Precision Cooling
For Business-Critical Continuity™
Liebert® XDP™ with Liebert® iCOM® Control
User Manual–50-60 Hz; 160kW Nominal Capacity
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER 1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1 General Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1.1 Product/System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.1.2 Minimum Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Equipment Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.1 Handling the Liebert XDP While it is on Skid and Packaged . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3.2 Unpacking the Liebert XDP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3.3 Removing the Unit from the Skid Using a Forklift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3.4 Removing the Unit from the Skid using Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.3.5 Moving the Liebert XDP Using Piano Jacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.3.6 Removing the Unit from the Piano Jacks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1 Positioning the Liebert XDP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2.1 Connecting High-Voltage Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2.2 Extra Low Voltage (ELV) Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.2.3 DIP Switch and Jumper Settings for Remote Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3 Field Connections—Optional for All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.4 Remote Sensor Installation—Proper Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.0 PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.1 European Union Fluorinated Greenhouse Gas Requirements . . . . . . . . . . . . . . . . . . . . . . . 18
3.2 Connection Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.2.1 Recommended Pipe Size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3 Liebert XDP Interconnection with Liebert XD Cooling Modules . . . . . . . . . . . . . . . . . . . . . 19
3.4 Piping Installation Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4.1 Piping Installation—R-134a Pumped Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 3.4.2 Piping Mains. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.4.3 Bypass Flow Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5 Piping Details—Shutoff/Isolation Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5.1 Evacuation and Leak Check—R-134a Pumped Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3.5.2 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.6 Filling the Pumped Circuit—R-134a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.6.1 Calculating Refrigerant Charge—Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.7 Checklist for Proper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.0 LIEBERT ICOM CONTROL—FIRMWARE VERSION XP1.00.010.STD. . . . . . . . . . . . . . . . . .26
4.1 Liebert iCOM Components and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 4.2 Display Lamp Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
i
4.3 Navigating Through the Liebert iCOM Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3.1 Accessing Menus and Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 4.3.2 Cooling Module Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 4.3.3 Entering the Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.4 Changing Liebert iCOM’s Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 4.5 Changing Operational Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 4.6 Graphical Data Record. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.7 Liebert iCOM User Menu Icons and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.8 Liebert iCOM User Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 4.9 Liebert iCOM Service Menu Icons and Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4.10 Liebert iCOM Service Menu Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.0 START THE LIEBERT XDP WITH LIEBERT ICOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
5.1 Checklist for Liebert XDP Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 5.2 Starting the Liebert XDP with Liebert iCOM Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.0 ALARM DESCRIPTIONS AND SOLUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
6.1 Alarm Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 6.2 Warning Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 6.3 System Shutdown Causes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
7.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69 8.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
8.1 Fluorinated Greenhouse Gas Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
9.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
COMPLIANCE WITH EUROPEAN UNION DIRECTIVES. . . . . . . . . . . . . . . . . . . . . . INSIDE BACK COVER
ii
FIGURES
Figure 1 Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Figure 2 Liebert XDP components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 3 Unpacking the Liebert XDP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 4 Use a forklift to remove the Liebert XDP from the skid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 5 Removing the unit from the skid using rigging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 6 Securing the Liebert XDP to piano jacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Figure 7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Figure 8 Piping access points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Figure 9 Front view of Liebert XDP and electrical enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 10 Electrical enclosure knockout location for hazardous voltage wiring . . . . . . . . . . . . . . . . . . . . . . 12 Figure 11 High voltage connections—60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Figure 12 High voltage connections—50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 13 Electrical enclosure knockout locations for Extra Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 14 Connecting the remote temperature/humidity sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 15 DIP switch and jumper settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 16 Unit-to-unit networking connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 17 Liebert XDP extra low voltage field connections points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Figure 18 Suggested remote sensor placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Figure 19 Liebert XD system diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 20 Bypass flow controller details, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 21 Bypass flow controller arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 22 Bypass flow controller piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 23 General piping details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure 24 Liebert iCOM display components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Figure 25 Liebert iCOM default home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Figure 26 Cooling module overview, first 10 modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Figure 27 Entering the password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Figure 28 Display setup screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Figure 29 Liebert iCOM User Menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Figure 30 Liebert XDP User Menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Figure 31 Setpoints screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Figure 32 Set Alarms screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Figure 33 Sensor Data screen, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Figure 34 Sensor Data screen, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Figure 35 Display Setup screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Figure 36 Module Status screen, page 1 of 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Figure 37 Liebert XDV Smart Module Status screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Figure 38 Liebert XDH Smart Module Status screen—each bank shown separately . . . . . . . . . . . . . . . . . . 40 Figure 39 Liebert XDO Smart Module Status screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Figure 40 Total Run Hours screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Figure 41 Liebert iCOM Service Menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Figure 42 Liebert XDP Service Menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Figure 43 Setpoints screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Figure 44 Maintenance—Basic Settings screen, page 1 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Figure 47 Maintenance screens, pages 4 through 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Figure 48 Diagnostics/Service Mode screen, page 1 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 49 Diagnostics/Service Mode screen, page 2 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
iii
Figure 50 Diagnostics/Service Mode screen, page 3 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Figure 51 Diagnostics/Service Mode screen, page 4 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Figure 52 Diagnostics/Service Mode screen, page 5 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 53 Diagnostics/Service Mode screen, page 6 of 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 54 Set Alarms screen, page 1 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Figure 55 Set Alarms screen, page 2 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Figure 56 Set Alarms screen, page 3 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Figure 57 Set Alarms screen, page 4 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 58 Set Alarms screens, pages 5 and 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Figure 59 Set Alarms screen, page 7 of 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Figure 60 Sensor Calibration/Setup screen, page 1 of 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Figure 61 Sensor Calibration/Setup screen, page 2 of 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Figure 62 Sensor Calibration/Setup screen, page 3 of 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Figure 63 System/Network Setup screen—System, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Figure 64 System/Network Setup screen—System, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Figure 65 System/Network Setup screen—Unit, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Figure 66 System/Network Setup screen—Unit, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Figure 67 Options Setup screen, page 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Figure 68 Options Setup screen, page 2 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Figure 69 Module Setup screen, page 1 of 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Figure 70 Module Setup screen, page 1 of 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Figure 71 System R-134a liquid level at 160kW load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
TABLES
Table 1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H)
load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Table 2 Liebert XDP dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Table 3 Unit piping outlet connection sizes, inches, OD Cu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Table 4 Supply, return pipe sizes for refrigerant loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Table 5 Bypass flow controllers for a Liebert XDP-based system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/
Liebert XDV/Liebert XDCF/Liebert XDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Table 7 System refrigerant charge for the supply and return mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 9 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 10 Calculating refrigerant charge—example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 11 Worksheet to calculate refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 12 Keyboard icons and functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Table 13 Liebert XDP pump light indicator—208V and 400V units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Table 14 Troubleshooting the Liebert XDP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Table 15 Liebert XDP160 specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
iv
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert XDP. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
! WARNING
Risk of arc flash and electric shock. Can cause property damage, injury or death.
Disconnect all local and remote electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM control.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
! WARNING
Risk of unit falling over. Can cause property damage, injury or death.
The XDP is top-heavy. Use extreme caution and care when moving and installing this unit.
! CAUTION
Risk of piping and component rupture. Can cause injury or equipment damage.
System is pressurized. Relieve pressure through access valve before working on unit.Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves. System is pressurized. Relieve pressure through access valve before working on unit
NOTE
This document is intended to be used together with site specific documentation and
documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE
Before any action that could cause a disturbance in the XD system’s cooling function is begun,
the facility manager MUST be informed. In addition, after the action is taken and the work is finished, the facility manager MUST be informed.
NOTICE
Risk of leaking chilled water lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson Network Power recommends installing monitored leak detection equipment for the unit and supply and return lines.
1
|
|
Example: XDP160RA– –4 |
|
|
|
||
XD |
P |
160 |
R |
A |
– |
– |
* |
|
|
|
|
|
|
|
|
Pumping |
Pump |
Place holder |
Revision |
||||
unit |
Redundancy |
|
|
level |
|||
|
|
|
|
|
|
|
|
Liebert |
160kW |
A = 460V-3ph-60Hz |
Place holder |
X-treme heat |
nominal |
(voltage-phase-frequency) |
|
Density system |
capacity |
C = 208V-3ph-60Hz |
|
|
|
M = 380/415-3ph-50Hz |
|
2
1.0PRODUCT DESCRIPTION
Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP is rated for 160kW (546,000BTU/H) of cooling.
The Liebert XDP consists of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls, valves and piping.
The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the refrigerant being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are automatic.
Liebert XDP Unit
Liebert XD Cooling Modules
Control Valve
Chilled Water
Heat Exchanger
Receiver Pumps
The Liebert XDP's minimum recommended operating load is 30% of system nominal capacity. The Liebert XDP160 is rated for 160kW (546,000BTU/H) of cooling, therefore the system's minimum recommended load is 48kW (163,800BTU/H). Loading below this value can unfavorably affect system operation. Consult the factory for any loading below this recommendation.
To achieve the minimum recommended load, the capacity of all connected modules must total at least 48kW (163,800BTU/H). See Table 1.
|
|
|
Liebert XD Module Type |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
XDCF10 |
XDV8 |
XDV10 |
XDO16 |
XDO20 |
XDH20 |
XDH32 |
XDR20 |
|
|
|
|
|
|
|
|
|
|
|
Number of Liebert XD |
|
|
|
|
|
|
|
|
|
cooling modules required |
5 |
6 |
5 |
3 |
3 |
3 |
2 |
3 |
|
to achieve at least 48kW |
|||||||||
|
|
|
|
|
|
|
|
||
(163,800BTU/H) load |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Emerson and to your sales representative.
3
Product Description
! WARNING
Risk of unit falling over. Can cause injury or death.
The Liebert XDP is top-heavy. Use extreme caution and care when moving and installing this unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified rating organization. See Table 15 for unit weights. Unit weights are specified in section 9.0 Personnel should be properly trained and certified to move and rig equipment
! CAUTION
Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.
•Always keep the unit upright, indoors and protected from damage.
•If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In either case, do NOT press on the top edges of the packaging.
•If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
•When moving the skidded unit with a forklift truck, do not lift the unit any higher than
6" (152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift point of the unit.
NOTICE
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard doorway. Any attempt to move the unit, while skidded, through a standard doorway will cause damage to the unit and to the building.
NOTICE
Risk of damage from forklift. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert XDP upright, indoors and protected from dampness, freezing temperatures and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that the straps are not tightened to a point of damaging panels.
4
Product Description
1.Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and side packaging planks.
2.Remove and set aside filter dryer kit.
3.Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The bag may remain in place for dust and panel protection or removed for immediate unit installation.
4.Remove the bag from the unit when ready to remove the skid for installation.
Stretch
Wrap
Filter
Dryer
Kit
Remove Stretch Wrap |
Remove Filter Dryer Kit |
Remove Packaging Planks |
1.Align the forklift with either the front or rear side of the unit. Make sure the tines of the forklift are locked to the widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be equally spaced on either side of the center of gravity indicator.
2.Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3.Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4.Lift the unit to a height that it is not being support by the skid.
5.Move the skid from under the unit.
5
Product Description
Fit the forklift tines under the Liebert XDP.
The forklift tines must be equally spaced on either
side of the center of gravity indicator.
Move the forklift forward until the tines are fully under the unit.
1.Use the center of gravity indicators on the unit to position the slings. The slings must be equally spaced on either side of the center of gravity indicator. Refer to Figure 5.
2.Place slings under the unit using spaces provided between the skid deck boards.
NOTE
Unit is shown without outer packaging. These instructions may be applied with the outer packaging in place.
3.Use spreader bars or an equivalent method to ensure proper protection of the unit.
4.Ensure that the panels, if attached, are well protected from the slings.
NOTE
If rigging is to be used to move the unit closer to the site for installation, place one or two horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE
Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6.Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the unit.
7.Remove the skid from under the unit.
6
Product Description
Cushioning material not shown for clarity.
If rigging will be used to transport the Liebert XDP, place one or two horizontal straps around the unit and the vertical staps about this height.
Spreader
Bars
Center of
Gravity
Symbols
Lag |
Bracket |
|
|
Bolts |
|
Equally |
Equally |
Spaced |
Spaced |
1.Elevate the Liebert XDP with a lifting mechanism, such as a forklift or rigging.
2.Position one piano jack at each end of the Liebert XDP.
3.Lower the unit to a height suitable for placing it on the piano jacks.
4.Put protective material between the Liebert XDP and the piano jacks and straps.
5.Secure the Liebert XDP to the piano jacks.
6.Release the the Liebert XDP from the straps securing it to the lifting mechanism and move the mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
7
Product Description
Using a forklift to put a Liebert XDP on piano jacks
Using rigging to put a |
Liebert XDP Secured |
Liebert XDP on piano jacks |
to piano jacks |
1.Lower the Liebert XDP as far as the piano jacks will allow.
2.Undo all strapping holding the piano jacks to the unit.
3.Lift one end of the Liebert XDP off one piano jack with a pry bar or similar device, taking care not to damage the unit’s cabinet.
4.Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert XDP.
5.Remove all material used to protect the unit from the piano jacks and strapping.
8
2.0INSTALLATION
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
For additional technical information, refer to the System Design and Configuration Document for the Liebert XD™ System, SL-16655. The document is available in electronic format at Liebert’s Web site, www.liebert.com, as well as from your local Emerson representative.
A B
Overall Overall
C
Side Panel
F |
E |
D |
|
Height |
|||
5" |
|||
of Unit |
|
||
|
(127mm) |
|
|
|
1" (25mm) |
|
|
|
2-3/8" |
|
|
|
(60mm) |
|
D
Unit Base
E
Unit Base
Unit Dimensional Data
11"
(279mm)
Floor Cutout Dimensions
The shaded area indicates a recommended clearance
of 36" (914mm) for component access.
DPN001598
Pg. 2, Rev. 7
Model |
|
Dimensional Data, inches (mm) |
|
Shipping Weight, lb. (kg) |
||||
|
|
|
|
|
|
|
|
|
50/60Hz |
A |
B* |
C |
D |
E |
H |
Domestic |
Export |
|
|
|
|
|
|
|
|
|
XDP160 |
38 (965) |
34 (864) |
33-1/8 (841) |
33 (838) |
36 (914) |
78 (1981) |
1020(462) |
1083 (491) |
|
|
|
|
|
|
|
|
|
* The dimension does not include the bezel of the disconnect switch.
9
Installation
To first cooling module
or bypass flow controller **
Close this valve during normal operation
A - Return from Liebert XD Cooling Modules
17-1/4"
(438mm)
16-1/8" (409.6mm)
10" (254mm)
19" (483mm)
Install replaceable filter dryer assembly in liquid supply line B.
* Orientation determined by installer.
B - Supply to Liebert XD Cooling Modules
Emerson recommends field-installation of shutoff valves at these points to permit isolating the Liebert XDP for maintenance
Dimensions are approximate
and subject to change without notice.
* Allow 8" (204mm) clearance for filter replacement.
**To ensure ensure all refrigerant flow is filtered,
install the filter dryer assembly between the discharge
line of the Liebert XDP and the first bypass flow controller or the first Liebert XD cooling module.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C - Chilled Water Supply |
|
|
DPN001598 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
D - Chilled Water Return |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pg. 3, Rev. 7 |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
To Chilled Water Source |
|
|
|
|
|
|
|
|
|
|
|
|
From Chilled Water Source |
|
|
||||||||
|
Table 3 |
Unit piping outlet connection sizes, inches, OD Cu |
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pipe Connection Point |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50/60 Hz |
|
|
|
|
A |
|
|
|
|
|
|
B |
|
C |
|
D |
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
XDP160 |
|
|
|
|
2-1/8 |
|
|
|
|
|
|
|
1-1/8 |
|
2-5/8 |
|
2-5/8 |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated on the Liebert XDP’s rating plate. The unit must be installed in accordance with national wiring regulations.
Connect cables for high voltage supply to the electrical box in the Liebert XDP according to Figure 11 and make sure that the phases are correctly connected.
! WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit.
10
Installation
! WARNING
Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals. Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.
2.2.1Connecting High-Voltage Cables
1.Turn the Liebert XDP’s disconnect switch to the Off position (see Figure 9). Open the front doors and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Enclosure Cover Latch
Hazardous Volatge
Enclosure Cover
2.Determine which knockouts in the electrical enclosure will be used and remove them (see
Figure 10).
11
Installation
XDP Input Power
Knockout
Enclosure Cover
Not Shown for Clarity
3.Route the input hazardous voltage electrical power wiring through the top left knockout (see Figure 10) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12). Observe proper phasing.
4.Connect the ground wire to the ground lug (see Figures 11 and 12), which is in the middle left of the enclosure.
Customer
Power
Connection
Ground
Lug
Fused
Disconnect
Fuse
Blocks
Power Block
Transformer 2
(Supplied on 460V
Units Only)
Transformer 6
Transformer 1
Fuse
Block
Pump
Contactors
12
Installation
Customer Power |
|
|
Connection |
Transformer 2 |
|
Ground Lug |
|
|
Disconnect Switch |
Power Block |
|
Pump Circuit |
Transformer 6 |
|
Breakers |
||
|
||
Busbar |
Fuse Blocks |
|
Pump Contactors |
Transformer 1 |
|
|
Extra Low Voltage power output is 30V and 100VA or less.
1.Turn off all unit power before connecting cables or wires. Failure to do so may damage this equipment (refer to Figure 13).
2.Route low voltage electrical connections through the appropriate knockouts as indicated below.
User Interface Wiring
Temperature/Humidity
Sensor Wiring
Liebert XD Module Condensate |
Connections (optional; depends |
on features supplied with |
Liebert XD Module) |
Alternate Knockout
for Temperature/Humidity Sensor Wiring
Enclosure Cover Not Shown for Clarity
13
Installation
See Note 8 |
P66 |
P67 |
P66 |
P67 |
Liebert XD |
|
Liebert XD |
|
|
|
Cooling Module |
Cooling Module |
|
CAN Ground |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Coupler |
|
|
|
P2 |
|
|
P4 |
|
|
|
CAN Ground |
|
|
||
|
CAN |
|
|
|
CAN Iso |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
Coupler |
|
|
|
||||||
|
Cable |
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
Adapter |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
P1 |
P3 |
|
|
|
|
|
|
|
|
||
|
See |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note 4 |
|
|
|
|
|
|
See Note 8 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
See Note 5 |
|
See Note 5 |
|||
|
|
Termination |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Plug |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P64 P66 P67 |
|
|
|
|
|
|
|
|
P66 |
P67 |
|
|
P66 |
P67 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
See Note 4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit Display |
|
|
|
|
See |
|
Remote T/H Sensor A |
|
Remote T/H Sensor B |
||||||
|
|
|
|
|
Note 9 |
|
|
|
|
|
|
|
|
|||
|
(Rear View) |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
See Note 7 |
|
||
|
|
|
|
|
|
|
|
T6 Isolation |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
Transformer |
|
|
|
|
|
|||
|
Red Crossover |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ethernet Cable |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
T1 Unit Control |
|
24VAC Nominal |
|
||||||
|
Crossover Coupler |
|
|
|
|
|
Transformer |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
See Note 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
See Note 3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
P41 |
|
1 |
2 |
|
|
E5 |
|
|
P11 |
P13 |
P7 |
|
|
E4E3 |
|
|
|
|
|
|
|
|
P12 |
|
|
|
P43 |
|
|
|
P24 |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
IntelliSlotLiebert |
IntelliSlotLiebert |
|
|
|
|
|
|
P78 |
|
|
|
|
|
|||
|
|
P63 |
|
P67 |
|
SW2 |
|
TB1 E1E2 |
|
|
E1 |
Control |
||||
|
|
|
P66 |
|
|
|
|
|||||||||
|
|
|
Not |
|
|
P64 |
|
|
|
|
|
|
|
|
|
Fuse |
|
|
|
|
|
|
|
|
|
P68 |
|
|
|
|
Board |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
Used |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P61 |
|
|
|
|
|
|
|
|
|
P45 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
P65 |
|
|
|
|
P4 |
|
|
|
P4 |
|
|
Ribbon |
CableA |
See |
|
P18 |
|
|
|
|
|
|
P54 |
P51 |
|
|
|
|
Cables |
|
|
|
|
|
|
|
|
|
|
|||||
|
Note 2 |
|
Liebert iCOM Microprocessor |
|
|
|
||||||||||
|
|
P52 |
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
and I/O Board |
|
|
|
|
|
|
|
|||
|
P1 |
|
|
|
|
|
|
|
|
|
|
|
P53 |
|
|
|
|
P2 |
|
CableB |
|
|
|
|
|
|
|
|
|
P39 |
|
|
|
|
P65 |
|
|
|
|
|
|
See Table for |
|
P22P38 |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
P3 |
|
|
|
|
P40 |
|
|
Plug Assignments |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
P8 |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
P34 |
P35 |
|
|
|
|
|
|||
|
Liebert IntelliSlot |
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
P32 |
|
|
P33 |
|
P36 |
|
|
|
|
|
|
|
Power Supply |
|
77 78 |
|
|
|
|
|
|
|
|
|
|
|
|
|
1.See unit electrical schematic, installation and user manuals.
2.Cables “A” and “B” provided with each unit. Only one is used as follows: Liebert IntelliSlot-based communications - Cable “A” is preconnected to P65 on microprocessor and input/output board and P65 on Liebert IntelliSlot power supply non-Liebert IntelliSlot-based communications - Vable “B” is pre-connected to Terminals 77 and 78 but must be exchanged with Cable “A” at P65 on the microprocessor and input/output board.
3.Install applicable Liebert IntelliSlot cards.
4.Both cables (P64 and P66) are required.
5.It is not necessary to connect ground coupling on end of cable connected
to Sensor “A” or Sensor “B.”
302211 Rev. 2
6.A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug the red cable from P64 on the microprocessor and input/output board and connect to one side of the crossover coupler. The first customer connection point is to P64 on the microprocessor and input/output board. The second customer connection point is to the other side of the crossover coupler. This connects the microprocessor and input/output board and display to the private U2U network.
7.The remote sensors are interchangeable as to which connects to the Liebert XD cooling module and which connects to P2 on CAN Iso.
8.Field-install cables with factory-installed ferrite beads (when provided, typical two places). Each cable must make three passes through the ferrite bead. Locate the ferrite bead on top of the electric box. See instruction sheet provided with the cable assembly.
9.Factory-installed ferrite bead (when provided). Cable passes through ferrite bead three times
14
Installation
The Liebert XDP is shipped with jumpers and DIP switch settings for normal operation. See
Figure 15.
MICROPROCESSOR AND I/O BOARD |
||||||||||||||
DIP |
|
|
|
1 |
OFF ON |
|
|
|
|
|
||||
Switches |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
2 |
|
|
|
|
|
|
|
|
|
|||
OFF ON |
|
|
3 |
|
|
|
|
|
|
|
|
|
||
2 |
1 |
|
|
|
4 |
|
|
|
|
|
|
|
|
|
|
|
|
5 |
|
|
|
|
|
|
|
|
|
||
5 |
3 |
|
|
|
6 |
|
|
|
|
|
|
|
|
|
6 |
4 |
|
|
|
7 |
|
|
|
|
|
|
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
||
7 |
9 |
|
|
|
9 |
|
|
|
|
|
|
|
|
|
8 |
10 |
SW2 10 |
|
|
|
|
|
Jumpers |
||||||
|
Jumper |
|
|
|
|
|
on 1-2, 5-6 |
|||||||
1 |
|
P68 |
|
|
|
|
|
|||||||
on 1-2 |
|
|
|
|
|
|
|
|||||||
2 |
|
|
|
|
|
|
|
|||||||
P78 |
|
|
|
|
|
|
|
2 |
|
4 |
6 |
|||
3 |
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
1 |
|
3 |
5 |
|
|
DIP |
|
REMOTE T/HSENSOR “A” |
|||||||||||
|
|
|
ON |
|
|
|
|
|
|
|
|
|
||
Switches |
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
||||
OFF |
ON |
|
OFF |
|
|
|
|
|
|
|
|
|
||
2 |
|
1 |
|
SW1 |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
3 |
|
5 |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
4 |
|
|
|
|
P3 |
|
|
|
|
|
Jumper |
|
||
6 |
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
3 |
2 |
|
1 |
|
on 2-3 |
|
|||
7 |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT DISPLAY |
|
||
1 |
Jumper on 1-2 |
|||
2 |
P78 |
|
|
DIP |
|
Switches |
|||
3 |
|
|
||
|
|
OFF ON |
||
|
|
|
||
|
OFF ON |
|
1 |
None |
1 |
SW3 |
2 |
|
|
|
3 |
|
||
2 |
|
|
|
|
3 |
|
|
4 |
|
4 |
|
|
5 |
|
5 |
|
|
|
|
6 |
|
|
6 |
|
7 |
|
|
7 |
|
8 |
|
|
|
|
|
|
|
8 |
|
REMOTE T/H SENSOR “B”
ON |
|
|
|
|
|
|
|
|
|
|
DIP |
|||
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
Switches |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
OFF |
|
|
|
|
|
|
|
|
|
|
OFF |
ON |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
SW1 1 |
2 |
3 |
|
4 |
5 |
6 |
7 |
8 |
||||||
|
3 |
5 |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
P3 |
|
|
|
|
|
|
|
Jumper |
4 |
|
||||
|
|
|
|
|
6 |
|
||||||||
|
|
|
|
|
|
|
|
on 2-3 |
|
|||||
3 |
2 |
1 |
|
302211 |
||||||||||
|
7 |
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
Rev. 2 |
CAN Cable
|
|
|
Red Crossover |
|
|
||
|
|
|
Ethernet Cable |
Termination |
|||
|
|
|
|
|
|
||
|
|
|
Crossover |
|
Plug |
||
|
|
|
|
P64 P66P67 |
|
||
|
|
|
Coupler |
|
|
||
|
|
|
|
See Note 1 |
|
||
|
|
|
|
|
|
|
|
|
|
|
Customer |
|
|
|
|
|
|
|
Connection |
|
|
|
|
|
|
|
Points |
|
|
|
1. Both cables (P64 and P66) are required. |
|
|
|
|
|
|
Unit Display (Rear View) |
|
|
|
|
|
|
|
2. A crossover coupler is provided for unit-to-unit (U2U) |
|
|
|
|
|
|
|
|
networking. Unplug the red cable from P64 on the |
|
|
|
|
|
|
|
microprocessor and I/O board and connect to one side |
|
E5 |
P67 |
P11 |
P13 |
P7 |
|
of the crossover coupler. The first customer connection |
|
|
P12 |
|
|
|
point is to P64 on the microprocessor and I/O board. |
|
|
|
|
|
|
|
||
|
|
|
P66 |
|
|
|
|
|
|
|
|
|
U2U Networking Switch |
The second customer connection point is to the other |
|
|
|
|
P64 |
|
|
side of the crossover coupler. This connects the |
|
|
|
|
|
|
(Field Supplied) |
||
|
|
|
|
|
|
microprocessor and I/O board and display to the |
|
Not |
P63 |
|
Liebert iCOM |
|
|
||
|
|
|
private U2U network. |
||||
Used |
|
|
Microprocessor |
|
|
||
P61 |
|
|
|
|
|||
|
P65 |
& I/O Board |
|
|
|
||
|
|
|
|
|
To / From Other |
||
|
|
|
|
|
Networked Units |
||
|
|
|
|
|
|
||
|
|
|
|
|
|
Straight Through |
302211 |
|
|
|
|
|
|
Ethernet Cables |
Rev. 2 |
15
Installation
2.3Field Connections—Optional for All Units
•Connect field wiring from the optional Liebert XD cooling module condensation detection circuit to terminal strip locations COMM. (24) and H2O (51).
•Connect optional field wiring from remote devices to remote alarm device, common alarm outputs, site monitor and remote shutdown, if applicable. See terminal strip descriptions in Figure 17.
To P64 on Liebert iCOM |
|
|
|
To P66 on Liebert iCOM |
|
|
|
||
Control Board |
|
|
|
Control Board |
Red Ethernet Cable |
|
|
|
|
To Liebert XD Cooling |
|
Termination Plug |
|
|
|
Module(s) and Remote |
|
|
T/H Sensor B |
|
|
To Remote T/H Sensor A |
|
|
To Optional |
|
|
External |
|
|
Connections |
|
|
P64 |
P66 |
P67 |
UNIT DISPLAY (Rear View) |
||
Factory-Wired |
|
|
Temperature Sensor |
||
P67 |
|
|
Do Not |
|
|
Use |
|
|
|
|
1 |
NOTES: |
|
|
Control wiring must be Class 2 and installed in |
1 |
accordance with the National Electrical Code (NEC). |
Requires shielded cable.
2
DPN001598
Pg. 6, Rev. 7
16
Installation
2.4Remote Sensor Installation—Proper Placement
Placement of the two remote temperature/humidity sensors is critical to effective cooling of the conditioned space.
The remote sensors must be installed in areas where conditions are representative of the space conditioned by the Liebert XDP. Emerson recommends installing the sensors in different areas near the cooling modules served by the Liebert XDP. If the return air side of the primary air mover, such as a Liebert DS, represents the conditions where the Liebert XD cooling modules are located, one sensor could be placed there. Emerson suggests placing the other sensor on the wall opposite the heat load area (see Figure 18 for guidance).
Do not install the sensors where ambient air might cause false readings, for example, near unsealed doors or windows, or areas with stagnant air.
1.Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable; each bears labels indicating Sensor End and Unit End.
2.Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14).
3.Connect the Unit End of the sensor cable to P67 on the Liebert iCOM input/output board inside the Liebert XDP. Secure the ring terminal on the cable shield to the electric box adjacent to P67 (see Figure 14).
4.Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14).
5.Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the ring terminal on the cable shield to the grounding screw adjacent to P67.
17
3.0PIPING
Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f- gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F- gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation requires operators to use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.
The copper pipe connections on the Liebert XDP are:
Building Chilled Water Supply |
2-5/8" OD |
Building Chilled Water Return |
2-5/8" OD |
Refrigerant Supply |
1-1/8" OD |
Refrigerant Return |
2-1/8" OD |
Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to site specific documentation and the configuration guide for the Liebert XD system.
Elbows and restrictions must be minimized to get good fluid flow.
Pipe Function |
Size / Equivalent Pipe Length |
Liebert XDP supply line, from Liebert XDP supply |
1-1/8" OD for lengths up to 60 feet |
to farthest Liebert XD cooling module |
1-3/8" OD for lengths over 60 but less than 175 feet |
Liebert XDP return line, from farthest Liebert XD cooling |
2-1/8" OD for lengths up to 60 feet |
module to Liebert XDP return |
2-5/8" OD for lengths over 60 but less than 175 feet |
From any model Liebert XDO/Liebert XDH supply |
1/2" OD for lengths up to 10 feet |
to supply line of Liebert XDP |
7/8" OD for lengths over 10 but less than 25 feet |
From any model Liebert XDO/Liebert XDH return |
7/8" OD for lengths up to 10 feet |
to return line of Liebert XDP |
1-1/8" OD for lengths over 10 but less than 25 feet |
From any model Liebert XDV/Liebert XDCF supply |
1/2" OD for lengths up to 10 feet |
to supply line of Liebert XDP |
5/8" OD for lengths over 10 but less than 35 feet |
From any model Liebert XDV/Liebert XDCF return |
5/8" OD for lengths up to 10 feet |
to return line of Liebert XDP |
7/8" OD for lengths over 10 but less than 35 feet |
18