Liquid Controls LCI40 Installation And Parts

LCI40
Signal Converter for Mass Flowmeters
®
Series
Installation and Parts
L I Q UID C O N T R O L S
LCI40 Series IOM
WWW.LCMETER.COM
LC_LCRIIE26:V1-0716
1
PUBLICATION UPDATES AND TRANSLATIONS
The most current English versions of all Liquid Controls publications are available on our web site, www.lcmeter.com. It is the responsibility of the local distributor to provide the most current version of LC manuals, instructions, and specification sheets in the required language of the country or the language of the end user to which the products are shipping. If there are questions about the language of any LC manuals, instructions, or specification sheets, please contact your local distributor.
The documentation is only complete when used in combination with the relevant documentation for the signal converter.
All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the prior written authorization of Liquid Controls, LLC.
Content is subject to change without notice.
www.lcmeter.com
07/2016 LCI40
Copyright 2016 by Liquid Controls, LLC.
The documentation is only complete when used in combination with the relevant documentation for the signal converter.
2
WWW.LCMETER.COM
LCI40 Series IOM
TABLE OF CONTENTS
1. SAFETY INSTRUCTIONS
1.1 Software History .............................................. 4
1.2 Intended Use ................................................... 5
1.3 Safety Instructions From The Manufacturer .... 5
2. DEVICE DESCRIPTION
2.1 Scope of Delivery ............................................6
2.2 Device Description ..........................................7
2.3 Field Housing ..................................................8
2.4 Name Plates .................................................... 9
3. INSTALLATION
3.1 General Notes on Installation ........................ 10
3.2 Storage .......................................................... 10
3.3 Transport .......................................................10
3.4 Installation Specifications ..............................10
4. ELECTRICAL CONNECTIONS
4.9 Electrical Connection of the
Inputs and Outputs ........................................24
4.10 Description of the Inputs and Outputs ........ 25
5. START-UP
5.1 Switching on the Power ................................34
5.2 Starting the Signal Converter ........................ 34
6.OPERATION
6.1 Display and Operating Elements ................... 35
6.2 Zero Calibration (Menu C1.1.1) .....................40
6.3 Menu Structure .............................................. 42
6.4 Function Tables .............................................45
6.5 Description of Functions ...............................65
6.6 Status Messages and
Diagnostic Information ..................................79
3.5 Mounting of the Compact Version ................10
3.6 Mounting the Field Housing, Remote Version ..11
4. ELECTRICAL CONNECTIONS
4.1 Safety Instructions .........................................13
4.2 Important Notes on Electrical Connection ....13
4.3 Requirements for Signal Cables
Provided by the Customer ............................13
4.4 Connecting the Signal Cables ....................... 14
4.5 Grounding the Measuring Sensor .................16
4.6 Connecting Power, All Housing VariantS....... 16
4.7 Inputs and Outputs, Overview .......................17
4.8 Description of the Inputs and Outputs .......... 21
6.7 Function Tests and Troubleshooting .............87
6.8 Diagnostic Functions .....................................89
7. SERVICE
7.1 Replacing the Signal Converter Electronics .. 90
7.2 Sensor or Drive Coil Fault..............................91
7.3 Spare Parts Availability .................................. 92
7.4 Availability of Services ................................... 92
7.5 Disposal .........................................................92
8. TECHNICAL DATA
8.1 Measuring Principle (Twin Tube) .................... 93
8.2 Technical Data ............................................... 95
LCI40 Series IOM
8.3 Dimensions and Weights ............................. 106
WWW.LCMETER.COM
3
1. SAFETY INSTRUCTIONS
1.1 Software History
The “Electronic Revision” (ER) is consulted to document the revision status of electronic equipment according to NE 53 for all GDC devices. It is easy to
Changes and Effect on Compatibility
1
2-_
3-_
Downwards compatible changes and fault repair with no effect on operation (e.g. spelling mistakes on display)
Downwards compatible hardware and/or software change of interfaces:
P PROFIBUS
F Foundation Fieldbus
M Modbus
X all interfaces
Downwards compatible hardware and/or software change of inputs and outputs:
I Current output
F, P Frequency / pulse output
S Status output
C Control input
CI Current input
X all inputs and outputs
4 Downwards compatible changes with new functions
5 Incompatible changes, i.e. electronic equipment must be changed.
see from the ER whether troubleshooting or larger changes in the electronic equipment have taken place and how that has affected the compatibility.
Information
In the table below, “x” is a placeholder for possible multi-digit alphanumeric combinations, depending on the available version
4
WWW.LCMETER.COM
LCI40 Series IOM
1. SAFETY INSTRUCTIONS
1.2 Intended Use
The mass flowmeters are designed exclusively to directly measure mass flow rates, product density and temperature as well to indirectly measure parameters such as the total volume and concentration of dissolved substances as well as the volume flow rate.
DANGER
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation.
DANGER
For devices used in hazardous areas, additional safety notes apply.
WARNING
If the device is not used according to the operating conditions (refer to chapter Technical data), the intended protection could be affected.
LCI40 Series IOM
WWW.LCMETER.COM
5
1. SAFETY INSTRUCTIONS
1.3 Safety Instructions From The Manufacturer
1.3.1 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including, but not limited to direct, indirect ,or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross negligence. In the event any applicable law does not allow such limitations on implied warranties or the exclusion of limitation of certain damages, you may, if such law applies to you, not be subject to some or all of the above disclaimer, exclusions, or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable in any way for possible consequences of such changes.
Liquid Controls disclaims all liability for damage to meter or accessories because of corrosion, salting­out of product, or separation of chemicals, whether occurring during periods of use or storage.
1.3.2 Product Liability and Warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose.
The manufacturer accepts no liability for the consequences of misuse by the operator. Improper installation and operation of the devices (systems) will cause the warranty to be void. The respective “Standard Terms and Conditions” which form the basis for the sales contract shall also apply.
1.3.3 Information Concerning the Documentation
To prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards, safety requirements and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the text, we advise you to contact your local office for assistance. The manufacturer can not accept responsibility for any damage or injury caused by misunderstanding of the information in this document.
This document is provided to help you establish operating conditions, which will permit safe and efficient use of this device. Special considerations and precautions are also described in the document, which appear in the form of icons on page 16.
6
WWW.LCMETER.COM
LCI40 Series IOM
1. SAFETY INSTRUCTIONS
1.3 Safety Instructions From The Manufacturer
1.3.4 Warning
Be Prepared
• Before using this product, read and understand the
instructions.
• All work must be performed by qualified personnel
trained in the proper application, installation, and maintenance of equipment and/or systems in accordance with all applicable codes and ordinances.
• When handling electronic components and boards,
always use proper Electrostatic Discharge (ESD) equipment and follow the proper procedures
• Make sure that all necessary safety precautions have
been taken.
• Provide for proper ventilation, temperature control,
fire prevention, evacuation, and fire management.
• Provide easy access to the appropriate fire
extinguishers for your product.
• Consult with your local fire department, state, and
local codes to ensure adequate preparation.
• Read this manual as well as all the literature provided
in your owner’s packet.
1.3.5 Notice
This manual provides warnings and procedures that are intended to inform the owner and/or operator of the hazards present when using the Liquid Controls Meter on LP-Gas and other products. The reading of thee warnings and the avoidance of such hazards is strictly in the hands of the owner-operators of the equipment. Neglect of that responsibility is not within the control of the manufacturer of the meter.
1.3.6 Publication Updates and Translations
The most current English version of all Liquid Controls publications are available on our Web site, www. lcmeter.com. It is the responsibility of the local distributor to provide the most current version of Liquid Control manuals, instructions, and specification sheets in the required language of the country or the language of the end user to which the products are shipping. If there are questions about the language of any Liquid Controls manuals, instructions, or specification sheets, please contact you local distributor.
• Save these instructions for future reference.
• Failure to follow the instructions set forth in this
publication could result in property damage, personal injury, or death from fire and/or explosion, or other hazards that may be associated with this type of equipment.
Safely Evacuate Piping System
Before disassembly of any meter or accessory component:
• All internal pressures must be relieved and all liquid
drained from the system in accordance with all applicable procedures.
• Pressure must be 0 (zero) psi.
• Close all liquid and vapor lines between the meter
and liquid source.
For Safety Rules, refer to local authorities and relevant NFPA Codes.
Failure to follow this warning could result in property damage, personal injury, or death from fire and/or explosion, or other hazards that may be associated with this type of equipment.
LCI40 Series IOM
WWW.LCMETER.COM
7
2. DEVICE DESCRIPTION
2.1 Scope of Delivery
Scope of Delivery
1. Device in the version as ordered
2. Documentation
3. Signal cable (only for remote version)
Signal Converter / Measuring Sensor Combination Possibilities
Measuring Sensor Signal Converter LCI40
LCMass
LCMass
Compact Remote Field Housing
®
100 LCMass® 140 C LCMass® 140 F
®
600 LCMass® 640 C LCMass® 640 F
Information
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
Information
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
Information
Do a check of the packing list to make sure that you have all the elements given in the order.
8
WWW.LCMETER.COM
LCI40 Series IOM
2. DEVICE DESCRIPTION
2.2 Device Description
The mass flowmeters are designed exclusively to directly measure mass flow rates, product density and temperature as well to indirectly measure parameters such as the total volume and concentration of dissolved substances as well as the volume flow rate.
Your measuring device is supplied ready for operation. The factory settings for the operating data have been made in accordance with your order specifications.
Device Versions
1. Compact version
2. Measuring sensor with connection box
3. Field housing
The following versions are available:
• Compact version (the signal converter is mounted
directly on the measuring sensor)
• Remote version (electrical connection to the
measuring sensor via field current and signal cable)
LCI40 Series IOM
WWW.LCMETER.COM
9
2. DEVICE DESCRIPTION
2.3 Field Housing
Construction of the Field Housing
1. Cover for electronics and display
2. Cover for power supply and inputs/outputs terminal compartment
3. Cover for measuring sensor terminal compartment
4. Cable entry for measuring sensor signal cable
5. Cable entry for measuring sensor field current cable
6. Cable entry for power supply
7. Cable entry for inputs and outputs
8. Mounting plate for pipe and wall mounting
Information
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resin-free and acid-free grease.
Ensure that the housing gasket is properly fitted, clean, and undamaged.
10
WWW.LCMETER.COM
LCI40 Series IOM
2. DEVICE DESCRIPTION
2.4 Nameplates
2.4.1 Example of a Nameplate
➆ ➅
Example of a Nameplate
1. Approvals-related thresholds
2. Additional information on documentation, calibration and patents
3. Protection category
4. Electrical connection data
5. Software and hardware revision (Electronics Revision), CG number, order number for signal converter and measuring sensor
6. Product description
7. Manufacturer and manufacturer logo
Liquid Controls LLC Lake Bluff, IL 60044-2242
Information
Look at the device nameplate to ensure that the device is delivered according to your order.
2.4.2 Electrical Connection Data of Inputs/Outputs (Example of Basic Version)
• A = active mode; the signal converter supplies the
power for connection of the subsequent devices
• P = passive mode; external power supply required
for operation of the subsequent devices
• N/C = connection terminals not connected
Example of a Nameplate for Electrical Connection Data of Inputs and Outputs
1. Power supply (AC: L and N; DC: L+ and L-; PE for 24
VAC; FE for 24 VAC and DC)
2. Connection data of connection terminal D/D-
3. Connection data of connection terminal C/C-
4. Connection data of connection terminal B/B-
5. Connection data of connection terminal A/A-; A+ only
operable in the basic version
Check for the correct supply voltage printed on the nameplate.
LCI40 Series IOM
WWW.LCMETER.COM
11
3. INSTALLATION
3.1 General Notes on Installation
Information
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer.
Information
Do a check of the packing list to make sure that you have all the elements given in the order.
3.2 Storage
• Store the device in a dry, dust-free location.
• Avoid continuous direct sunlight.
3.3 Transport
Signal Converter
Compact Version
Information
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
• Store the device in its original packing.
• Storage temperature: -58°F to +158°F / -50°C to +70°C
• No special requirements.
• Do not lift the device by the signal converter housing.
• Do not use lifting chains.
• To transport flange devices, use lifting straps. Wrap
these around both process connections.
3.4 Installation Specifications
Information
The following precautions must be taken to ensure reliable installation.
• Makesurethatthereisadequatespacetothesides.
• Protectthesignalconverterfromdirectsunlightandinstallasunshadeifnecessary.
• Signalconvertersinstalledincontrolcabinetsrequireadequatecooling,e.g.byfanorheat
exchanger.
• Donotexposethesignalconvertertointensevibrations.Themeasuringdevicesaretestedfor
a vibration level in accordance with IEC 68-2-64.
12
WWW.LCMETER.COM
LCI40 Series IOM
3. INSTALLATION
3.5 Mounting of the Compact Version
Information
The signal converter is mounted directly on the measuring sensor. For installation of the flowmeter, please observe the instructions in the supplied product documentation for the measuring sensor.
3.6 Mounting the Field Housing, Remote Version
3.6.1 Pipe Mounting
Pipe Mounting of the Field Housing
1. Fix the signal converter to the pipe.
2. Fasten the signal converter using standard U-bolts and washers.
3. Tighten the nuts.
Information
3.6.2 Wall Mounting
Wall Mounting of the Field Housing
1. Prepare the holes with the aid of the mounting plate. For further information refer to Mounting plate, field housing on page 133.
2. Use the mounting material and tools in compliance with the applicable occupational health and safety directives.
3. Fasten the housing securely to the wall.
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools in compliance with the applicable occupational health and safety directives.
LCI40 Series IOM
Mounting Multiple Devices Next to Each Other
a 23.6” / 600 mm b 9.8” / 250 mm
WWW.LCMETER.COM
13
3. INSTALLATION
3.6 Mounting the Field Housing, Remote Version
3.6.3 Turning the Display of the Field Housing Version
Turning the Display of the Field Housing Version
The display of the field housing version can be turned in 90° increments.
CAUTION
The ribbon cable of the display must not be folded or twisted repeatedly.
Information
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resin-free and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
1. Unscrew the cover from the display and operation control unit.
2, Using a suitable tool, pull out the two metal puller
devices to the left and right of the display.
3. Pull out the display between the two metal puller devices and rotate it to the required position.
4. Slide the display and then the metal puller devices back into the housing.
5. Re-fit the cover and tighten it by hand.
14
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.1 Safety Instructions
DANGER All work on the electrical
connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate!
DANGER Observe the national regulations
for electrical installations!
DANGER For devices used in hazardous
areas, additional safety notes apply; please refer to the Ex documentation.
4.2 Important Notes on Electrical Connection
DANGER Electrical connection is carried
out in conformity with the VDE 0100 directive “Regulations for electrical power installations with line voltages up to 1000 V” or equivalent national regulations.
DANGER Observe without fail the local
occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists.
Information Look at the device nameplate
to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
CAUTION
Use suitable cable entries for the various
electrical cables.
The measuring sensor and signal
converter have been configured together at the factory. For this reason, please connect the devices in pairs.
4.3 Requirements for Signal Cables Provided by the Customer
Specifications for Standard Signal Cables
• 5 twisted pair circuits (24 AWG)
• Insulation thickness of cables: 0.008” / 0.2 mm)
• Each cable pair shielded with foil and drain wire
• Overall foil/braid shield
• Casing color: grey
• Color of wires:
Pair 1: yellow/black
Pair 2: green/black
Pair 3: blue/black
Pair 4: red/black
Pair 5: white/black
• Test voltage: 100 VAC
• Temperature range: -40°F to +185°F / -40°C to +85°C
• Capacity between cables: 41 pF/m
Specifications for Cables in Hazardous Areas
• 5 twisted pair circuits (24 AWG)
• Insulation thickness of cables: 0.008” / 0.2 mm)
• Each cable pair shielded with foil and drain wire
• Overall foil/braid shield
• Casing color: blue
• Color of wires:
Pair 1: yellow/black
Pair 2: green/black
Pair 3: blue/black
Pair 4: red/black
Pair 5: white/black
• Test voltage: 100 VAC
• Temperature range: -40 to +85°C / -40 to +185°F
• Capacity between cables: 41 pF/m
• Capacity compared to shielding: 73 pF/m
• Inductance: 0.8 μH/m
LCI40 Series IOM
• Capacity compared to shielding: 73 pF/m
• Inductance: 0.8 μH/m
WWW.LCMETER.COM
15
4. ELECTRICAL CONNECTIONS
4.4 Connecting the Signal Cables
DANGER Cables may only be connected
when the power is switched off.
DANGER The device must be grounded
in accordance with regulations in order to protect personnel against electric shocks.
DANGER For devices used in hazardous
areas, additional safety notes apply; please refer to the Ex documentation.
WARNING Observe without fail the local
occupational health and safety regulations. Any work done on the electrical components of the measuring device may only be carried out by properly trained specialists.
Information
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resin-free and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
4.4.1 Connection of Signal Cable - Field Housing and Connection Box for Sensor
Connection of Signal Cable - Field Housing and Connection Box for Sensor
1. Unscrew the terminal compartment cover.
2. Pass the prepared signal cable through the cable entry.
3. Secure the signal cable using the clip.
4. Connect the electrical conductors as shown. The shielding must also be connected to the spring terminal.
5. Re-fit the cover and tighten it by hand.
Cable Cable
Cable Pair Color
1 yellow X1 SA+
1 black X1 SA-
2 green X1 SB+
2 black X1 SB-
3 blue X2 T1
3 black X2 T2
4 red X2 T3
4 black X2 T4
5 white X3 DR+
5 black X3 DR-
Connection Terminal
16
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.4 Connecting the Signal Cables
4.4.2 Connection Diagram
Connection Diagram
1. Terminal compartment for signal converter
2. Terminal compartment for measuring sensor
3. Connect shielding to spring terminal (drain wire and overall shield)
Cable Cable
Cable Pair Color
1 yellow X1 SA+
1 black X1 SA-
2 green X1 SB+
2 black X1 SB-
3 blue X2 T1
3 black X2 T2
4 red X2 T3
4 black X2 T4
5 white X3 DR+
5 black X3 DR-
Connection Terminal
DANGER
The device must be grounded in accordance with regulations in order to protect personnel against electric shocks.
LCI40 Series IOM
WWW.LCMETER.COM
17
4. ELECTRICAL CONNECTIONS
4.5 Grounding the Measuring Sensor
• The measuring sensor must be properly grounded.
• The grounding cable should not transmit any
interference voltages.
• Do not use the grounding cable to connect more than
one device to ground.
• The measuring sensors are connected to ground by
means of a functional grounding conductor FE.
• In hazardous areas, grounding is used at the same
time for equipotential bonding. Additional grounding instructions are provided in the separate “Ex documentation”, which are only supplied together with hazardous area equipment.
4.6 Connecting Power, All Housing Variants
• The protection category depends on the housing
versions (IP65 to 67 to IEC 529 / EN 60529 or NEMA4/4X/6).
• The housings of the devices, which are designed
to protect the electronic equipment from dust and moisture, should be kept well closed at all times. Creepage distances and clearances are dimensioned to VDE 0110 and IEC 664 for pollution severity 2. Supply circuits are designed for overvoltage category III and the output circuits for overvoltage category II.
• Fuse protection (IN 16 A) for the infeed power
circuit, as well as a separator (switch, circuit breaker) to isolate the signal converter must be provided close to the device. The separator must be marked as the separator for this device.
DANGER
There should be no difference in potential between the measuring sensor and the housing or protective earth of the signal converter!
DANGER
The device must be grounded in accordance with regulations in order to protect personnel against electric shocks.
DANGER
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex documentation.
18
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.6 Connecting Power, All Housing Variants
100 to 230 VAC (tolerance range: -15% / +10%)
• Note the power supply voltage and frequency (50 to
60 Hz) on the nameplate.
• The protective ground terminal PE of the power supply
must be connected to the separate Uclamp terminal in the terminal compartment of the signal converter
24 VDC (tolerance range: -55% / +30%)
24 VAC/DC (tolerance ranges: AC: -15% / +10%; DC: -25% / +30%)
• Note the data on the nameplate!
• For measurement process reasons, a functional
ground FE must be connected to the separate U-clamp terminal in the terminal compartment of the signal converter.
• When connecting to functional extra-low voltages,
provide a facility for protective separation (PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national regulations).
Information
240 VAC+5% is included in the tolerance range.
Information
For 24 VDC, 12 VDC-10% is included in the tolerance range.
Power Supply Connection
1. 100 to230 VAC (-15% / +10%), 22 VA
2. 24 VDC (-55% / +30%), 12 W
3. 24 VAC/DC (AC: -15% / +10%; DC: -25% / +30%), 22 VA or 12 W
4.7 Inputs and Outputs, Overview
4.7.1 Combinations of the Inputs/Outputs (I/Os)
This signal converter is available with various input/output combinations.
Basic Version
• Has 1 current output, 1 pulse output and 2 status
outputs / limit switches.
• The pulse output can be set as status output/limit
switch and one of the status outputs as a control input.
Ex i Version
• Depending on the task, the device can be configured
with various output modules.
• Current outputs can be active or passive.
Modular Version
• Depending on the task, the device can be configured
with various output modules.
Bus Systems
• The device allows intrinsically safe and non
intrinsically safe bus interfaces in combination with additional modules.
• For connection and operation of bus systems, please
note the separate documentation.
Ex Option
• Optionally available also with Foundation Fieldbus
and PROFIBUS PA
LCI40 Series IOM
• For hazardous areas, all of the input/output variants
for the housing designs C and F with terminal compartment.
WWW.LCMETER.COM
19
4. ELECTRICAL CONNECTIONS
4.7 Inputs and Outputs, Overview
4.7.2 Description of the CG Number
The last 3 digits of the CG number (5, 6 and 7) indicate the assignment of the terminal connections. Please refer to the following examples.
Marking (CG Number) of the Electronics Module and Input/ Output Variants
1. ID number: 3
2. ID number: 0 = standard; 9 = special
3. Power supply option
4. Display (language versions)
5. Input/output version (I/O)
6. 1st optional module for connection terminal A
7. 2nd optional module for connection terminal B
The last 3 digits of the CG number (5, 6 and 7) indicate the assignment of the terminal connections. Please refer to the examples.
CG Number Examples
100 to 230 VAC & standard display;
CG 330 11 100
CG 330 11 7FK
CG 330 81 4EB
basic I/O: Ia or Ip & Sp/Cp & Sp & Pp/ S
p
100 to 230 VAC & standard display; modular I/O: Ia & PN/SN and optional module P
24 VDC & standard display; modular I/O: Ia & Pa/Sa and optional module P
p/Sp
& I
N/SN
p
& C
N
Description of Abbreviations and CG Identifier for Possible Optional Modules on Terminals A and B
Abbreviation Identifier for CG No. Description
A Active current output
I
a
B Passive current output
I
p
/ Sa C Active pulse output, frequency output, status output or limit switch (changeable)
P
a
/ S
P
p
p
G Active control input
C
a
C
p
- 8 No additional module installed
- 0 No further module possible
E Passive pulse output, frequency output, status output or limit switch (changeable)
K Passive control input
20
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.7 Inputs and Outputs, Overview
4.7.3 Fixed, Non-alterable Input/Output Versions
This signal converter is available with various input/ output combinations.
• The grey boxes in the tables denote unassigned or
unused connection terminals.
• In the table, only the final digits of the CG no. are
depicted.
• Connection terminal A+ is only operable in the basic
input/output version.
CG No. Connection Terminals
A+ A A- B B- C C- D D-
Basic I/Os (standard)
1
I
1 0 0
Ia
p
1
S
/ Cp passive 2 Sp passive Pp / Sp passive
p
PROFIBUS PA (Ex i) (option)
D 0 0
/ SN
P
D 1 0 I
D 2 0 I
active
a
passive
p
N
C
passive
p
/ SN
P
N
C
passive
p
2
2
2
PA+ PA- PA+ PA
FISCO Device FISCO Device
PA+ PA- PA+ PA
FISCO Device FISCO Device
PA+ PA- PA+ PA
FISCO Device FISCO Device
FOUNDATION Fieldbus (Ex i) (option)
E 0 0
E 1 0 I
E 2 0 Ip passive
1 Function changed by reconnecting 2 Changeable
active
a
/ SN
P
N
C
passive
p
P
/ SN
N
C
passive
p
V/D+ V/D- V/D+ V/D
FISCO Device FISCO Device
V/D+ V/D- V/D+ V/D
2
FISCO Device FISCO Device
V/D+ V/D- V/D+ V/D
2
FISCO Device FISCO Device
LCI40 Series IOM
WWW.LCMETER.COM
21
4. ELECTRICAL CONNECTIONS
4.7 Inputs and Outputs, Overview
4.7.4 Alterable input/output versions
This signal converter is available with various input/ output combinations.
• In the table, only the final digits of the CG no. are
depicted.
• The grey boxes in the tables denote unassigned or
• Term. = (connection) terminal
unused connection terminals.
CG No. Connection Terminals
A+ A A- B B- C C- D D-
Modular IOs (option)
4 _ _ max. 2 optional modules for term. A + B Ia Pa / Sa active
8 _ _ max. 2 optional modules for term. A + B Ip Pa / Sa active
6 _ _ max. 2 optional modules for term. A + B Ia Pp / Sp passive
B _ _ max. 2 optional modules for term. A + B I
p
Pp / Sp passive
1
1
1
1
PROFIBUS PA (option)
D _ _ max. 2 optional modules for term. A + B PA+ (2) PA- (2) PA+ (1) PA- (1)
FOUNDATION Fieldbus (option)
E _ _ max. 2 optional modules for term. A + B V/D+ (2) V/D- (2) V/D+ (1) V/D- (1)
PROFIBUS DP (option)
F _ 0
1 optional module for term. A
Termination PRxD/
TxDP(2)
RxD/ TxDN(2)
Termination NRxD/
Modbus (option)
G _ _ 2 max. 2 optional modules for term. A + B Common
3
H _ _
max. 2 optional modules for term. A + B Common
1 changeable 2 not activated bus terminator 3 activated bus terminator
TxDP(1)
Sign. B (D1)
Sign. B (D1)
RxD/ TxDN(1)
Sign. A (D0)
Sign. A (D0)
22
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.8 Description of the Inputs and Outputs
4.8.1 Current Output
• All outputs are electrically isolated from each other
and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode: external power Uext 32 VDC at I
22 mA
• Active mode: load impedance RL 1 kΩ at I 22
mA; RL 450 Ω at I 22 mA for Ex i outputs
• Self-monitoring: interruption or load impedance too
high in the current output loop
• Error message possible via status output, error
indication on LCI40 display.
• Current value error detection can be adjusted. Default
setting: 3.6 mA
• Automatic range conversion via threshold or
control input. The setting range for the threshold is between 5 and 80% of Q (corresponding ratio from smaller to larger range of 1:20 to 1:1.25). Signaling of the active range possible via a status output (adjustable).
• Forward / reverse flow measurement (F/R mode) is
possible.
, ± 0 to 5% hysteresis
100%
Information
The current outputs must be connected depending on the version! Which I/O versions and inputs/outputs are installed in your signal converter are indicated on the sticker in the cover of the terminal compartment.
Information
For further information refer to Description of the inputs and outputs on page 25 and refer to technical data on page 96.
DANGER
For devices used in hazardous areas, additional safety notes apply.
LCI40 Series IOM
WWW.LCMETER.COM
23
4. ELECTRICAL CONNECTIONS
4.8 Description of the Inputs and Outputs
4.8.2 Pulse and Frequency Output
• All outputs are electrically isolated from each other
and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U I 20 mA at f 10 kHz (over range up to f kHz) I 100 mA at f 100 Hz
• Active mode:
Use of the internal power supply: U I 20 mA at f 10 kHz (over range up to f kHz) I 20 mA at f 100 Hz
• Scaling:
Frequency output: in pulses per time unit (e.g. 1000 pulses/s at Q Pulse output: quantity per pulse.
• Pulse width:
Symmetric (pulse duty factor 1:1, independent of output frequency) Automatic (with fixed pulse width, duty factor approx. 1:1 at Q Fixed (pulse width adjustable as required from 0.05 ms to 2 s)
• Forward / reverse flow measurement (F/R mode) is
possible.
100%
100%
) or
);
32 VDC
ext
= 24 VDC
nom
max
max
12
12
Information
Depending on the version, the pulse and frequency outputs must be connected passively or actively. Which I/O version and inputs/ outputs are installed in your signal converter are indicated on the sticker in the cover of the terminal compartment.
Information
For further information refer to Description of the inputs and outputs on page 25 and refer to technical data on page 96.
DANGER
For devices used in hazardous areas, additional safety notes apply.
• All pulse and frequency outputs can also be used as
a status output / limit switch.
24
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.8 Description of the Inputs and Outputs
4.8.3 Status Output and Limit Switch
• The status outputs / limit switches are electrically
isolated from each other and from all other circuits.
• The output stages of the status outputs/limit
switches during simple active or passive operation behave like relay contacts and can be connected with any polarity.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
U
32 VDC; I 100 mA
ext
• Active mode: use of the internal power supply:
U
= 24 VDC; I 20 mA
nom
• For information on the adjustable operating states
refer to Function tables on page 46.
4.8.4 Control Input
• All control inputs are electrically isolated from each
other and from all other circuits.
Information
Depending on the version, the pulse and frequency outputs must be connected passively or actively. Which I/O version and inputs/ outputs are installed in your signal converter are indicated on the sticker in the cover of the terminal compartment.
Information
For further information refer to Description of the inputs and outputs on page 25 and refer to technical data on page 96.
• All operating data and functions can be adjusted.
• Passive mode: external power supply required:
U
32 VDC
ext
• Active mode: use of the internal power supply:
U
= 24 VDC
nom
• For information on the adjustable operating states
refer to Function tables on page 46.
DANGER
For devices used in hazardous areas, additional safety notes apply.
LCI40 Series IOM
WWW.LCMETER.COM
25
4. ELECTRICAL CONNECTIONS
4.9 Electrical Connection of the Inputs and Outputs
4.9.1 Field Housing, Electrical Connection of the Inputs and Outputs
Information
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools In compliance with the applicable occupational health and safety directives.
Terminal Compartment for Inputs and Outputs in Field Housing
1. Open the housing cover.
2. Push the prepared cable through the cable entry and connect the necessary conductors.
3. Connect the shield if necessary.
4. Close the touch guard.
5. Close the housing cover.
4.9.2 Laying Electrical Cables Correctly
Protect Housing from Dust and Water
1. Lay the cable in a loop just before the housing.
2. Tighten the screw connection of the cable entry securely.
3. Never mount the housing with the cable entries facing upwards.
4. Seal cable entries that are not needed with a plug.
DANGER
All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate!
Information
For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from electrical interferences (EMC).
Information
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resin-free and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.
26
WWW.LCMETER.COM
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.10 Description of the Inputs and Outputs
4.10.1 Important Notes
• All groups are electrically isolated from each other
and from all other input and output circuits.
• Passive mode: An external power supply is
necessary to operate (activation) the subsequent devices (U
• Active mode: The signal converter supplies the
power for operation (activation) of the subsequent devices, observe max. operating data.
• Terminals that are not used should not have
any conductive connection to other electrically conductive parts.
ext
).
Information
Depending on the version, the pulse and frequency outputs must be connected passively or actively. Which I/O version and inputs/ outputs are installed in your signal converter are indicated on the sticker in the cover of the terminal compartment.
Description of Used Abbreviations
Ia I
P
a
S
a
C
p
Pp Pulse/frequency output active or passive
Sp Status output/limit switch active or passive
Cp Control input active or passive
a
Current output active or passive
4.10.2 Description of the Electrical Symbols
Description of Symbols
mA meter. 0 to 20 mA or 4 to 20 mA and other. RL is the internal resistance of the measuring point including the cable resistance
DC voltage source (Uext), external power supply, any connection polarity
DC voltage source (Uext), observe connection polarity according to connection diagrams
Internal DC voltage source
Controlled internal power source in the device
DANGER
For devices used in hazardous areas, additional safety notes apply.
Electronic or electromagnetic counter. At frequencies above 100 Hz, shielded cables must be used to connect the counters. Ri Internal resistance of the counter.
Button, NO contact or similar
LCI40 Series IOM
WWW.LCMETER.COM
27
4. ELECTRICAL CONNECTIONS
4.10 Description of the Inputs and Outputs
4.10.3 Basic Inputs/Outputs
Current Output Active, Basic I/Os
• U
= 24 VDC nominal
int, nom
• I 22 mA
• RL 1 kΩ
Current Output Active I
a
Current Output Passive, Basic I/Os
• U
• U
= 24 VDC nominal
int, nom
32 VDC
ext
• I 22 mA
• U0 1.8 V
• RL (U
- U0) / I
ext
max
Pulse/Frequency Output Passive, Basic I/Os
• U
ext
• f
max
I 100 mA
open:
I 0.05 mA at U
closed:
U
0, max
U
0, max
• f
max
I 20 mA
Open:
I 0.05 mA at U
Closed:
U
0, max
U
0, max
U
0, max
• If the following maximum load impedance RL, max is
exceeded, the load impedance RL must be reduced accordingly by parallel connection of R:
f ≤ 100 Hz: R
f 1 kHz: R f 10 kHz: R
• The minimum load impedance R
follows: R
L, min
• Can also be set as a status output; for the electrical
connection refer to status output connection diagram
32 VDC
in the operating menu set to f
= 32 VDC
ext
max
= 0.2 V at I 10 mA = 2 V at I 100 mA
in operating menu set to 100 Hz < f
= 32 VDC
ext
= 1.5 V at I 1 mA = 2.5 V at I 10 mA = 5.0 V at I 20 mA
= 47 kΩ
L, max
= 10 kΩ
L, max
= 1 kΩ
L, max
is calculated as
L, min
= (U
- U0) / I
ext
max
100 Hz:
10 kHz:
max
Current Output Passive I
p
CAUTION
Observe connection polarity.
28
WWW.LCMETER.COM
Pulse/Frequency Output Passive Pp
Information
Compact and field housing versions: Shield connected via the cable terminals in the terminal compartment.
Any connection polarity.
LCI40 Series IOM
4. ELECTRICAL CONNECTIONS
4.10 Description of the Inputs and Outputs
4.10.3 Basic Inputs/Outputs
Status Output / Limit Switch Passive, Basic I/Os
• U
32 VDC
ext
• I 100 mA
• RL, max = 47 kΩ
RL, min = (U
- U0) / I
ext
max
• Open:
I ≤ 0.05 mA at U
= 32 VDC
ext
• Closed:
U0, max = 0.2 V at I 10 mA
U0, max = 2 V at I 100 mA
• The output is open when the device is de-energized.
• X stands for the connection terminals B, C or D. The
functions of the connection terminals depend on the settings refered to in Function tables on page 68.
Control Input Passive, Basic I/Os
• 8 V Uext 32 VDC
• I
max
I
max
• Switching point for identifying “contact open or
closed”: Contact open (off): U0 2.5 V with I Contact closed (on): U0 8 V with Inom = 2.8 mA
• Can also be set as a status output; for the electrical
connection refer to status output connection diagram.
= 6.5 mA at U
= 8.2 mA at U
24 VDC
ext
32 VDC
ext
= 0.4 mA
nom
Status Output / Limit Switch Passive S
Control Input Passive C
1. Signal
p
Information
Compact and field housing
p
versions: Shield connected via the cable terminals in the terminal compartment.
Any connection polarity.
LCI40 Series IOM
WWW.LCMETER.COM
29
4. ELECTRICAL CONNECTIONS
4.10 Description of the Inputs and Outputs
4.10.4 Modular Inputs/Outputs and Bus Systems
Current Output Active, Modular I/Os
• U
• I 22 mA
• RL 1 kΩ
• X designates the connection terminals A, B or C,
depending on the version of the signal converter.
Current Output Active I
int, nom
= 24 VDC
a
CAUTION
Observe connection polarity.
Information
For further information on electrical connection refer to Description of the inputs and outputs on page 25.
For the electrical connection of bus systems, please refer to the separate documentation for the respective bus systems.
Current Output Passive, Modular I/Os
32 VDC
• U
ext
• I 22 mA
• U0 1.8 V
• RL (U
- U0) / I
ext
max
• X designates the connection terminals A, B, or C,
depending on the version of the signal converter.
Current Output Passive I
p
30
WWW.LCMETER.COM
LCI40 Series IOM
Loading...
+ 78 hidden pages