Liquid Controls SP2800 User Manual

Software V ersions
8.x & 12.x
BATCHERBATCHER
BATCHER
BATCHERBATCHER
Installation and Operating Manual
Description
The Batcher is a programmable, microprocessor based unit which provides batch control, monitors flow rate and controls the flow of processing liquids. Start/Stop controls can be used in conjunction with prewarn and final relays to provide valve actuation or pump control. An optional configuration of fers streamlined preset adjustments, remote Start, Stop & Reset, and weighted averaging.
Features
Pulse or Analog InputDisplay Batch, Rate or Grand TotalPulse Count Input up to 20 KHz16 Point Linearization8 Digit K-Factors for Rate and TotalSecurity Lockout2-Way RS232/422 CommunicationsNEMA 4X/IP65 Front PanelScalable 4-20 mA OutputScaled Pulse OutputOptional Configuration Includes:
- Streamlined Preset Adjustment (Easy Preset)
- Remote Start, Stop and Reset
- Weighted A veraging
Batcher
Application
The unit is normally used for batch control or inventory tracking. The display may be toggled between batch, rate, and grand total. A programmable K-factor makes keying-in engineering units easy. The unit accepts pulse, contact closures or analog inputs and provides two separate preset controls.
Principle of Operation
The batcher receives an input from a pulse producing flowmeter through a sensor. The user programs the batcher to condition the incoming pulses signal and compute the batch flow and flow rate. A wide variety of different functions can then be performed based on the programmed configurations such as start/stop functions, totalizing, and/or flow rate monitoring. Several other inputs, outputs and functions are available.
99502 01/10/03
Batcher Series Technical Manual
SAFETY INSTRUCTIONS
!
The following instructions must be observed.
This instrument was designed and is checked in accordance with regulations in force EN 60950 (Safety of information technology equipment, including electrical business equipment”). A hazardous situation may occur if this instrument is not used for its intended purpose or is used incorrectly. Please note operating instructions provided in this manual.
The instrument must be installed, operated and maintained by personnel who have been properly trained. Personnel must read and understand this manual prior to installation and operation of the instrument.
The manufacturer assumes no liability for damage caused by incorrect use of the instrument or for modifications or changes made to the instrument.
T echnical Improvements
The manufacturer reserves the right to modify technical data without prior notice.
1. INTRODUCTION
1-1 General Description ................................................................................................ 1
1-2 T ypical Application................................................................................................... 1
1-3 Principles of Operation............................................................................................ 1
1-4 STD PRE and EZ PRE Operation Modes ............................................................... 3
1-5 Specifications .......................................................................................................... 4
1-6 Dimensions ............................................................................................................. 5
2. INSTALLATION
2-1 Receipt of Equipment.............................................................................................. 6
2-2 Return Shipment ..................................................................................................... 6
2-3 Panel Mounting ....................................................................................................... 6
2-4 Electrical Connections............................................................................................. 6
2-5 Wiring Connections and Diagrams.......................................................................... 7
3. OPERATION
3-1 Front Panel Operation............................................................................................. 8
3-2 VER 8.7 Programming ............................................................................................ 9
3-3 VER 8.7 K-Factor Programming ............................................................................. 9
3-4 Software Version 8.7 Programming Flow Chart.................................................... 10
3-5 VER 12.0 Programming .........................................................................................11
3-6 VER 12.0 16 Point Linearization Notes..................................................................11
3-7 Software Version 12.0 16 Pt. Programming Flow Chart........................................ 12
3-8 How to Program .................................................................................................... 13
3-9 Frequently Asked Questions About Setting Up The Batcher................................. 13
3-10 Setup Procedure For The Batcher ...................................................................... 14
3-11 Run Mode............................................................................................................ 27
3-12 Internal Operation ............................................................................................... 29
CONTENTS
4. INPUTS
4-1 Digital Pulse Inputs ............................................................................................... 30
4-2 Analog Inputs ........................................................................................................ 30
4-3 DC Power Inputs ................................................................................................... 32
4-4 AC Power Inputs ................................................................................................... 32
5. OUTPUTS
5-1 Frequency Output ................................................................................................. 32
5-2 Control Outputs ..................................................................................................... 33
5-3 Optional Analog Output......................................................................................... 33
5-4 Optional RS232 / RS422 Serial Communications................................................. 34
CONTENTS
6. TROUBLE SHOOTING AND MAINTENANCE GUIDE
6-1 Warning Messages................................................................................................ 34
6-2 Troubleshooting..................................................................................................... 35
6-3 Removing The Case ............................................................................................. 36
6-4 Maintenance.......................................................................................................... 36
7. CALCULATING THE K FACTORS
7-1 General ................................................................................................................. 36
7-2 Calculating the K Factors ...................................................................................... 37
7-3 Calculating 16 Point K Factors.............................................................................. 39
8. SERIAL COMMUNICATIONS
8-1 Unit Code .............................................................................................................. 40
8-2 Baud Rate ............................................................................................................. 40
8-3 Parity ..................................................................................................................... 40
8-4 RS232 Electrical Requirements ............................................................................ 40
8-5 RS232 Card Wiring ............................................................................................... 41
8-6 RS422 Electrical Requirements ............................................................................ 41
8-7 RS422 Card Wiring ............................................................................................... 42
8-8 Strobe Input Electrical Requirements.................................................................... 42
8-9 Strobe Wiring ........................................................................................................ 43
8-10 Serial Interface Operation ................................................................................... 43
8-11 Strobe Address Operation................................................................................... 45
9. Programming Worksheet ................................................................................................ 46
SECTION 1 INTRODUCTION
1-1 General Description Sections 1 through 8 of this manual describe
the wiring, programming and functionality of the standard Batch controller. Section 9 de­scribes the wiring, programming and function­ality of Batch controllers with software version
8.7 (Option 6). Software version 8.7 incorpo­rates Remote Start, Stop & Reset with EZ PRE (easy preset). EZ PRE is a useful tool for applications that require frequent changes to the Preset amount.
1-3 Principles of Operation
Presets
When the start button is pushed, two relays engage simultaneously to start flow. When the prewarn number is reached, one relay drops out. When the preset number is reached, the other relay drops out. The user may enter the two numbers when setting up the batch counter. The prewarn is set a cer­tain number of counts less than the preset number. If the prewarn is set larger than the preset, the message "PREWRONG" will ap­pear on the display.
The Batch controller uses the following soft­ware versions:
VER 8.7 (Basic unit; Remote Start, Stop
& Reset with EZ PRE “Easy Preset”)
VER 12.0 (Option 4; 16 point linearization)
1-2 Typical Application
Remote
Totalizer
123456
Strip Chart
Recorder
Analog Output
Flowmeter
Pulse Output
RS232 Output
Solenoid Valve
Computer
The above application involves liquid flow. The start button is pushed and the Batcher receives pulses from the flowmeter. The pulses are scaled by the K Factor and sent out via the pulsed output to an external counter. The Analog output is directed to a strip chart recorder which gives a hardcopy of the rate. As the Prewarn is reached, the control valve partially closes. When the final Preset is reached the valve shuts down com­pletely. At any time the flow can be sus­pended by hitting the stop button. Through the serial communications, a computer keeps a record of the daily events.
Ratemeter
Accurate to 5 1/2 digits (±1 display digit). The ratemeter can be programmed to accept al­most any number of pulses per unit of mea­surement, sample from 2 to 24 seconds maxi­mum, and auto range up to 6 digits of signifi­cant information. The ratemeter with a K Fac­tor of 1 displays the rate of pulses per second. Simply dial in the proper K Factor to display in minutes, hours or other units of measurement. Press the C button, while the unit is displaying the batch, to display the rate; 'R' is displayed on the left side of the display.
K Factor
The K Factor is used to convert the input pulses or analog input into workable units. The 8 digit K Factor is a divider with a range of 0.00011 to 99999999 (the decimal point may be keyed into any position). Separate K Factors may be entered into the count and rate sections of the Batcher. Thus, you may batch in gallons and display rate in liters per hour. The maximum factored count speed is 20000 Hz. The maximum factored rate is 7 digits.
16 Point Linearization (Optional) This option extends the accurate range by al­lowing users to dial in different K Factors for different input rates. This option may be used with digital or analog inputs. (See Section 7-
3.)
1
1-3 Principles of Operation (continued)
Counter
The maximum count is 99999999. In the setup mode choose "RO" (Reset to Zero) for adding (count up) operation or "SP" (Set to Preset) for subtracting (count down) opera­tion. At any time, the display can be made to flash the Grand Total by pressing the ENT button while in the run mode. Activating the CLR button while the Grand Total is flashing, resets the Grand Total counter.
Lockout
Unauthorized front panel changes can be pre­vented by entering a user selected, four digit code, in the "Lockout" mode. The status of the unit can be observed but "LOCK ON" ap­pears if changes are attempted. Entering the code again returns the unit to "LOCK OFF" status.
Analog Output (Optional) The Analog Output option is available on all units except those with Square Law inputs. Controlled by an Open Collector transistor, it gives a 4 to 20mA (or 0-20mA) output which corresponds to predefined rate or total read­ings. In the Setup mode the user is prompted to set the low and high (4 to 20 mA) values and also decide if the analog signal will corre­spond to the ratemeter or totalizer.
Frequency out
The Batcher generates a pulse out for each factored count. An NPN transistor output (Pin
2), can drive external devices at rates of 10, 200, 2000 or 20000 counts per second as se­lected through the keypad menu. If the K Factor scaled inputs generate pulses faster than the output speed selected, an internal buffer will store up to 9,999 counts before "DATALOST" flashes on the screen. This in­dicates that the counts being totaled and the scaled outputs may be incorrect. Note that all counts stored in the internal buffer will be pulsed out at the selected frequency even if the counter is reset.
Outcard (Optional) RS232 or RS422 serial two way communica­tions are available. Up to 15 units can be linked together in parallel and addressed separately to transmit unit status or accept new set points in the standard ASCII format. Baud rates of 300, 600, 1200, 2400, 4800 or 9600 as well as choice of odd, even, space, or mark parity can be selected by keypad con­trol.
A sinking driver generates a linear current across the user's external device (such as a strip chart recorder, PLC, computer, external meter, etc). The Batcher can supply the 24 VDC to power the current loop. (Connect pin 15 to 13, Pin 16 is now +24 VDC with respect to pin 12.) Connect Pin 16 to the + DC side of the external device and connect Pin 3 to -DC side of the external device.
2
1-4 STD PRE and EZ PRE Operation Modes
STD PRE and EZ PRE Operation Modes
Version 8.7 of the batcher software allows the user to choose between STD PRE (Standard Preset) and EZ PRE (Easy Preset) operation modes. STD PRE operation is well suited for batch amounts that do not change, since the program mode must be entered to change the preset and the batch count must be cleared before starting a new batch. EZ PRE has been designed for users who frequently change the batch amount. During EZ PRE operation, the preset can be viewed and changed without entering the program mode and another batch can be started without resetting the unit. Note:
inputs.
Note:
Before a batch is started and after a batch is complete, the unit will continue to totalize all EZ PRE is not available on units with 16 Point Linearization.
Using STD PRE Programming
Select STD PRE - Go into the Program Mode and
select STD PRE in the PRE TYP sub menu.
Set the PRESET and PREWARN - Go into the
Program Mode and enter the desired values for the PRESET and the PREWARN.
Program the Counter - Go into the Program
Mode and set up the counter in the COUNT sub menu.
Operation Start a Batch - In the Run Mode, reset the total
by pressing “CLR”, then press “A” to start. When started, both relays energize and the counter begins to count. When the batch is complete, the relays drop out and the unit displays the amount that was batched (0 if in Set to Preset mode).
Stop a Batch - Press “B, to temporarily stop
process by de-energizing the PRESET and PREWARN relays. Press start, “A”, to continue process.
Repeat a Batch - In the Run Mode, reset the total
and press the start button.
Change the Batch Size - Go to the Program
Mode and enter new PRESET and PREWARN values.
Using EZ PRE Programming
Select EZ PRE - Go into the Program Mode and
select EZ PRE in the PRE TYP sub menu.
Set the PRESET and PREWARN - Go into the
Program Mode and enter the desired values for the PRESET and the PREWARN.
Program the Counter - Go into the Program
Mode and set up the counter in the COUNT sub menu.
Operation Start a Batch - In the Run Mode, press A to
start. When started, both relays energize and the counter begins to total. When complete, the relays drop out and the display flashes the current PRESET value.
Stop a Batch - Press “B, to temporarily stop
process by de-energizing the PRESET and PREWARN relays. Press start, “A”, to continue process.
Repeat a Batch - Press the start button. Change the Batch Size - With the current
PRESET flashing on the display, type a new number using the keypad. This number becomes the PRESET.
Display Batch Total or Rate - With the current
PRESET flashing, press “ENT” to place the PRESET value in memory and use the “C” button to toggle between the Batch Total and the Rate.
3
1-5 Specifications Housing:
High impact plastic case with NEMA 4X front panel.
Dimensions: See Section 1-5, Page 4.
Display: 8 Digit, 0.55" High, 15 Segment, Red Orange, LED.
Input Power: A: 110 VAC ± 15% or 12 to 27 VDC B: 220 VAC ± 15% or 12 to 27 VDC
NOTE: AC Inputs are internally fused with a
160mA slow blow fuse.
Current: Maximum 280 mA DC or 5.3 VA at rated AC voltage.
Output Power: (On AC powered units only): +12 VDC at 100 mA. Separate Isolated 12 VDC at 100 mA to allow ± 12 VDC or +24 VDC, regulated ± 5% worst case.
Temperature: Operating: +32°F (0° C) to +130 ° F (+54° C) Storage: -40°F (-40° C) to +200 ° F (+93° C)
(Extended operating temperature range available, consult factory)
Memory: EEPROM stores all program, display mode and count data for a minimum of 10 years if power is lost.
Reset Front push button: "CLR" resets displayed number and control output. Remote Input (Terminal 5): Open or 0 to 1 VDC (low), 3 to 30 VDC (high), 10K ohm input impedance to ground. Minimum pulse on / off time 5 msec.
Accuracy over full temperature range: Analog - Zero error: ±0.175% full scale max.
Overall error: ±0.5% full scale max.
Digital - 100% (within specified voltage
ranges)
Pulse Inputs: 3A: Standard. High impedance pulse input. Open or 0 to 1 VDC (low), 3 to 30 VDC (high), 10K ohm input impedance. 20 KHz maximum speed (min. on / off 25 usec).
3B: Same as 3A except 4.7 K ohm pull up resistor to +5 VDC with respect to Terminal
12. Analog Inputs:
The current or voltage input is converted to a highly linear 0 to 10 KHz frequency. This fre­quency can then be scaled by 8 digit K-factors to display rate or count in the appropriate engi­neering units.
5A: 4-20 mA; 250 input impedance. 5B: 0-20 mA; 250 input impedance. 5C: 1-5 VDC; 15 K input impedance. 5D: 0-5 VDC; 15 K input impedance. 5E: 0-10 VDC; 15 K input imped-
ance.
6A: Square Law: 4-20 mA; 250 in-
put impedance.
4
1-5 Specifications (continued)
1-6 Dimensions
Factored Output: One pulse per each factored count Sinking (NPN Transistor) Open Collector sinks 250 mA maximum to 1 volt maximum from 30 VDC maximum Internal buffer: 9999 pulses Output speed: user selectable (see table below)
Speed (Hz) 10 200 2000 20000 Min. on/off (msec) 47.5 2.0 0.2 0.013
Analog output: (Not available with 4-20 mA, Square Law input type) 4-20 mA (or 0-20 mA) Sinking, (NPN transistor), Open Collector Compliance voltage: 3-24 VDC, non-inductive Accuracy: ±100 uA worst case Update Rate: Follows ratemeter
ABCD
8.17
(207.5)
7.375
(187.3)
(NOM.)
1 2 3
4 5 6
7 8 9
CLR0SET
3.31 (84)
Control Outputs: SPDT Relays Contact rating: 10 A 120/240 VAC or 28 VDC.
NPN Transistor Output Open Collector sinks maximum of 100 mA from 10 VDC when active Note: 10 VDC is provided at transistor outputs through the relay coils. If current greater than 2 mA is drawn, the relay will remain energized. Applying greater than 10 VDC may destroy the unit. The transistor will sink 100 mA in the "ON" state with relays installed.
0.53
(13.5)
6.0
(152.4)
(NOM.)
7.375 -0, +0.04 (187.3 -0, +1)
PANEL
CUTOUT
2.48 (63)
(NOM.)
2.50 -0, +0.02
(63.5 -0, +0.5)
All Dimensions are in inches (mm)
5
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1-5 Dimensions (continued)
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
Full Size Panel Cutout Template
(copy before using)
SECTION 2 INSTALLATION
2-1 Receipt of Equipment When the equipment is received, the outside packing case should be checked for damage incurred during shipment. If the packing case is damaged, the local carrier should be notified at once regarding his liability. A report should be submitted to the factory. Carefully remove the equipment from the pack­ing case and inspect for damaged or missing parts.
2-2 Return Shipment Do not return assembly or part with out a Return Material Authorization. The RMA is obtained by calling your local distributor.
2-3 Panel Mounting The controller should be located in an area with a clean, dry atmosphere which is relatively free of shock and vibration. The Batcher is installed in a 7.365" (187 mm) wide by 2.495" (63.4 mm) high panel cutout. To mount the controller proceed as follows: a. Prepare the panel opening. b. Slip the gasket (provided) over the rear of the
counter case and slide it forward until it engages the inner surface of the front bezel.
c. Install the screws (provided) in the mounting
brackets and insert in the holes located on both sides of the Batcher.
d. Tighten the screws firmly to attach the
counter bezel to the panel.
2-4 Electrical Connections (Reference Figures 2-1 to 2-3) All connections are completed at terminal blocks located at the rear of the case. Make sure all power is disconnected before making any electrical connections. In cases where cables are situated in areas with heavy electrical fields,
6
3-1 Front Panel Operation
A
STOP
START
START - Pressing “A, starts the process by energizing the PRESET and PREWARN relays. Press “CLR” to reset Batch Total before starting new batch.
RATE/TOTAL
MENU
D
CBA
ENT
Weighted Averaging
Version 8.7 of the batcher software includes weighted averaging of the rate display. Weighted
1
2
3
4
5
6
7
9
8
CLR
0
averaging is not available on units with 16 Point Linearization.
Weighted averaging can be used to create a more stable display when the rate input is fluctuating. A weight, W, from 00 to 99 is applied to the old rate data before the new rate data is sent to the display. The following equation is used:
Rate Display =
W = Weight (00-99)
(Old Data x W + New Data)
(W + 1)
B
C
D
ENT
CLR
STOP - Pressing B, will temporarily stop
the process by de-energizing the PRESET and PREWARN relays. Use START to continue the process from where it stopped.
RATE/TOTAL - Pressing “C toggles between rate and total count displays. The rate display has an “R” on the left side of the screen.
MENU - Pressing “D takes the unit out of the Run Mode and into the Programming Mode (See Programming, Page 43 and
45). D is also used make to some programming selections.
ENT - With Count showing in the Run Mode, pressing “ENT” displays the Grand Total, which begins flashing on the screen. Press “ENT” again to return to the Count. In the Programming Mode, “ENT” is used to accept a selection (See Programming, Page 43 and 45).
CLR - When the count total is displayed, pressing CLR will reset the counter to 0 or to Preset A depending on how it was programmed. When the Grand Total is displayed, pressing “CLR” will reset it to
0. When the Preset or Program Mode values are displayed, pressing “CLR” will reset them to 0, so that new values can be entered.
If a weight of 00 is used, the new rate data will go directly to the display without being averaged. If a number other than 00 is entered for the weight, then the new data will be averaged with the old data before being sent to the display. Higher weight numbers will create a more stable rate display. Small rate changes will be more noticeable when lower weight numbers are used.
Programming Weighted Averaging
1. In the Program Mode, got to the RATE sub menu and program the K-FACTOR, the WINDOW, and the SIG FIG parameters.
2. When the display shows WEIGHTXX (XX represents the current WEIGHT value), either accept the current value and return to the Run Mode by pressing “ENT” or clear the current value by pressing “CLR”.
3. If the current value was cleared, the display shows WEIGHT00. Using the keypad, enter a new WEIGHT value from 00 to 99. Press “ENT” to accept the new value and return to the Run Mode.
Remote Start, Stop, and Reset
A 4 to 30 VDC positive pulse will activate these inputs. Remote Start, Stop, and Reset is not available on units ordered with the Control Input option 7A (4-20 mA In, 4-20 mA Out).
START (Pin 10): When activated, the unit will
START as described in Front Panel Operation.
STOP/RESET (Pin 5): When activated, the unit will
STOP (If the unit is started and the batch is not complete). A second pulse to pin 5 will reset the counter (When the unit is stopped or when the batch is complete). If pin 5 is held high (4 to 30 VDC), the display will flash “STOPPED” and any start inputs will be inhibited.
8
3-2 VER 8.7 Programming
Overview:
This Section of the manual provides an outline of programming procedures for the batcher software version 8.7. Detailed descriptions and programming instructions for this unit are available in previous sections of this manual. Page number references are included to help you find related information in this manual.
Programming Procedures: Enter Program Mode - Press the MENU button,
D, in the Run Mode.
Choosing a Sub Menu - Once in the Program
Mode, continue pressing the “D” button until the desired Sub Menu is displayed. Press “ENT” to enter the selected Sub Menu.
Making a Selection - An arrow,
only the “D” button indicates that “D” is used to change the selection. When an arrow appears over B and D, one must be selected.
Entering a Value - The keypad is used to enter a
number. Use the “D” button to enter a decimal. (Ex: 34.5 would be entered by pressing “3”, “4”, D, and 5)
Accept a Value or Selection - Press “ENT to
accept the value and go to next step.
Exit Program Mode - Program or skip each step of
one of the menus to return to the Run Mode. Pressing ENT allows a step to be skipped without changing its value.
”, appearing over
3-3 VER 8.7 K-Factor Programming
(See Programming Flow Chart, Page 10) (For information on entering a K-Factor on a unit
with 16 Point Linearization, see 16 Point Linear- ization Notes, page 11) The K-Factor is usually provided in pulses per unit, and will have to be modified before entering it into the unit. On most flowmeters, the K-Factor is stamped on the name­plate. (see section 7 for Calculating K-Factors)
Count K-Factor:
The Count K-Factor must be modified to allow for the decimal point location chosen in the DEC LOC step.
K-Factor
DPF
DPF - The Decimal Point Factor is a divider to compensate for the displayed decimal point.
DPF Table
DPF Decimal DPF Decimal
1 XXXXXX. 1000 XXX.XXX
10 XXXXX.X 10000 XX.XXXX
100 XXXX.XX 100000 X.XXXXX
Rate K-Factor:
The Rate K-Factor must be modified to display the correct volume per time unit. The Rate K-Factor is not affected by the decimal point location selected in the Count menu. The decimal point displayed by the Rate Meter floats according to the significant figure setting used in the SIG FIG step.
K-Factor
TF
= Count K-Factor
= Rate K-Factor
Key to Programming Flow Chart:
Display - This box represents the unit's display. In the Run Mode, the flow rate, the batch total, or the grand total will be displayed.
XX Current Value - The number that is currently
programmed for that step. It must be cleared (CLR button) before entering a new value.
00 No Value - Indicates that programmed value
for that step has been cleared, and a new number may be entered.
Keypad - Use the front panel keypad to enter a value or select a decimal point location for this step.
TF - The Time Factor is a divider to adjust the time units that the Rate Meter shows.
TF Table
TF Time Units Rate Display
1 Seconds Units per Second
60 Minutes Units per Minute
3600 Hours Units per Hour
9
ENT
ENT
ODD
MARK
EVEN↓ SPACE
ENT
ENT
87654321
D.E.C. . .L.O.C.
ENT
D
B
R0 SP
ENT
ENT
WEIGHT00
CLR
ENT
WEIGHTXX
ENT
300↓ 4800
0
CLR
SIGFIG00
CLR
XXXX
CODE
SIGFIGXX
ENT
D
PARITY
ENT
600
1200
2400
D
BAUDRATE
ENT
D
B
PLSER
0
CLR
XXXX
SET HIGH
9600
ENT
0
CLR
XXXX
ENT
ENT
0
CLR
0
CLR
Software Version 8.7 Programming Flow Chart
ENT
EZ PRE
STD PRE
D
ENT
Page 1, 14
D
PRE TYP
XXXX
K-FACTOR
ENT
Page 15
D
COUNT
XXXX
K-FACTOR
ENT
Page 2, 15
D
RATE
D
Run Mode
0
CLR
XXXX
ENT
0
CLR
XXXX
ENT
Page 1, 14
D
MENU
PRESET
PREWARN
3-4
WINDOW00
CLR
WINDOWXX
Page 1, 17
D
10
ENT
SECUR 00
CLR
SECUR XX
ENT
Page 2, 19
D
LOCKOUT
ENT
UNIT 00
CLR
ANLG RT
UNIT XX
ENT
§ Page 2, 21
D
OUTCARD
SET LOW
ENT
ANLG CT
ENT
2000 ↓200
20000 ↓10
D
ENT
§ Page
2, 23
ENT
D
- On a Standard unit (Without 16 Point Linearization), the Count and/or the Rate must be programmed for basic operation.
§ - Sub menu will always appear, but feature may not be included in the unit. (Check Model Number).
D
Page
2, 24
D
ALG OUT↓OUTFREQ
3-5 VER 12.0 Programming
(Unit with 16 Point Linearization)
Overview:
This Section of the manual provides an outline of programming procedures for the software version
12.0. Detailed descriptions and programming instructions for this unit are available in the follow­ing sections of this manual. Page number refer­ences are included to help you find related informa­tion in this manual.
Programming Procedures: Enter Program Mode - Press the MENU button,
D, in the Run Mode.
Choosing a Sub Menu - Once in the Program
Mode, continue pressing the “D” button until the desired Sub Menu is displayed. Press “ENT” to enter the selected Sub Menu.
Making a Selection - An arrow, , appearing over
only the “D” button indicates that “D” is used to change the selection. When an arrow appears over B and D, one must be selected.
Entering a Value - The keypad is used to enter a
number. Use the “D” button to enter a decimal. (Ex: 34.5 would be entered by pressing “3”, “4”, D, and 5)
Accept a Value or Selection - Press “ENT to
accept the value and go to next step.
Exit Program Mode - Program or skip each step of
one of the menus to return to the Run Mode. Pressing ENT allows a step to be skipped without changing its value. (Note: “B” or “D” must be pressed on the first step in the DEV TYP menu)
3-6 VER 12.0 16 Point Linearization Notes
(See Programming Flow Chart, Page 12)
A K-Factor and a Frequency must be entered for at least three points on a unit with Linearization.
Linearization K-Factor: The K-Factor for each Linearization point must be modified to allow for the display decimal point location chosen in the “DEC LOC step of the DEV TYP menu. Modify each K-Factor using the following equation:
K-Factor
DPF
DPF - The Decimal Point Factor is a divider to compensate for the displayed decimal point.
DPF Table
DPF Decimal DPF Decimal
1 XXXXXX. 1000 XXX.XXX
10 XXXXX.X 10000 XX.XXXX
100 XXXX.XX 100000 X.XXXXX
Calculating K-Factors and Frequencies: If a Linearization table is not available, the K-Factor and the frequency for each point can be calculated using the Test Mode on the unit. Refer to Section 7-
3.2, Test Mode Operation and K-Factor Calculation, on page 37.
Entering K-Factors and Frequencies: Refer to Section 7-3, Calculating 16 Point K-Factors, on page 37 and the programming step listing on page
23.
= Linearization K-Factor
Key to Programming Flow Chart:
Display - This box represents the unit's display. In the Run Mode, the flow rate, the batch total, or the grand total will be dis­played.
XX Current Value - The number that is currently
programmed for that step. It must be cleared (CLR button) before entering a new value.
00 No Value - Indicates that programmed value
for that step has been cleared, and a new number may be entered.
Keypad - Use the front panel keypad to enter a value or select a decimal point location for this step.
11
ENT
ODD
MARK
EVEN↓ SPACE
D
ENT
0
CLR
ENT
K 00
CLR
ENT
ENT
ENT
87654321
D.E.C. . .L.O.C.
ENT
R0 SP
ENT
SIGFIG00
D
CLR
B
SIGFIGXX
ENT
PARITY
ENT
600
300↓ 4800
1200
2400
9600
D
BAUDRATE
ENT
ENT
D
B
PLSER
0
Do not use PL. Select SER.
ENT
K XX
XXXX
SET HIGH
ENT
ENT
F 00
CLR
F XX
Increment to next point (Ex. POINT 02, POINT 03, Etc.
0
CLR
ENT
CLR
POINT 01
XXXX
1
To Exit
0 at any point to exit the 16 Point settupeep all data entered up to that point.
- At least three points in the 16 Point Linearization sub menu must be programmed for basic operations.
Enter a Point # of
§ - Sub menu will always appear, but feature may not be included in the unit. (Check Model Number).
CLR
0
CLR
0
CLR
D
WINDOW00
CLR
XXXX
WINDOWXX
CODE
UNIT 00
CLR
SET LOW
ENT
ANLG RT
ANLG CT
SECONDS↓ TEST
Software Version 12.0 16 Point Linearization Programming Flow Chart
D
Run Mode
XXXX
ENT
MENU
PRESET
XXXX
ENT
D
PREWARN
RT CNT
ENT
D
DEV TYP
B
D
ENT
D
LOCKOUT
UNIT XX
ENT
D
OUTCARD
D
ENT
D
ALG OUT
3-7
12
ENT
POINT 00
ENT
MINUTES
HOURS
D
ENT
D
16 POINT
ENT
2000 ↓200
20000 ↓10
D
ENT
D
OUTFREQ
3-8 How to Program The initial programming of the unit is accom-
plished by first depressing the MENU button. After pressing the MENU button once, the display will read preset. To cycle to the next control parameter option, merely press the MENU button and Prewarn will appear on the display. If the user does not wish to choose this section of the menu, depress MENU but­ton again and the next control or parameter will appear. Selection of all MENU control parameters is accomplished through the routine described for Preset.
3-9 Frequently Asked Questions About Setting Up The Batcher
Q. Is there any way to backspace if the wrong
button is hit by accident?
A. No, you can depress the CLR button and
start entering the number all over again or press ENT repeatedly until back in the Run mode and start over again from there.
Q. Is there any way to put a decimal point in a
number such as a preset or K Factor?
A. Yes, simply press the D button after the digit
that you would like the decimal point. It will appear to the right of the digit.
The following is the sequence for entering a Preset quantity.
1. Depress the Menu D button once. The display will read MENU. After a one sec­ond pause the display will read PRESET.
2. Depress the Enter ENT button; the dis­play will flash indicating that you are not in the Run Mode and not displaying the cur­rent batch total.
3. If the batch size is satisfactory, depress the ENT button. This value will be entered into memory. Simultaneously, the unit will return to the Run Mode.
4. To change the preset value, depress the CLR button and enter new number. Ex­ample: Suppose "250" is the new batch size. Press CLR, then 2 , then 5 , then 0 . When the display holds the desired value, depress the ENT button. The new batch size will be stored in memory and simulta­neously the batcher will return to the Run Mode.
Q. Is there any way to enter a negative number
for one of the Presets or K Factors?
A. No, negative values are not allowed. Q. Is there any way to ruin the unit or completely
erase it by entering a bad number?
A. No, if a number or entry is not valid the unit
will ignore it or flash an error message.
Q. If the unit does not have serial communica-
tions or analog out, does the OUTCARD and ALG OUT sections of the menu still have to be set up?
A. No, there are default settings from the fac-
tory already in the unit. No setup of these menu items is necessary for normal opera­tion.
Q. Does the Batcher have to be told what type
of input it has connected to it?
A. No, The input signals are conditioned in
hardware. This allows the input cards to be interchanged without modifying the soft­ware.
Q. If CLR is not pressed, numbers can still be
written over the Presets or K Factors. Will these numbers be accepted if the ENT button is pushed?
A. No, in order for a Preset or K Factor to be
changed, the old number must be cleared out first by depressing the CLR button.
13
3-10 Setup Procedure For The Batcher MENU ITEM 1 PRESET
PRESS DISPLAY
D
PRESET
↓↓
↓↓
Menu Button.
ENT
Flashing PRESET number.
Enters Preset Routine.
CLR
0 Flashes.
Clears out existing PRESET.
1 2 3 4
1234 PRESET Flashes.
Sample Preset.
ENT
Last count, unit now in run mode.
Store new Preset.
Final Preset is Set.
MENU ITEM 2 PREWARN
The Prewarn value is the amount before the Preset value that the Prewarn relay will deactivate. For example, if you want the Prewarn relay to drop out 10 counts before the Preset and your Preset is 1234, then set your Prewarn at 10 (not at 1224). Enter a Prewarn of “0” for the Prewarn and Preset relays to activate together. To disable the Prewarn relay, enter the same value for Preset and Prewarn.
PRESS DISPLAY
D
PRESET
↓↓
↓↓
MENU Button.
D
ENT
PREWARN Flashing PREWARN number.
↓↓
↓↓
Enters Prewarn Routine.
CLR
0 Flashes.
Clears out existing PREWARN.
1 2 3 4
1234 Prewarn Flashes.
Sample Prewarn.
ENT
Last count, unit now in Run Mode.
Store new Prewarn.
The Prewarn is Set.
Note: Remember, if the prewarn is a larger number than the preset, then the warning "PREWRONG" will flash on
the display. Enter a prewarn value that is less than or equal to the preset to clear this warning.
14
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 3 PRE TYP This menu item is used to set up the Preset Type.
PRESS DISPLAY
D
D
D
ENT
Press D toggle between selections.
ENT
Enters displyed selection Run Mode
MENU ITEM 4 COUNT Setting the Counter
PRESS DISPLAY
D D
D D
PRESET PREWARN PRE TYP STD PRE
The PRE TYP is Set.
PRESET PREWARN PRE TYP COUNT
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
EZ PRE
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
ENT
K FACTOR K FACTOR flashes then shows the current K Factor. Note: The K Factor setup is skipped if the unit has 16 Point option. The unit goes di­rectly to R0 SP.
CLR
0 Flashes. Clears out existing K FACTOR.
3 7 D 6
37.6 Flashes.
Sample K Factor, or enter calculated value from notes or worksheet.
continued on next page
15
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 4 COUNT (continued)
PRESS DISPLAY
ENT
↓↓
R0
SP
↓↓
↓↓
↓↓
Store new K Factor. RO is Reset to zero. SP is Reset to Preset. This selection determines whether the unit
counts up or counts down. If RO is selected ( B is pressed), the unit will count in the "up" direction towards the Preset (dropping out the Prewarn, if passed). If SP is selected ( D is pressed), the unit starts at the Preset and counts "down" towards zero (dropping out the Prewarn at its set value.)
or Selects by moving the cursor under the
B
B
B
B
D
arrow by R0 or SP
ENT
DEC LOC Store R0 or SP.
DEC LOC allows the user to choose where the decimal point will be located when the Batch Count or Grand Total are displayed. The decimal point is for display only
and does not affect K Factors. (The K Factor must be scaled to reflect the DEC LOC, see Section 7 for calculating the K Factors) Simply press the keypad numbers to move the decimal point. Only one decimal point can be displayed, multiple decimal points are not available. Pressing 0 turns off the decimal point.
4
DEC LOC As an example, the decimal point will move to the right of the fourth digit from the right (displays units and thousandths).
ENT
Run Mode. Store new DEC LOC.
The Counter portion of the Batcher is now set up.
16
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 5 RATE Setting the Ratemeter
PRESS DISPLAY
D D
D D
D
ENT
PRESET
PREWARN
PRE TYP
COUNT
RATE
K FACTOR
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
This selects the Ratemeter portion of the menu. K FACTOR flashes then shows the current Ratemeter K Factor. Note: The K Factor setup is skipped if the unit has 16 Point option. The unit goes directly to WINDOW.
CLR
0 Flashes. Clears out existing K FACTOR.
1 2 D 0 5 6
12.056 Flashes.
Sample K Factor, or enter calculated value from notes or worksheet.
ENT
WINDOW ## Store new K Factor. Normally the ratemeter updates each second. If no signal comes in during that time, the ratemeter will wait until the window times out or a signal comes in; the display will not update. The window is the maximum sample time, in seconds, on which the waiting period is based. The range is from 02 to 24 seconds.
CLR
WINDOW 00 Clears out existing WINDOW number value.
5
WINDOW 05 As an example, extends the window to 5 seconds.
continued on next page
17
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 6 RATE (continued from previous page)
From the previous page, we are in the SIG FIG setting portion of the Ratemeter setup Menu.
PRESS DISPLAY
ENT
SIG FIG ## Store new WINDOW.
SIG FIG indicates how many meaningful digits are shown. For example, if SIG FIG is set at three; a rate of 24737.89 will be displayed as 24700; a rate of 0.739216 will be displayed as 0.739. Note that trailing zeroes will be inserted only if necessary. Digits beyond the SIG FIG value are truncated and zeroes are inserted as needed, no round­ing is done.
CLR
SIG FIG 00 Clears out existing SIG FIG number value.
4
SIG FIG 04 As an example, display will show 4 significant figures.
ENT
WEIGHT## Store new SIG FIG. WEIGHT is an averaging factor. Higher settings provide more averaging for a more stable rate display. Derived from:
(OLD DATA WEIGHT + NEW DATA)
(WEIGHT + 1)
CLR
Clears out existing WEIGHT value.
4
As an example,
ENT
The Ratemeter portion of the Batcher is now setup.
WEIGHT 00
WEIGHT04
RUN MODE
18
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 6 LOCKOUT This menu item uses a 4 digit security code to prevent unwanted changes in the programming
or improper use of the Batcher. The unit is shipped from the factory with a security setting of 00 and a lockout code of 1000.
Security example: First set the security shut down time in the Lockout menu then go to the Run Mode. Press the START button. The word STARTED should briefly appear. If no signal comes in before the security time is reached, the unit locks and displays SECURITY. Once the unit locks all buttons except 0 thru 9 are disabled. To unlock the unit simply press in the lockout code. When the unit is unlocked all menu features are available for change.
Lockout example: To lock the unit, first make sure it is in the Run Mode, then press 1 - 0 - 0 -
0. The words LOCK ON should briefly appear. Once the unit is locked:
a. Preset can still be accessed and changed. b. Prewarn can still be accessed but cannot be changed. c. the rest of the menu cannot be accessed.
To unlock the unit simply press 1 - 0 - 0 - 0. The words LOCK OFF will appear briefly. When the unit is unlocked all menu features are available for change.
To put in a different security time or lockout code follow this setup procedure.
PRESS DISPLAY
D D D D
ENT
PRESET
PREWARN
DEV TYP
LOCKOUT
SECUR ##
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
SECUR is the time, in seconds, that the unit will wait between pulses or for a signal to come in once STARTED. For example: The SECUR is set at 15, in run
mode the START button is pressed. If at any time the unit does not receive a signal for 15 seconds the display will go to security and the unit will lock itself. The unit retains elapsed security time if STOPPED before security times out. When restarted, the unit resumes security timing from where it left off. As soon as a signal comes in the security time is reset. Entering a security time of 00 disables the security feature.
CLR
SECUR 00 Clears out existing security time.
3 4
SECUR 34 As an example, unit waits 34 seconds before Security Mode.
Continued on next page
19
3-10 Setup Procedure For The Batcher (continued) From the previous page, we are in the CODE setting portion of the Lockout setup Menu.
PRESS DISPLAY
ENT
CODE Store new security time.
Enters device routine to program in a 4 digit Lockout Code. The word CODE appears briefly then the current Lockout Code number is displayed.
CLR
0 Flashes. Clears out existing Lockout Code.
1 2 3 4
1234 Flashes. Sample Lockout Code, or enter desired value from notes or worksheet.
Be sure to record any changes in the lockout code in case it is forgotten!
ENT
Last count, unit now in Run Mode. Store new LOCKOUT Code. (Sample tryout below.)
1 2 3 4
LOCK ON Enter the sample / new value . . . the unit is now locked!
1 2 3 4
LOCK OFF Enter the sample / new value. . . the unit is now unlocked!
The lockout procedure is finished.
20
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 7 OUTCARD
If the unit is equipped with a serial communications card, the setup parameters in the following menu will make the Batcher compatible with the master terminal. The Unit Identification Number (if multiple units are used), Baud Rate (speed at which the signal is transmitted) and Parity are selectable. A 7 bit, ASCII character, with one start bit, one stop bit and the parity makes up the standard ten bit transmission character. For more details see Section 8.
PRESS DISPLAY
D
D
D D
D
ENT
PRESET
PREWARN
DEV TYP
LOCKOUT
OUTCARD
UNIT ##
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
The Unit ID Number identifies the unit for multi-drop communications. Up to 15 units may be on one line. A unit will stay off line until its Unit ID number is received. It will then stay on line until a carriage return is sent. At which time, it will send any requested information and take itself off line. The range of the unit ID number is 00 to 15
NOTE:
A Unit ID number of 00 will keep the unit on line at all times. No Unit Number prompt is needed and carriage returns will not take the unit off line.
Regardless of the above, all requests for information are replied to at the units earliest convenience.
CLR
UNIT 00 Clears out existing Unit ID number.
1 2
UNIT 12 Sample Unit ID number.
ENT
PL Enters new Unit ID number.
D
Chooses SER (PL not available)
ENT
BAUDRATE flashes then shows current Baud rate.
Continued on next page.
21
BAUDRATE
↓↓
SER
↓↓
↓↓
↓↓
3-10 Setup Procedure For The Batcher (continued) From the previous page, we are in the BAUDRATE setting portion of the Outcard setup Menu.
PRESS DISPLAY By pressing the D button repeatedly, the available Baud rates will be displayed. The
menu will cycle through the rates again whenever the bottom of the list is reached. Simply stop on the Baud rate desired and hit the ENT button. The Baudrate is the speed at which the unit communicates.
D D D
D
D D
ENT
1200 2400 4800 9600
Press D to go to 300
PARITY
300 600
↓↓
↓↓ ↓↓
↓↓ ↓↓
↓↓ ↓↓
↓↓ ↓↓
↓↓ ↓↓
↓↓ ↓↓
↓↓
Press ENT at desired Baud rate. PARITY flashes then last Parity selected is displayed.
By pressing the D button, the available Parity selections will be displayed. The menu will cycle through the rates again whenever the bottom of the list is reached. Simply stop on the Parity desired and hit the ENT button.
Parity is a way for the terminal to determine if the signal it received has reached it intact.
It does this by counting the number of bits received and checking it against the parity bit. The parity bit is turned on if it corresponds to the number of bits in the character. For example: If the bits add up to an odd number and the parity selected is even then the parity bit will not be turned on. (If the parity was odd then it would be turned on.) Mark or Space turn on (or off respectively) the parity bit with each character sent, all of the time.
Note: The Batcher will always ignore the parity bit for all characters it receives. The parity selection is provided for the master terminal only.
D
D
D
D
ENT
EVEN
ODD
MARK
SPACE
Press D to go to EVEN
↓↓
↓↓ ↓↓
↓↓ ↓↓
(Parity Bit always on)
↓↓ ↓↓
(Parity bit always off)
↓↓ ↓↓
↓↓
Last count, unit now in Run Mode. Press ENT at desired Parity, Parity stored.
The Serial Communications Port is now set up.
22
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 8 ALG OUT
This section is for models of the batcher with the analog output feature. The Analog Output card is a (0 - 20) or (4 - 20) mA current sink. The low (0mA) or (4 mA) and high (20mA) settings may be set at any range. Attempting to set the high setting lower than or the same as the low setting will display the warning message HIGH LOW and send the unit back to the low setting section of the routine. The unit will not exit the ALG OUT routine until a proper setting has been entered. If the displayed rate is below the 4 mA setting, the current driver will stay at 4 mA. This allows for offsetting the low end of the output signal. If the displayed rate exceeds the 20 mA setting the current driver will stay at 20 mA.
Note: The current sink follows (tracks) the display. The Analog Output option is not available on Square Law Analog Input units.
PRESS DISPLAY
D D
D
D
D D
ENT
PRESET
PREWARN
DEV TYP
LOCKOUT
OUTCARD
ALG OUT
ANLG RT
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
The analog output may correspond to the ratemeter or the totalizer. At this point, the selection is made by pressing ENT on the appropriate prompt. ANLG RT is the prompt for the rate meter. ANLG CT is the prompt for the batch totalizer.
D
ANLG CT
↓↓
↓↓
Press D to toggle between selections.
ENT
SET LOW Enters the routine for setting up the Analog Output card. SET LOW flashes then shows the 4 mA Setpoint value.
CLR
0 Flashes. Clears out existing Low Setpoint value.
1 7 5 D 5
175.5 Flashes.
Sample Low Setpoint, or enter value from notes or worksheet. (D for decimal point.)
ENT
SET HIGH Low Setpoint is stored. SET HIGH flashes then shows the 20 mA Setpoint value.
Continued on next page.
23
3-10 Setup Procedure For The Batcher (continued) From the previous page, we are in the SET HIGH setting portion of the ALG OUT setup Menu.
PRESS DISPLAY
CLR
0 Flashes. Clears out existing High Setpoint value.
6 7 5 9 D 5
6759.5 Flashes. Sample High Setpoint, or enter value from notes or worksheet. (D for decimal point.) If High Setpoint is too low, the warning HIGHLOW will be displayed and the unit will return to the SET LOW routine.
ENT
Last count, unit now in Run Mode.
High Setpoint is stored.
Analog Output is set. MENU ITEM 9 OUT FREQ All models of the Batcher have a pulse generator built in to them. This Output Frequency
generator sends pulses out which are scaled relative to the input signal via the counter K Factor. This means that for every time the counter increments a pulse is available at the output.
Various output frequencies are available to the user for driving external devices. In case the rate exceeds the output frequency selected, a 9999 pulse buffer is provided to hold the excess pulses. If the buffer is completely filled the warning message DATALOST will flash on the display.
PRESS DISPLAY
D D
D PREWARN Press until . . . OUT FREQ
D
ENT
PRESET
20000
↓↓
↓↓
↓↓
↓↓
Enters the routine for setting up the Frequency Output. The display shows the last Frequency selection.
D D
D
Press D to go to 20000
2000 200 10
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
Press ENT at desired Frequency.
ENT
Last count unit now in Run Mode.
Pulse Output is now set.
↓↓
↓↓ ↓↓
↓↓
24
3-10 Setup Procedure For The Batcher (continued) MENU ITEM 10 16 POINT This section is for models of the Batcher which have 16 Point Linearization. This option
allows the user to key in from 3 to 16 different frequency points (inputs per second) and assign different K Factors dividers from 0.00011 to 999999 for each of these frequen­cies.
Please refer to the K Factor worksheets (Section 7) or other notes you may have prepared.
PRESS DISPLAY
↓↓
D
PRESET
↓↓
D
Press until . . . 16 POINT
D
ENT
D MINUTES
D
D HOURS
D
The unit calculates the base rate per second from the incoming frequency and the specified K Factor. The rate can then be displayed in 3 ways: SECONDS: The base rate. MINUTES: The base rate times 60. HOURS: The base rate times 3600.
D
TEST is used to help set up the points and K Factors. In this mode the K Factor is automatically set to (1) one for both rate and total for all 16 points. Further information on this mode can be found in Section 7-3 of this manual.
ENT
Press ENT on desired rate display. The unit now enters the Frequency and K Factor setup mode.
PREWARN
SECONDS
TEST
POINT 00
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
↓↓
To escape from this mode, press ENT when POINT 00 is being displayed.
Enter any other point from 1 to 16 via the front keypad and press ENT to continue. Note: If the point number entered is greater than 16, the unit will default back to point
16. Continued on next page.
25
3-10 Setup Procedure For The Batcher (continued)
From the previous page, we are in the POINT setting portion of the 16 Point setup Menu.
PRESS DISPLAY then
1
ENT
POINT 01
ENT
F 1
The unit displays the last frequency entered for Point 01.
CLR
F 0
Clears out existing frequency for Point 01.
1 0 0
F 100
Sample frequency, or enter desired value from worksheets.
ENT
K 1
The unit displays the last K Factor entered for Point 01.
CLR
K 0
Clears out existing K Factor for Point 01.
1 0
K 10
Sample K Factor, or enter desired value from worksheets.
ENT
POINT 02 The above procedure is now repeated for Point 02. The setup continues in this manner until up to 16 points are entered.
Note: A minimum of (3) three points must be entered. All frequencies of consecutive point numbers must be entered in ascending order, beginning with 0 for the first point.
Please read Section 7-3 for all rules concerning 16 Point Frequency and K Factor entry. PRESS DISPLAY
CLR
POINT 00 Clears Point number in preparation for exit of 16 Point setup routine.
ENT
Last count, unit now in Run Mode. Press ENT on Point 00 to exit 16 Point routine.
Note: Unit will flash BAD FREQ if there is a sequence error. The unit will then display the sequence error point number so that corrections can be made.
16 Point linearization is now setup.
26
3-11 Run Mode 3-11.1 The Display
In the Run Mode the display will initially dis­play:
a) Zero, if setup to reset to zero. b) Preset number, if set to reset to preset . c) A warning message (See Section 6-1)
The unit will accept input signals and dis­play Rate, Batch Total or Grand total.
The Batch Total is displayed as a number. The Rate is displayed as "R" followed by a number. The Grand Total is displayed as a flashing number. (The Grand Total flashes so that it will not be confused with the Batch Total.)
To toggle between the Rate and Batch Total, press the C button. Press the ENT button at any time to view the Grand Total, then press it again to go back to the Rate or Batch Total.
3-11.2 Resetting (Clearing) the Totalizers. To clear the Batch Totalizer,
a) the unit must be in the Run Mode. b) the unit must be displaying the Batch
Total.
c) the unit must not be locked out.* If the above conditions are met, press the CLR (clear) button. The display should then show the preset or zero depending on how the unit is configured.
3-11.3 Locking the Unit The unit is shipped from the factory unlocked. To lock the unit, it must be in the Run Mode. The unit is shipped from the factory with a Lockout Code of 1000.
As a test, when you receive the unit, power it up and press 1 then 0 three times. The display should briefly show LOCK ON. This means that the unit is now "locked out". Press 1 then 0 three times again. The display should then show LOCK OFF briefly. This means that the unit is now unlocked.
What LOCK ON or "Locked Out" means:
a) the Grand Totalizer cannot be reset. b) only the preset can be accessed and
changed.
c) the prewarn can be accessed but not
changed.
d) the rest of the Menu cannot be ac-
cessed.
The unit will still:
e) accept input signals f) display Rate, Batch Total and Grand total. g) have Start, Stop and Rate/Total buttons
enabled.
LOCK OFF means that the unit functions normally as described in this manual.
The Lockout code can be changed or viewed by accessing Lockout in the setup Menu. (See Section 3-3; Menu Item 4; Lockout.) The unit must Unlocked to do this so be sure to record any Lockout code changes in case it is forgot­ten.
To clear the Grand Totalizer,
a) the unit must be in the Run Mode.
b) the unit must be displaying the Grand
Total.
c) the unit must not be locked out. If the above conditions are met, press the CLR button. The display should then show zero. * The unit may be reset if it is locked out by putting a 3-30 VDC signal to pin 5 on the rear of the unit.
The Lock toggles back and forth from LOCK ON to LOCK OFF each time the code sequence is entered. The last four digits pressed, while in the Run mode, are the ones that the unit checks for Lockout code sequence. For example: while 1000 will unlock/lock a new unit from the factory, so will the number 347191000 (the last four digits are the code sequence, so, this number works also!).
RECORD ALL LOCKOUT CODE CHANGES.
27
3-11 Run Mode (continued)
3-11.4 Start and Stop Operation (continued).
3-11.4 Start and Stop Operation. The Batcher is designed for batching opera­tions. The batching operation is controlled by two internal relays, Preset and Prewarn set­tings and the CLR , START and STOP but­tons on the front panel. A typical operation proceeds as follows:
a) The Preset is accessed and changed
to the amount desired.
b) The unit accepts input signals
c) The CLR button is pushed to reset
the Batch Totalizer.
d) The Start button is pushed and the
process begins.
e) The Stop button can be pushed at any
time to temporarily halt the process (the Start button resumes it from where it stopped).
f) The display shows Rate, Total or
Grand Total.
g) The Prewarn is reached and the pro-
cess is slowed down.
h) The Preset is reached and the process
is halted.
The Batcher will always accept input pulses whether the unit is Started or not! All pulses on the input terminal are counted and shown on the display. This means that all pre-run and post-run pulses will be recorded. For this reason, always press the CLR button before start.
The START button initiates the batch se­quence. Once the unit is started:
a) The display will prompt the operator
with the word STARTED.
b) Both relays will engage (Unless the
Prewarn has been reached already).
c) All buttons on the front panel will be
locked out except the STOP button and ENT button which allows ac­cess to the Grand Totalizer.
NOTE: Once both Prewarn and Preset points are reached, the unit cannot be started until it receives a reset signal or the CLR button is pressed.
The STOP button is used to stop a batch that has already started. When the STOP button is pressed:
a) The display will prompt the operator
with the word STOPPED.
b) The Preset and Prewarn relays will de-
energize.
c) The unit will still accept input pulses. d) All buttons on the front panel will be
usable.
e) The unit may be restarted by pressing
the START button.
The START button energizes the Preset and Prewarn relays. The STOP button de-energizes the Preset and Prewarn relays.
(The CLR button is discussed in section 3-11.2.)
28
3-12 Internal Operation
3-12.2 Analog Inputs and Computations 3-11.1 Digital Inputs and Computations The 3-30 Volt input signal is filtered electroni-
cally (See Section 4-1, Digital Pulse Inputs). Computations:
Pulses In = Count Count K Factor
Pulses In = Rate Rate K Factor
Batch Total
Grand Total
Rate
Tau = 1 sec or WINDOW if (Rate / 1 sec) = 0
(See Sections 1-3 and 3-10, Setting the
=Rate
Ratemeter)
= Count (since last
Batch Reset)
= ∑ Count (since last
Grand Total Reset)
Tau
The Analog input signal is filtered electronically
and converted to a 0 - 10000 Hz input frequency.
(See Section 7, K Factor Calculation and Sec-
tion 4-2, Analog Inputs).
Computations:
Pulses In = Count Count K Factor
Pulses In = Rate Rate K Factor
Batch Total
Grand Total
Rate
Tau = 1 sec or WINDOW if (Rate/1 sec) = 0
(See Sections 1-3 and 3-10, Setting the
=Rate
Ratemeter)
= Count (since last Batch
Reset)
= ∑ Count (since last Grand
Total Reset)
Tau
Frequency Out
(Sequenced out as per OUT FREQ selec­tion and buffered to 9999 pulses) (See Sections 1-3 and 3-10, OUT FREQ)
Analog Out
(See Sections 1-3 and 3-10, ALG OUT)
=(
Prewarn Out
Count Preset - Prewarn (if Reset to 0) Count Prewarn (if Reset to Preset)
Preset Out
Count Preset (if Reset to Zero) Count 0 (if Reset to Preset)
= Count
Rate
- SET LOW) x16 + 4
(SET HIGH - SET LOW)
=
=
Frequency Out
(Sequenced out as per OUT FREQ selec­tion and buffered to 9999 pulses) (See Sections 1-3 and 3-10, OUT FREQ)
Prewarn Out
Count Preset - Prewarn (if Reset to 0) Count Prewarn (if Reset to Preset)
Preset Out
Count Preset (if Reset to Zero) Count 0 (if Reset to Preset)
= Count
=
=
29
SECTION 4 INPUTS
4-1 Digital Pulse Inputs (continued)
4-1 Digital Pulse Inputs (Terminal 4) Digital Pulse Inputs: The input board is a
separate board that is plugged into the mother board just behind the display. All digital inputs are on the same board. There are four dip switches on the board. The input condi­tioning characteristics may be altered by changing the dip switches. A valid pulse is one which makes a transition from the off state (low) to the on state (high): a positive going edge. The off state is 0 - 1 VDC with respect to Terminal 12 (Ground). The on state is 3 - 30 VDC with respect to Terminal
12. The input impedance is 10 K ohms. At 30 VDC, the current draw will be 3 mA. This should be the maximum current that the Batcher will draw. Acceptable pulse width is determined by the dip switch settings (See Table 4-1 below).
DIP SWITCH SETTINGS
SW1 SW2 SW3 SW4 Conditioning
4-1.1 STANDARD: High Impedance (Terminal
4).
Has a 10 K Ohm pull down resistor to ground
(Terminal 12) and must be driven high. Typi-
cal drivers include a contact closure from a 3-
30 VDC source (such as Terminal 13), a PNP
transistor (proximity switch or other device) or
an amplified signal from an inductive pickup.
Remember, the input signal must be refer-
enced to Terminal 12 of the Batcher. (See
Section 2-5, Fig. 2-2 Typical Digital Wiring
Connections)
4-1.2 High Impedance with pull-up (Terminal
4).
Has a 4.7 K Ohm pull up resistor to +5 VDC
and must be pulled low. Typical drivers in-
clude a contact closure to Ground (such as
Terminal 12), or an NPN transistor (proximity
switch or other device). Remember, the input
signal must be referenced to Terminal 12 of
the Batcher. (See Section 2-5, Fig. 2-2 Typi-
cal Digital Wiring Connections)
ON ON --- --- 0-40 Hz
ON OFF --- --- 0-400 Hz
OFF OFF --- --- 0-20000 Hz
--- --- OFF OFF needs sourcing input
--- --- OFF ON needs sinking input
min. 12.5 msec on/off
min. 1.25 msec on/off
min. 0.25 usec on/off
(drive input high)
(pull input low)
ON
S1S2 S3 S4
Table 4-1
Idea: This input works well with TTL devices.
4-1.3 Reset Input (Terminal 5)
Identical to the Standard, High Impedance In-
put with one exception. The input speed is
fixed for a minimum pulse width of 5 msec.
Note: The reset input will not be changed to
a sourcing type of input even if the dip switch
is set for pull up or is changed to the pull up
settings.
4-2 Analog Inputs 5A - 5E, 6A (Terminal 4)
The input signal modules are mounted, just
like the Digital board, behind the display.
Analog inputs all use the same board, like-
wise so do the Analog-In/Out inputs. These
boards are not field modifiable (unlike the
Digital board). Each board is calibrated at the
factory for its particular input type.
30
4-2 Analog Inputs (continued)
4-2.3 Analog Inputs Exchange
4-2.1 5A: 4-20 mA; 250 input impedance.
5B: 0-20 mA; 250 input impedance. 5C: 1-5 VDC; 15 K input impedance. 5D: 0-5 VDC; 15 K input impedance. 5E: 0-10 VDC; 15 K input imped-
ance. The above inputs take the analog signal and scale it from 0 to 10000 pulses per second by using a highly linear voltage to frequency con­verter. These pulses go to the processor to be scaled by the K Factors. To determine the K Factor, see Section 7, Calculating the K Factor.
4-2.2 6A: Square Law: 4-20 mA; 250 in-
put impedance. The Square Law input is a special input that compensates for non- linear input types. Spe­cifically, inputs that require square root extrac­tion to provide accurate count and rate deter­minations. The input signal is converted to a 0 to 10000 pulse per second input to the pro­cessor (See Table 4-2 below).
mA Input Freq. mA Input Freq.
4 0000 10 6123 5 2500 12 7071 6 3535 16 8660 7 4330 18 9354 8 5000 20 10000
Table 4-2
To calculate the freq. for a particular input use the following formula.
mA - 4 x 10000 = Freq. to processor
16
If an analog sensor cannot be obtained that matches the Batcher input, it is recommended that the Batcher be returned to have the analog input module exchanged and recalibrated. Recalibration should only be attempted by someone who has the training to open the unit and work with grounded equipment necessary to protect the static sensitive CMOS circuitry. For instructions on how to return the unit for exchange see Section 2-2.
4-2.4 Analog Inputs Calibration (All units have been calibrated at the factory)
Warning: This unit contains static sensitive components. Observe proper precautions!
a) Set the ratemeter at 6 SIG FIG; the
window at 01; and the K Factor at 1.00.
b) Remove the case and locate the analog
input card mounted behind the display (see Section 6-3).
c) Locate the two 0.3 inch square pots R3
and R15. These numbers should be silkscreened underneath them on the board.
d) Input a very accurate low signal and
adjust R3 (left side from the front) so that the display reads .0001 to 0000.
e) Input a very accurate high signal and
adjust R15 (right side from the front) so that the display reads 9999 to 10000.
f) Repeat steps d and e until the unit is
reading as close as possible to 0000 on the low side and 10000 on the high side. This should only take a few tries.
g) Re-case the unit and setup the Menu as
desired.
For example: to calculate the frequency for 9 mA Input.
9 - 4 x 10000 = 5590 Freq. to processor.
16
If problems occur during calibration please con­tact the factory for exchange or to arrange for factory calibration.
31
4-3 DC Power Inputs (Terminals 12, 14)
SECTION 5 OUTPUTS
The Batcher may be powered by an external DC power supply. The supply must provide 12 - 27 Volts DC and at least 280 mA of current. The positive side (+DC) of the DC supply should be hooked to Terminal 14 and the negative (or Ground) side to Terminal 12. NOTE: Units powered by DC Voltages do not have an isolated voltage out on Terminals 15 and 16 or +12 VDC on Terminal 13.
4-4 AC Power Inputs (Terminals 17, 18) The Batcher may be ordered for 110 or 220 VAC
power. The unit requires single phase 50/60 Hz AC power. The voltage range is ±15% of the rated voltage. Voltages below this range will not power the unit. Voltages above this range may damage the unit. The Batcher is relatively immune from electrical noise on the AC lines. However, in extremely noisy applications some line condi­tioning or filtering may be necessary. If fusing is required, external fusing must be supplied. Note: The Batcher has no internal fuse to blow out. If the unit does not function when power is applied, contact the factory for assistance or to arrange for repair.
The Batcher has five different possible types of outputs for controlling external devices or moni­toring the rate and totals. They are: Frequency Output, Relay Outputs, Open Collector Outputs, and Optionally available Analog Output (not available on models with (Square Law input), and RS232, RS422, or RS422M Serial Commu­nications.
5-1 Frequency Output (Terminal 2) 5-1.1 Electrical Characteristics of Frequency
Output The Batcher generates a pulse out for each
factored count. A sinking NPN transistor output (see Figure 5-0.1), can drive external devices at various rates selected through the keypad menu see Table 5-0.2 below). The Open Col­lector sinks 30 VDC maximum to 1 volt maxi­mum with a maximum current of 100 mA.
Speed (Hz) 10 200 2000 20000 Min. on/off (msec) 47.5 2.0 0.2 0.013
Table 5-0.2
Caution: An external fuse is required:
!
DC Power: 0.5 Amp AC Power: 0.125 Amp
Applications: Remote totalizers, ratemeters or other monitoring devices.
10 Hz: Electromechanical totalizers
Programmable Controller inputs
200 Hz: Electronic totalizers
Programmable controllers with high
speed input cards. 2000 Hz: High speed totalizers. 20000 Hz: High speed totalizers.
32
5-1.2 Internal Buffer for Frequency Output An internal buffer will store up to 9,999 counts if
the scaled input generates pulses faster than the output speed selected. The warning mes­sage "DATALOST" flashes on the screen when the buffer overflows (see Section 6-1, Warning Messages). This indicates that the counts being totalled and the scaled outputs may be incor­rect. Note: All counts stored in the internal buffer will
be pulsed out at the selected frequency even if the counter is reset before it is finished sending them.
5-2.2 Open Collector Version (Terminal 19,
20). The NPN, Open Collector Transistors, sink a maximum of 250 mA at 30 VDC when active. They behave in the same manner as the Re­lay Outputs (see Section 5-2.1 above). The Open Collector outputs are available on units with relay outputs, but, please observe the fol­lowing precautions.
Note: When relays are used, 10 VDC is pro-
vided at the transistor outputs through the relay coils. If current greater than 2 mA is drawn, the relay will remain energized. Applying greater than 10
VDC to the Open Collector outputs may destroy the unit. The transis­tor will sink 100 mA in the "ON" state with relays installed.
5-3 Optional Analog Output (Terminal 3)
Figure 5-0.1
5-2 Control Outputs 5-2.1 SPDT Relay Version (Standard) When the start button is pushed, the two relays engage simultaneously to start flow. When the prewarn number is reached, one relay drops out. When the preset number is reached, the other relay drops out. The user may enter the two numbers when setting up the batch counter (see Section 3-3, Menu Items 1 and 2). The contacts are rated at 10 A, 120/240 VAC or 28 VDC.
5-3.1 Electrical Characteristics of Analog Output The Analog Output option is not available on units with Square Law inputs. Controlled by an Open Collector transistor, it gives a linear 4 to 20 (or 0 to 20) mA sink which corre­sponds to displayed rate or total readings. A sinking driver pulls a current to ground, across the user's external device (such as a strip chart recorder, computer, external meter, etc). In the Setup mode the user is prompted to set the output to correspond to rate or total and set the low and high (4/0 to 20mA) parame­ters to which the analog signal will corre­spond.
Idea: The Batcher can supply the 24VDC to
power the current loop. (Connect pin 15 to 13, Pin 16 is now +24 VDC with respect to pin 12.) Connect Pin 16 to the + DC side of the external device and connect Pin 3 to -DC side of the external device (see Figure 5-2.1).
33
5-3 Optional Analog Output (continued) SECTION 6 TROUBLE SHOOTING AND
MAINTENANCE GUIDE
4-20 mA Out Wiring
6-1 Warning Messages 6-1.1 PREWRONG
Indicates that the values in Preset and Prewarn are not acceptable. This condition will occur
3 Analog Output
4 Input A
13 (+) 12 Volts Out
12 Ground (-DC)
110/220 VAC
when the Preset value is less than the Prewarn value. The display will continue to display this
18 AC In
17 AC In
16 Isolated 12 V (+)
15 Isolated 12 V (-)
14 (+) DC Power In
message until the error is corrected. To change
Fuse
4-20mA Source
4-20mA Return
+
Strip Chart
Voltage Out Wiring
Recorder
the Preset and Prewarn values see Section 3-3, Setup Procedure.
6-1.2 DATALOST Warning message that indicates the unit is re­ceiving pulses faster than 20000 pulses per second or the data buffer is full. In either case the display will not show the proper count or rate and the frequency output will be inaccurate. There are three possible remedies:
a) Check to see that your input is not ex-
3 Analog Output
4 Input A
12 Ground (-DC)
13 (+) 12 Volts Out
14 (+) DC Power In
15 Isolated 12 V (-)
16 Isolated 12 V (+)
17 AC In
18 AC In
110/220 VAC
ceeding the Batcher ratings of 20 KHz Max. Input speed.
b) Change your OUT FREQ settings to
handle a higher count speed (Section 3­3, Menu Item 7).
c) Change your count K Factor to a larger
number, since the output frequency is based on the factored count (Section 3­3, Menu Item 3).
Voltage Out
Return
Voltage Out Source
Figure 5-2.1
Fuse
+
Strip Chart
Recorder
5-4 Optional RS232 / RS422 Serial Communi­cations
This option allows the Batcher to act as a slave to a master terminal. It may be accessed for counts, rate, presets and K Factors. Up to 15 units can be linked together in parallel and addressed separately to transmit unit status or accept new set points using the standard ASCII format. Baud rates of 300, 600, 1200, 2400, 4800 or 9600 as well as choice of odd, even, space, or mark parity can be selected by keypad control. Further information and more details are provided in Section 8 at the end of this manual.
6-1.3 RFFFFFFF Indicates that the factored input rate has ex­ceeded a 7 digit number. The ratemeter cannot handle numbers larger than 7 digits (i.e.
9999999). Change the Rate K Factor to a larger number (Section 3-3, Menu Item 3) to correct this problem.
6-1.4 LOCK ON Indicates that the unit has been locked out! The unit must be unlocked before any changes can be made. See Section 3-3, Menu Item 4 to unlock the unit.
34
6-1 Warning Messages (continued) 6-1.5 BAD FREQ
Indicates that the values in the 16 Point setup are not acceptable. This condition will occur when the frequency values are not in ascending order. The display will continue to display this message until the error is corrected. To correct the error see Section 3-3, Setup Procedure.
6-1.6 SECURITY Indicates that no signal has come in for the duration time set in the Lockout menu. Lockout code must be entered before the unit will con­tinue. Section 3-3, Setup Procedure.
6-2 Troubleshooting 6-2.1 General
The following troubleshooting procedures have been developed as an aid in locating defects. Not every possible problem has been listed, but a general isolation procedure for tracking down problems has been given. A standard recom­mendation is the removal of power for 2 sec­onds. This allows the microprocessor to go through a reinitialization cycle at power up. If it is determined that the unit is faulty, contact your local Factory Representative or Sales Office concerning replacement. The Batcher is not field serviceable and all repairs should be per­formed by the factory.
6-2.2 Problems Symptom: Display will not light. Possible Cause: No power to unit, power to unit not to specifications or bad connection between display board and mother board. Test Procedure: See Specifications Section 1­4 for proper input voltages. Then; a) Check AC voltage input on terminals 17 &
18.
b) (if DC Powered unit) Check DC voltage input
on terminals 12 & 14.
c) Check connection of display board to mother
board
Corrective Action:
unit.
If all checks okay, replace
6-2.2 Problems Symptom: Unable to start batch. Possible Cause #1: Displayed Batch count al­ready exceeds the Preset value. Test Procedure: Check Preset value against the displayed value. If the Preset is less, go to corrective action.
Corrective Action:
the CLR button or change the Preset to a larger value.
Possible Cause #2: Incorrect programming. Test Procedure: Check for programming er­rors, review manual.
Corrective Action:
quired. Possible Cause #3: Defective Circuit board or
component. Test Procedure: Press the Start button and check for relay action. An OHM meter across the appropriate relay terminals should give the proper indication. (Be sure to disconnect all power to the relay terminals first!)
Corrective Action:
unit. Symptom: Unit not totalizing.
Possible Cause #1: Incorrect programming. Test Procedure: Check for programming er­rors, review manual. For Example, if the K Factor is too large it may take some time be­fore a count is registered on the display.
Corrective Action:
quired. Possible Cause #2: Input signal invalid.
Test Procedure: See Specifications Section 1-4 for proper input signals. Then use oscillo­scope to;
a) Check Analog input on terminals 3 and
12 for proper current or voltage levels.
b) (if Digital unit) Check Digital voltage
input on terminals 3 and 12.
Corrective Action:
place unit.
Reset the unit by pressing
Reprogram unit as re-
If no relay action replace
Reprogram unit as re-
If inputs check okay, re-
35
6-3 Removing the Case To install or change the input or data interface cards, the case must be removed. all power before opening the case. CMOS logic is used so observe standard precautions against damage by static discharge. On units RS232 or RS422, two screws on the back, holding the top left connector, have to be re­moved. Next, remove the six (6) flat head screws behind the front bezel and lift off the bezel assembly. Slide the main board display out the front of the case by pushing from the rear. Once modifications are made, reverse the procedure to reassemble the unit. Make sure that the main board is in the track. The six (6) screws that hold the panel must be tight to seal the rubber keypad panel assem­bly, approximately 0.6 in-lb torque.
6-3.1 Input Card Modification Follow the instructions for removing the case in Section 6-3. The Input card is mounted just behind the display and plugs onto the 15 pin post connector. Remove the board and make desired changes. When installing the Input card, make sure that the component side of the board is facing the front and that the 15 pin connector is mated properly and not offset to the side. Replace the front panel per Sec­tion 6-3.
6-3.2 Serial Communications Interface Instal­lation Follow the instructions for removing the case in Section 6-3. The RS232, RS422 and RS422M cards have a 15 contact ribbon cable that plugs into the female connector next to the heat sink. Choose the proper In­terface card. With components on top and subminiature connector to the back plug in the harness and mount the card on the four (4) standoffs provided. After the main board is inserted into the case replace the front panel as per Section 6-3.
Remove
6-4 Maintenance The Batcher does not require any "Routine Maintenance" by the user. If a problem should occur, and all troubleshooting proce­dures have been exhausted, contact your lo­cal representative or distributor (phone num­ber on cover of manual).
SECTION 7 CALCULATING THE K FACTORS 7-1 General
The key to accurate flow measurement with the Batcher is correct scaling. The electronics of the unit have been designed for stability and repeatability. Even the finest measuring device and equipment cannot make up for im­proper factoring and programming. Due to the complexity of the concept of K Factors, this special section has been provided for those who still find it hard to understand. A separate worksheet has also been provided with this manual to help in calculating the K Factors. It is hoped, that between this section of the manual and the worksheet, that any questions you may have, regarding the K Fac­tor, will be answered.
7-1.1 What is a K Factor? The K Factor is a divider. This means that if the K Factor is greater than 1, it will diminish any input signal. Conversely, if it is less than 1, it will increase any input signal. The K Factor range of the Batcher is from 0.0001001 to 99999999. This allows a wide range of factoring from greatly increasing (to display a large value) to decreasing the input (to display a very small value).
36
7-2 Calculating the K Factors. The following steps are the recommended procedure forcalculating the K Factors. Take your time and go through the procedure slowly at first. After several tries you should be fairly adept at calculating the K Factor for any given input.
7-2.1 Calculating the K Factor for Digital Pulse Inputs.
Step 1. Find out what value the pulses repre-
sent. This should be specified on your device or with its paper
work. Example #1: 360 Pulses = 1 yard Example #2: 1 Pulse = 2 gallons Example #3: 2000 Pulses = 1 m
3
Step 2. The Count K Factor is equal to the
number of pulses per value from
Step 1 (Pulses ÷ Value). Example #1: Count K Factor = 360 Example #2: Count K Factor = 0.5 (1 pulse ÷
2 gallons)
Example #3: Count K Factor = 2000
Step 3. Enter the Count K Factor. (See
Section 3-3, Menu Item 3).
Step 4. Modify the Count K Factor to reflect
any time conversions for the rate display to the Rate K Factor. This is done by dividing the Count K Factor by the Time Conversion Fac­tor. If no conversion is necessary skip this step and let the Rate K Factor be the same as the Count K Factor. USE THE TIME CONVER­SION CHART AS NEEDED.
Example #1: Convert yds per sec to yds per
hour.
Rate K Factor = 360 ÷ 3600 = 0.100
Example #2: Convert gallons per sec to gal-
lons per min.
Rate K Factor = 0.5 ÷ 60 = 0.0083333
Example #3: No conversion necessary.
Rate K Factor = 2000
Step 5. Enter the Rate K Factor.
(See Section 3-3, Menu Item 3)
TIME CONVERSION CHART
To convert: divide by sec to min 60.00 sec to hr 3600 min to sec 0.01666667 min to hr 60.00 hr to min 0.01666667
hr to sec 0.0002778 7-2.2 Digital K Factor Formulas Pulses = Base K Factor
Units Value Base K Factor . = Count K Factor
Units Conversion Factor Count K Factor . = Rate K Factor
Time Conversion Factor
37
7-2.3 Calculating the K Factor for Analog Inputs.
Step 1. Find out what value the maximum
input signal represents. This should be specified on your device
or with its paper work. Example #1: 20 mA = 100 gal / min Example #2: 5 V = 10 ft / sec Example #3: 10 V = 32 m3 / hr
Step 2. The Rate K Factor is equal to
10000 divided by the value from
Step 1. Example #1:
Base K Factor = 10000 ÷ 100 = 100
Example #2:
Base K Factor = 10000 ÷ 10 = 1000
Example #3:
Base K Factor = 10000 ÷ 32 = 312.5
Step 3. Enter the Rate K Factor.
(See Section 3-3, Menu Item 3). Step 4. Modify the Rate K Factor to make
the time conversion to seconds for
the count display. This is done by
dividing the Rate K Factor by the
Time Conversion Factor. If no con-
version is necessary skip this step
and let the Rate K Factor be the
same as the Count K- Factor. USE
THE TIME CONVERSION CHART
AS NEEDED.
7-2.4 Analog K Factor Formulas. 10000 = Rate K Factor
Maximum Input Signal
Rate K Factor = Count K Factor Time Conversion Factor
Q. Is it possible to count in one system of measurement and display rate in another? A. Yes, modify the Count K Factor to reflect any units conversions. This is done by divid­ing the Count K Factor by another Units Con­version Factor. REFER TO THE UNITS CONVERSION CHART AS NEEDED.
UNITS CONVERSION CHART
To convert: divide by To convert: divide by
ft to m 0.3048 kg to lb 2.2046 ft2 to m ft3 to m
ft3 to gal 7.4805 m to ft 3.2808
gal to l 3.7854 m2 to ft
gal to m
gal to ft
gal to lb(H2O) 8.3378 lb to kg 0.45359
2
3
3
0.0929 l to ft
0.02832 l to gal 0.2642
3
0.00379 m3 to ft
0.1337 m3 to gal 264.172
3
2
3
0.0353
10.7639
35.3147
Example #1: Convert pounds per min to pounds per sec
Count K Factor = 100 ÷ 0.01666667 = 6000
Example #2: No conversion needed.
Count K Factor =1000
Example #3: Convert gal per hr to gal per sec.
Count K Factor = 312.5 ÷ 0.0002778 = 1124910
Step 6. Enter the Count K Factor. (See Section 3-3, Menu Item 3)
38
7-3 Calculating 16 Point K Factors
Units equipped with the 16 Point option allow the user to enter in from 3 to 16 different frequency points (inputs per second) and assign different K Factor dividers from 0.00011 to 999999 for each of these frequencies. The 16 Point unit deter­mines the incoming frequency and calculates a K Factor line slope from the two closest data points that had been entered. The specific K Factor is then proportionally interpolated using 8 position floating math. This K Factor is applied to all in­puts until the next frequency calculation, usually 1 second later. If a 0 frequency is entered into point 1, the point 1 K factor will be applied to all inputs received before the first frequency calculation.
In order to keep track of data, each Frequency / K Factor data entry is assigned a point number. Any point number may be selected to view and / or change the Frequency / K Factor data as long as the frequencies of the ascending point num­bers are also entered in ascending frequencies. 7-
3.1 Some Notes on 16 Point Setup
1) The unit will not accept a K Factor of (0) zero. If a zero is entered the unit automatically puts a (1) one in its place. Division by zero is not al­lowed.
auto-ranging decimal point in the rate display will be shifted to the left as the dummy decimal is shifted to the left. This is so that the rate display will be as same as the count. For example: The input pulses are coming in at 100 pulses per minute. The decimal point is set at (1) one (DEC LO.C). At the end of one minute the count will read 10.0. During the minute the rate will read
10.0 while it would show 100.0 if no decimal point were added.
7-3.2 Test Mode Operation and K Factor Calcula­tion A special TEST mode can be accessed through the 16 Point setup menu. This is used to help set the points and K Factors as well as calibration of the metering device. If TEST is selected, the K Factor is set to (1) one for all frequencies. Thus, the totalizer will accumulate one count for each incoming pulse. Below are steps for calculating the K Factors with pulsing devices or analog transmitters.
1) Set the 16 Point unit to TEST and press ENT on POINT 00 to go to the run mode.
2) At the counter and let the unit count the incoming signal while the rate displayed is recorded.
lowest desired flow rate, reset the
2) Point 01 will be the low shut-off frequency. Below this frequency no rate will be displayed nor count recorded. Point 01 should be assigned a frequency of (0) zero with a K Factor for lowest flow especially if very slow flow is to be counted.
3) The entry of a frequency of (0) zero for Point 03 or above will tell the unit to continue the K Factor slope line calculated from the two previous Frequency / K Factor points and ignore any higher point data. If a fixed K Factor is desired, assign the same K Factor to two ascending frequency points and enter a frequency of (0) zero in the next higher point entry.
4) Extrapolated K Factors are always positive numbers. Make sure that the last two points do not project the K Factor slope towards zero.
5) The dummy decimal point is still set up with DEC LOC menu under DEV TYP. However, the
3) Interrupt the input signal when the known tested amount has gone through the metering de­vice. Switch to count display and read the number of counts that came in from the known volume as displayed on the unit. Divide the counts by the volume that passed through the meter to deter­mine the number of counts for 1 unit of measure, gallon, cubic feet, etc.
4) Record this frequency and K Factor for later entry into Point 01 or Point 02. (See 7-3.1 Note 2 to determine if the data should be entered in point 1 or 2)
5) Assign ascending point numbers to corre­sponding ascending frequencies when recording Frequency / K Factor data. Repeat process until desired number of points are set up.
39
SECTION 8 SERIAL COMMUNICATIONS
This section applies to units which have the Serial Communications interface option. Up to 15 units can be linked together. Unit sta­tus can be accessed and new set points and K Factors can be entered through the serial port. The unit cannot be taken out of the Run Mode through the serial port. Menu changes must always be made through the front key­pad (except Preset, Prewarn, and K Factors). Data is transmitted at selected baud rates us­ing standard seven bit ASCII characters and parity with two additional bits of "Start" and "Stop" to make up the standard ten bit charac­ter.
8-1 Unit Code Each Batcher in the hookup must be assigned a code number from 1 to 15, through the front keypad, in the OUTCARD setup mode (see Section 3-3, Menu Item 5). Number "00" is reserved for a dedicated hookup to only one terminal and its transmit output line remains in an "on" active state. (Units assigned other numbers have outputs that remain in the "off" high impedance state until addressed by their code number or brought on line by a positive edge of the Strobe input). Once a unit is ad­dressed, do not address another unit until the data has been sent and any data requested has been transmitted back.
8-2 Baud Rate
The Baud rate is the speed at which data is transmitted, expressed in bits per second.
Baud rates of 300, 600, 1200, 2400, 4800, or 9600 are available. Use the front keypad to call up the OUTCARD setup mode (see Sec­tion 3-3, Menu Item 5) and select the desired baud rate that is compatible with the remote terminal.
8-3 Parity
Parity is a bit of information that is in­serted before the stop bit and is used to help check if the transmission is correct.
In the OUTCARD setup mode, select be­tween:
a) ODD (Parity bit is logical zero if total
number of logical 1's in the first seven bits is odd)
b) EVEN (Parity bit is logical zero if total
number of logical 1's in the first seven data bits is even.)
c) MARK (Parity data bit is always logical
1.)
d) SPACE (Parity data bit is always logi-
cal 0.). The Batcher does not check the parity but does transmit the parity chosen.
Idea: Use the MARK parity for terminals that
need two stop bits and/or no parity
since these terminals ignore the parity
anyway. Note: If the parity of the terminal is not
known, it is often practical to key in a different parity until the correct one is found.
8-4 RS232 Electrical Requirements The Batcher uses standard EIA specifications. Standard inputs must present a load of 3000 to 7000 ohms. A voltage level of +3 V to +25 V (referenced to signal ground) is read as a "Space" or "0" and indicates an active state (asserts a control line). A voltage level of -3 V to -25 V (referenced to signal ground) is read as a "Mark" or "1" and does not indicate an active state (does not assert a control line). Outputs must send a voltage of +5 V to +25 V (referenced to signal ground) for a "Space" and a voltage level of -5 to -25 V for a "Mark" when loaded with a 3000 ohm load to signal ground. Outputs must be capable of being shorted to other signal lines without burning out. Note: It is normally recommended. that cable length be limited to 50 feet.
40
8-5 RS232 Card Wiring This option has a subminiature D, 25 pin, fe­male connector and is wired as a DCE (Data Communications Equipment) device. If it is connected to a DTE (Data Terminal Equip­ment) device, the interconnect cable should have wires 2 and 3 connected straight to the same pins on each end. If it is connected to another DCE device, Pins 2 and 3 must be crossed. This means that the wire to pin 2 on one end goes to pin 3 on the other end and the wire to pin 3 on one end goes to pin 2 on the other end.
8-5.1 Wiring Diagram RS232 / Strobe (25 Pin Connector)
8-6 RS422 Electrical Requirements The input of the Batcher follows the standard EIA high impedance minimum of 12 K Ohms. When the 422+ (A) input is more positive than the 422- (B) input by 0.2 V to 6 V, a "1" or "Mark" condition is recognized. When the 422+ input is more negative than the 422- in­put by 0.2 V to 6V, a "0" or "Space" is recog­nized. Data is recognized by the polarity of the voltage difference between the two lines. Noise picked up in the line will make little dif­ference since the noise is usually added to each line and the voltage differential remains the same. The output driver drives the trans­mit lines to a differential of 2 to 6 V. It is designed to handle loads up to 60 mA of sink or source current and features positive and negative current conditions. Since the RS422 is more immune to noise, cable links up to 1000 feet or more can be used. Because of the high input impedance of RS422, line ter­minating loads are recommended. For hookup to a single unit, a 150 to 200 Ohm resistor across Receive Data+ and Receive Data(-), at the Batcher and at the remote terminal is often sufficient. For multiple hook­ups, other standard terminations should be used. Note: Total loading should not be greater than 90 Ohms.
8-5.2 RS232 Wiring Notes The Batcher requires only three wires for RS232 communication:
a) Pin 7 (Signal Ground) b) Pin 2 (Receive Data) c) Pin 3 (Transmit Data)
Other pins are jumped to simulate appropriate responses required for some terminals.
a) Pin 4 (Request To Send), Pin 5 (Clear
To Send). Jumped internally to echo back signals.
b) Pin 6 (Data Set Ready), Pin 8 (Re-
ceived Line Signal Detector), Pin 20 (Data Terminal Ready). Jumped inter­nally to echo back signals.
41
8-7 RS422 Card Wiring This option has a subminiature D, 37 pin, fe­male connector and is wired as a DCE (Data Communications Equipment) device. It is de­signed to be connected to a DTE (Data Termi­nal Equipment) device. If it must be con­nected to a DCE device, it will be necessary to cross wires 4 and 6 as well as 22 and 24 at one end of the connector harness.
8-7.1 Wiring Diagram RS422 / Strobe (37 Pin Connector)
8-7.2 RS422 Wiring Notes The Batcher requires only four wires for RS422 communication:
a) Pin 22 (Receive Data +A) b) Pin 4 (Receive Data -B) c) Pin 24 (Transmit Data +A) d) Pin 6 (Transmit Data -B)
Other pins are jumped to simulate appropriate responses required for some terminals.
a) Pins 7, 25 (Request To Send), Pins 9,
27 (Clear To Send). Jumped internally
to echo back signals.
b) Pins 11, 29 (Data Set Ready), Pins 13,
31 (Received Line Signal Detector),
Pins 12, 30 (Data Terminal Ready).
Jumped internally to echo back signals. 8-8 Strobe Input Electrical Requirements
Both the RS232 and RS422 interface option cards have inputs that allow data to be re­quested over a separate strobe input and a 3 bit, data request, code input. Any number of unit's, data request, code lines can be linked in parallel; as long as the source can drive the combined load of all inputs linked together (1.5 K Ohm divided by the total number linked together). Data is transmitted over the serial lines using standard RS232 or RS422 charac­teristics. Note: Strobe and data request inputs are positive true with signal ground as reference:
8-8.1 Strobe Input Levels
0 or low: Open or 0 to 1 VDC
1 or high: 3 to 30 VDC
Impedance: 1.5 K Ohm
42
8-9 Strobe Wiring 8-9.1 RS232 Strobe Wiring (RS232, 25 Pin
Connector) The 3 data lines are hooked up to Pins 9, 10, and 11. These lines must be held high while a strobe of at least 25 milliseconds is given on Pin 18. Data is transmitted in RS232 serial format on the Transmit Data Line (Pin 3).
a) Pin 9, Binary 1's Input b) Pin 10, Binary 2's Input c) Pin 11, Binary 4's Input d) Pin 18, Strobe Input e) Pin 3, Transmit Data f) Pin 7, Signal Ground for Reference
Refer to 8-5.1 Wiring Hookup RS232 / Strobe (25 Pin Connector) for diagram.
8-9.2 RS422 Strobe Wiring (RS422, 37 Pin Connector) The 3 data lines are hooked up to Pins 9, 10, and 11. These lines must be held high while a strobe of at least 25 milliseconds is given on Pin 3. Data is transmitted in RS422 format on the Transmit Data Line (Pins 6, 24).
a) Pin 21, Binary 1's Input b) Pin 14, Binary 2's Input c) Pin 10, Binary 4's Input d) Pin 3, Strobe Input e) Pins 6, 24, Transmit Data f) Pins 19, 20, Signal Ground for Refer-
ence Refer to 8-7.1 Wiring Hookup RS422 / Strobe (37 Pin Connector) for diagram.
8-10 Serial Interface Operation Data is received and transmitted over stan­dard EIA RS232 or RS422 levels. To ad­dress a Batcher unit, transmit a "D" (device) followed by the 1 to 15 code number and a "Space". Once the space has been re­ceived the Batcher becomes active and re­sponds back, "Device XX:" (Device number). (Once active, the unit works in a full duplex echo back mode, so that data sent from the terminal will be transmitted back for verifica­tion.) Once the unit is "on line", use the
proper serial transmit codes to request data or set a new value. (See Section 8-10.2 RS232/RS422 Serial Input Codes). Up to 80 characters of data may be linked together and transmitted to the Batcher (as long as there is a space between the different codes). If an error is made, a correction can be made by back spacing and retyping correct data before the "Carriage Return" (Enter) is sent. Once "Carriage Return" (Enter) is sent, the Batcher starts processing the data and will transmit the requested data on a non-priority basis over the data transmit line. A Batcher keypad entry or incoming data will halt the data com­munication cycle. Therefore, there should be a pause after data is requested to insure that all data has been transmitted before another unit is addressed and brought on line. When transmitting, the Batcher will precede each data value with a "Carriage Return" and "Line Feed" code and answer only with requested data in the order the requests were made. After all requested data has been transmitted any new communication must be started again by DXX (Device number) and space.
8-10.1 Serial Communications Timing. If the Batcher is not busy, it should not require more than 5 msec to process each request. To find the cycle time to process and transmit a request, calculate the bit transmit time by dividing 1 by the baud rate; multiply that by 80 (8 characters each; 10 bits per character); add 5 msec. to this product and multiply by the number of requests made. Example: Typical time to transmit 1 uninterrupted re­quest at 300 baud rate is .272 sec = (1÷300) x (80) + 0.005. This time will be extended if the Batcher must service the front keypad or one of the inputs. In practice, if transmission has not started within 2 seconds after data is re­quested, it can be assumed that there is a problem.
43
8-10.2 RS232/RS422 Serial Input Codes DXX(S) (Device and address number followed
by space) activates the Batcher that had been assigned that number. That unit comes on line and transmits "Device XX:". Unit is now ready to receive a code or string of codes separated by a space. A "Carriage Return" (Enter) code enters the codes and processing of requests begins.
Note: After device is activated, there must be
a delay to allow "Device # _ _" to be
transmitted by the unit before any new
commands are sent to the unit. DC Will transmit Count.
DR Will transmit Rate. DT Will transmit Grand Total. GO Will start the unit on a Batch. KC Will transmit counter K Factor.* KC(S)XXX Will load Counter K Factor num-
ber.* KR Will transmit Rate K Factor.* KR(S)XXX Will load Rate K Factor num-
ber.* PA Will transmit Preset value. PA(S)XXX Will load Preset value number. PW Will transmit Prewarn value. PW(S)XXX Will load Prewarn value number. RC Will reset counter to zero if in
"RO" mode (adding) or set
counter to Preset value if in "SP"
mode (subtracting). Output is
reset. RC(S)XXX Will set counter to number (no
other change is made). RT Will reset Grand Total to zero. RT(S)XXX Will reset Grand Total to num-
ber. ST Will stop the unit from the batch
in progress.
8-10.3 RS232/RS422 Serial Input Examples Example A: (S) = Space
Transmit from terminal Receive from Batcher D13(S) [Unit 13 activated] Device #13 PA(S)76546(S)PA(S) PA 76546 PA KC(S)1575(S)KC(S) KC 1575 KC RC(ENTER) RC {Preset set to 76546, Count K Factor set to 1575, and Counter is reset.}
Example B: (S) = Space Transmit from terminal Receive from Batcher D7(S) [Unit 7 activated] Device #7 PA(S)12347(S)PA(S) PA 12347 PA RC(S)456789(S)RCC(S) RC 456789 RC RT(S)376(S)DT(ENTER) RT 376 DT {Batcher Preset set to 12347, Counter set to 456789, and Grand Total set to 376.}
8-10.4 16 Point Data Entry Commands FA Will transmit frequency of A
(Point 01)
KA Will transmit K Factor of A
(Point 01)
FA(S)XXX Will load frequency into A
(Point 01)
KA(S)XXX Will load K Factor into A
(Point 01)
FB Will transmit frequency of B
(Point 02)
KB Will transmit K Factor of B
(Point 02)
- - (Use letters A to O for Points 01 to 16)
FO Will transmit frequency of O
(Point 16)
KO Will transmit K Factor of O
(Point 16)
FO(S)XXX Will load frequency into O
(Point 16)
KO(S)XXX Will load K Factor into O
(Point 16)
To request a transmit of data, send a code for information desired. To change data, send the desired address code followed by a space and the new number desired.
* See Section 8-10.4 for 16 Point Option data entry commands.
44
8-10.5 RS232/RS422 16 Point Serial Input Example
Example : (S) = Space
Transmit from terminal Receive from Batcher D11(S) [Unit 7 activated] Device #11 FC(S)500(S)KC(S)305 FC 500 KC 305
{Frequency for C (Point 03) is set to 500,} {K Factor for C (Point 03) is set to 305.}
FC(S)KC(S)(ENTER) FC KC
{Unit echoes back commands as sent.} Frequency of C is sent 500 K Factor of C is sent 305
The 3 bit data request code would be latched in at the positive edge of a 3 to 30 VDC strobe input that remained high a minimum of 25 mil­liseconds. Requests are processed on a non­priority basis. Normally data will begin to be transmitted from the Batcher over the RS232 or RS422 serial transmit lines within 5 msec unless interrupted by a keypad entry or other signal input.
Note: No other unit should be brought on line
until data requested has been transmit­ted.
8-11 Strobe Address Operation
Another method of reading the status of a unit with either a RS232 or RS422 option is by means of a separate strobe address and a 3 bit data request code. The strobe address method does not allow changes of set points. Theoretically hundreds of units could be linked together to transmit data from the Batchers over a serial transmit line. The units could be assigned any code number except "00".
Note: There are no allowances for Frequency
or K Factor access on units with the 16 Point Option.
8-11.1 Strobe Input Codes
# DL4 DL2 DL1 Code Description 0 0 0 0 PA Will transmit Preset value.
1 0 0 1 PW Will transmit Prewarn value. 20 1 0 KC 3 0 1 1 KR Will transmit Rate K Factor. 4 1 0 0 DC Will transmit Count. 5 1 0 1 DT Will transmit Grand Total. 6 1 1 0 DR Will transmit Rate.
Will transmit counter K Factor.
45
9 Programming Worksheet
Model #_____________________________ Serial # _____________________________ Unit # ______________________________
PRESET _ _ _ _ _ _ _ _ PREWARN _ _ _ _ _ _ _ _ PREset TYPe ■ EZ PRE ■ STD PRE
COUNTer
K-FACTOR _ _ _ _ _ _ _ _ Reset to 0 Set to Preset Decimal Location (0-8)
876543210
None
RATEmeter
K-FACTOR _ _ _ _ _ _ _ _ WINDOW (02-24) _ _ SIGnificant FIGures (1-6) _ WEIGHT (00-99) _ _
Lockout Code
SECUR _ _ CODE _ _ _ _
Output Communication (If applicable) UNIT (00-15) _ _ Parallel Serial BAUDRATE 300 2400 ■
600 4800
1200 9600
PARITY Space Odd
Even Mark
Analog Output (If applicable) Rate Count SET LOW 4 mA= _ _ _ _ _ _ _ _ SET HIGH 20 mA= _ _ _ _ _ _ _ _
OUTput FREQuency 20000
2000
200
10
Terminals
1 - Not Used 2 - Scaled Pulse Output O.C. 3 - Analog Output 4 - Input A (Pulse/Analog) 5 - Remote Stop/Reset Input 6 - Not Used 7 - Not Used 8 - Not Used 9 - Not Used 10 - Remote Start Input 11 - Ground (-DC), Input Common 12 - Ground (-DC), Input Common 13 - +12 Volts Out 14 - DC Power In (12 - 27 VDC) 15 - Isolate -12 Volts 16 - Isolate +12 Volts 17 - AC In 18 - AC In 19-Prewarn Transistor O.C. 20-Preset Transistor O.C.
R1-N.O R2-N.C. Preset R3-Common R4-N.O R5-N.C. Prewarn R6-Common
46
Terminals
Ordering
1 - Not Used
2 - Scaled Pulse Output O.C.
3 - Analog Output
4 - Input A (Pulse/Analog)
5 - Remote Stop/Reset Input
6 - Not Used
7 - Not Used
8 - Not Used
9 - Not Used
10 - Remote Start Input
11 - Ground (-DC), Input Common
12 - Ground (-DC), Input Common
13 - +12 Volts Out
14 - DC Power In (12 - 27 VDC)
15 - Isolate -12 Volts
16 - Isolate +12 Volts
17 - AC In
18 - AC In
19-Prewarn Transistor O.C.
20-Preset Transistor O.C.
R1-N.O
R2-N.C. Preset
R3-Common
R4-N.O
R5-N.C. Prewarn
R6-Common
Decoding Part Number:
Example BT28 A 7AX 2 A 1 3 Series:
Batchtrol II
Operating Voltage:
A: 110 VAC ±15% or 12 to 27 VDC B: 220 VAC ±15% or 12 to 27 VDC
Control Inputs:
* 3A: STD Pulse 3-30 VDC 20 kHz Max. * 3B: As 3A, with 4.7 K pull up resistors
5A: 4-20 mA 5B: 0-20 mA 5C: 1-5 VDC 5D: 0-5 VDC 5E: 0-10 VDC 6A: 4-20 mA Square Law 7A:
4-20mA in, 4-20mA out
7B: 0-20mA in, 4-20mA out 7C: 1-5VDC in, 4-20mA out 7D: 0-5VDC in. 4-20mA out 7E: 0-10VDC in, 4-20mA out
Control Outputs:
1: Open Collector 2: SPDT Relay 10A
Input Speed:
* A: 0-40 CPS (Inputs 3A, 3B) * C: 0-400 CPS (Inputs 3A, 3B) * E: 0-20K CPS (Inputs 3A, 3B)
K: Inputs 5A-5E, 6A, 7A-7E
* Dip switch selectable,
all units can be field modified easily.
For Other Outputs:
Add X for 0-20mA out Add Y for 0-5V out Add Z for 0-10V out
}
WARRANTY
This product (excluding batteries) is warranted against defects in materials and workmanship for a period of two (2) years from the date of shipment to Buyer.
The Warranty is limited to repair or replacement of the defective unit at the option of the manufacturer. This warranty is void if the product has been altered, misused, dismantled, or otherwise abused.
ALL OTHER WARRANTIES, EXPRESSED OR IM­PLIED, ARE EXCLUDED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PAR-
TICULAR PURPOSE.
Options: (Multiple Options Available)
1: RS232 Serial Interface 2: RS422 Serial Interface 3: 4-20 mA Output (Input 3A or 3B only) 3X: 0-20 mA Output (Input 3A or 3B only) 3Y: 0-5VDC Output (Input 3A or 3B only) 3Z: 0-10VDC Output (Input 3A or 3B only) 4: 16 Point Linearization Opt. ET: Extended Temperature:
-40° to 158°F (-40° to 70° C)