Maytag MMV1153WB, MMV6186WW, MMV6186WS, MMV6186WB, MMV6180WW Dimension Guide

...
0 (0)
Maytag MMV1153WB, MMV6186WW, MMV6186WS, MMV6186WB, MMV6180WW Dimension Guide

Microwave Hood Combination

PRODUCT MODEL NUMBERS

MMV1153W

MMV1164W

MMV6180W

MMV1163W

MMV5208W

MMV6186W

Electrical: A 120-Volt, 60-Hz, AC-only, 15or 20-amp fused electrical supply with a fuse or circuit breaker. A time-delay fuse or time-delay circuit breaker is recommended. It is recommended that a separate circuit serving only this microwave oven be provided.

VENTING REQUIREMENTS

PRODUCT DIMENSIONS

17

"

16

"

(41.3 cm)

(43.8 cm)

 

 

A 3¹⁄" x 10" (8.3 x 25.4 cm) rectangular or 6" (15.2 cm) round vent should be used.

The total length of the vent system including straight vent, elbow(s), transitions and wall or roof caps must not exceed the equivalent of 140 ft (42.7 m) for either type of vent.

For best performance, use no more than three 90° elbows.

15

"

(40.

0

cm)

 

 

)

 

.0 cm

29

" (76

To calculate the length of the system you need, add the equivalent length for each vent

 

 

 

 

 

 

 

 

 

 

CABINET OPENING DIMENSIONS

 

 

 

 

 

piece used in the system. See the following examples:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

The grounded 3-prong outlet must be inside the upper cabinet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30"

 

 

 

 

(76.2 cm)

 

 

 

 

min.

 

 

 

 

30" (76.2 cm) typical*

D

E

F

G

12" (30.5 cm) min.

14" (35.6 cm) max.

A. Rectangular to round transition piece: 3

" x 10" to 6" = 5 ft

 

(8.3 x 25.4 cm to 15.2 cm = 1.5 m)

 

66" (167.6 cm) min.

B. Roof cap: 3 " x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)

 

C. 90° elbow: 3 " x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)

 

D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)

 

 

E. Wall cap: 3 " x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)

 

F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)

 

 

G. 90° flat elbow: 3 " x 10" = 10 ft (8.3 x 25.4 cm = 3 m)

 

6" (15.2 cm) vent system = 73 ft (22.2 m) total

 

A

 

 

B

 

 

 

6 ft (1.8 m)

 

 

2 ft

 

A. Two 90° elbows = 20 ft (6.1 m)

 

A. 2" x 4" wall stud

(0.6 m)

 

B. 1 wall cap = 40 ft (12.2 m)

 

 

 

B. Grounded 3-prong outlet

 

 

 

 

 

 

 

C. 1 rectangular to round transition

 

 

 

 

 

 

 

 

piece = 5 ft (1.5 m)

*30" (76.2 cm) is typical for 66" (167.6 cm) installation height.

 

D. 2 ft (0.6 m) + 6 ft (1.8 m)

Exact dimensions may vary depending on type of range/cooktop

 

straight = 8 ft (2.4 m)

below.

C

D

 

3 " x 10" (8.3 x 25.4 cm) vent system = 73 ft (22.2 m) total

Rectangular to Round Transition for Roof Venting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The minimum 3" (7.6 cm) clearance must exist between

 

 

 

 

A

B

 

 

 

 

 

 

the top of the microwave oven and the rectangular to round

 

 

 

 

 

 

 

 

6 ft (1.8 m)

 

 

 

transition piece so that the damper can open freely and fully.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 ft

 

 

 

 

 

 

 

 

 

 

(0.6 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

B

 

 

A. One 3 " x 10" (8.3 x 25.4 cm) 90° elbow = 25 ft (7.6 m)

D

 

C

A. Roof cap

B. 1 wall cap = 40 ft (12.2 m)

 

 

 

 

 

 

 

 

 

 

 

B. 6" (15.2 cm) min. diameter round vent

C. 2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C. Elbow (for wall venting only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D. Wall cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

E. 3 " x 10" to 6" (8.3 x 25.4 cm to 15.2 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" (7.6 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rectangular to round transition piece

F. Vent extension piece, at least 3" (7.6 cm) high

Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to change materials and specifications without notice.

Dimensions are for planning purposes only. For complete details, see Installation

Ref. W10238252A

Instructions packed with product. Specifications subject to change without notice.