The last three digits of le name identify the software version which the manual refers to;
it is visualized at the instrument start up, or by specic function on DIAGNOSTIC menu.
This manual is an integral part of the product. Read carefully the instructions contained,
they give important indications for it’s safe use and maintenance. Technical information
and related products in this manual may undergo modifications without prior notice.
The flow meter must be used within the specified limits. The improper use, possible
tampering, or substitutions of one or any of the original components renders the
manufacturers warranty void with immediate effect. The manufacturer accepts
responsibility only if the instrument it’s used within the published or prior agreed
specification.
Reproduction of this manual and any software supplied with this
converter is strictly forbidden.
SYMBOLS USED IN THIS MANUAL
TTENTION
DANGER ELECTRIC SHOC
WARNING
PRECAUTIONS
HML 110
3
110_EN_LC_5_3_6X.doc
g
)
TECHNICAL CHARACTERIST ICS
ELECTRIC CHARACTERISTICS
Classification of the converter: class I, IP 65, category of installation II
Power supply
versions
HV 90-265 Vac 44 - 66 Hz 3W/5VA 35 mA
LV
Power supply
voltage
12-60 Vdc
18-45 Vac
INPUT/OUTPUT ISOLATION
Input/output insulated up to 500V
The output 4-20 mA and output 24 Vdc are electrically connected
The converter can be installed internally or externally with in the following specification
Altitude: from –200 to 6000 m (from -656 to 19685 feet)
Humidity range: 0 - 98%
Line volta
ENVIRONMENTAL CONDITIONS OF USE
e range: (see table of Electrical Characteristics above
OPERATING TEMPERATURE
Ambient Temp.
Min. Max
°C °F °C°F
-10* -14* 50122
* In situations of discontinuous use in cold ambient temperatures, the
installation of an additional heat source may be necessary.
Power supply
frequency
Pmax
0 - 44 - 66 Hz 3W/5VA 300 mA
CONVERTER
current
max
HML 110
4
110_EN_LC_5_3_6X.doc
HML 110
DIMENSIONS ( HOUSING IN NYLON )
COMPACT VERSION
168
SEPARATE VERSION
129
78
1
2
7
4
2
1
5
110_EN_LC_5_3_6X.doc
HML 110
DIMENSIONS ( HOUSING IN ALUMINUM )
COMPACT VERSION
0
6
1
193
169
SEPARATE VERSION
78
6
110_EN_LC_5_3_6X.doc
ELECTRICAL CONNECTIONS
GROUNDING INSTRUCTIONS
ALWAYS ensure that the Converter and the Sensor are grounded (earthed) correctly.
The grounding of t he sensor and converter ensures th at the equipment and liquid are
equipotential.
CONVERTER POWER SUPPLY
L
(-)
N
(+)
Before connecting the power supply, verify that the
mains voltage falls between the limits indicated on
the tag plate.
ATTENTION: Converters on a dc power supply line
are not protected against the inversions of p o larity.
When wiring the converter and sensor equipme nt use
only approved conductors, with fire- proof p r op erties.
The power supply line must be equipped with an
external protection for current overload (fuse or
automatic line breaker, limiting current to less than
10 A).
Provide in close proximity to the converter a circuit
breaker that must be easily accessible to the operator
and clearly identified.
NOTE: For characteristics of the converter’s power
supply, see page 4
The sensor, hardwired inputs and outputs are connected to the converter
through a terminal block locate inside the converter.
To locate the terminal block loosen the 4 screws on the front cover. Lift the
front panel. With the front cover lifted, the terminal block is visible. The
terminal block is the hardwire connection of the converter to external
equipment, including the sensor.
The following pages give information on the terminal block numbering, and the
respective connecting of the senor cables, and input/outputs.
HML 110
7
110_EN_LC_5_3_6X.doc
INTERNAL VIEW OF CONVERTER
Power supply
IF2 socket
Signalling LED:
See interpretation notes page 12
Dangerous voltage on block 12-13:
- 60 Vdc Max
- 250 V Max on commutation coils (switching )
Keyboard
CONVERTER TO SENSOR ELECTRICAL CONNECTIONS
SEPARATE VERSION
C018 CABLE
1
2
3
4
11
12
13
E1
E2
C
SH
B1
B2
Sudden movements to the electrodes
cable can cause noise during
measurement Max length of electrodes cable: 20 m
11 12 13 14 15 16 17 18 19 20
TERMINAL BLOCK
OUT2
24V
-
E C
E C
10
-
+
A
4-20mA
RS 485* : OPTIONAL
RS 485*INPUT
12345678910
OUT1
B
24V
-
+
Power supply
>HV<
90..265VAC
SC
B2
+
SC
HML 110
>LV<
15...45VAC
10...63VDC
COILS
SC
B1
11121314151617181920
C
E2
ELECTRODES
123456789
E1
8
110_EN_LC_5_3_6X.doc
R
INTERNAL VIEW OF THE ALUMINUM CONVERTE
Power supply
IF2 socket
Signalling LED:
See interpretation notes page 10
Dangerous voltage on block 12-13:
- 60 Vdc Max
- 250 V Max on commutation coils (switching )
Keyboard
Shield
C018 cable
ALUMINIUM CONVERTER TO SENSOR, ELECTRICAL CONNECTIONS
SEPARATE VERSIONTERMINAL BLOCK M1
1
C018 CABLE
2
3
S
S
12
13
E1
E2
C
SH
SH
B1
B2
24V
-
10
OUT2
E
OUT1
24V
+
E
C
C
SC
Sudden movements to the
electrodes cable can cause noise during
measurement Max length of electrodes cable: 20 m
-
+
A
4-20mA
RS 485*INPUT
RS 485* : OPTIONAL
-
B
+
>HV<
90..265VAC
COILS
B1
B2
C
ELECTRODES
HML 110
Power supply
>LV<
15...45VAC
10...63VDC
11121314151617181920
123456789
E1
E2
9
110_EN_LC_5_3_6X.doc
DIGITAL INPUT
A
External power supplyInternal power supply
10 K
5 (+)
3/40 Vdc (ON)
0/1,5 Vdc (OFF)
6 (-)
10 K
+24
15
5
6
0
20
OPERATION ON INPUT ON/OFF
uto-calibration
AUTOCALIB. OFF
3-40 V
Tmin<T<1sec. = autocalibr ation
T > 1 sec. = Auto zero
Necessary conditions for enabling the function
POS. 5.7 ENABLED (Autozero calibration external command)
0-1,5 V
T
Reset totalizes
3-40 V
0-1,5 V
BLOCK
T
RESET
Tmin = 100ms
Necessary conditions f or en abling the function
POS. 5.1 to 5.4 ENABLED (partial positive or reverse
flow totalise reset enable).
Block totalizes
Block totalizes
3-40 V
Necessary conditions f or en abling the function
POS. 5.6 ENABLED (totalise counting lock command)
0-1,5 V
Totalizers active
Range change
3-40 V
Scale 2
0-1,5 V
Scale 1
Necessary conditions f or en abling the function
POS. 5.8 ENABLED (range change)
SAMPLE RAT E
10 Hz
20 Hz
50 Hz
Tmin
220 ms
110 ms
45 ms
SAMPLE RATE
80 Hz
150 Hz
Tmin
30 ms
T must be > to Tmin
15 ms
HML 110
10
110_EN_LC_5_3_6X.doc
A
OUTPUTS WIRING
Output on/off 1250
16 (out1)
18 (out2)
43V
17 (out1)
19 (out2)
Output 0/4-20mA
+24V INTERNAL
m
I
9 (+)
0/4..20mA OUT
10 (-)
24V COMMON
There is a Converter load CHECK on the 4 - 20mA output; to disable this
function set the value "mA Val. Fault" to 0 (Pos. 4.5, see page 15)
CONVERTER START UP AND MAINTENANCE INSTRUCTIONS
Before starting up the equipment please verify the following:
Power supply voltage must correspond to that speci f ied on the data plate
Electric connections must be completed as described at page 7-8
Ground (earthed) connections must be comp leted as specified on page 7
Verify periodically:
The integrity of the pow er supply cables, w iring and other con nected electrical
parts
The integrity of the converter’s housing (this must not have dents or other
damage that may compromises it’s hermetical sealing)
The tightening of the sealing elements (cable glands, covers, etc.)
The integrity of the front panel (display and keyboard), any damage may
compromise the equipment sealing
The mechanical fixing of the converter to the pipe or wall stand
11
HML 110
Opto-insulated output with floating collector and
emitter terminals freely connectable
Maximum switching v o lt age: 40 Vdc
Maximum switching current : 100m A
Maximum saturation voltage between collector and
emitter @100mA: 1,2V
Maximum switching frequency (load on the
collector or emitter, RL=470Ω, VOUT=24Vdc):
1250Hz
Maximum reverse current bearable on the input
during and accidental polarity reversion (VEC):
100mA
Insulation from other secondary circu it s: 500 Vdc
Opto-insulated output
Maximum load: 1000 ohm
Maximum voltage without load: 27 Vdc
Refresh frequency is the same of the sample
frequency of the connected sensor
Protected against persistent over voltages to
maximum 30 Vdc
110_EN_LC_5_3_6X.doc
HML 110
DISPLAY FLAGS AND LED WARNING INTERPRETATION
At ‘Power on’ of the converter, the user will see the following display screen. In the top right
hand corner there may be a range of symbols. The symbols can be interpreted from the table
below. Interpretation of the flashing LED can be made from the LED Interpretation table at the
bottom of this page
FLAGS
FLAG INTERPRETATION
FLAG DESCRIPTION
M Alarm max activated
m Alarm min activated
C Calibration running
S Simulation
- Interruption coils circuit
!
- Segnal error
- Empty pipe
Pulse output saturation (reduce
TIME PULSE )
LED
PERMANENT LIGHT: initialisation
FLASHING LIGHT ( 1 sec.): normal function
FLASHING LIGHT (<1 SEC.): alarm on
The LED signals the alarm status only if the display shows one of the
suitable visualisation screens as shown on page 14
LED INTERPRETATION
12
110_EN_LC_5_3_6X.doc
HML 110
ACCESS TO THE CONVERTER KEYPAD
M3
KEYBOARD
The keypad is accessible by loosening the 4 cover screws,
and opening the front cover of the converter. Three KEYS
are set aside of the M1 terminal block allowing the user to
change screen display visualizations and select functions.
Key pad function
SHORT PRESSING (< 1 SECOND):
Increases the numeric figure or the parameter selected by the cursor
Accesses the previous subject when in the Quick start or Main menus
Batch start/stop (when enabled)
LONG PRESSING (> 1 SECOND):
Decreases the numeric figure or the parameter selected by the cursor
Accesses the next subject in the Quick start or Main menus
SHORT PRESSING (< 1 SECOND):
Moves the cursor rightwards on the input field
Accesses to the following subject in the Quick start or Main menus
Changes the display of the process data
LONG PRESSING (> 1 SECOND):
Moves the cursor leftwards on the input field
Accesses the previous subject in the Quick start or Main menus
SHORT PRESSING (< 1 SECOND):
Enters/leaves the selected function
Enables the main menu for the converter configuration
Cancels the selected function under progress
LONG PRESSING (> 1 SECOND):
Leaves the current function, in the Quick start or Main menus.
Enables the ‘EXECUTE?’ prompt in the Main menu functions, and total reset
request (when enabled) from the required function
Confirms the selected function
Blind converters
For converters without a keyboard (blind version),
functions are programmed utilizing the IF2 device:
13
110_EN_LC_5_3_6X.doc
A
A
A
A
y
HML 110
ACCESSING THE CONVERT FUNCTIONS AT START-UP (Power On)
Example of visualized display pages at start-up
ctive scale
larm on
Flow rate visualization
The direct exposure of the converter to the solar rays, could damage
the liquid crystals display.
Note: The user will see the
screen displayed (left) at
power on of the converter.
Use the keys on the keypad
as indicated centrally on
this page to move
between the screens
shown (not all shown).
* Direct/Reverse totalizer
visualization
lternate visualization
Push keypad button
indicated to move
between pages
CURRENCY FUNTION ENABLE
* Direct totalizer
Reverse totalizer
Currency value
If the user dwells on this screen the converter
will automatically scr oll through the rest o f the
initial visualizatio n pages. If the user presses t h e
lower key on the keypad they will access the
Quick start menu . Pressing the middle key will
move to the next initial visu alization screen.
Flow rate visualization Flow rate visualization
Push keypad button
indicated to move
between pages
* Direct Reverse totalizer Flow speed
larm description
Push keypad button
indicated to view the
Flow rate Alarm
Sampling frequenc
* The maximum number shown on the totalizer is 999999999 regardless of the number of user selected
decimals (see page 19 Pos 2.3) . Beyond this value the totalizers are reset to zero.
Note: if the converter is not connected to the
sensor then an ‘Excitation Fail’ will be shown
14
110_EN_LC_5_3_6X.doc
FLOW RATE VISUALIZATION
The ML110 allow showing 5 digit character display for flow rate units. This mean
the maximum flow rate value that can be represent on the display i s 19999* (no
matter the positioning of the decimal point ) and the minimum is 0.025.
The converter’s calculation are based on the following formula :
- DN x DN x 0,008
The results of above calc ulat io n give th e m aximum f low rat e at 10 m/s of speed
according to sensor’s diameter; the permitted units for the display are the unit
measure that, in reference to this calculated value, do not exceed the number
19999 ( higher limit ) and 0,25 ( lower limit )
Example for DN 100 :
- Full scale value : 100 x 100 x 0,008 = 80 l/s
- PERMITTED unit of measure ( example ) : l/s ( 80.00 ) ; mc/h ( 288.0 ) …
- NOT PERMITTED unit of measure ( example ) : cm3/s ( 0,08 ) ….
The not permitted example has a unit of measure greater than 5 character digits in
length including the ‘/’, cm3/s.
HML 110
15
110_EN_LC_5_3_6X.doc
CONVERTER FUNCTION SETTING ACCESS CODES
Factory preset access
The converter is delivered with the default
L2 (level 2) access code. The code if
required for accessing ‘Main menu’
functions from the ‘Quick start menu’.
11111
The first level configuration "Quick start
menu" can be automatically a cces sed with
out the access code by pressing the key
from one of the visualization pages at start
up (power on) of the converter. See page
14 to see the screens from which the Quick
start menu can be accessed
User defined acces s codes
Functions in the converter’s ‘Main menu’ are
enabled by the a ccess codes. The
information of this manual is related to all the
functions available with in the L2 level. All
higher level functions are reserved for
servicing and not available.
Description of the L2 access code
(menu “11 Internal data” pos. 11.1, see page
21)
with code L2 = 00000 (with this code
only) you can disable the request of code
L2
*with L2 customized (freely chosen by
the user) you can program all the
functions up to L2 security level, entering
this code whenever you enter the Main
menu.
*ATTENTION: take careful note of the
customized code you have ch osen, t here is no
way for the user to retrieve or reset it if lost.
ACCESS TO THE CONFIGURATION MENUES
The converter’s configuration menus can be acce ssed in two different modes:
Through the “Quick start menu” it is possible to access directly a
range of principal functions for setting the scale reading and display
characteristics of the sensor (see function explanations pages 18-19)
Through the “Main menu” it is possible to access functions with an
access code ≤ 2, which control more of the sensor’s monitoring, data
processing and output, as well further disp lay options.
The following example (page 17) illustrates how to change some of the values
in the Fs1 display field of the Quick Start menu. The second example (page 18)
illustrates how to change a function parameter in the ‘Main menu’.
HML 110
16
110_EN_LC_5_3_6X.doc
HML 110
EXAMPLE: “Quick start menu” function modification. Full scale value 1 (Fs1)
from 4dm³/s to 5dm³/s.
Enter in the “Quick start menu”
The keypad button to be pressed at
each step is indicated by the icon
symbol place on one of the three
keys of the keypad (here lower key)
Access the function “Fs1” by
pressing the button indicated for less
than 1 second
Push the key repeatedly and rapidly
to move the cursor to the value to
modify
To increase the value press
the upper key for short
periods of less than 1 second,
to reduce the value press t h e
upper key for more than 1
second repeatedly
Confirm the new value with a
short press of the key (less
than 1 second)
Long push to leave the quick
start menu and return to the
initial visualizati on page
Initial visualizat io n page
17
110_EN_LC_5_3_6X.doc
HML 110
EXAMPLE: “Main menu” function modification. Full scale value 1 (Fs1) from
4dm³/s to 5dm³/s. (Quick start menu enabled)
Enter in the “Quick start menu”
From any of the start-up
(power on) screens
Press the button indicated
to enter the Main menu
page screen from the Quick
menu page
Access to the “Main Menu”
by pressing the key
indicated
To enter the main menu
input the key code (11111
as default) by increasing
the ‘0’ to ‘1’ and moving to
the next ‘0’ until the key
code is entered
To enter the key code press
the lower key
To move between main
menu function groups press
the arrow key indicated
Access the “Scale” menu
with a short key press.
Access the function “Fs1”
with a short key press
Move between the
modifiable options by short
pressing the key indicated
on the key pad
Change the value by pushing
the button rapidly as many
times as required
Confirm the new value with
a short press of the key
indicated on the keypad
Long push to return to
the main menu groups
Initialization page
Long push to return to
the initialization pag es
18
110_EN_LC_5_3_6X.doc
HML 110
MAIN MENU GROUPS AND FUNCTION DESCRIPTIONS.
The main menu is selected from the Quick Start Menu by pressing the key) and entering the factory
code(11111). Functions denoted in grey are displayed only with other acti ve functions, or with optional
modules.
displayed on the converter are shown below are reserved for serving purposes only and not configurable.
(for details of the func tions with the symbol “*” refer to pages 22-27) .
Not all the functions
1.1 Nominal Diameter (ND) of sensor, (enter input value 0-3000 mm )
1.2 Sensor calibration data (En ter value as specified on sensor label)
1.3 Type of sensor: Enter the first two characters of the sensor serial number
1.4 Position of insertion sensor: 0=1/8DN, 1=1/2DN, 2=7/8DN
1.5 Factory parameters
1.6 Enables the empty pipe detection featu re
1.7 Value of empty pipe sensibility detection
1.8 Enables the automatic calibration procedure of zero calibration
2.1* Full scale value set for range N.1 (function info & modification pa ge 22)
2.2* Full scale value set for range N.2
2.3* Unit of measure and number of decimal place (Info & modification page 23)
2.4* Pulse value on channel 1 (Function Info & modification page 23)
2.5* Pulse value on channel 2 (Function Info & modification page 23)
2.6* Duration of the pulse generated on channe l 1 (Info & mo di fic ation page 23)
2.7* Duration of the pulse generated on channel 2 (Info & modification page 23)
2.8 Full scale frequency for channel 1 (0.1Hz-1000.0H z)
2.9 Full scale frequency for channel 2 (0.1Hz-1000.0H z)
3.1* Time constant (function info & modification page 23)
3.2* Acceleration threshold (function info & modification page 23)
3.3* Anomalous signal peak cut off threshold (Info & modification page 24)
3.4 Low flow zero threshold: 0-25% of full scale value
3.5 Filter on the power supply: 0.1s="ready" measure; 0.5s=filter of noise on the liquid
8.10*Partial reverse (negative) flow totalise res et (in fo & modifi cat ion page 27)
8.11 Visualizes the values of the partial totalise in the unit of selected cu rrency
8.12 Choice of the numbers of decimals for the visualization currency value: From 0 to 3
8.13*Value of conversion/currency for direct totalizer (info & modification page 27)
8.14*Value of conversion/currency for reverse totalizer (info & modificati on page 27)
20
110_EN_LC_5_3_6X.doc
HML 110
10.1* Calibration of the converter (single occurrence each time function is selected)
10.2* Converter auto test (single occurrence each time function is selected)
10.3* Flow rate simulation enabling
11.1 Level 2 access code enter (user choice and setting of access code if required)
11.2 Load factory data pre-set
11.3 Load user data saved
11.4 Save user data
11.5 Visualisation of the total operation hours of the converte r ( func ti on no t ed it abl e)
11.6 Ignore the calibration error during th e switch on test (ena bl e/di sable)
11.7 KS Coefficient
21
110_EN_LC_5_3_6X.doc
R
HML 110
MAIN MENU FUNCTION PRGRAMMING
(description of the functions with access code< 3)
MENU 1 - SENSO
(POS. 1) Nominal diameter of sensor [ND= XXXX]
The following pages give a description of the most important functions and how they can be changed or
enabled/disabled by the user.
MENU 1 - SENSOR
(POS. 1.7) “Autozero” calibration [Autozero cal.]
This function allow to zeroing the meter . To perform the zero calibration, it is necessary for t he
sensor to be full of liquid, and the liquid be perfectly still.
Even very small movement of the liquid may affect the result, and, c onsequently, the acc uracy of the
system.
Once you are sure the above conditions have been fulfilled (and the percentage flow rate value is
stable) press the key for one second or more. Check the percentage flow rate value goes to zero.
If this does not occur repeat the o peration again . When the value is stable at zero, then press the
key.
(POS. 1.7) “Empty pipe” threshold [E.P. thr.]
Value of empty pipe threshold detection. The span of this function is 0-255.
Since the sensibility of empty pipe detection could be change by the liquid conductivity, ground
connections, type of lining, in case of needed it’s possible to adjust manually the preset threshold.
It’s recommended to check periodically its proper functioning.
Increasing of value means decreasing the sensibility.
MENU 2 - SCALES
(POS. 2.1-2.2) Full scale N. 1-2 [Fs1-2=dm³/s X.XXXX]
The Full scale range N.1.-2 is the corresponding output signal (20mA) to the meters maximum flow
rate (max 10m/s). There are four fields to fill in order to set this parameter, from left to right: 1)
volume unit of measure, 2) type of unit, 3 ) time unit of measure and 4) numeric value. The select ion
is made by positioning the cursor on the field to modify. To change the type of unit of measure
(metric, British or American, mass or volume) the cursor has to be positioned on the symbol “/” ( field
N. 2). When the nominal diameter is set to zero it is possible to modify only the n umeric field, since
the unit of measure stays at m/sec.
The following tables show the units of measure available and the conversion factor by comparison
with 1 dm3 and 1 kg. The converter accepts any kind of combination of uni ts of measure satisfying
both the following conditions:
Numeric field value ≤ 9999
1
/25 fs
≤ numeric field value ≤ fs
max
max
.
where fsmax is the maximum full scale value corresponding to the sens or, equal to a 10 m/ sec liquid
speed. The units of measure are shown as appear on the display. The British and American units are
diversified by using capital and small characters.
Identification of the function (not visualized on display)
Converter request
Menu visualized on the convert er ( from 1 to 11)
Synthetic description of the function
22
110_EN_LC_5_3_6X.doc
cm3 Cubic centimeter
Ml Milliliter
L Liter
dm3 Cubic decimeter
Dal Decalitre
Hl Hectolitre
m3 Cubic meter
in3 Cubic inch
Gal American gallon
GAL British gallon
ft3 Cubic foot
Bbl Standard barrel
BBL Oil barrel
yd3 Cubic yard
kgl KAmerican gallon
KGL KBritish gallon
Oz Ounce
Lb Pound
Ton Short tons
G Gram
Kg Kilogram
T Ton
When a mass unit of measure is set, the specific gravity function is automatica lly enabled by the
system. Please, note that the mass measure is heavily affected by the temperature. With certain
liquids this may cause significant measurement errors. The following measure of time units can be
selected: s = second, m = minute, h = hour, d = day.
(POS. 2.3) Unit of measure and number of decimal places [Tot.MU=dm³ X.XXX]
Setting the unit of measure and number of decimals places dis pla ye d for the vol umes. To se t the uni t
of measure, position the cursor on field of the unit of measure. To s et the type of unit, position the
cursor on the blank space between the unit of measure and the numeric value; The number of
decimal places can be selected by placing the cursor on numeric field and choosing one of the
possible combinations: 1000-01.00-001.0-00001.
(POS. 2.4-2.5) Pulse value channel 1-2 and unit of total measure. [Pls1-2=dm³ X.XXXXX]
Setting of a flow volume by which a corresponding pulse wil l be emitted on channel 1-2. (units mus t
be identical to ‘Full scale’(POS 2.1 and 8) and ‘Totalizer’ functions. To set the parameter, complete the
three fields, from left to right: 1) unit of measure , 2) unit type and 3) numeric value. The selection is
performed by positioning the cursor in the field to be modified. To change the unit type (metric,
British or American, mass or volume) position the cursor on the blank space betw een the measure
unit and the numeric value. When the nom inal diam eter is s e t to z ero it is pos sible to modify only the
numeric field since the measure unit stays a t meters(m) or feet(ft) . Only t hose units des cribed above
are available to be selected. This function is active only if the pulse emission on channel 1 is enabled.
Setting of the duration of the pulse generated on channel 1-2 as set in (POS 2.4-2.5). This value is
expressed in milliseconds and has to be between 0,4 and 9999,99. When the high frequency output is
present, then the minimum value can be set to a minimum of 0,04 milliseconds. ATTENTION: since
the converter cannot detect which type of device is connected to the converter, the user must verify
that the set pulse duration is compatible with the external device processing such pulses. If, for
example, an electro-mechanical pulse counter is c onnected, one of tw o problems may oc cur; firs t ly, i f
the pulse is too long the coils may burn out, secondly, if the pulse is too short, the c ounter may not
be able to function, with the possibility of causing damage of the output.
MENU 3 - MEASURE
(POS. 3.1) Time constant [Tconst=s XXXX.X]
This parameter affects the integrating filter, setting a quicker or s lower response time, according to
the value set. A higher value corresponds to a more stable but slower measure, a smaller gives and
faster measure but is more unstable. The most common values are f rom 1 to 5 sec onds. The value of
this parameter has to be within the range fr om 0 (integral filter disabled) to 6000.0 seconds. The
following diagram shows the response of the instrument for a flow rate variation from 0 to 100%
within the T time constant period.
Acceleration threshold set. The acceleration threshold is the lim it beyond which a flow rate variation
gives an immediate response at the output, withou t being filtered b y the time constant . This func tion
allows the converter to have an immediate response in cases of big flow rate variations, while filtering
(and delaying) the response to small variations, resulting in a very s table measure. The set valu e is a
percentage of the full scale value (from 0 to 125%). If such a value is set to zero any flow rate
variation bigger than 0.5% of the full scale value will immediately activate an output response. The
following graphs show the instrument response in two cases: Firstly, a flow rate variation from 0 to
10% completely absorbed by the time constant effect
HML 110
23
110_EN_LC_5_3_6X.doc
HML 110
Secondly a variation form 10% to 100%, exceeding the acceleration threshold and then immedia tely
sent to the output. In reality there is always a minimum time between the measure acquisition and
the outputs update.
(POS. 3.3) Peak cut off threshold [Peak thr=% XXX]
Anomalous signal peak cut off threshold set. This parameter al lows for setti ng the maximum va lue of
deviation of the measured sample in comparison to the average. If a successive value is higher than
the set limit, than such a value is “cut” to the limiting value. This function is used to make the meter
less sensitive to big perturbations of the flow rate measure. This may happen when there are solids
suspended in the liquid in contact with the electrodes resulting in higher electrical noise. The
permitted values of this function range from 0 to 125 % in reference to the full scale value. I f this
parameter is set to zero the peak detection function is disabled and any subsequent measured sample
will be accepted and processed by the converter.
Enables/disables the automatic change of scale. The meter may have two different w orking ranges in
order to suit variable process conditions. In order to get the best results out of this function it is
important that range N.2 is greater than N.1. When the flow rate increases and reaches the 100% of
the scale N.1, the meter automatically switches to scale N.2. When the flow rate subsequently
decreases to an equivalent value on scale N.2 (equal to the 9 0% of full scale N.1), scale N.1 will
assume the active scale. Allowed values for this parameter: ON / OFF.
(POS. 3.8) Energy saving enable [E.saving=ON/OFF]
Automatic energy saving function enables. This funct ion is us ed whe n the instr ument is powered by a
battery or solar cells, allowing an energy saving up the 6 0-80%. The energy saving function contr ols
the powering cycles ratio of the coils while the measuring cycling remain unaffected. When the
energy saving function is enabled and the flow rate is stable the number of “off” cycles is greater
than the “on” cycles, reducing the average power consumption. If the flow rate suddenly changes,
the meter switches to a higher number of measuring cycles, achieving a higher respons e time. Once
the flow rate resumes stability the number of powering cycles is reduced. If the flow rate varies below
the “acceleration threshold” percentage value, th e meter assumes the “off” cycles. When the flow
rate exceeds such a threshold, the meter incr eases the measuring cycles. The speed at which the
meter will switch between the increased and reduced powering cycles are different. From a constant
to a variable flow rate is a very fast process, while from variable to a stable flow rate is much slower.
The allowed values for this parameter: ON/OFF. N.B.: to optimize this function, a value for the
acceleration threshold between 10 – 15 is recommended
MENU 4 - ALARMS
(POS. 4.5) Current output value in case of failure [mA v.fault =% XXX]
Setting of the value of the 0/4...20 mA current output in one or more of the following cas es; empty
pipe , ADC error, and coils interrupted.
The permitted range is from 0 to 120% of the 0 - 20 mA scales, 120% corresponds to 24 mA and
does not depend on the selected range (0…20 / 4…20 mA).
24
110_EN_LC_5_3_6X.doc
The NAMUR NE43 recommendations requires alarms signaling value for a current output lower than
HML 110
3.6 mA (<18%) or greater than 21 mA (>105%). It is preferable to set the val ue of this function at
10%, so that the current value in cases of a.m. would be 2 mA, allowing the following diagnostics:
current < 2 mA - 5%: line interrupted, power supply failure or faulty converter;
2 mA -5% ≤ current ≤ 2 mA + 5%: hardware alarm;
4 mA ≤ current ≤ 20 mA: normal working range;
20 mA < current ≤ 22 mA: out of range, measure above 100% full scale (f.s.).
(POS. 4.6) Frequency output value in case of failure [Hz v.fault=% XXX]
To set the frequency value assigned to the on/off output in one or more of the following cases:
Empty pipe; Coils interrupted ; ADC error
Allowable range from 0 to 125% of the frequency full scale value.
Although there are no specific rules regulating cases such as these, i t would be c onvenien t to use t he
failure information as follows:
0% Hz ≤ frequency ≤ 100% f.s.: normal working range;
100% f.s. < frequency ≤ 110% f.s.: overflow, measure above the 100% of the f.s.;
115% f.s. ≤ frequency ≤ 125% f.s.: hardware alarm condition.
When this function is active, the totalizers may be reset applying a voltage on the on/off input or
from keyboard.
(POS.5.7) Autozero” calibration external command enable [Calibration=ON/OFF]
This function enables/disables the automatic z ero calibration system. When this function is active,
applying a voltage on the meter’s on/off input terminals performs an autozero calibration cycle.
ATTENTION: if the voltage pulse is less 1 sec., the meter performs an Auto calibration cycle to
compensate for possible thermal drifts. If the voltage pulse is more 1 sec, the meter performs a
Autozero calibration of measure.
MENU 6 - OUTPUTS
(POS. 6.1) Choice of the function corresponding to on/off output 1 [Out1=XXXXXX]
Function choice corresponding to digital Output 1. The functions are listed in the table below.
(POS. 6.2) Choice of the function corresponding to on/off output 2 [Out2=XXXXXX]
Function choice corresponding to digital Output 2. The functions are listed in the table below.
OFF: DISABLED
#1PULS+: PULSE ON CHANNEL 1 FOR POSITIVE FLOW RATE
#1PULS-: PULSE ON CHANNEL 1 FOR NEGATIVE FLOW RATE
#1PULS±: PULSE ON CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE
#2PULS+: PULSE ON CHANNEL 2 FOR POSITIVE FLOW RATE
#2PULS-: PULSE ON CHANNEL 2 FOR NEGATIVE FLOW RATE
#2PULS±: PULSE ON CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE
#1FREQ+: FREQUENCY CHANNEL 1 FOR POSITIVE FLOW RATE
#1FREQ-: FREQUENCY CHANNEL 1 FOR NEGATIVE FLOW RATE
#1FREQ±: FREQUENCY CHANNEL 1 FOR P OSITIVE AND NEGATIVE FLOW RATE
#2FREQ+: FREQUENCY CHANNEL 2 FOR POSITIVE FLOW RATE
#2FREQ-: FREQUENCY CHANNEL 2 FOR NEGATIVE FLOW RATE
#2FREQ±: FREQUENCY CHANNEL 2 FOR P OSITIVE AND NEGATIVE FLOW RATE
SIGN: FLOW DIRECT ION OUTPUT (ENERGISED = -)
RANGE: RANGE INDICATION OUTPUT (ENERGISED = SCALE 2)
MAX AL: MAX FLOW RATE OUTPUT(ENERGISED = AL. OFF)
MIN AL: MIN FLOW RATE OUTPUT(ENERGISED = AL. OFF)
MAX+MIN: MAX AND MIN FLOW RATE ALARM OUTPUT (ENERGISED = AL. OFF)
EMPTY PIPE: EMPTY PIPE ALARM OUTPUT (ENERGISED = FULL PIPE)
OVERFLOW.: OUT OF RANGE ALARM OUTPUT (ENERGISED = FLOW RATE OK)
HW ALARM: CUMULATIVE ALARM OUT interrupt coils, empty pipe, measure error (ENERGISED=NO ALARMS)
FUNCTION FOR OUTPUT 1, 2.
25
110_EN_LC_5_3_6X.doc
(POS. 6.3) Duty cycle value for pulses/frequency output [Duty cycle=% XX]
HML 110
The duty cycle function defines t he time ratio between ON and O FF state when frequency output is
used: 50% means that the ON phase will equal that of the OFF phase, 60% means that the ON phase
will be 60 % and the OFF phase will be 40% of the total cycle time. When the pulse outputs are used,
the duty cycle defines the OFF phase, this is because the ON phase is already set with the "PULSE
DURATION" function ( see Main menu “2 - SCALE” ). In this case, for example, the duty cycle is set at
50% and the pulse duration at 50ms, the OFF phase w ill be the same of th e ON phase. The formula
to calculate the minimum time of the OFF phase and the time of total cycle is the following:
T. total cycle= 100 x (pulse duration in ms)/ (duty cycle)
T. OFF phase = T. total cycle - pulse duration
N.B.: When using the function in frequency mode, DO NOT set the duty cycle to 0. If the value of the
function is set to 0 the emission of the pulses occ urs in synchronous mode with the flow rate. The
function is active only if one of the outputs is set on pulse and/or frequency function.
(POS. 6.4) Current output option and range [Out mA=X_XX±XXX]
This function sets the current output N .1. This function is optional and will not appear unless the
option has been requested.There are three fields to modify for this function:
• Scale zero: 4 or 0 mA
• Full scale: 20 or 22 mA
• Field: + = positive, - = negative, ± = both, -0+ = central zero scale
The values corresponding to the scale points are shown in the following chart:
CURRENT VALUES IN mA ASSOCIATE TO THE % VALUE OF FULL SCALE
REVERSE FLOW VA L UE ZERO DIRECT FLOW VALUE
≤ -110%
-100% 0% +100%
≥+110%
In hardware alarm conditions “HW ALARM” (interrupted coils, empty pipe, measure error) the current
value is programmed by the function “mA v.fault” (pos. 4 .5) and it is expressed as percentage of a
fixed current range, where: 0% = 0 mA and 110% = 22 mA.
Enable this function to modify the totalizer. From visualization pages, proceed in the following mode:
1) Push the key , Set the L2 CODE if required (otherwise go to step 2) and then push the key
2) Positioning by the key to modify the numerical value push the key to access and then to
confirm the modified value
3) Positioning the cursor on “RESET TOTALIZ.?” Push the key and then the key to confirm
or any other key to cancel this operation.
With the function 8.5 disabled it’s possible reset the totalizer by pushing the key from
visualization page, at the required “RESET TOTALIZ.?” Push the key and then the key to
confirm or any other key to cancel this operation
(POS. 8.7-8.8-8.9-8.10) Total/Partial – totalizer reset enable [T/P/-/+ reset]
Activates the reset of Total and partial flow totalizer.
Functions 8.7-8.8-8.9-8.10 are activated by pressing the key during the visualization of the
function itself. When " EXE CUTE?" is required, press the key to proceed. Press any other key to
delete the operation
N.B.: The PARTIAL totalizers reset can also be achieved in the following way:
From one of the visualization page press the key .
Set the L2 code and press the key . The following prompt will be visualized: "EXECUTE?"
Press the key to proceed . Press any other key to delete the operation.
(POS. 8.13-8.14) Conversion factor for direct flow rate totalizers [EUR/dm³+/- =X]
Setting of the conversion/currency value for direct flow to talizers (positive). There are three setting
fields for this parameter, from le ft to right: 1) monetary symbol, 2 ) default/personalized monetary
symbol, 3 ) conversion coefficient. To select, s et the cursor over the field to be modified. Sett ing the
monetary symbol can be achieved in two ways:
1. Choosing one of the 7 predetermined monetary symbols (standard ISO 4217REV81):EUR=Euro; USD=USA dollar; CAD=Canadian dollar; AUD=Australian dollar;
GPB=English pound; CHF=Swissfranc; JPY=Japanese yen.
2. Entering a three character (numbers or letters) personalized currency. To change the
characters, the cursor must be set on the symbol “/” (second field)
MENU 10 - DIAGNOST IC
(POS. 10.1) Meter “calibration” [Calibration]
Enables the calibration function of the meter. The activati on of this function happens by pressing the
key during the visualization of the function. The following question will be visualized: "
EXECUTE?". Press the key to proceed . Press any other key to delete the operation.
(POS. 10.2) “Self test” function [Self test]
Meter auto test function. This function stops the normal functions of the meter and performs a
complete test cycle on the measuring input circuits and the excitation generator. To activate this
function, selecting it, by pressing the key , at the prompt: “EXECUTE?” press the key to start
the test, any other key will delete the operation. The result of the tes t is shown on the dis play, the
display will return to one of the visualiz ation pages at the test end. The function is automatically
performed when the device is switched on. For any errors see page 28 for corrective actions.
Flow rate simulation enabling. This function a llows for the possible generation of an internal s ignal
that simulates the flow rate, allowing the outputs and all the connected instruments to be tested.
After enabling it, the flow rate simulation can be:
- set: by pushing the key from one of the four visualization pages
- started: by pushing the key after setting it
- finished: by pushing the key from the visualization pages and then by pushing the key .
(see page 12 for description of key symbols)
27
110_EN_LC_5_3_6X.doc
HML 110
ALARMMESSAGES,CAUSESANDCORRECTIVEACTIONS
Messages ANOMALIES ACTION TO TAKE
NO ALARMS All works regularly -----
MAX ALARM The flow rate is higher than the maximum threshold set
MIN ALARM The flow rate is lower than the minimum threshold set
FLOW RATE >FS
PULSE/FREQ>FS
EMPTY PIPE
INPUT NOISY
EXCITATION
FAIL
CURR. LOOP
OPEN
P.SUPPLY FAIL Power supply different from that indicated on the label.
The flow rate is higher than th e f u ll scale v alue set on the
instrument
The pulse generation output of the device is saturated and
cannot generate the sufficient number of impulses
The measuring pipe is empty or the detection system has not
been properly calibrated
The measure is strongly effect ed by external noise or the
connecting cable from converter to the sensor may be broken
The coils or the cable connecting the sensor are interrupted Check the connect in g cables to the sensor
The 0/4...20mA output on board or the optional one are not
correctly closed on a v a lid load
Check the maximum flow rate threshold set and
the process condition s
Check the minimum flow rate threshold set and
the process condition s
Check the full scale value set on the instrument
and the process conditions
Set a bigger unit of vo lu m e o r , if the connected
counting device allows it, reduce the pulse
duration value
Check whether the pipe is empt y , or rep eat t he
empty pipe calibration procedure
Check the status of the cables connecting t h e
sensor, the grounding connections of the devices
or the possible presence of nois e sou r ces
Verify the load is applied to the output (max 1000
ohm).
To disable the alarm, set the “mA VAL.FAULT”
value ( menu alarm ) to 0.
Verify that the power supply is as indicated on the
label
ANOMOLY CODES
CODES ANOMALIE DESCRIPTIONS ACTION TO TAKE
0001 problem with watch-dog circu i t
0002 wrong configuration work data in eeprom
0004 wrong configuration safety data in eeprom
0008 defective eeprom
defective keyboard (one or more key are pushed
0010
during the test)
0020 Power supply voltage (+3.3) is out of range
0040 Power supply voltage (+13) is too low (<10V)
0080 Power supply voltage (+13) it’s too high (>14V)
0200 timeout calibration input (input circuit is broken)
0400 Input stage gaining is out of range
0800 Interruption on the coils circuit
0C00 Cumulative alarm 0800 + 0400
ADDRESS TO SERVICE
Check the status of the cables connecting the sensor to the
converter, the grounding connections or the possible presence of
strong and anomalous noise sources
Check the status of the cables connecting the sensor to the
converter
see single code
28
110_EN_LC_5_3_6X.doc
it declares under the own responsibility that the product:
MS 500 – MS 501 – MS 600 – MS 1000 – MS 2410- MS 2500 – MS
3700 MS 3770 – MS 5000
to which this declaration refers, is in compliance with the following
Harmonized European Norms:
CEI EN 61010-1(2001)
CEI EN 61326-1 (2007)
and therefore answering to essential requirement of CE directives: