PE
CIRCUIT BREAKER
SYMBOL
C11
DSAR
F11 F12
HIC1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
MU-24RV -
INDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A) THERMAL FUSE(93°C) DC / DC CONVERTER
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
E1
OUTDOOR UNIT
MODEL WIRING DIAGRAM
TB
BLU
BRN
RED
BLU
WHT
F12
1
DSAR
BLU
BLU
WHT
GRN/YLW
SYMBOL
IC141
MF
MV NR11 RT11
2
BLU
1
WHT
CN
LD1
102
3
DISPLAY P.C. BOARD
HYBRID IC INDOOR FAN MOTOR(INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMIST OR
3
N
2
L
GRN/YLW
NAME
MODEL WIRING DIAGRAM
TB
220-240V~
220-240V~
3
BLU
N
2
WHT WHT
F
A2/b
52C
52C
21
REDRED
A1/a
HIC1
CN201
3 1
CN
151
MV
5
4
52C
3
CN 101
3
RECEIVER P.C. BOARD
TRANS
F11
ELECTRONIC CONTROL P.C. BOARD
NAME NAME
TB2
1
WHT
RED
BLU
RED
26F1
C1
CR
RED
REDBLU BLK
GRY
78
X1
S
MC
R
IC141
NR11
REMOTE CONTROLLER
SYMBOL
RT12
TB
52C
3
X1
5 6
1
BLU
YLW
YLW
C
CN
112
CN
111
3
CN
121
CN211
4
C11
2 1
RT12
RT11
BRN YLW GRY WHT RED BLK
INDOOR COIL THERMISTOR TERMINAL BLOCK CONTACTOR
VG79B020H01
C2
RED
BLK
ORN
WHT
123456
WHT
BLK
RED
ORN
MF
MF
FROM INDOOR UNIT CONNECTING
SYMBOL
CR
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
CR SURGE ABSORBER COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
FUSE(2A)
F
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
GRN/YLW
SYMBOL
MC
MF
TB
TB2
NAME NAME COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK TERMINAL BLOCK
14
SYMBOL
X1
26F1
52C
FAN MOTOR RELAY THERMOSTAT (AIR FLOW CONTORL) COMPRESSOR CONTACTOR
SG79J003H01
MS-30RV -
E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220-240V
~
MODEL WIRING DIAGRAM
TB
3 N L
RED BLU BRN
CN
151
GRN/YLW
15
CN201
3 2 1
TAB12
CN
102
CN 101
ELECTRONIC CONTROL P.C. BOARD
33
HIC1
TRANS
F11
NR11
SR141
C11
4 3 2 1
CN112
CN 121
1 3 4
CN211
CN 111
RT13 RT12
3
BLK GRY YLW BRN
MF
WHT RED
RT11
MV1
MV2
MV2
SYMBOL
C11 F11
HIC1
MF
MV1
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(3.15A) DC/DC CONVERTER INDOOR FAN MOTOR(INNER PROTECTOR) VANE MOTOR(HORIZONTAL)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL
MV2
NR11
RT11 RT12 RT13
DISPLAY P.C.BOARD
VANE MOTOR(VERTICAL) VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
RECEIVER P.C.BOARD
NAME NAME
REMOTE CONTROLLER
SYMBOL
SR141
TB
SOLID STATE RELAY TERMINAL BLOCK
SG79J148H01
15
MU-30RV - MODEL WIRING DIAGRAM
E1
OUTDOOR UNIT
CIRCUIT BREAKER
~ /N 220-240V
POWER SUPPLY
50Hz
12V
220-240V~
TO INDOOR UNIT
CONNECTING
TB2
L
N
3
N
L
TB1
PE
GRN/YLW
WHT
DSAR
BLU
WHT
BLU
BRN
BLU
RT62 RT63
CN662
X52
T61
MF
LEV
WHT
YLW21BLK
6
SR62
SR61
3456
YLW
BLK
WHT
123
DEICER P.C. BOARD
1
A2 A1
52C
ORN
CN711CN724
NR61
CZ
52C
C1
RED
X52
COM
RED ORN
2
F61
CN730
WHTWHT
C2
TAB52
NO
WHT
RED BLK
1 3 5
WHT
BLU
RED
BLU
C
MC
S
R
SYMBOL
CZ C1 C2
DSAR
F61
LEV
MC
NOTE 1. Use copper conductors only (For field wiring).
CZ SURGE ABSORBER COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE(3.15A) EXPANSION VALVE COIL COMPRESSOR (INNER PROTECTOR)
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N, L).
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL
MF
NR61
RT62 RT63 SR61 SR62
TB1
NAME NAME OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DISCHARGE TEMPERATURE THERMIST OR AMBIENT TEMPERA TURE THERMIST OR SOLID STATE RELAY SOLID STATE RELAY TERMINAL BLOCK
SYMBOL
TB2
T61 X52
52C
TERMINAL BLOCK TRANSFORMER CONTACTOR COMPRESSOR CONTACTOR
SG79J153H02
16
7
REFRIGERANT SYSTEM DIAGRAM
MS-18RV -
E1
INDOOR UNIT
Indoor heat exchanger
Distributor
Room temperature thermistor RT11
Indoor coil thermistor
RT12
Refrigerant pipe [15.88 (with heat insulator)
Stop valve (with service port)
Flared connection
Stop valve
Refrigerant pipe [6.35
(with heat insulator)
Accumulator
Capillary tube [3.0X[2.0X700
Compressor
Refrigerant flow in cooling
MU-18RV -
OUTDOOR UNIT
Outdoor heat
Strainer
exchanger
Unit:mm
E1
MS-24RV -
E1
INDOOR UNIT
Indoor heat exchanger
Distributor
Room temperature thermistor RT11
Indoor coil thermistor
RT12
Refrigerant pipe [15.88 (with heat insulator)
Stop valve (with service port)
Flared connection
Stop valve
Refrigerant pipe 9.52
(with heat insulator)
Accumulator
Compressor
Discharge
Capillary tube [3.0X[1.6X350
Capillary tube [3.0X[2.0X700
Pressure Regulator open 26kgf/F
Unit:mm
MU-24RV -
E1
OUTDOOR UNIT
Outdoor heat exchanger
Strainer
17
Refrigerant flow in cooling
Indoor heat exchanger
Outdoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube [3.6[2.450
Refrigerant flow in cooling
Compressor
Refrigerant pipe [15.88 (with heat insulator)
Refrigerant pipe [9.52 (with heat insulator)
Indoor coil thermistor RT12(main)
LEV
Strainer
Strainer
Accumulator
Ambient temperature thermistor RT63
Strainer
Capillary tube [4.0[2.4200 (Upper path)
Capillary tube [4.0[2.4100 (Lower path)
Unit:mm
MS-30RV -
INDOOR UNIT
E1
MU-30RV -
E1
OUTDOOR UNIT
18
Model
Refrigerant piping
Max. length : m
A
Piping size O.D : mm
Length of connecting pipe : m
Indoor unit
Gas 0.43
Liquid 0.5
Gas
15.88
Liquid
6.35
9.52
Outdoor unit
Gas 0
Liquid 0
MS-18RV -
E1
MU-18RV - E1 MS-24RV - E1
MU-24RV - E1
15
30
MS-30RV - E1 MU-30RV - E1
MAX. REFRIGERANT PIPING LENGTH
Outdoor unit
precharged
0
45
120
Refrigerant piping length (one way)
15m10m7m
Model
2,400
20m 25m
30m
195 345270
MS-30RV -
E1
MU-30RV -
E1
MAX. HEIGHT DIFFERENCE
Indoor unit
w Max. Height difference 5m (MS-18/24RV) /15m(MS-30RV)
w Height difference should be within 5m(MS-18/24RV) /15m(MS-30RV) regardless of which unit, indoor or outdoor position is high.
Refrigerant Piping
ADDITIONAL REFRIGERANT CHARGE(R22 : g)
Model
MS-18RV - E1 MU-18RV - E1 MS-24RV - E1 MU-24RV - E1
Outdoor unit precharged
1,050
2,150
Max.length
A
Outdoor unit
Refrigerant piping length (one way)
7m
0
Calculation : Xg=15g/mx(Refrigerant piping length (m)-7)
10m
45
15m
120
Calculation : Xg=15g/mo(Refrigerant piping length(m)-7)
19
MS-18RV - E1
MS-24RV - E1
14.9
13.5
12.2
11.0
9.8
8.6
MS-30RV - E1
18.9
17.1
15.4
13.7
12.2
10.7
8
PERFORMANCE CURVES
MS-18RV - MU-18RV ­MS-24RV - MU-24RV ­MS-30RV - MU-30RV -
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB (2) Indoor outlet air wet-bulb temperature :°CWB (3) Outdoor intake air dry-bulb temperature :°CDB (4) Total input :W Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry -bulb temperature for your reference at service.
E1E1
E1E1
E1E1
Cooling
}
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
Wet-and dry-bulb thermometers
OUTDOOR UNIT
Wet-and dry-bulb thermometers
20
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
15 20
50
25 60
30 70(%)
35(:)
0.3
0.4
0.5
0.6
0.7
7
6
5
4
3
18 32
220V-240V
15 20
50
25 60
30 70(%)
35(:)
6
7
8
9
10
11
220V-240V
18
32
8
7
6
5
4
3
15 18 20
50
25 60
30 327035(:)
(%)
0.2
0.3
0.4
0.5
0.6
220-240V
2
3
4
5
6
15 18 20
50
25 60
30 327035(:)
(%)
10
11
12
13
14
15
16
17
220V
240V
COOL operation
11
Both indoor and outdoor unit are under the same temperature/humidity condition. Dry-bulb temperature
20 25 30 70
22
Air flow should be set at MAX.
33
The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge])
Relative humidity(%)
50 60
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
(kgf/F[Gauge])(MPa[Gauge])
MU-18RV -
MU-24RV -
E1
MU-18RV -
E1
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
E1
MU-24RV -
E1
220V
240V
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
220-240V
MU-30RV -
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
E1
MU-30RV -
E1
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
21
PERFORMANCE DATA
INDOOR INDOOR
21 25 27 30
DB(:) WB(:)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
OUTDOOR DB
(:)
21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 18 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
5.99
6.25
5.99
6.25
6.50
5.99
6.25
6.50
5.99
6.25
6.50
6.83
5.99
6.25
6.50
6.83
5.99
6.25
6.50
6.83
7.04
5.99
6.25
6.50
6.83
7.04
5.99
6.25
6.50
6.83
7.04
5.99
6.25
6.50
6.83
7.04
5.99
6.25
6.50
6.83
7.04
5.99
6.25
6.50
6.83
7.04
5.99
6.25
6.50
6.83
7.04
2.88
2.25
3.12
2.50
1.82
3.36
2.75
2.08
3.60
3.00
2.34
1.64
3.84
3.25
2.60
1.91
4.07
3.50
2.86
2.19
1.41
4.31
3.75
3.12
2.46
1.69
4.55
4.00
3.38
2.73
1.97
4.79
4.25
3.64
3.01
2.25
5.03
4.50
3.90
3.28
2.53
5.27
4.75
4.16
3.55
2.82
5.51
5.00
4.42
3.83
3.10
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
1528 1604 1528 1604 1662 1528 1604 1662 1528 1604 1662 1738 1528 1604 1662 1738 1528 1604 1662 1738 1834 1528 1604 1662 1738 1834 1528 1604 1662 1738 1834 1528 1604 1662 1738 1834 1528 1604 1662 1738 1834 1528 1604 1662 1738 1834 1528 1604 1662 1738 1834
5.74
5.99
5.74
5.99
6.27
5.74
5.99
6.27
5.74
5.99
6.27
6.58
5.74
5.99
6.27
6.58
5.74
5.99
6.27
6.58
6.83
5.74
5.99
6.27
6.58
6.83
5.74
5.99
6.27
6.58
6.83
5.74
5.99
6.27
6.58
6.83
5.74
5.99
6.27
6.58
6.83
5.74
5.99
6.27
6.58
6.83
5.74
5.99
6.27
6.58
6.83
2.75
2.16
2.98
2.40
1.76
3.21
2.64
2.01
3.44
2.88
2.26
1.58
3.67
3.12
2.51
1.84
3.90
3.36
2.76
2.11
1.37
4.13
3.60
3.01
2.37
1.64
4.36
3.84
3.26
2.63
1.91
4.59
4.07
3.51
2.89
2.19
4.82
4.31
3.76
3.16
2.46
5.05
4.55
4.01
3.42
2.73
5.28
4.79
4.27
3.68
3.01
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
1604 1700 1604 1700 1767 1604 1700 1767 1604 1700 1767 1834 1604 1700 1767 1834 1604 1700 1767 1834 1929 1604 1700 1767 1834 1929 1604 1700 1767 1834 1929 1604 1700 1767 1834 1929 1604 1700 1767 1834 1929 1604 1700 1767 1834 1929 1604 1700 1767 1834 1929
5.51
5.81
5.51
5.81
6.12
5.51
5.81
6.12
5.51
5.81
6.12
6.43
5.51
5.81
6.12
6.43
5.51
5.81
6.12
6.43
6.73
5.51
5.81
6.12
6.43
6.73
5.51
5.81
6.12
6.43
6.73
5.51
5.81
6.12
6.43
6.73
5.51
5.81
6.12
6.43
6.73
5.51
5.81
6.12
6.43
6.73
5.51
5.81
6.12
6.43
6.73
5.30
5.61
5.30
5.61
5.87
5.30
5.61
5.87
5.30
5.61
5.87
6.22
5.30
5.61
5.87
6.22
5.30
5.61
5.87
6.22
6.53
5.30
5.61
5.87
6.22
6.53
5.30
5.61
5.87
6.22
6.53
5.30
5.61
5.87
6.22
6.53
5.30
5.61
5.87
6.22
6.53
5.30
5.61
5.87
6.22
6.53
5.30
5.61
5.87
6.22
6.53
2.64
2.09
2.86
2.33
1.71
3.08
2.56
1.96
3.30
2.79
2.20
1.54
3.53
3.02
2.45
1.80
3.75
3.26
2.69
2.06
1.35
3.97
3.49
2.94
2.31
1.62
4.19
3.72
3.18
2.57
1.88
4.41
3.95
3.43
2.83
2.15
4.63
4.19
3.67
3.08
2.42
4.85
4.42
3.92
3.34
2.69
5.07
4.65
4.16
3.60
2.96
2.55
2.02
2.76
2.24
1.64
2.97
2.47
1.88
3.18
2.69
2.11
1.49
3.39
2.92
2.35
1.74
3.61
3.14
2.58
1.99
1.31
3.82
3.37
2.82
2.24
1.57
4.03
3.59
3.05
2.49
1.83
4.24
3.81
3.28
2.74
2.09
4.46
4.04
3.52
2.99
2.35
4.67
4.26
3.75
3.24
2.61
4.88
4.49
3.99
3.48
2.87
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
1681 1738 1681 1738 1815 1681 1738 1815 1681 1738 1815 1891 1681 1738 1815 1891 1681 1738 1815 1891 1986 1681 1738 1815 1891 1986 1681 1738 1815 1891 1986 1681 1738 1815 1891 1986 1681 1738 1815 1891 1986 1681 1738 1815 1891 1986 1681 1738 1815 1891 1986
1757 1815 1757 1815 1891 1757 1815 1891 1757 1815 1891 1986 1757 1815 1891 1986 1757 1815 1891 1986 2044 1757 1815 1891 1986 2044 1757 1815 1891 1986 2044 1757 1815 1891 1986 2044 1757 1815 1891 1986 2044 1757 1815 1891 1986 2044 1757 1815 1891 1986 2044
CAP ACITY: 5.1(kW) SHF : 0.66 INPUT: 1910(W)
COOL operation
E1E1
22
MS-18RV - : MU-18RV - (220V)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB: Wet-bulb temperature
PERFORMANCE DATA
INDOOR INDOOR
35 40 43 46
DB(:) WB(:)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
OUTDOOR DB
(:)
21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 18 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
5.00
5.25
5.00
5.25
5.56
5.00
5.25
5.56
5.00
5.25
5.56
5.87
5.00
5.25
5.56
5.87
5.00
5.25
5.56
5.87
6.17
5.00
5.25
5.56
5.87
6.17
5.00
5.25
5.56
5.87
6.17
5.00
5.25
5.56
5.87
6.17
5.00
5.25
5.56
5.87
6.17
5.00
5.25
5.56
5.87
6.17
5.00
5.25
5.56
5.87
6.17
2.40
1.89
2.60
2.10
1.56
2.80
2.31
1.78
3.00
2.52
2.00
1.41
3.20
2.73
2.22
1.64
3.40
2.94
2.45
1.88
1.23
3.60
3.15
2.67
2.11
1.48
3.80
3.36
2.89
2.35
1.73
4.00
3.57
3.11
2.58
1.97
4.20
3.78
3.34
2.82
2.22
4.40
3.99
3.56
3.05
2.47
4.60
4.20
3.78
3.28
2.72
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
1872 1948 1872 1948 2025 1872 1948 2025 1872 1948 2025 2101 1872 1948 2025 2101 1872 1948 2025 2101 2177 1872 1948 2025 2101 2177 1872 1948 2025 2101 2177 1872 1948 2025 2101 2177 1872 1948 2025 2101 2177 1872 1948 2025 2101 2177 1872 1948 2025 2101 2177
4.59
4.90
4.59
4.90
5.20
4.59
4.90
5.20
4.59
4.90
5.20
5.51
4.59
4.90
5.20
5.51
4.59
4.90
5.20
5.51
5.81
4.59
4.90
5.20
5.51
5.81
4.59
4.90
5.20
5.51
5.81
4.59
4.90
5.20
5.51
5.81
4.59
4.90
5.20
5.51
5.81
4.59
4.90
5.20
5.51
5.81
4.59
4.90
5.20
5.51
5.81
2.20
1.76
2.39
1.96
1.46
2.57
2.15
1.66
2.75
2.35
1.87
1.32
2.94
2.55
2.08
1.54
3.12
2.74
2.29
1.76
1.16
3.30
2.94
2.50
1.98
1.40
3.49
3.13
2.71
2.20
1.63
3.67
3.33
2.91
2.42
1.86
3.86
3.53
3.12
2.64
2.09
4.04
3.72
3.33
2.86
2.33
4.22
3.92
3.54
3.08
2.56
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
1986 2044 1986 2044 2139 1986 2044 2139 1986 2044 2139 2197 1986 2044 2139 2197 1986 2044 2139 2197 2273 1986 2044 2139 2197 2273 1986 2044 2139 2197 2273 1986 2044 2139 2197 2273 1986 2044 2139 2197 2273 1986 2044 2139 2197 2273 1986 2044 2139 2197 2273
4.41
4.72
4.41
4.72
5.02
4.41
4.72
5.02
4.41
4.72
5.02
5.36
4.41
4.72
5.02
5.36
4.41
4.72
5.02
5.36
5.64
4.41
4.72
5.02
5.36
5.64
4.41
4.72
5.02
5.36
5.64
4.41
4.72
5.02
5.36
5.64
4.41
4.72
5.02
5.36
5.64
4.41
4.72
5.02
5.36
5.64
4.41
4.72
5.02
5.36
5.64
4.23
4.54
4.23
4.54
4.85
4.23
4.54
4.85
4.23
4.54
4.85
5.20
4.23
4.54
4.85
5.20
4.23
4.54
4.85
5.20
5.46
4.23
4.54
4.85
5.20
5.46
4.23
4.54
4.85
5.20
5.46
4.23
4.54
4.85
5.20
5.46
4.23
4.54
4.85
5.20
5.46
4.23
4.54
4.85
5.20
5.46
4.23
4.54
4.85
5.20
5.46
2.12
1.70
2.29
1.89
1.41
2.47
2.08
1.61
2.65
2.26
1.81
1.29
2.82
2.45
2.01
1.50
3.00
2.64
2.21
1.71
1.13
3.18
2.83
2.41
1.93
1.35
3.35
3.02
2.61
2.14
1.58
3.53
3.21
2.81
2.36
1.80
3.71
3.40
3.01
2.57
2.03
3.88
3.59
3.22
2.78
2.25
4.06
3.77
3.42
3.00
2.48
2.03
1.63
2.20
1.82
1.36
2.37
2.00
1.55
2.54
2.18
1.74
1.25
2.71
2.36
1.94
1.46
2.88
2.54
2.13
1.66
1.09
3.05
2.72
2.33
1.87
1.31
3.22
2.90
2.52
2.08
1.53
3.39
3.09
2.71
2.29
1.75
3.56
3.27
2.91
2.50
1.96
3.73
3.45
3.10
2.71
2.18
3.89
3.63
3.29
2.91
2.40
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
0.48
0.36
0.52
0.40
0.28
0.56
0.44
0.32
0.60
0.48
0.36
0.24
0.64
0.52
0.40
0.28
0.68
0.56
0.44
0.32
0.20
0.72
0.60
0.48
0.36
0.24
0.76
0.64
0.52
0.40
0.28
0.80
0.68
0.56
0.44
0.32
0.84
0.72
0.60
0.48
0.36
0.88
0.76
0.64
0.52
0.40
0.92
0.80
0.68
0.56
0.44
2025 2101 2025 2101 2177 2025 2101 2177 2025 2101 2177 2244 2025 2101 2177 2244 2025 2101 2177 2244 2321 2025 2101 2177 2244 2321 2025 2101 2177 2244 2321 2025 2101 2177 2244 2321 2025 2101 2177 2244 2321 2025 2101 2177 2244 2321 2025 2101 2177 2244 2321
2063 2158 2063 2158 2216 2063 2158 2216 2063 2158 2216 2292 2063 2158 2216 2292 2063 2158 2216 2292 2368 2063 2158 2216 2292 2368 2063 2158 2216 2292 2368 2063 2158 2216 2292 2368 2063 2158 2216 2292 2368 2063 2158 2216 2292 2368 2063 2158 2216 2292 2368
CAP ACITY: 5.1(kW) SHF : 0.66 INPUT: 1910(W)
COOL operation
MS-18RV - : MU-18RV - (220V)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB: Wet-bulb temperature
E1E1
23