The Batcher is a programmable, microprocessor based unit which provides batch control, monitors flow
rate and controls the flow of processing liquids. Start/Stop controls can be used in conjunction with
prewarn and final relays to provide valve actuation or pump control. An optional configuration of fers
streamlined preset adjustments, remote Start, Stop & Reset, and weighted averaging.
Features
❑ Pulse or Analog Input
❑ Display Batch, Rate or Grand Total
❑ Pulse Count Input up to 20 KHz
❑ 16 Point Linearization
❑ 8 Digit K-Factors for Rate and Total
❑ Security Lockout
❑ 2-Way RS232/422 Communications
❑ NEMA 4X/IP65 Front Panel
❑ Scalable 4-20 mA Output
❑ Scaled Pulse Output
❑ Optional Configuration Includes:
- Streamlined Preset Adjustment (Easy Preset)
- Remote Start, Stop and Reset
- Weighted A veraging
Batcher
Application
The unit is normally used for batch control or inventory tracking. The display may be toggled between
batch, rate, and grand total. A programmable K-factor makes keying-in engineering units easy. The unit
accepts pulse, contact closures or analog inputs and provides two separate preset controls.
Principle of Operation
The batcher receives an input from a pulse producing flowmeter through a sensor. The user programs the
batcher to condition the incoming pulses signal and compute the batch flow and flow rate. A wide variety
of different functions can then be performed based on the programmed configurations such as start/stop
functions, totalizing, and/or flow rate monitoring. Several other inputs, outputs and functions are available.
99502 01/10/03
Batcher Series Technical Manual
SAFETY INSTRUCTIONS
!
The following instructions must be observed.
•This instrument was designed and is checked in accordance with
regulations in force EN 60950 (“Safety of information technology
equipment, including electrical business equipment”).
A hazardous situation may occur if this instrument is not used for its
intended purpose or is used incorrectly. Please note operating
instructions provided in this manual.
•The instrument must be installed, operated and maintained by
personnel who have been properly trained. Personnel must read and
understand this manual prior to installation and operation of the
instrument.
•The manufacturer assumes no liability for damage caused by incorrect
use of the instrument or for modifications or changes made to the
instrument.
T echnical Improvements
•The manufacturer reserves the right to modify technical data without
prior notice.
1. INTRODUCTION
1-1 General Description ................................................................................................ 1
1-2 T ypical Application................................................................................................... 1
1-3 Principles of Operation............................................................................................ 1
1-4 STD PRE and EZ PRE Operation Modes ............................................................... 3
1-1 General Description
Sections 1 through 8 of this manual describe
the wiring, programming and functionality of
the standard Batch controller. Section 9 describes the wiring, programming and functionality of Batch controllers with software version
8.7 (Option 6). Software version 8.7 incorporates Remote Start, Stop & Reset with EZ
PRE (easy preset). EZ PRE is a useful tool
for applications that require frequent changes
to the Preset amount.
1-3 Principles of Operation
Presets
When the start button is pushed, two relays
engage simultaneously to start flow. When
the prewarn number is reached, one relay
drops out. When the preset number is
reached, the other relay drops out. The user
may enter the two numbers when setting up
the batch counter. The prewarn is set a certain number of counts less than the preset
number. If the prewarn is set larger than the
preset, the message "PREWRONG" will appear on the display.
The Batch controller uses the following software versions:
VER 8.7(Basic unit; Remote Start, Stop
& Reset with EZ PRE “Easy
Preset”)
VER 12.0 (Option 4; 16 point linearization)
1-2 Typical Application
Remote
Totalizer
123456
Strip Chart
Recorder
Analog
Output
Flowmeter
Pulse Output
RS232
Output
Solenoid Valve
Computer
The above application involves liquid flow.
The start button is pushed and the Batcher
receives pulses from the flowmeter. The
pulses are scaled by the K Factor and sent
out via the pulsed output to an external
counter. The Analog output is directed to a
strip chart recorder which gives a hardcopy of
the rate. As the Prewarn is reached, the
control valve partially closes. When the final
Preset is reached the valve shuts down completely. At any time the flow can be suspended by hitting the stop button. Through
the serial communications, a computer keeps
a record of the daily events.
Ratemeter
Accurate to 5 1/2 digits (±1 display digit). The
ratemeter can be programmed to accept almost any number of pulses per unit of measurement, sample from 2 to 24 seconds maximum, and auto range up to 6 digits of significant information. The ratemeter with a K Factor of 1 displays the rate of pulses per second.
Simply dial in the proper K Factor to display in
minutes, hours or other units of measurement.
Press the C button, while the unit is displaying
the batch, to display the rate; 'R' is displayed
on the left side of the display.
K Factor
The K Factor is used to convert the input
pulses or analog input into workable units.
The 8 digit K Factor is a divider with a range
of 0.00011 to 99999999 (the decimal point
may be keyed into any position). Separate K
Factors may be entered into the count and
rate sections of the Batcher. Thus, you may
batch in gallons and display rate in liters per
hour. The maximum factored count speed is
20000 Hz. The maximum factored rate is 7
digits.
16 Point Linearization (Optional)
This option extends the accurate range by allowing users to dial in different K Factors for
different input rates. This option may be used
with digital or analog inputs. (See Section 7-
3.)
1
1-3 Principles of Operation (continued)
Counter
The maximum count is 99999999. In the
setup mode choose "RO" (Reset to Zero) for
adding (count up) operation or "SP" (Set to
Preset) for subtracting (count down) operation. At any time, the display can be made
to flash the Grand Total by pressing the ENT
button while in the run mode. Activating the
CLR button while the Grand Total is flashing,
resets the Grand Total counter.
Lockout
Unauthorized front panel changes can be prevented by entering a user selected, four digit
code, in the "Lockout" mode. The status of
the unit can be observed but "LOCK ON" appears if changes are attempted. Entering the
code again returns the unit to "LOCK OFF"
status.
Analog Output (Optional)
The Analog Output option is available on all
units except those with Square Law inputs.
Controlled by an Open Collector transistor, it
gives a 4 to 20mA (or 0-20mA) output which
corresponds to predefined rate or total readings. In the Setup mode the user is prompted
to set the low and high (4 to 20 mA) values
and also decide if the analog signal will correspond to the ratemeter or totalizer.
Frequency out
The Batcher generates a pulse out for each
factored count. An NPN transistor output (Pin
2), can drive external devices at rates of 10,
200, 2000 or 20000 counts per second as selected through the keypad menu. If the K
Factor scaled inputs generate pulses faster
than the output speed selected, an internal
buffer will store up to 9,999 counts before
"DATALOST" flashes on the screen. This indicates that the counts being totaled and the
scaled outputs may be incorrect. Note that
all counts stored in the internal buffer will be
pulsed out at the selected frequency even if
the counter is reset.
Outcard (Optional)
RS232 or RS422 serial two way communications are available. Up to 15 units can be
linked together in parallel and addressed
separately to transmit unit status or accept
new set points in the standard ASCII format.
Baud rates of 300, 600, 1200, 2400, 4800 or
9600 as well as choice of odd, even, space,
or mark parity can be selected by keypad control.
A sinking driver generates a linear current
across the user's external device (such as a
strip chart recorder, PLC, computer, external
meter, etc). The Batcher can supply the 24
VDC to power the current loop. (Connect pin
15 to 13, Pin 16 is now +24 VDC with respect
to pin 12.) Connect Pin 16 to the + DC side of
the external device and connect Pin 3 to -DC
side of the external device.
2
1-4 STD PRE and EZ PRE Operation Modes
STD PRE and EZ PRE Operation Modes
Version 8.7 of the batcher software allows the user to choose between STD PRE (Standard Preset)
and EZ PRE (Easy Preset) operation modes. STD PRE operation is well suited for batch amounts
that do not change, since the program mode must be entered to change the preset and the batch
count must be cleared before starting a new batch. EZ PRE has been designed for users who
frequently change the batch amount. During EZ PRE operation, the preset can be viewed and
changed without entering the program mode and another batch can be started without resetting the
unit.
Note:
inputs.
Note:
Before a batch is started and after a batch is complete, the unit will continue to totalize all
EZ PRE is not available on units with 16 Point Linearization.
Using STD PRE
Programming
Select STD PRE - Go into the Program Mode and
select STD PRE in the PRE TYP sub menu.
Set the PRESET and PREWARN - Go into the
Program Mode and enter the desired values for
the PRESET and the PREWARN.
Program the Counter - Go into the Program
Mode and set up the counter in the COUNT sub
menu.
Operation
Start a Batch - In the Run Mode, reset the total
by pressing “CLR”, then press “A” to start.
When started, both relays energize and the
counter begins to count. When the batch is
complete, the relays drop out and the unit
displays the amount that was batched (0 if in
Set to Preset mode).
Stop a Batch - Press “B”, to temporarily stop
process by de-energizing the PRESET and
PREWARN relays. Press start, “A”, to continue
process.
Repeat a Batch - In the Run Mode, reset the total
and press the start button.
Change the Batch Size - Go to the Program
Mode and enter new PRESET and PREWARN
values.
Using EZ PRE
Programming
Select EZ PRE - Go into the Program Mode and
select EZ PRE in the PRE TYP sub menu.
Set the PRESET and PREWARN - Go into the
Program Mode and enter the desired values
for the PRESET and the PREWARN.
Program the Counter - Go into the Program
Mode and set up the counter in the COUNT
sub menu.
Operation
Start a Batch - In the Run Mode, press “A” to
start. When started, both relays energize and
the counter begins to total. When complete,
the relays drop out and the display flashes the
current PRESET value.
Stop a Batch - Press “B”, to temporarily stop
process by de-energizing the PRESET and
PREWARN relays. Press start, “A”, to continue
process.
Repeat a Batch - Press the start button.
Change the Batch Size - With the current
PRESET flashing on the display, type a new
number using the keypad. This number
becomes the PRESET.
Display Batch Total or Rate - With the current
PRESET flashing, press “ENT” to place the
PRESET value in memory and use the “C”
button to toggle between the Batch Total and
the Rate.
3
1-5 Specifications
Housing:
High impact plastic case with NEMA 4X front
panel.
Dimensions:
See Section 1-5, Page 4.
Display:
8 Digit, 0.55" High, 15 Segment, Red Orange,
LED.
Input Power:
A: 110 VAC ± 15% or 12 to 27 VDC
B: 220 VAC ± 15% or 12 to 27 VDC
NOTE: AC Inputs are internally fused with a
160mA slow blow fuse.
Current:
Maximum 280 mA DC or 5.3 VA at rated AC
voltage.
Output Power:
(On AC powered units only): +12 VDC at 100
mA. Separate Isolated 12 VDC at 100 mA to
allow ± 12 VDC or +24 VDC, regulated ± 5%
worst case.
Temperature:
Operating: +32°F (0° C) to +130 ° F (+54° C)
Storage: -40°F (-40° C) to +200 ° F (+93° C)
(Extended operating temperature range
available, consult factory)
Memory:
EEPROM stores all program, display mode
and count data for a minimum of 10 years if
power is lost.
Reset
Front push button: "CLR" resets displayed
number and control output.
Remote Input (Terminal 5): Open or 0 to 1
VDC (low), 3 to 30 VDC (high), 10K ohm input
impedance to ground. Minimum pulse on /
off time 5 msec.
Accuracy over full temperature range:
Analog - Zero error: ±0.175% full scale max.
Overall error: ±0.5% full scale max.
Digital - 100%(within specified voltage
ranges)
Pulse Inputs:
3A: Standard. High impedance pulse input.
Open or 0 to 1 VDC (low), 3 to 30 VDC (high),
10K ohm input impedance. 20 KHz maximum
speed (min. on / off 25 usec).
3B: Same as 3A except 4.7 K ohm pull up
resistor to +5 VDC with respect to Terminal
12.
Analog Inputs:
The current or voltage input is converted to a
highly linear 0 to 10 KHz frequency. This frequency can then be scaled by 8 digit K-factors to
display rate or count in the appropriate engineering units.
Factored Output:
One pulse per each factored count
Sinking (NPN Transistor)
Open Collector sinks 250 mA maximum to 1 volt
maximum from 30 VDC maximum
Internal buffer: 9999 pulses
Output speed: user selectable (see table
below)
Speed (Hz)10200 2000 20000
Min. on/off (msec) 47.52.00.20.013
Analog output:
(Not available with 4-20 mA, Square Law
input type)
4-20 mA (or 0-20 mA)
Sinking, (NPN transistor), Open Collector
Compliance voltage: 3-24 VDC, non-inductive
Accuracy: ±100 uA worst case
Update Rate: Follows ratemeter
ABCD
8.17
(207.5)
7.375
(187.3)
(NOM.)
1 2 3
4 5 6
7 8 9
CLR0SET
3.31
(84)
Control Outputs:
SPDT Relays
Contact rating: 10 A 120/240 VAC or 28
VDC.
NPN Transistor Output
Open Collector sinks maximum of 100 mA from
10 VDC when active
Note: 10 VDC is provided at transistor outputs
through the relay coils. If current greater than
2 mA is drawn, the relay will remain energized.
Applying greater than 10 VDC may destroy the
unit. The transistor will sink 100 mA in the "ON"
state with relays installed.
0.53
(13.5)
6.0
(152.4)
(NOM.)
7.375 -0, +0.04
(187.3 -0, +1)
PANEL
CUTOUT
2.48
(63)
(NOM.)
2.50 -0, +0.02
(63.5 -0, +0.5)
All Dimensions are in inches (mm)
5
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1-5 Dimensions (continued)
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
234567890123456789012345678901212
Full Size Panel Cutout Template
(copy before using)
SECTION 2 INSTALLATION
2-1 Receipt of Equipment
When the equipment is received, the outside
packing case should be checked for damage
incurred during shipment. If the packing case is
damaged, the local carrier should be notified at
once regarding his liability. A report should be
submitted to the factory.
Carefully remove the equipment from the packing case and inspect for damaged or missing
parts.
2-2 Return Shipment
Do not return assembly or part with out a Return
Material Authorization. The RMA is obtained by
calling your local distributor.
2-3 Panel Mounting
The controller should be located in an area with
a clean, dry atmosphere which is relatively free
of shock and vibration. The Batcher is installed
in a 7.365" (187 mm) wide by 2.495" (63.4 mm)
high panel cutout. To mount the controller
proceed as follows:
a. Prepare the panel opening.
b. Slip the gasket (provided) over the rear of the
counter case and slide it forward until it
engages the inner surface of the front bezel.
c. Install the screws (provided) in the mounting
brackets and insert in the holes located on
both sides of the Batcher.
d. Tighten the screws firmly to attach the
counter bezel to the panel.
2-4 Electrical Connections (Reference Figures
2-1 to 2-3)
All connections are completed at terminal
blocks located at the rear of the case. Make sure
all power is disconnected before making any
electrical connections. In cases where cables
are situated in areas with heavy electrical fields,
6
3-1 Front Panel Operation
A
STOP
START
START - Pressing “A”, starts the process
by energizing the PRESET and
PREWARN relays. Press “CLR” to reset
Batch Total before starting new batch.
RATE/TOTAL
MENU
D
CBA
ENT
Weighted Averaging
Version 8.7 of the batcher software includes
weighted averaging of the rate display. Weighted
1
2
3
4
5
6
7
9
8
CLR
0
averaging is not available on units with 16 Point
Linearization.
Weighted averaging can be used to create a more
stable display when the rate input is fluctuating. A
weight, “W”, from 00 to 99 is applied to the old
rate data before the new rate data is sent to the
display. The following equation is used:
Rate Display =
W = Weight (00-99)
(Old Data x W + New Data)
(W + 1)
B
C
D
ENT
CLR
STOP - Pressing “B”, will temporarily stop
the process by de-energizing the
PRESET and PREWARN relays. Use
START to continue the process from
where it stopped.
RATE/TOTAL - Pressing “C” toggles
between rate and total count displays.
The rate display has an “R” on the left
side of the screen.
MENU - Pressing “D” takes the unit out of
the Run Mode and into the Programming
Mode (See Programming, Page 43 and
45). “D” is also used make to some
programming selections.
ENT - With Count showing in the Run
Mode, pressing “ENT” displays the Grand
Total, which begins flashing on the
screen. Press “ENT” again to return to the
Count. In the Programming Mode, “ENT”
is used to accept a selection (See
Programming, Page 43 and 45).
CLR - When the count total is displayed,
pressing “CLR” will reset the counter to 0
or to Preset A depending on how it was
programmed. When the Grand Total is
displayed, pressing “CLR” will reset it to
0. When the Preset or Program Mode
values are displayed, pressing “CLR” will
reset them to 0, so that new values can
be entered.
If a weight of 00 is used, the new rate data will go
directly to the display without being averaged. If a
number other than 00 is entered for the weight,
then the new data will be averaged with the old
data before being sent to the display. Higher
weight numbers will create a more stable rate
display. Small rate changes will be more
noticeable when lower weight numbers are used.
Programming Weighted Averaging
1. In the Program Mode, got to the RATE sub menu
and program the K-FACTOR, the WINDOW, and
the SIG FIG parameters.
2. When the display shows WEIGHTXX (XX
represents the current WEIGHT value), either
accept the current value and return to the Run
Mode by pressing “ENT” or clear the current value
by pressing “CLR”.
3. If the current value was cleared, the display
shows WEIGHT00. Using the keypad, enter a
new WEIGHT value from 00 to 99. Press “ENT” to
accept the new value and return to the Run Mode.
Remote Start, Stop, and Reset
A 4 to 30 VDC positive pulse will activate these
inputs. Remote Start, Stop, and Reset is not
available on units ordered with the Control Input
option 7A (4-20 mA In, 4-20 mA Out).
START (Pin 10): When activated, the unit will
START as described in Front Panel Operation.
STOP/RESET (Pin 5): When activated, the unit will
STOP (If the unit is started and the batch is not
complete). A second pulse to pin 5 will reset the
counter (When the unit is stopped or when the
batch is complete). If pin 5 is held high (4 to 30
VDC), the display will flash “STOPPED” and any
start inputs will be inhibited.
8
3-2 VER 8.7 Programming
Overview:
This Section of the manual provides an outline of
programming procedures for the batcher software
version 8.7. Detailed descriptions and programming
instructions for this unit are available in previous
sections of this manual. Page number references
are included to help you find related information in
this manual.
Programming Procedures:
Enter Program Mode - Press the MENU button,
“D”, in the Run Mode.
Choosing a Sub Menu - Once in the Program
Mode, continue pressing the “D” button until the
desired Sub Menu is displayed. Press “ENT” to
enter the selected Sub Menu.
Making a Selection - An arrow, “
only the “D” button indicates that “D” is used to
change the selection. When an arrow appears
over “B” and “D”, one must be selected.
Entering a Value - The keypad is used to enter a
number. Use the “D” button to enter a decimal.
(Ex: 34.5 would be entered by pressing “3”, “4”,“D”, and “5”)
Accept a Value or Selection - Press “ENT” to
accept the value and go to next step.
Exit Program Mode - Program or skip each step of
one of the menus to return to the Run Mode.
Pressing “ENT” allows a step to be skipped
without changing its value.
↓”, appearing over
3-3 VER 8.7 K-Factor Programming
(See Programming Flow Chart, Page 10)
(For information on entering a K-Factor on a unit
with 16 Point Linearization, see 16 Point Linear-ization Notes, page 11) The K-Factor is usually
provided in pulses per unit, and will have to be
modified before entering it into the unit. On most
flowmeters, the K-Factor is stamped on the nameplate. (see section 7 for Calculating K-Factors)
Count K-Factor:
The Count K-Factor must be modified to allow for
the decimal point location chosen in the ”DEC LOC“
step.
K-Factor
DPF
DPF - The Decimal Point Factor is a divider to
compensate for the displayed decimal point.
DPF Table
DPFDecimalDPFDecimal
1XXXXXX.1000XXX.XXX
10XXXXX.X10000XX.XXXX
100XXXX.XX100000X.XXXXX
Rate K-Factor:
The Rate K-Factor must be modified to display the
correct volume per time unit. The Rate K-Factor is
not affected by the decimal point location selected
in the Count menu. The decimal point displayed by
the Rate Meter floats according to the significant
figure setting used in the SIG FIG step.
K-Factor
TF
= Count K-Factor
= Rate K-Factor
Key to Programming Flow Chart:
■
Display - This box represents the unit's
display. In the Run Mode, the flow rate, the
batch total, or the grand total will be displayed.
XXCurrent Value - The number that is currently
programmed for that step. It must be cleared
(CLR button) before entering a new value.
00No Value - Indicates that programmed value
for that step has been cleared, and a new
number may be entered.
Keypad - Use the front panel keypad to enter
a value or select a decimal point location for
this step.
TF - The Time Factor is a divider to adjust the time
units that the Rate Meter shows.
TF Table
TFTime UnitsRate Display
1SecondsUnits per Second
60MinutesUnits per Minute
3600HoursUnits per Hour
9
ENT
ENT
↓
↓
↓
ODD
MARK
EVEN↓ SPACE
ENT
ENT
87654321
D.E.C. . .L.O.C.
ENT
D
⇔
B
R0↓ SP↓
ENT
ENT
WEIGHT00
CLR
ENT
WEIGHTXX
ENT
300↓ 4800
0
CLR
SIGFIG00
CLR
XXXX
CODE
SIGFIGXX
ENT
D
PARITY
ENT
↓
↓
↓
600
↓
1200
2400
D
BAUDRATE
ENT
D
⇒
B
PL↓ SER↓
0
CLR
XXXX
↓
SET HIGH
9600
ENT
0
CLR
XXXX
ENT
ENT
0
CLR
0
CLR
Software Version 8.7 Programming Flow Chart
ENT
↓
↓
EZ PRE
STD PRE
D
ENT
Page 1, 14
↓
D
PRE TYP
XXXX
K-FACTOR
ENT
↓
Page 15
D
COUNT
XXXX
K-FACTOR
ENT
↓
◊ Page 2, 15
D
RATE
D
Run Mode
0
CLR
XXXX
ENT
↓
0
CLR
XXXX
ENT
Page 1, 14
↓
D
MENU
PRESET
PREWARN
3-4
WINDOW00
CLR
WINDOWXX
◊ Page 1, 17
D
10
ENT
SECUR 00
CLR
SECUR XX
ENT
↓
Page 2, 19
D
LOCKOUT
ENT
UNIT 00
CLR
↓
ANLG RT
UNIT XX
ENT
↓
§ Page 2, 21
D
OUTCARD
SET LOW
ENT
↓
ANLG CT
ENT
2000 ↓200
20000 ↓10
D
ENT
§ Page
2, 23
ENT
↓
D
◊ - On a Standard unit (Without 16 Point Linearization), the Count and/or the Rate must be programmed for basic operation.
§ - Sub menu will always appear, but feature may not be included in the unit. (Check Model Number).
↓
↓
D
Page
2, 24
D
ALG OUT↓OUTFREQ
3-5 VER 12.0 Programming
(Unit with 16 Point Linearization)
Overview:
This Section of the manual provides an outline of
programming procedures for the software version
12.0. Detailed descriptions and programming
instructions for this unit are available in the following sections of this manual. Page number references are included to help you find related information in this manual.
Programming Procedures:
Enter Program Mode - Press the MENU button,
“D”, in the Run Mode.
Choosing a Sub Menu - Once in the Program
Mode, continue pressing the “D” button until the
desired Sub Menu is displayed. Press “ENT” to
enter the selected Sub Menu.
Making a Selection - An arrow, “↓”, appearing over
only the “D” button indicates that “D” is used to
change the selection. When an arrow appears
over “B” and “D”, one must be selected.
Entering a Value - The keypad is used to enter a
number. Use the “D” button to enter a decimal.
(Ex: 34.5 would be entered by pressing “3”, “4”,“D”, and “5”)
Accept a Value or Selection - Press “ENT” to
accept the value and go to next step.
Exit Program Mode - Program or skip each step of
one of the menus to return to the Run Mode.
Pressing “ENT” allows a step to be skipped
without changing its value. (Note: “B” or “D” must
be pressed on the first step in the DEV TYP
menu)
3-6 VER 12.0 16 Point Linearization Notes
(See Programming Flow Chart, Page 12)
A K-Factor and a Frequency must be entered for at
least three points on a unit with Linearization.
Linearization K-Factor: The K-Factor for each
Linearization point must be modified to allow for the
display decimal point location chosen in the “DEC
LOC” step of the “DEV TYP” menu. Modify each
K-Factor using the following equation:
K-Factor
DPF
DPF - The Decimal Point Factor is a divider to
compensate for the displayed decimal point.
DPF Table
DPFDecimalDPFDecimal
1XXXXXX.1000XXX.XXX
10XXXXX.X10000XX.XXXX
100XXXX.XX100000X.XXXXX
Calculating K-Factors and Frequencies: If a
Linearization table is not available, the K-Factor
and the frequency for each point can be calculated
using the Test Mode on the unit. Refer to Section 7-
3.2, Test Mode Operation and K-Factor Calculation,
on page 37.
Entering K-Factors and Frequencies: Refer to
Section 7-3, Calculating 16 Point K-Factors, on
page 37 and the programming step listing on page
23.
= Linearization K-Factor
Key to Programming Flow Chart:
■
Display - This box represents the unit's
display. In the Run Mode, the flow rate, the
batch total, or the grand total will be displayed.
XXCurrent Value - The number that is currently
programmed for that step. It must be cleared
(CLR button) before entering a new value.
00No Value - Indicates that programmed value
for that step has been cleared, and a new
number may be entered.
Keypad - Use the front panel keypad to enter
a value or select a decimal point location for
this step.
11
ENT
↓
↓
↓
ODD
MARK
EVEN↓ SPACE
D
ENT
0
CLR
ENT
K 00
CLR
ENT
ENT
ENT
87654321
D.E.C. . .L.O.C.
ENT
⇔
R0↓ SP↓
ENT
SIGFIG00
D
CLR
B
SIGFIGXX
ENT
PARITY
ENT
↓
↓
↓
600
300↓ 4800
↓
↓
1200
2400
9600
D
BAUDRATE
ENT
ENT
D
⇒
B
PL↓ SER↓
0
Do not use PL. Select SER.
ENT
K XX
XXXX
SET HIGH
ENT
ENT
F 00
CLR
F XX
Increment to next point (Ex. POINT 02, POINT 03, Etc.
0
CLR
ENT
CLR
POINT 01
XXXX
1
To Exit
“0” at any point to exit the 16 Point settupeep all data entered up to that point.
◊ - At least three points in the 16 Point Linearization sub menu must be programmed for basic operations.
Enter a Point # of
§ - Sub menu will always appear, but feature may not be included in the unit. (Check Model Number).
CLR
0
CLR
0
CLR
D
WINDOW00
CLR
XXXX
WINDOWXX
CODE
UNIT 00
CLR
SET LOW
ENT
↓
↓
ANLG RT
ANLG CT
SECONDS↓ TEST
Software Version 12.0 16 Point Linearization Programming Flow Chart
D
Run Mode
XXXX
ENT
↓
MENU
PRESET
XXXX
ENT
↓
D
PREWARN
RT↓ CNT↓
ENT
↓
D
DEV TYP
B
D
ENT
↓
D
LOCKOUT
UNIT XX
ENT
↓
D
OUTCARD
D
ENT
↓
D
ALG OUT
3-7
12
ENT
POINT 00
ENT
↓
↓
↓
MINUTES
HOURS
D
ENT
↓
D
16 POINT
ENT
↓
↓
2000 ↓200
20000 ↓10
D
ENT
↓
D
OUTFREQ