All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of KROHNE Messtechnik GmbH.
7.6 Electrical data for outputs and inputs............................................................................ 48
8 Notes49
4
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 5
OPTITEMP TT 10 C/R
1.1 Intended use
DANGER!
You may only use transmitters labelled with the "Ex" symbol in potentially explosive areas or
connect them to a sensor located in those areas. Additionally always note the zone(s) for which
the devices have an approval. Otherwise the transmitters might cause an explosion that can
result in fatal injuries.
DANGER!
Responsibility for the correct use of the devices with special regard to suitability, intended use
and the field of application lies solely with the operator. To avoid any kind of incorrect use, also
note the information in the chapter "Device description".
DANGER!
The transmitters do not contain any serviceable parts inside. Any substitution of components
may impair the intrinsic safety of the versions with an Ex approval. Always send defective devices
to the manufacturer or the local distributor for repair or exchange. If this is the case, attach a
clear description of the malfunction for warranty claims.
SAFETY INSTRUCTIONS 1
INFORMATION!
The manufacturer is not liable for any damage resulting from improper use or use for other than
the intended purpose. To avoid any kind of incorrect use, also note the information in the chapter
"Device description"!
The manufacturer has constructed these transmitters only for temperature measurements with
single resistance thermometers of the type Pt100 or with thermocouples type J, L, T, K, N. The
main field of application is industrial environment.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
5
Page 6
1 SAFETY INSTRUCTIONS
1.2 Certifications
1.2.1 EC directive compliance
CE marking
The device fulfils all applicable statutory requirements of the following EC directives:
• EMC Directive 2004/108/EC, harmonized standard EN 61326-1:2006
• Devices for use in hazardous areas: ATEX Directive 94/9/EC, harmonized standards
EN 60079-0:2006, EN 60079-11:2007 and EN 60079-26:2007
• CE Directive 93/68/EEC
The manufacturer certifies successful testing of the product by applying the CE marking.
See also "Certificates" in the download area of the manufacturer's website.
6
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 7
OPTITEMP TT 10 C/R
1.3 Safety instructions from the manufacturer
1.3.1 Copyright and data protection
The contents of this document have been created with great care. Nevertheless, we provide no
guarantee that the contents are correct, complete or up-to-date.
The contents and works in this document are subject to copyright. Contributions from third
parties are identified as such. Reproduction, processing, dissemination and any type of use
beyond what is permitted under copyright requires written authorisation from the respective
author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created
in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the
manufacturer's documents is always on a voluntary basis whenever possible. Whenever
feasible, it is always possible to make use of the offerings and services without providing any
personal data.
SAFETY INSTRUCTIONS 1
We draw your attention to the fact that data transmission over the Internet (e.g. when
communicating by e-mail) may involve gaps in security. It is not possible to protect such data
completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish
an imprint for the purpose of sending us any advertising or informational materials that we have
not expressly requested.
1.3.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including,
but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross
negligence. In the event any applicable law does not allow such limitations on implied warranties
or the exclusion of limitation of certain damages, you may, if such law applies to you, not be
subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant
product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this
disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable
in any way for possible consequences of such changes.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
7
Page 8
1 SAFETY INSTRUCTIONS
1.3.3 Product liability and warranty
The operator shall bear responsibility for the suitability of the device for the specific purpose.
The manufacturer accepts no liability for the consequences of misuse by the operator. Improper
installation and operation of the devices (systems) will cause the warranty to be void. The
respective "Standard Terms and Conditions" which form the basis for the sales contract shall
also apply.
1.3.4 Information concerning the documentation
To prevent any injury to the user or damage to the device it is essential that you read the
information in this document and observe applicable national standards, safety requirements
and accident prevention regulations.
If this document is not in your native language and if you have any problems understanding the
text, we advise you to contact your local office for assistance. The manufacturer can not accept
responsibility for any damage or injury caused by misunderstanding of the information in this
document.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device. Special considerations and precautions are also described in the
document, which appear in the form of underneath icons.
OPTITEMP TT 10 C/R
8
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 9
OPTITEMP TT 10 C/R
1.3.5 Warnings and symbols used
Safety warnings are indicated by the following symbols.
DANGER!
This information refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
This warning refers to the immediate danger when using this device in a hazardous atmosphere.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead to
serious health problems and even death. There is also the risk of seriously damaging the device
or parts of the operator's plant.
SAFETY INSTRUCTIONS 1
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems.
There is also the risk of damaging the device or parts of the operator's plant.
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's
plant.
INFORMATION!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
• HANDLING
HANDLING
HANDLINGHANDLING
This symbol designates all instructions for actions to be carried out by the operator in the
specified sequence.
iRESULT
RESULT
RESULTRESULT
This symbol refers to all important consequences of the previous actions.
1.4 Safety instructions for the operator
WARNING!
In general, devices from the manufacturer may only be installed, commissioned, operated and
maintained by properly trained and authorized personnel.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
9
Page 10
2 DEVICE DESCRIPTION
2.1 Scope of delivery
The scope of delivery always consists of the transmitter and its documentation.
2.2 General description
TT 10 C
TT 10 C
TT 10 CTT 10 C
RTD
RTD
RTDRTD
The TT 10 C is an analogue 2-wire in-head transmitter for temperature measurements with
single resistance thermometers of the type Pt100. The TT 10 C provides a temperature linear 420 mA output. The main field of application is industrial environments.
The transmitter is optionally available in an intrinsically safe version for installation in
potentially explosive areas. These devices are labelled with the "Ex" symbol and are approved for
use in zone 0.
Thermocouple
Thermocouple
ThermocoupleThermocouple
OPTITEMP TT 10 C/R
The TT 10 C T/C is an analogue 2-wire in-head transmitter for temperature measurements with
single thermocouple input of type J, L, T, K and N. It provides a mV linear 4-20 mA output. The
main field of application is industrial environments.
The TT10 C T/C is not available in an intrinsically safe version.
Installation on rail
Installation on rail
Installation on railInstallation on rail
All in-head versions are intended for installation in a "B connection head" or larger according to
DIN 43729. As an alternative you can also mount the in-head version on a rail according to EN
60715 TH35 with the help of the rail installation kit (further information on page 18). In this way
you may operate an in-head transmitter with an Ex approval with sensors in potentially explosive
areas, if the transmitter is installed in the safe area (though this case is very uncommon).
TT 10 R
TT 10 R
TT 10 RTT 10 R
RTD
RTD
RTDRTD
The TT 10 R is an analogue 2-wire rail-mount transmitter for temperature measurements. It has
the same features like the in-head version, except that a version with an Ex-approval does not
exist.
Thermocouple
Thermocouple
ThermocoupleThermocouple
10
The TT 10 R T/C is an analogue 2-wire rail-mount transmitter for temperature measurements. It
has the same features like the in-head version.
The rail-mount transmitter is intended for installation on a rail according to EN 60715 TH35.
The TT10 R T/C is not available in an intrinsically safe version.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 11
OPTITEMP TT 10 C/R
INFORMATION!
In the standard delivery condition the transmitters are not preset. Therefore you have to make a
complete solder pad configuration and adjust the potentiometers before using the transmitter
for the first time (refer to chapter "Operation"). As an option the manufacturer offers preset
transmitters according to the customer's order.
DEVICE DESCRIPTION 2
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
11
Page 12
2 DEVICE DESCRIPTION
2.3 Nameplate
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
The transmitter can be identified by the information on the nameplates.
2.3.1 In-head transmitter (Non-Ex version)
Figure 2-1: Nameplate of the in-head transmitter, RTD (Non-Ex,side)
1 Product name
2 Manufacturer
OPTITEMP TT 10 C/R
T/C
Figure 2-2: Nameplate of the in-head transmitter, thermocouples (Non-Ex,side)
1 Product name
2 Sensor type
3 Manufacturer
12
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 13
OPTITEMP TT 10 C/R
Figure 2-3: Nameplate for the in-head transmitter, RTD (Non-Ex, bottom)
1 WEEE dustbin symbol
2 Manufacturer
3 CE marking (EC conformity)
4 Address of manufacturer
5 Part number
6 Serial number
7 Batch number
Ludwig-Krohne-Str. 5; 47058 Duisburg
4000107901
Nyyww.xxxxxx
VO ZZZZZZZZZ
DEVICE DESCRIPTION 2
Ludwig-Krohne-Str. 5; 47058 Duisburg
4002122601
Nyyww.xxxxxx
VO ZZZZZZZZZ
Figure 2-4: Nameplate for the in-head transmitter, thermocouples (Non-Ex, bottom)
1 WEEE dustbin symbol
2 Manufacturer
3 CE marking (EC conformity)
4 Address of manufacturer
5 Part number
6 Serial number
7 Batch number
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
13
Page 14
2 DEVICE DESCRIPTION
2.3.2 In-head transmitter (Ex version)
Figure 2-5: Nameplate for the in-head transmitter (Ex, side)
1 Product name
2 Symbol for Ex-approval
3 CE marking (EC conformity)
4 Identification code of PQAN notified body
5 Supplementary Ex-data
6 Manufacturer
VIA04HRFX010000
OPTITEMP TT 10 C/R
Figure 2-6: Nameplate of the in-head transmitter (Ex, bottom)
1 WEEE dustbin symbol
2 Manufacturer
3 CE marking (EC conformity)
4 Address of manufacturer
5 Part number
6 Serial number
7 Batch number
14
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 15
OPTITEMP TT 10 C/R
2.3.3 Rail-mount transmitter
Figure 2-7: Nameplate of the rail-mount transmitter, RTD
1 Product name
2 Top down: part number, serial number and batch number
3 Manufacturer and address
4 Printable field, sensor configuration
5 Website of the manufacturer
6 WEEE dustbin symbol and CE marking (EC conformity)
DEVICE DESCRIPTION 2
4000267801
Nyyww.xxxxxx
VO ZZZZZZZZZ
4002122701
T/C
Figure 2-8: Nameplate of the rail-mount transmitter, thermocouple
1 Product name
2 Top down: part number, serial number and batch number
3 Manufacturer and address
4 Printable field, sensor configuration
5 Website of the manufacturer
6 WEEE dustbin symbol and CE marking (EC conformity)
Nyyww.xxxxxx
VO ZZZZZZZZZ
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
15
Page 16
3 INSTALLATION
3.1 Notes on installation
INFORMATION!
Inspect the cartons carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
3.2 In-head transmitter (Ex and Non-Ex)
DANGER!
Never install or operate the Non-Ex version in potentially explosive areas, it might cause an
explosion that can result in fatal injuries! Only use the Ex version in potentially explosive areas!
Also note the following items which concern the Ex version:
OPTITEMP TT 10 C/R
•
It must be installed in a housing that has the protection category IP20 or better according
to DIN IEC 60529 (an exception are in-head transmitters mounted on a rail as described in the
next section). Additionally the magnesium component of the housing must not exceed 6% as a
higher magnesium component may increase the flammability and the Ex capability.
•
If it is mounted in a housing which is isolated from the ground and can be charged to an
ignition capable level, then the housing must be electrostatically grounded when installed in
hazardous areas.
•
It is approved for potentially explosive areas (zone 0).
•
It must be electrically connected (terminal 4 and 5) via a certified isolating interface/zener
barrier having double or reinforced insulation which shall be placed outside the hazardous
area.
CAUTION!
The manufacturer has developed the Non-Ex version for an operating temperature range of
°
-40...+85
C / -40...+185°F (the Ex version has the same ambient temperature range). To avoid
destruction or damage of the device, always assure that the operating temperature or the
ambient temperature does not exceed the permissible range and note the following items:
•
If you operate the Ex version in potentially explosive areas, the ambient temperature also
depends on the temperature classification. For detailed information refer to the section about
the temperature data for potentially explosive areas on page 46
The thermowell also transfers the process temperature to the transmitter housing. If the
•
.
process temperature is close to or exceeds the maximum temperature of the transmitter,
then the temperature in the transmitter housing can rise above the maximum permissible
temperature!
16
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 17
OPTITEMP TT 10 C/R
One way to decrease the heat transfer via the thermowell is to install the transmitter farther
away from the heat source. An alternative is to make the thermowell longer. Inversely you can
take similar measures if the temperature is below the specified minimum temperature.
The in-head transmitters (Ex and Non-Ex version) are intended for installation in DIN B
connection heads or larger. The large Ø7.5 mm / 0.29" center hole facilitates the electrical
connection of the measurement sensor and the installation (for detailed information refer to the
chapter "Dimensions and weights"). The following drawing shows the installation of the in-head
transmitter with the help of the connection head installation kit:
INFORMATION!
The connection head installation kit does not belong to the standard scope of delivery of the
transmitter, you have to order it separately. For more information refer to Accessory parts on
page 39
INSTALLATION 3
.
Figure 3-1: Connection head installation kit
1 M4 screw
2 Spring
3 Lock washer
4 Wires of measuring insert
5 Sheath
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
17
Page 18
3 INSTALLATION
3.3 Rail mounting kit for in-head transmitters
DANGER!
To avoid fatal injuries, destruction or damage of the transmitter, always note the relevant
admonitions in the previous section if you install the in-head-transmitter on a rail!
INFORMATION!
The rail mounting kit allows to install the in-head transmitter on a rail according to EN 60715
TH35. The kit does not belong to the standard scope of delivery, you have to order it separately.
For more information refer to the section about the accessory parts in the chapter "Service".
Rail mounting kit for in-head transmitters
OPTITEMP TT 10 C/R
1 Rail (not included in the kit)
2 Screws
3 Clamp
4 Transmitter (not included in the kit)
Step 1
1 Place the transmitter on the clamp as shown above.
2 Push the transmitter down until it reaches the plate and secure with a screw.
18
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 19
OPTITEMP TT 10 C/R
Step 2
1 Hook one end of the clamp into the rail as shown above.
2 Push the other end of the the kit down until it snaps onto the rail.
3 Release by pushing the hook, shown in the picture, and at the same time lift the clip out of the rail.
3.4 Rail-mount transmitter
DANGER!
Neither operate this transmitter in potentially explosive areas, nor connect it to a sensor located
in a potentially explosive area! Otherwise the transmitter might cause an explosion that can
result in fatal injuries!
INSTALLATION 3
INFORMATION!
The rail-mount transmitter is intended for installation on a rail according to EN 60715 TH35.
Figure 3-2: Installation of the rail-mount version
1 Hook the upper groove of the transmitter onto the rail.
2 Press the lower part of the transmitter against the rail.
iWhen you hear a "click" from the snap fastener, the transmitter is fixed onto the rail
(drawing in the centre).
3 To remove the transmitter, use a small screwdriver to push the snap fastener downwards.
4 Carefully move the lower part of the transmitter in the forward direction and then upwards.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
19
Page 20
4 ELECTRICAL CONNECTIONS
4.1 Safety instructions
DANGER!
All work on the electrical connections may only be carried out with the power disconnected.
DANGER!
Observe the national regulations for electrical installations!
CAUTION!
Before you connect and operate a transmitter, always note the following items to avoid an
electric shock:
•
For all work on the electrical connections use an electrostatic safe (i.e. grounded)
workplace! In this way you minimize the risk of electrostatic discharge (ESD).
•
Assure that the cover was closed after any work on the device. The cover prevents
electrostatic discharge if the solder pads are touched inadvertently; furthermore it protects
the solder pads against dirt.
OPTITEMP TT 10 C/R
DANGER!
Never connect or operate a non-Ex version of a transmitter in potentially explosive areas,
otherwise it might cause an explosion that can result in fatal injuries! Before you connect and
operate a transmitter version with an Ex approval, always note the following items to avoid an
explosion which may result in fatal injuries:
•
Never do any soldering work in potentially explosive areas!
•
Connect the Ex version only to Ex approved sensors or sensors that meet the requirements
for "simple apparatus" in EN 60079-11:2007, section 5.7.
•
Observe the corresponding regulations, the declaration of conformity, the type test certificate
of the device, the ATEX certificate "Special conditions for safe use" for Ex versions and the
relevant instructions of this document.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
INFORMATION!
Look at the device nameplate to ensure that the device is delivered according to your order.
20
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 21
OPTITEMP TT 10 C/R
INFORMATION!
The transmitter is protected against polarity reversal. No damage will occur to the device if the
polarity of the supply voltage is switched. The output will then indicate 0 mA.
INFORMATION!
The calibration of this transmitter works with potentiometers. Therefore assure that the
transmitter is protected against heavy impacts or strong vibrations. Otherwise the calibration
data could change.
4.2 Electrical input connections
CAUTION!
Always establish the electrical connections according to the following diagrams. Otherwise it
can come to destruction or damage of the transmitter.
INFORMATION!
To avoid measuring errors, assure that all cables are connected properly and that the screws
are tightened correctly.
ELECTRICAL CONNECTIONS 4
4.2.1 In-head transmitter (Ex and Non-Ex)
RTD
RTD
RTDRTD
Figure 4-1: Pt100, 3-wire input connection (Ex and Non-Ex version)
Thermocouple
Thermocouple
ThermocoupleThermocouple
Figure 4-2: Thermocouple, 2-wire input connection
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
21
Page 22
4 ELECTRICAL CONNECTIONS
4.2.2 Rail-mount transmitter
RTD
RTD
RTDRTD
Figure 4-3: Pt100, 3-wire connection
Thermocouple
Thermocouple
ThermocoupleThermocouple
OPTITEMP TT 10 C/R
Figure 4-4: Thermocouple, 2-wire input connection
22
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 23
OPTITEMP TT 10 C/R
4.3 Electrical connection diagrams
CAUTION!
Always establish the electrical connections according to the following diagrams. Otherwise it
can come to destruction or damage of the transmitter.
INFORMATION!
To avoid measuring errors, assure that all cables are connected properly and that the screws
are tightened correctly.
4.3.1 In-head transmitter (Non-Ex)
DANGER!
Neither operate this transmitter in potentially explosive areas, nor connect it to a sensor located
in a potentially explosive area! Otherwise the transmitter might cause an explosion that can
result in fatal injuries!
CAUTION!
Note that the maximum output load always depends on the power supply. If the maximum output
load is exceeded, then the measured value will become incorrect. For further information refer
to the output load diagrams in the chapter "Technical data".
ELECTRICAL CONNECTIONS 4
INFORMATION!
The transmitter has a polarity protection. Connecting the power supply with a wrong polarity will
not damage the transmitter.
Figure 4-5: Connection diagram of the in-head transmitter (Non-Ex)
1 Terminals for input signal (1, 2 and 3)
2 Potentiometer for zero point setting
3 Potentiometer for measuring span setting
4 Output signal, terminals 4 and 5 (4...20 mA)
5 Load resistance
6 Power supply (6.5...32 VDC)
7 Solder pads
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
23
Page 24
4 ELECTRICAL CONNECTIONS
4.3.2 In-head transmitter (Ex)
DANGER!
The Ex transmitter can be installed in potentially explosive areas of zone 0. It may only be
connected to sensors that meet the requirements for "simple apparatus" in EN 60079-11:2007,
section 5.7. During operations in potentially explosive areas always note the relevant safety
instructions and especially the following items:
•
The transmitter must be electrically connected (terminal 4 and 5) via a certified isolating
interface/zener barrier having double or reinforced insulation which shall be placed outside
the hazardous area.
•
The output parameters of the Ex approved Zener barrier or voltage supply have to be less or
equal than the input parameters of the transmitter (i.e. U
CAUTION!
Note that the maximum output load always depends on the power supply. If the maximum output
load is exceeded, then the measured value will become incorrect. For further information refer
to the output load diagrams in the chapter "Technical data".
, Ii, Pi, Li, Ci).
i
OPTITEMP TT 10 C/R
INFORMATION!
The transmitter has a polarity protection. Connecting the power supply with a wrong polarity will
not damage the transmitter.
Figure 4-6: Connection diagram of the in-head transmitter (Ex)
1 Input signal (terminals 1, 2 and 3)
2 Potentiometer for zero point setting
3 Potentiometer for measuring span setting
4 Output signal, terminals 4 and 5 (4...20 mA)
5 Load resistance
6 Power supply
7 Safe area
8 Potentially explosive area
9 Solder pads
24
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 25
OPTITEMP TT 10 C/R
4.3.3 Rail-mount transmitter
DANGER!
Neither operate this transmitter in potentially explosive areas, nor connect it to a sensor located
in a potentially explosive area! Otherwise the transmitter might cause an explosion that can
result in fatal injuries!
CAUTION!
Note that the maximum output load always depends on the power supply. If the maximum output
load is exceeded, then the measured value will become incorrect. For further information refer
to the output load diagrams in the chapter "Technical data".
INFORMATION!
The transmitter has a polarity protection. Connecting the power supply with a wrong polarity will
not damage the transmitter.
ELECTRICAL CONNECTIONS 4
Figure 4-7: Connection diagram of the rail-mount transmitter (2-wire connection)
1 Output signal (4...20 mA)
2 Power supply
3 Potentiometer for zero point setting (Z)
4 Potentiometer for measuring span setting (S)
5 Terminals for input signal
6 Load resistance
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
25
Page 26
5 OPERATION
5.1 Configuring the in-head version
DANGER!
To avoid electric shocks and destructions or damages of the device, assure that all electrical
connections comply with the instructions within the chapter "Electrical connections".
DANGER!
Only perform the configuration described in this section if no sensor is connected to the
transmitter. Otherwise you could damage the cable insulation during soldering, furthermore the
cables could handicap during soldering.
INFORMATION!
In the standard delivery condition the transmitters are not preset. Therefore you have to make a
complete solder pad configuration and adjust the potentiometers before using the transmitter
for the first time. Also note the following items:
•
The steps in this section show the complete configuration procedure in the correct order for
new transmitters. The manufacturer strongly recommends to follow this procedure,
otherwise the calibration may not be proper.
•
As an option the manufacturer offers preset transmitters according to the customer's order.
Only in this case the solder pad configuration and potentiometer adjustment is not necessary.
•
In some cases you have to change the solder pad configuration and perform a new
potentiometer adjustment of a transmitter that has already been in use. This may be the case
e.g. if you must define a new zero point or measuring span for a new application.
OPTITEMP TT 10 C/R
Step 1: removing the cover
• Take the transmitter with thumb and forefinger (bottom part lies on the forefinger while the
thumb grips the terminals).
• Grip the cover with the thumb and the forefinger of the other hand beside the holes for the
screws (the cover is not fixed with screws, but it is plugged on the bottom part).
• Pull the cover upwards (refer to previous drawing).
26
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 27
OPTITEMP TT 10 C/R
Step 2-3 for TT10 C RTD version
Step 2-3 for TT10 C RTD version
Step 2-3 for TT10 C RTD versionStep 2-3 for TT10 C RTD version
Step 2: setting the zero point
1 Measuring span
2 Zero point
OPERATION 5
Step 3: setting the measuring span
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
27
Page 28
5 OPERATION
Step 2-3 for TT10 C thermocouple version
Step 2-3 for TT10 C thermocouple version
Step 2-3 for TT10 C thermocouple versionStep 2-3 for TT10 C thermocouple version
Step 2: Select thermocouple type T/C
OPTITEMP TT 10 C/R
Step 3: Select recommended mV span according to table
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 29
OPTITEMP TT 10 C/R
CAUTION!
You have to choose one sensor break configuration, i.e. you may only set one of the two solder
jumper! If you establish both solder jumper connections, this could lead to damage or
destruction of the transmitter.
Step 4: setting the sensor break monitoring
1 Lower solder jumper: the output signal for sensor break is in this case ≤ 3.6 mA
2 Upper solder jumper: the output signal for sensor break is in this case ≥ 23 mA
CAUTION!
After the solder pad configuration of the sensor break monitoring is complete, assure that the
cover is on its original place again! The cover prevents electrostatic discharge if the solder pads
are touched inadvertently; furthermore it protects the solder pads against dirt.
The setting of the sensor break monitoring is the last step in the configuration procedure. After
the configuration is complete, a calibration and an adjustment of the potentiometers is
necessary to achieve correct measuring results.
OPERATION 5
5.2 Configuration example (in-head version, RTD)
The previous drawing shows an example of a configuration with the following parameters:
• Measuring range: -50...+250°C / -58...+482°F
• Measuring span: 300°C / 540°F
• Sensor break: ≥23 mA
• Zero point: -50°C/ -58°F
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
29
Page 30
5 OPERATION
5.3 Configuration example (in-head version, thermocouple)
The previous drawing shows an example of a configuration with the following parameters:
• Measuring range: 0...+800°C / 32...+1472°F
• Measuring span: 775-900°C / 1395-1620°F
• Sensor break: ≥23 mA
• Zero point: 0°C/ 32°F
OPTITEMP TT 10 C/R
30
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 31
OPTITEMP TT 10 C/R
5.4 Configuring the rail-mount version
DANGER!
To avoid electric shocks and destructions or damages of the device, assure that all electrical
connections comply with the instructions within the chapter "Electrical connections".
DANGER!
Only perform the configuration described in this section if no sensor is connected to the
transmitter. Otherwise you could damage the cable insulation during soldering, furthermore the
cables could handicap during soldering.
INFORMATION!
In the standard delivery condition the transmitters are not preset. Therefore you have to make a
complete solder pad configuration and adjust the potentiometers before using the transmitter
for the first time. Also note the following items:
•
The steps in this section show the complete configuration procedure in the correct order for
new transmitters. The manufacturer strongly recommends to follow this procedure,
otherwise the calibration may not be proper.
•
As an option the manufacturer offers preset transmitters according to the customer's order.
Only in this case the solder pad configuration and potentiometer adjustment is not necessary.
•
In some cases you have to change the solder pad configuration and perform a new
potentiometer adjustment of a transmitter that has already been in use. This may be the case
e.g. if you must define a new zero point or measuring span for a new application.
OPERATION 5
Step 1: removing the cover
• Take a screwdriver and press the tip between the housing and the cover as shown in the
previous drawing.
• Remove the cover.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
31
Page 32
5 OPERATION
Step 2-3 for TT10 R RTD version
Step 2-3 for TT10 R RTD version
Step 2-3 for TT10 R RTD versionStep 2-3 for TT10 R RTD version
Step 2: setting the zero point
1 Measuring span
2 Zero point
OPTITEMP TT 10 C/R
32
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 33
OPTITEMP TT 10 C/R
Step 3: setting the measuring span
OPERATION 5
Step 3: setting the measuring span
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
33
Page 34
5 OPERATION
Step 2-3 for TT10 R thermocouple version
Step 2-3 for TT10 R thermocouple version
Step 2-3 for TT10 R thermocouple versionStep 2-3 for TT10 R thermocouple version
Step 2: Select thermocouple type
OPTITEMP TT 10 C/R
Step 3: Select recommended mV span according to table
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 35
OPTITEMP TT 10 C/R
CAUTION!
You have to choose one sensor break configuration, i.e. you may only set one of the two solder
jumper! If you establish both solder jumper connections, this could lead to damage or
destruction of the transmitter.
Step 4: setting the sensor break monitoring
1 Right solder jumper: the output signal for sensor break is in this case ≤ 3.6 mA
2 Left solder jumper: the output signal for sensor break is in this case ≥ 23 mA
CAUTION!
After the solder pad configuration of the sensor break monitoring is complete, assure that the
cover is on its original place again! The cover prevents electrostatic discharge if the solder pads
are touched inadvertently; furthermore it protects the solder pads against dirt.
OPERATION 5
The setting of the sensor break monitoring is the last step in the configuration procedure. After
the configuration is complete, a calibration and an adjustment of the potentiometers is
necessary to achieve correct measuring results.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
35
Page 36
5 OPERATION
5.5 Configuration example (rail-mount version, RTD)
• Measuring range: -50...+250°C / -58...+482°F
• Measuring span: 300°C / 540°F
• Sensor break: ≥ 23 mA
• Zero point: -50°C/ -58°F
5.6 Configuration example (rail-mount version, thermocouple)
OPTITEMP TT 10 C/R
• Measuring range: 0...+800°C / 32...+1472°F
• Measuring span: 775-900°C / 1395-1620°F
• Sensor break: ≥ 23 mA
• Zero point: 0°C/ 32°F
36
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 37
OPTITEMP TT 10 C/R
5.7 Calibration
DANGER!
To avoid electric shocks and destructions or damages of the device, assure that all electrical
connections comply with the instructions within the chapter "Electrical connections".
INFORMATION!
The manufacturer recommends checking the calibration annually. To achieve the best possible
accuracy, note the following items:
•
All calibration instruments (i.e. resistance decade and amperemeter) must have an accuracy
of at least 0.02%.
•
Assure that the complete solder pad configuration has taken place before the calibration.
•
The calibration has to take place according to the temperature scales ITS 90 (IEC 60751 for
Pt100, IEC 60584 for thermocouple type J, K, N and T and DIN 43710 for thermocouple type L).
The simulation source for RTD input on the transmitter must have a temperature coefficient
setting for platinum (= 0.00385). The simulation source for thermocouple input on the
transmitter must have the selected thermocouple type and used with correct thermocouple
wire that is connected with the correct polarity.
•
If you set an input signal that delivers an outputs signal of 12 mA as described in the following
actionsequence, wait about 15 minutes and check the stability of the output signal
afterwards. Only if the output signal is stable then, the transmitter is ready for calibration.
OPERATION 5
Potentiometers of the in-head version
1 Potentiometer for zero point setting
2 Potentiometer for measuring span setting
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
37
Page 38
5 OPERATION
Potentiometers of the rail-mount version
1 Potentiometer for zero point setting
2 Potentiometer for measuring span setting
INFORMATION!
The following calibration procedure is valid not only for the rail-mount transmitter, but also for
the Ex and the Non-Ex version of the in-head transmitter.
OPTITEMP TT 10 C/R
• Connect the power supply and the precision measuring device for current measurement
according to the connection diagram in the chapter "Electrical connections" (the typical power
supply is 24 VDC and depends on the overall output load (also refer to
Output load diagrams
on page 47).
• Connect the input signal (Pt100 or thermocouple simulator) according to the connection
diagram in the chapter "Electrical connections".
• Set an input signal that delivers an output signal of approximately 12 mA.
• Wait circa 15 minutes and check the stability of the output signal afterwards. Only if the output
signal is stable then, the transmitter is ready for calibration and you can go to the next step!
• Use the input simulation source to set an input signal T
that corresponds to the selected
in
lower measuring range value (e.g. 100 Ω for a measuring span from 0...+100°C / +32...212°F).
• Use the potentiometer for zero point setting to set exactly a current of I
= 4.00 mA (refer to
out
the drawing above).
• Use the input simulation source to set an input signal T
that corresponds to the selected
in
upper measuring range value (e.g. 138.5 Ω for a measuring span from 0...+100°C/
+32...212°F).
• Use the potentiometer for the measuring span setting to set exactly a current of
I
= 20.00 mA
out
• Repeat the steps 5 till 8 until all of the signals are set exactly.
• Secure the potentiometers with varnish.
iThe calibration is complete now.
38
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 39
OPTITEMP TT 10 C/R
6.1 Accessory parts
Accessory partOrder code
Connection head installation kit70ADA00011
Rail mounting kit for in-head version (10 units)70ADA00027
6.2 Spare parts availability
The manufacturer adheres to the basic principle that functionally adequate spare parts for each
device or each important accessory part will be kept available for a period of 3 years after
delivery of the last production run for the device.
This regulation only applies to spare parts which are subject to wear and tear under normal
operating conditions.
6.3 Availability of services
SERVICE 6
The manufacturer offers a range of services to support the customer after expiration of the
warranty. These include repair, maintenance, technical support and training.
INFORMATION!
For more precise information, please contact your local sales office.
6.4 Returning the device to the manufacturer
6.4.1 General information
This device has been carefully manufactured and tested. If installed and operated in accordance
with these operating instructions, it will rarely present any problems.
CAUTION!
Should you nevertheless need to return a device for inspection or repair, please pay strict
attention to the following points:
•
Due to statutory regulations on environmental protection and safeguarding the health and
safety of our personnel, manufacturer may only handle, test and repair returned devices that
have been in contact with products without risk to personnel and environment.
•
This means that the manufacturer can only service this device if it is accompanied by the
following certificate (see next section) confirming that the device is safe to handle.
CAUTION!
If the device has been operated with toxic, caustic, flammable or water-endangering products,
you are kindly requested:
•
to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from
such dangerous substances,
•
to enclose a certificate with the device confirming that is safe to handle and stating the
product used.
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
39
Page 40
6 SERVICE
6.4.2 Form (for copying) to accompany a returned device
Company:Address:
Department:Name:
Tel. no.:Fax no.:
Manufacturer's order no. or serial no.:
The device has been operated with the following medium:
OPTITEMP TT 10 C/R
This medium is:water-hazardous
toxic
caustic
flammable
We checked that all cavities in the device are free from such
substances.
We have flushed out and neutralized all cavities in the
device.
We hereby confirm that there is no risk to persons or the environment through any residual media
contained in the device when it is returned.
Date:Signature:
Stamp:
6.5 Disposal
CAUTION!
Disposal must be carried out in accordance with legislation applicable in your country.
40
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 41
OPTITEMP TT 10 C/R
7.1 Measuring principle
7.1.1 Resistance thermometer
The transmitter works together with a measuring insert that has a Pt100 RTD. This kind of
measuring inserts features a temperature-sensitive sensor made from a platinum RTD, whose
value at 0°C / +32°F is 100 Ω. That is where the name "Pt100" comes from.
It is generally valid that the electric resistance of metals increases according to a mathematical
function as the temperature rises. This effect is taken advantage of by resistance thermometers
to measure temperature. The "Pt100" thermometer features a measuring resistance with
defined characteristics, standardised in IEC 60751. The same is true for the tolerances. The
average temperature coefficient of a Pt100 is 3.85 x 10
+32...+212°F.
During operation, a constant current I (≤ 1 mA) flows through the Pt100 RTD, which brings about
a voltage drop U. The resistance R is calculated using Ohm's Law (R=U/I). As the voltage drop U
at 0°C / +32°F is 100 mV, the resulting resistance of the Pt100 thermometer is 100 Ω (100 mV /
1 mA = 100 Ω).
TECHNICAL DATA 7
-3K-1
in the range from 0...+100°C/
Figure 7-1: Pt100 resistance thermometer in 3-wire connection at 0°C / +32°F, schematic.
1 Pt100 RTD
2 Voltage meter
3 Current source
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
41
Page 42
7 TECHNICAL DATA
7.1.2 Thermocouples
The thermocouple features two electric conductors made from different metals, connected at
one end. Each free end is connected to a compensation cable extension or direct connected to a
millivolt meter. This circuitry forms a "thermal circuit". The point at which the two electric
conductors connect is called the measuring point or hot junction and the point at which the
compensation cables connect to the conductors of the millivolt meter is called the cold junction.
If the measuring point of this thermal circuit is heated up, a small electrical voltage (thermal
voltage) can be measured. If, however, the measuring point and the cold junction are at the same
temperature, no thermoelectric voltage is generated. The degree of thermoelectric voltage, also
known as electromotive force (EMF), depends on the thermocouple material and the extent of
the temperature difference between the measuring point and the cold junction. It can be
measured using the millivolt meter with no auxiliary power.
Compensation cable has the same thermoelectric behavior as the thermocouple in a limited
temperature range.
Extension cable is a thermocouple but designed as an installation cable.
OPTITEMP TT 10 C/R
Simply put, the thermocouple behaves like a battery, the voltage of which also increases as the
temperature rises.
INFORMATION!
The characteristic curves and tolerances of commercially available thermocouples are
standardised in IEC 60584.
3 Transition junction t
4 Compensation cable / extension cable
5 Reference junction t
6 Copper conductor
7 Voltage meter U
(hot junction)
1
2
(cold junction)
3
th
42
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 43
OPTITEMP TT 10 C/R
TECHNICAL DATA 7
7.2 Technical data
INFORMATION!
•
The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.
•
Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).
Measuring system
Application rangeTemperature measurements in an industrial environment.
Design
Versions
Versions
VersionsVersions
TT 10 CIn-head transmitter for RTD input, optionally available in an intrinsically safe
TT 10 C T/CIn-head transmitter for thermocouple input, not available as intrinsically
TT 10 RRail-mount transmitter for RTD input, not available as intrinsically safe
TT 10 R T/CRail-mount transmitter for thermocouple input, not available as intrinsically
Special feature
Special feature
Special featureSpecial feature
Sensor break monitoringUser-definable output: ≤ 3.6 mA or ≥ 23 mA
version for installation in potentially explosive areas (zone 0).
safe version.
version.
safe version.
Measuring accuracy
AccuracyCalibration: ± 0.1% of span
Cold Junction Compensation (CJC)
for TT 10 T/C
Temperature influencePt100: ± 0,024% of span per °C
Linearity: ± 0.1% of span
±1.0 °C / ±1.8 °F
Thermocouple: ± 0,024% of span per °C plus temperature influence CJC
± 0,05°C per °C
Operating conditions
Temperature
Temperature
TemperatureTemperature
In-head transmitterOperating and storage temperature:
Rail-mount transmitterOperating and storage temperature:
Operating and storage temperature:Operating and storage temperature:
Non-Ex version: -40...+85°C / -40...+185°F
Ex version: -40...+85°C / -40...+185°F (storage temperature), for detailed
information about the ambient temperatures refer to
potentially explosive areas
Operating and storage temperature:
Operating and storage temperature:Operating and storage temperature:
-20...+70°C / -4...+158°F
on page 46.
Temperature data for
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
43
Page 44
7 TECHNICAL DATA
OPTITEMP TT 10 C/R
Installation conditions
MountingIn-head transmitter: "B connection head" or larger according to DIN 43729;
WeightIn-head transmitter (Non-Ex and Ex version): 40 g / 0.09 lb
DimensionsFor detailed information refer to
with the help of the rail mounting kit you can also fix this transmitters on a
DIN rail according to EN 60715 TH35 (formerly EN 50022) ( refer to
mounting kit for in-head transmitters
Rail-mount transmitter: rail according to EN 60715 TH35 (formerly EN
50022), 35 mm / 1.38".
For detailed information refer to chapter "Installation".
Rail-mount transmitter: 55 g / 0.12 lb
on page 18).
Dimensions
on page 45.
Rail
Materials
HousingIn-head transmitter: PC (Non-Ex), Zinc alloy + PC (Ex version)
Rail-mount transmitter: PC + Glassfibre
Flammability acc. to ULV0 (all versions)
Electrical connections
Power supply
Power supplyIn-head transmitter: 6.5...32 VDC (Non-Ex version), 8.5...30 VDC (Ex version)
Power supplyPower supply
Rail-mount transmitter: 6.5...32 VDC
Galvanic isolationNo
Connection
Polarity protectionStandard for all versions
Single/stranded wires: max. 1.5 mm2/ AWG 16
Inputs / Outputs
Input
Input
InputInput
Pt100 (IEC 60751, α=0.00385)Type of connection: 3-wire
Span: 50/100/150/200/300/400/500°C and 100/200/300/400/600/800/1000°F
Zero point: -50...+50°C / -60...+120°F
Fine adjustment of span: ±10% of span (±5% for 600, 800 and 1000°F)
ThermocoupleConfiguration span: 9 mV to 55 mV continuous
Corresponding to:
T/C J: 170-950 °C / 305-1710 °F
T/C L: 165-900 °C / 300-1620 °F
T/C K: 220-1370 °C / 400-2470 °F
T/C N: 290-1300 °C / 520-2340 °F
T/C T: 200-400 °C / 360-720 °F
Zero point: ±10% of span
Output
Output
OutputOutput
Output signal4...20 mA, temperature linear, 2-wire connection
Update time≤ 200 ms
Permissible loadIn-head (Non-Ex) and rail-mount transmitter: 700 Ω at 24 VDC and 25 mA
NAMUR complianceNAMUR NE 21 (for frequencies ≥ 150 kHz)
44
4...20 mA, mV linear, 2-wire connection
In-head transmitter (Ex): 620 Ω at 24 VDC and 25 mA
www.krohne.com02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Page 45
OPTITEMP TT 10 C/R
TECHNICAL DATA 7
Approvals and certifications
CEThe device fulfils the statutory requirements of the EC directives.
Ex approvals
Ex approvals
Ex approvalsEx approvals
Non-Ex versionWithout
Ex version (only TT 10 C Ex, RTD version) Intrinsically safe according to II 1 G Ex ia IIB T4/T5/T6
Other standards and approvals
Other standards and approvals
Other standards and approvalsOther standards and approvals