Microwave Hood Combination

PRODUCT MODEL NUMBERS

MMV1164W MMV6180W

MMV4203W MMV6186W

MMV5208W

Electrical: A 120-Volt, 60-Hz, AC-only, 15or 20-amp fused electrical supply with a fuse or circuit breaker. A time-delay fuse or time-delay circuit breaker is recommended. It is recommended that a separate circuit serving only this microwave oven be provided.

VENTING REQUIREMENTS

A 3¹⁄" x 10" (8.3 x 25.4 cm) rectangular or 6" (15.2 cm) round vent should be used.

The total length of the vent system including straight vent, elbow(s), transitions and wall or roof caps must not exceed the equivalent of 140 ft (42.7 m) for either type of vent.

For best performance, use no more than three 90° elbows.

To calculate the length of the system you need, add the equivalent length for each vent piece used in the system. See the following examples:

A B C

PRODUCT DIMENSIONS

17¹⁄ " (43.8 cm)

16

¹⁄

"

(41.

 

0

cm)

 

16¹⁄ " (41.3 cm)

 

 

.0 cm)

 

" (76

 

29

 

 

CABINET OPENING DIMENSIONS

The grounded 3-prong outlet must be inside the upper cabinet.

A B

 

 

 

 

 

12" (30.5 cm) min.

 

 

 

 

 

14" (35.6 cm) max.

 

 

 

 

30"

upper cabinet and

 

 

 

 

(76.2 cm)

side cabinet depth

 

 

 

 

min.

 

D

E

F

G

30"

 

(76.2 cm)

 

A. Rectangular to round transition piece: 3

" x 10" to 6" = 5 ft

typical*

 

 

 

(8.3 x 25.4 cm to 15.2 cm = 1.5 m)

 

 

 

B. Roof cap: 3 " x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)

 

 

C. 90° elbow: 3

" x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)

66" (167.6 cm) min.

 

D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)

 

 

 

 

 

E. Wall cap: 3 " x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)

 

 

F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)

 

 

 

G. 90° flat elbow: 3 " x 10" = 10 ft (8.3 x 25.4 cm = 3 m)

 

 

6" (15.2 cm) vent system = 73 ft (22.2 m) total

 

 

A

 

 

B

 

 

 

 

6 ft (1.8 m)

 

 

 

2 ft

 

A. Two 90° elbows = 20 ft (6.1 m)

 

 

 

(0.6 m)

 

B. 1 wall cap = 40 ft (12.2 m)

 

 

 

 

 

 

 

 

 

 

 

 

C. 1 rectangular to round transition

 

 

 

 

 

 

 

 

 

 

 

 

piece = 5 ft (1.5 m)

 

 

 

 

 

 

D. 2 ft (0.6 m) + 6 ft (1.8 m)

 

 

A. 2" x 4" wall stud

 

 

 

 

 

C

 

straight = 8 ft (2.4 m)

 

 

B. Grounded 3-prong outlet

 

D

*30" (76.2 cm) is typical for 66" (167.6 cm) installation height.

 

 

 

 

 

 

 

 

 

Exact dimensions may vary depending on type of range/cooktop below.

3 " x 10" (8.3 x 25.4 cm) vent system = 73 ft (22.2 m) total

A B

6 ft (1.8 m)

2 ft

(0.6 m)

C

A.One 3" x 10" (8.3 x 25.4 cm) 90° elbow = 25 ft (7.6 m)

B.1 wall cap = 40 ft (12.2 m)

C.2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)

Rectangular to Round Transition for Roof Venting

NOTE: The minimum 3" (7.6 cm) clearance must exist between the top of the microwave oven and the rectangular to round transition piece so that the damper can open freely and fully.

A

B

C

D

A. Roof cap

 

 

 

 

B. 6" (15.2 cm) min. diameter round vent

 

 

 

E

C. Elbow (for wall venting only)

 

 

 

D. Wall cap

 

 

 

 

 

 

F

E. 3 " x 10" to 6" (8.3 x 25.4 cm to 15.2 cm)

3" (7.6 cm)

rectangular to round transition piece

F. Vent extension piece, at least 3" (7.6 cm) high

Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to change materials and specifications without notice.

Dimensions are for planning purposes only. For complete details, see Installation

Ref. W10344702B

Instructions packed with product. Specifications subject to change without notice.