Sound Test Results
Genset:
Enclosure:
G070LG 6.8L Ford
Level 2 Acoustic
Back
Pos 1
Pos 1
GENERATOR END
GENERATOR END
Right Left
Pos 4
Pos 4
RADIATOR END
RADIATOR END
Pos 3
Pos 3
Pos 2
Pos 2
Front
Measured Sound Levels - 60 Hz
90
88
86
84
82
80
78
76
74
72
70
68
dB (A) @ 7 Meters
68.9
66
64
62
60
58
56
1234
69.0
Position Number
Avg. 70.6 dBA
72.8
71.8
Actual Average
Notes: 1. All positions 23 ft (7M) from side faces of generator set.
OLYMPIAN POWER SYSTEMS
OLYMPIAN POWER SYSTEMS
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.
4. Non-enclosed sets do not include exhaust sound during testing.
DATA SUBJECT TO CHANGE WITHOUT NOTICE
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0601650SSD 10/11
0601650SSD 10/11