Lg Arnu073b1g2 Installation Guide

Page 1
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
P/NO : MFL42803121
www.lg.com
TYPE: Ceiling Concealed Duct - Low Static
ENGLISH
FRANÇAIS
ESPAÑOL
Page 2
IMPORTANT!
CAUTION
: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-410A causes frostbite burns.
• R-410A is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
or prominently displayed near the indoor Furnace/Air Handler Unit.
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
dripping and water damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid,
level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Special warnings
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
2 Indoor Unit
Page 3
Ceiling Concealed Duct - Low Static Type Indoor Unit Installation Manual
TABLE OF CONTENTS
o Four type "A" screws o Connecting cable
o Pipes: Gas side
Liquid side (Refer to Product Data)
o Insulation materials o Additional drain pipe
o Level gauge o Screw driver o Electric drill o Hole core drill
o Flaring tool set o Specified torque wrenches
(different depending on model No.)
o Spanner .......Half union
o A glass of water o Screw driver
o Hexagonal wrench o Gas-leak detector o Vacuum pump o Gauge manifold
o Owner's manual o Thermometer
Safety Precautions.................4
Introduction .............................7
Installation
Selection of the best
location ...................................8
Ceiling opening dimension
and hanging bolt location ......9
Indoor Unit Installation.........10
Wiring Connection ...............10
Part name and functions .....11
Checking the Drainage........12
Installation of Wired
Remote Controller ...............16
Name and function of wired remote controller(Accessory).18
Dip Switch Setting of Indoor unit
PCB.........................................19
Group Control Setting ............20
How to Set E.S.P? ...................25
Installation Requirements
Required Parts Required Tools
ENGLISH
Installation Manual 3
Page 4
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
n Be sure to read before installing the air conditioner. n Be sure to observe the cautions specified here as they include important items related to safety. n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the
following indications.
n Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
n Installation
Do not use a defective or under­rated circuit breaker. Use this appliance on a dedicated circuit.
• There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electri­cian, or an Authorized Service Center.
• Do not disassemble or repair the product. There is risk of fire or elec­tric shock.
Always ground the product.
• There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Always install a dedicated cir­cuit and breaker.
• Improper wiring or installation may cause fire or electric shock.
Use the correctly rated breaker or fuse.
• There is risk of fire or electric shock.
4 Indoor Unit
Page 5
Safety Precautions
n Operation
Do not modify or extend the power cable.
• There is risk of fire or electric shock.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furniture.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air condi­tioner could fall with it, causing prop­erty damage, product failure, and personal injury.
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
ENGLISH
Installation Manual 5
Gasolin
Page 6
Safety Precautions
Always check for gas (refriger­ant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away prop­erly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the out­door unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the con­denser and evaporator fins, could cause product malfunction or inefficient operation.
n Installation
If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.
6 Indoor Unit
90˚
Page 7
Introduction
Introduction
Air outlet vents
Air filters
Wired Remote Controller
R e m
o t e C
o n t r oll
er
T E
M P
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Features
Low static Duct type
ENGLISH
Installation Manual 7
Page 8
Installation
Installation
Indoor unit
Install the air conditioner in the location that satisfies the fol­lowing conditions.
• The place shall easily bear a load exceeding four times the indoor unitʼs weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit
Confirm the positional relationship between the unit and suspension bolts.
• Installation the ceiling opening to clean the filter or service under the product.
Selection of the best location
A(Min)
B(Min)
Ceiling
Service Space
A
B
H
600
(23-5/8)
600
(23-5/8)
Top view
[Unit : mm(inch)]
Front view
Inspection hole [600(23-5/8) x 600(23-5/8)]
Control box
Capacity(Btu/h) A B
7/9/12/15k 600(23-5/8) 900(35-7/16)
18/24k 600(23-5/8) 1,100(43-5/16)
Unit:mm(inch)
Low static Duct type
8 Indoor Unit
Page 9
Installation
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.
• A place where the unit will be leveled and that can support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CE
G
D
A J
B
M10 Nut M10 SP. washer M10 washer
X 4 X 4
(Local supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4 X 4
(Local supply)
X 4
I
F
H
Drainage hole
Drain Pump use
CASE 2
POSITION OF CONSOLE BOLT
[Unit: mm(inch)]
7/9/12/15k BTU/h
18/24k BTU/h
Dimension
Chassis
ABCDEFGHI J
850 900 383 575 93 190 21 795 163 820 (33-7/16) (35-7/16) 383(15) (22-5/8) (3-11/16) (7-7/16) (7/8) (31-5/16) (6-7/16) (32-5/16) 1130 1180 383 575 93 190 21 1065 163 1100 (44-7/16) (46-7/16) 383(15) (22-5/8) (3-11/16) (7-7/16) (7/8) (41-15/16) (6-7/16) (43-5/16)
ENGLISH
Installation Manual 9
Page 10
Installation
• Select and mark the position for fixing bolts.
• Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspen­sion bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer 3 Spring washer
4 Nut
5 Suspension bolts
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Terminal Block Indoor
1(L1) 2(L2) 3(A) 4(B)
INDOOR POWER INPUT
IDU IDU
Outdoor unit
Indoor unit
Central controller
SODU SODU
DRY1
DRY2
GND
INTERNET
12V
Outdoor unit
Wiring Connection
Indoor Unit Installation
CAUTION : Tighten the nut and bolt
to prevent unit falling.
WARNING : Make sure that the screws of the terminal are free from looseness.
B1/B2 Series
WARNING : Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazzard may also exist. Therefore, be sure all wiring is tightly connected.
Connection method of the connecting cable(Example)
10 Indoor Unit
1(L1) 2(L2)
Lock nut
Conduit
Conduit mounting plate
Power Supply
High Voltage
(208/230V)
4(B)
3(A)
Transmission
Page 11
Installation
• Low static duct type in case of suction from back side.
• Low static duct type in case of suction from bottom side.
Air Filter
Air outlet
Panel Rear
Air outlet
Air Filter
Panel Rear
Part name and functions
ENGLISH
Installation Manual 11
Page 12
Installation
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon the evaporator.
• Ensure that water flows drain hose of indoor unit without any leakage.
Checking the Drainage
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
n After all workings are finished, check the working and operation.
• Air distribution ............... Is the air circulation good?
• Drain ............................. Is the drainage smoothly and no sweating?
• Gas leakage ................. Is the piping connection correctly?
• Wiring ........................... Is the wiring connection correctly?
• Lock-bolt ....................... Is the lock-bolt of compressor loosened?
• Insulation Is the unit fully insulated?
• Ground Is the unit safely grounded?
THERMAL INSULATION
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal insulator for piping.
Thermal insulator for refrigerant pipe (Local supply)
Thermal insulator for piping(Local supply)
Hose clip for thermal insulator(Local supply)
Union for gas pipe
Refrigerant pipe and thermal
insulator(Local supply)
Union for liquid pipe
Thermal insulator for refrigerant pipe
(Local supply)
Hose clip for thermal insulator
(Local supply)
Felt
Rubber
Insulation
No clearance
Cabinet
12 Indoor Unit
Page 13
Installation
CAUTION
Ceiling
Drain Pump use
Drainage hole
Front of view
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 19mm.
• The unit must be horizontal or declined to the drain hose connected when finished installation.
• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
• During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit is 32mm(1-1/4 inch).
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm(1 inch) and pipe fittings
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
• Feed water to the flexible drain hose and check the piping for leakage.
• Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
• When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Heat insulation material: Polyethylene foam with thick­ness more than 8mm(5/16 inch).
Drain test
Upward routing not allowed
Pipe clamp
1/50~1/100
MAX 700mm (27-9/16 inch)
Maintenance drain port
Indoor unit
Feed water
Drain Pump
Drain pan
Flexible drain hose
Main drain pipe
Glue the joint
Drain port
Drain hose connection Use the clip
Drain Piping
ENGLISH
Installation Manual 13
Page 14
Installation
CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the nor­mal function of an overload protection device.
• Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)
1/50~1/100
MAX 700mm (27-9/16 inch)
Flexible drain hoseFlexible drain hoseFlexible drain hose
CAUTION : The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
14 Indoor Unit
Page 15
WIERED REMOTE CONTROLLER INSTALLATION
• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average tempera­ture.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)
R
e
m
o
t
e
C
o
n
t
r
o
l
l
e
r
T
E
M
P
5feet
(1.5meters)
no
no
no
yes
Remote Controller
TEMP
Remote Controller
TEMP
Fig.1 Typical locations for remote controller
Installation
ENGLISH
Installation Manual 15
Page 16
Installation
Installation of Wired Remote Controller
1. Please fix tightly using provided screw after placing remote controller setup board on the place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup board bends. Please set up remote controller board fit to the reclamation box if there is a reclamation box.
2. Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller cable guide groove.
h
Remove guide groove with long nose.
Reclamation to the surface of the wall
Upper part guide groove
Right part guide groove
Wall Side
Wall Side
Wall Side
Wall
Side
<Connecting order>
<Separating order>
3. Please fix remote controller upper part into the setup board attached to the surface of the wall, as the picture below, and then, connect with setup board by pressing lower part.
- Please connect not to make a gap at the remote con­troller and setup boardʼs upper and lower, right and left part.
When separating remote controller from setup board, as the picture below, after inserting into the lower separating hole using screw driver and then, spinning clockwise, remote controller is separated.
- There are two separating holes. Please individually separate one at a time.
- Please be careful not to damage the inside components when separating.
16 Indoor Unit
2
3
1
2
3
<Wire guide grooves>
Page 17
Installation
4. Please connect indoor unit and remote controller using connection cable.
5. Please use extension cable if the distance between wired remote controller and indoor unit is more than 10m.
Please check if connector is normally connected.
Connecting cable
Indoor Unit side
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the temperature sensor.) Do not install the cable to be 50m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
ENGLISH
Installation Manual 17
Page 18
18 Indoor Unit
Installation
Name and function of wired remote controller(Accessory)
※ Some functions may not be operated and displayed depending on the product type. ※ It will display strange value to the room temperature if wired remote controller is not connected.
Model : PQRCVSL0 (Black Color)
PQRCVSL0QW (White Color)
1. Operation indication screen
2. Set temperature button
It will set not room temperature but outlet air temperature.
3. Fan speed button
• Fan Speed have 3 Steps.
• Middle and Low step is same
4. ON/OFF button
5. Opration mode selection button
6. Wireless remote controller receiver
• Some products don't receive the wireless signals.
7. Air flow button
8. Subfunction button
9. Function setting button
10. Ventilation button
11. Reservation
12. Up,down,left,right button
To check the indoor temperature, press button.
13. Room temperature button
• Displays only the room temperature of the remote controller perception.
• There is no control of room temperature.
• In case of fresh air intake unit, displays only the temperature around remote controller.
14. Setting/Cancel button
15. Exit button
1
10
9 8
7
11 12 13
14
15
Please attach the inform label inside of the door. Please choose proper language depend on your country.
2 3
4
5
6
Page 19
Installation Manual 19
ENGLISH
19 Indoor Unit
Installation
Dip Switch Setting of Indoor unit PCB
For Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.
Function Description Setting Off Setting On Default
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
Communication
Cycle
Group Control
Dry Contact Mode
Installation
Heater linkage
Ventilator linkage
Vane selection (Console)
Region selection
Etc.
N/A (Default)
N/A (Default)
Selection of Master or Slave
Selection of Dry Contact Mode
Fan continuous operation
N/A
Selection of Ventilator link­age
Selection of up/down side Vane
Selection tropical region
Spare
-
-
Master
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Continuous operation Removall
-
Linkage Removal
Up side + Down side Vane
General model
-
-
-
Slave
Auto
-
-
Working
Up side Vane
Only
Tropical model
-
Off
Off
Off
Off
Off
Off
Off
Off
Page 20
Installation
Group Control Setting
1. Group Control 1
n Wired remote controller 1 + Indoor units
n Dip Switch in PCB (Cassette and Duct Type indoor units)
1. It is possible to 16 indoor units(Max) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
- In case of Central controller and Group controller at the same time, it is possible to connect stan­dard 2series indoor units or later since Feb. 2009.
- In case of Central controller setting, the Central controller can control indoor units after setting only the address of master indoor unit.
- Slave indoor unit will be operated like master indoor unit.
- Slave indoor unit can not be individually controlled by Central controller.
- Some remote controller canʼt perform with Dry Contact and Central controller at the same time. So contact us further information about it.
20 Indoor Unit
LGAP Network System
Master
Master
Slave
Display Error Message
Slave
Only connect serial signal and GND lines
between slave indoor unit
Slave
GND Signal 12 V
Master Setting Slave Setting
- No. 3 Off - No. 3 On
Page 21
21 Indoor Unit
Installation
5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.
6. In case of Group Control, it is possible to use following functions.
- Selection of operation options (operation/stop/mode/set temperature)
- Control of flow rate (High/Middle/Low)
- It is not possible at some functions.
h Master/Slave setting of indoor units be set possible using a PCB Dip Switch. h It is possible to connect indoor units since Feb. 2009. In the other cases, please contact LGE. h It can be the cause of malfuctions when there is no setting of master and slave.
h It is possible to control N indoor units by wired remote controller M units. (M + N ≤ 17 Units)
Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave. Other than those, it is same with the Group Control 1.
2. Group Control 2
ENGLISH
Installation Manual 21
LGAP Network System
Master
Master
Slave
Donʼt connect serial 12V line
Display Error Message
Slave
Slave
Slave
GND Signal 12 V
Page 22
Installation
3. Group Control 3
n Mixture connection with indoor units and Fresh Air Intake Unit
h In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air
Intake Unit with standard units. (Because setting temperature are different.)
h Other than those, it is same with Group Control 1.
22 Indoor Unit
LGAP Network System
FAU
Master
Display Error Message
Master
FAU
Slave
Master
Master
Slave
GND Signal 12 V
FAU
Standard Standard
FAU FAU
Standard Standard
FAU
* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
Page 23
23 Indoor Unit
Installation
4. 2 Remote Control
n Wired remote controller 2 + Indoor unit 1
1. It is possible to connect two wired remote controllers with one indoor unit.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
6. There isn’t limits of indoor unit function.
h Maximum 2wired remote controllers can be connected with 1 indoor unit.
ENGLISH
Installation Manual 23
LGAP Network System
Master
Display Error Message
Master
Slave
Page 24
Installation
5. Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA +Wired remote controller Indoor unit 1 EA +Wired remote controller 2EA
h PZCWRCG3 cable used for connection h PZCWRC2 cable used for connection
Slave
Mas te r
Mas ter
PZCWRCG3
Mas ter Sl ave
PZCWRC2
24 Indoor Unit
Page 25
25 Indoor Unit
How to Set E.S.P?
How to Set E.S.P?
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
This is the function that decides the strength of the wind for each wind level and because this function is to make the installation easier.
When setting ESP value on the product without very weak wind or power wind function, it may not work.
ENGLISH
Installation Manual 25
If pressing button long for 3
1
seconds, it enters into remote controller setter setup mode.
- If pressing once shortly, it enters into user setup mode. Please press more than 3 seconds for sure.
Function code, ESP code
ESP value
If entering into ESP setup mode by using
2
button, it indicates as the picture below.
ESP step
Function Code ESP value
Select ESP fan step by pressing
3
button. (01: very low, 02: low, 03: medium, 04: high, 05: power)
Move to ESP value setting by pressing
4
button. (It is 000 when delivering from the warehouse.)
Press button to setup ESP value.
5
(It is possible to setup ESP value from 1 to 255, and 1 is the smallest and 255 is the biggest.)
Page 26
How to Set E.S.P?
26 Indoor Unit
Function code, ESP code
ESP value
Select ESP fan step again by using
6
button and setup ESP value, as No. 4 and 5, that corresponds each wind flow
Press button to save.
7
Press button to exit.
8
After setup, it automatically gets out of
setup mode if there is no button input for 25 seconds.
When exiting without pressing set
button, the manipulated value is not reflected.
Page 27
27 Indoor Unit27 Indoor Unit
How to Set E.S.P?
Note :
1. The above table shows the correlation between the air rates and E.S.P.
Setting Value
60 6.02(212) 2.25(79) 0.61(21) - ­65 6.95(245) 3.32(117) 0.73(25) 0.54(19) 0.48(16) 70 7.69(271) 5.16(182) 1.19(42) 0.65(22) 0.56(19) 75 84.6(298) 6.93(244) 2.42(85) 0.77(27) 0.63(22) 80 9.5(335) 7.37(260) 3.4(120) 0.87(30) 0.72(25) 85 10.35(365) 8.72(307) 5.33(188) 1.35(47.6) 0.88(31) 90 10.81(381) 9.66(341) 6.75(238) 3.15(111) 0.98(34)
95 11.57(408) 10.31(364) 8.56(302) 4.73(167) 1.03(36) 100 12.58(444) 11.22(396) 9.75(344) 7.46(263) 2.31(81) 105 13.31(470) 12.27(433) 10.89(384) 8.64(305) 5.01(176) 110 14.2(501) 13.24(467) 12.15(429) 10.49(370) 7.7(271) 115 14.82(523) 13.92(491) 12.64(446) 11.16(394) 9.48(334)
0(0) 1(3.93) 2(7.87) 3(0.11) 4(0.15)
Static Pressure(mmAq (in.Aq))
Setting Value
65 10.07(355) 6.9(243) 0.82(28) - -
70 11.39(402) 8.49(299) 2.2(77) - -
75 12.01(424) 9.79(345) 4.2(148) - -
80 13.21(466) 11.03(389) 5.92(209) 0.92(32) -
85 14.24(502) 12.36(436) 9.41(332) 2.1(74) -
90 15.04(531) 13.34(471) 10.8(381) 5.29(186) 1.01(35)
95 16.02(565) 14.63(516) 12.5(441) 7.59(268) 1.34(47) 100 17.11(604) 15.56(549) 13.66(482) 11.53(407) 5.35(188) 105 17.99(635) 16.53(583) 15.17(535) 12.35(436) 7.67(270) 110 19.04(672) 17.71(625) 16.22(572) 14.23(502) 10.45(369) 115 19.77(698) 18.62(657) 17.1(603) 15.23(537) 13.25(467) 120 20.94(739) 19.92(703) 18.56(655) 16.98(599) 14.66(517) 125 21.97(775) 20.56(726) 19.25(679) 17.68(624) 16.06(567) 130 22.83(806) 21.98(776) 20.75(732) 19.32(682) 17.73(626)
0(0) 1(3.93) 2(7.87) 3(0.11) 4(0.15)
Static Pressure(mmAq (in.Aq))
ARNU073B1G2, ARNU093B1G2, ARNU123B1G2, ARNU153B1G2
ARNU183B2G2, ARNU243B2G2
(Unit;cmm(cfm))
(Unit;cmm(cfm))
ENGLISH
Installation Manual 27
Page 28
28 Indoor Unit
Page 29
Loading...