LG Multi V Series, Multi V ARNU12GTL 4 Series, Multi V ARNU09GTL 4 Series, Multi V ARNU18GTL 4 Series, Multi V ARNU24GTL 4 Series Svc Manual

Multi V Air Conditioner
SVC MANUAL(Exploded View)
MODEL : ARNU09GTL*4 ARNU12GTL*4 ARNU18GTL*4 ARNU24GTL*4
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
Internal Use Only
- 2 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1. Specification
Type Model Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Body
mm
Dimensions (WxDxH)
inch
Front Panel
mm
inch
Coil
Rows x Columns x FPI Face Area m2(ft2) Type Motor Output x Number
W
Running Current A
Fan Air Flow Rate(H/M/L) CMM
cfm Drive Motor type
Temperature Control Sound Absorbing Thermal Insulation Material Safety Device
Liquid Side mm(inch)
Pipe Connections
Gas Side mm(inch) Drain Pipe(Internal Dia.)
mm(inch) Net Weight Body kg(lbs) Noise Level
(Sound Press, 1.5m, H/M/L)
dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Acc'y)
ARNU09GTL*4
2.8 2,400 9,600
3.2 2,800
10,900
Galvanized Steel Plate
830x550x225
32-11/16 x 21-21/32 x 8-27/32
1,050x640x28.5
41-11/32 x 25-3/16 x 1-3/32
2x11x20
0.13(1.4)
Cross Flow Fan
20x2
0.18x2
9 / 8 / 7
318 / 283 / 247
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse Ø6.35(1/4) Ø12.7(1/2)
25.0(1)
20.6(45.4)
36 / 34 / 32
1,220-240,50
EEV
CV 1.5 x 3C**
CVV-SB 1.0 ~ 1.5 × 2C
Morning fog
PT-HL*
ARNU12GTL*4
3.6
3,100
12,300
4.0
3,400
13,600
Galvanized Steel Plate
830x550x225
32-11/16 x 21-21/32 x 8-27/32
1,050x640x28.5
41-11/32 x 25-3/16 x 1-3/32
2x11x20
0.13(1.4)
Cross Flow Fan
20x2
0.18x2
10 / 9 / 8
353 / 318 / 283
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse Ø6.35(1/4) Ø12.7(1/2)
25.0(1)
20.6(45.4)
38 / 36 / 32
1,220-240,50
EEV
CV 1.5 x 3C**
CVV-SB 1.0 ~ 1.5 × 2C
Morning fog
PT-HL*
Notes:-
1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
* Model Name
A:Basic, C:Plasma
Conversion Formula
kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
2Way Ceiling Cassette
** : Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for
electrical work and design. Especially the power cable and circuit breaker should be selected in accordance with that
- 3 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Type Model Unit
kW
Cooling Capacity kcal/h
Btu/h
kW
Heating Capacity kcal/h
Btu/h
Casing
Body
mm
Dimensions (WxDxH)
inch
Front Panel
mm
inch
Coil
Rows x Columns x FPI Face Area m2(ft2) Type Motor Output x Number
W
Running Current A
Fan Air Flow Rate(H/M/L) CMM
cfm Drive Motor type
Temperature Control Sound Absorbing Thermal Insulation Material Safety Device
Liquid Side mm(inch)
Pipe Connections
Gas Side mm(inch) Drain Pipe(Internal Dia.)
mm(inch) Net Weight Body kg(lbs) Noise Level
(Sound Press, 1.5m, H/M/L)
dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Acc'y)
ARNU18GTL*4
5.6
4,800
19,100
6.3
5,400
21,500
Galvanized Steel Plate
830x550x225
32-11/16 x 21-21/32 x 8-27/32
1,050x640x28.5
41-11/32 x 25-3/16 x 1-3/32
2x11x20
0.13(1.4)
Cross Flow Fan
20x2
0.18x2
13/12/10
459/424/353
Direct BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse Ø6.35(1/4) Ø12.7(1/2)
25.0(1)
20.6(45.4) 40/35/30
1,220-240,50
EEV
CV 1.5 x 3C**
CVV-SB 1.0 ~ 1.5 × 2C
Morning fog
PT-HL*
ARNU24GTL*4
7.1
6,100
24,200
8.0
6,900
27,300
Galvanized Steel Plate
830x550x225
32-11/16 x 21-21/32 x 8-27/32
1,050x640x28.5
41-11/32 x 25-3/16 x 1-3/32
2x11x20
0.13(1.4)
Cross Flow Fan
20x2
0.18x2
17/15/13
601/530/459
Direct BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25.0(1)
20.6(45.4) 42/37/32
1,220-240,50
EEV
CV 1.5 x 3C**
CVV-SB 1.0 ~ 1.5 × 2C
Morning fog
PT-HL*
Notes:-
1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
* Model Name
A:Basic, C:Plasma
Conversion Formula
kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
2Way Ceiling Cassette
** : Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for
electrical work and design. Especially the power cable and circuit breaker should be selected in accordance with that
2. List of Functions
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right)
Air flow
Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus) Drain pump
Installation
E.S.P. control Electric heater(operation) High ceiling operation Hot start
Reliability Self diagnosis
Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock
Convenience Forced operation
Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Wide Character wired remote controller
Picto wired remote controller Individual Deluxe wired remote controller control Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Special
Zone control
function kit
CTIE
Electro thermostat
2
-
auto
-
O
4/5/4
X O O O X
Option
O O O X O O O O
O(only heat recovery)
X
O(only heat pump or cooling only)
O O O O O O O O
Accessory
Accessory
Accessory Accessory Accessory
X
Accessory
-
-
-
FunctionCategory
ARNU09GTL*4 ARNU12GTL*4 ARNU18GTL*4 ARNU24GTL*4
- 4 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only