Addition to the installation and
operating instructions
CORIMASS E + P Class
MFM 3081 K/F
MFM 2081 K/F
Ex-Version
Page 2
These instructions should be used in conjunction with the Standard Installation and
Operating Instructions for the MFM 2081/3081 K/F. If you require a copy, please contact
your nearest KROHNE Office or representative.
Product liability and warranty
The CORIMASS mass flowmeter MFM 2081/3081 K/F is designed for the direct
measurement of mass flow rate, product density and product temperature, and also
indirectly enables measurement of parameters such as total mass, concentration of
dissolved substances and the volume flow.
For use in hazardous areas, special codes and regulations are applicable which are
specified in the special ”Ex installation and operating instructions” (supplied only with
hazardous-duty equipment).
Responsibility as to suitability and intended use of our instruments rests solely with the
purchaser.
Improper installation and operation of the flowmeters may lead to loss of warranty.
In addition, the ”general conditions of sale” forming the basis of the purchase agreement
are applicable.
If you need to return CORIMASS flowmeters to KROHNE, please complete the form on the
last page of the Installation and Operating manual and return it with the meter to be
repaired. KROHNE regrets that it cannot repair or check your flowmeter unless accompanied
by this completed form.
2.1Location and connecting cables ........................................................................6
2.2Electrical Connection on converter without intrinsically safe outputs.....................6
2.3Electrical connection on converter with intrinsically safe outputs..........................9
2 Additional Instruction for Ex version MFM 2081 / 3081
Page 3
1 Description
The mass flowmeter MFM 2081/3081 K EEx and MFM 2081/3081 F EEx consists of two
main components:
The Signal Converter, which calculates and displays the measured values and the
transducer which supplies the converter with the analog signals.
A Cable Seal, which is screwed into the converter housing, leads the electric signals from
the transducer to the converter. The signal cable between the transducer and converter is
intrinsically safe.
In the separate version MFM 20381/3081 F EEx the transducer MFS 2000/3000 EEx and
the converter MFC 081 F EEx are connected to each other via a shielded multi-conductor
cable. The maximum cable length is 50 m.
The converter housing of the compact version MFM 2081/3081 K EEx is permanently
screwed onto the transducer and must not be removed at any time.
Cenelec Approvals
PTB approves the conformity of the mass flow meter according to the harmonized European
Standards:
EN50018"d" - Pressure tight housing
for the electronics housing and the terminal compartment
EN50019
EN50020
"e" - Increased safety
for the standard termination compartment
"i" - Intrinsically Safe
"b" for the Zener barriers and all electrical circuits inside the transducer
"a" for the converter outputs
The following approvals are valid:
Compact P and E meters, including intrinsically safe
EEx de [ib] IIC T6...T3
EEx d [ib] IIC T6-T3
EEx de [ia/ib] IIC T6-T3
EEx d [ia/ib] IIC T6-T3
Converter, remote mounted version, including intrinsically safe
EEx de [ib] IIC T6-T3
EEx d [ib] IIC T6-T3
EEx de [ia/ib] IIC T6-T3
EEx d [ia/ib] IIC T6-T3
P meter, remote mounted version
EEx ib IIC T6-T3MFS 2000 FPTB Ex 98.D.2038 X
E meter, remote mounted version
EEx ib IIC T6-T3MFS 3000 FPTB Ex 98.D.2039 X
Additional Instruction for Ex version MFM 2081 / 30813
MFM 2081 K
MFM 3081 K
MFM 2081 Ki
MFM 3081 Ki
MFC 081 F
MFC 081 Fi
PTB Ex 96.D.2037 X
PTB Ex 98.D.2037 X
Page 4
US-American Approvals
FM Class I, II & III Div. 1
Group A,B,C,D,E,F,G
FM Class I, II & III Div. 2
Group A,B,C,D,E,F,G
1.1 Description of the Transducer
The transducer MFS 2000-EEx and MFS 3000-EEx are intrinsically safe units and contains
three separated safe circuits. These are:
MFM 2081 K/F
MFM 3081 K/F
MFM 2081 K/F
MFM 3081 K/F
J.I.4B8A1.AX
J.I.4B7A7.AX
• ?Driver Circuit
• ?Sensor Circuit
• ?PT100 Circuit
The cables of these circuits are fed through the transducer housing via a special seal. There
are various transducer sizes available with different end connection options. Although
standard and EEx transducers appear the same, in fact the EEx version has a longer
converter mount (neck) and also contains specific clamping diodes fitted across the driver
coil. Therefore, it is essential to avoid using a standard converter with EEx transducer and
vice versa.
In order to fulfil the Ex certification requirements, it is absolutely necessary to comply with
the technical data. The maximum allowed process temperatures are:
MFS 3000 / E meter200°C
MFS 2000 / P meter200°C
MFS 2000 / P meter high temperature option, 60ºC
environmental temperature
MFS 2000 / P meter high temperature option, 55ºC
environmental temperature
1.2 Description of the Converter
The Ex converter is available in two different versions:
The ‘de’ version
The electronics are placed in a pressure tight section of the converter housing, protection
class ‘d’, while the termination compartment is not pressure tight. The converter housing
may be fitted with different cable glands such as NPT, PG16 or NPF glands for the mains
supply and the input/output cables. The protection class of the termination compartment
in ‘e’.
The ‘d’ version
The electronics as well as the termination compartment are placed in a pressure tight
housing. The termination compartment is not fitted with any gland for the mains supply or
the input/output cables. The customer is responsible for fitting an Ex approved cable gland
into the PG16 thread of the housing. There are various suppliers for such cable glands on
the market. The protection class of the termination compartment is ‘d’.
4 Additional Instruction for Ex version MFM 2081 / 3081
240°C
255°C
Page 5
For both cases the required waiting time between switching off the electronics and opening
the housing has to be considered. The waiting time is mentioned on the data plate of the
system and amounts to 25 minutes for T6 and 10 minutes for T5.
The Ex protection of the system is not valid if the electronics housing is not closed securely.
Make sure after opening the converter housing, to close it fully with the enclosed wrench.
The programming of the converter may also be performed with a closed lid by using the
supplied magnet. Three magnet sensors are assembled on the display board, which allow
the user to operate the converter without touching the display itself.
KROHNE MFC 081
Fig. 1: Converter
After opening the converter housing as described above, one of the following operations
may be performed by the local KROHNE service engineer :
• Replace supply fuse F9
• Changing electronics
• Changing supply voltage setting
• Changing EPROM’s
These operations are to be performed in an identical manner to the standard converter.
(Please refer to the standard operation manual). Make sure the correct mains fuse (right
value, ceramic body, 1500A breaking capacity) and the corresponding fuse label on the
fuse housing is used. Fuses and labels may be ordered from KROHNE.
Using wrong fuses violates the Ex approval and may damage the system. The earthing
metal sheet of the electronic must be fastened firmly with the screw onto the converter
housing!
The converter should be ‘high pot’ tested according to a specific procedure. Therefore, it is
not permitted to change output modules or any other hardware components (except the list
mentioned above by the local service engineer) without repeating the ‘high pot’ test.
Please contact KROHNE for advice.
1.3 Installation of MFM 2081 / MFM 3081 EEx
In order to get the highest possible accuracy, the user is advised to carry out the pipework
installation as described in the standard manual.
Additional Instruction for Ex version MFM 2081 / 30815
Page 6
Further requirements / differences are listed below:
• ?The ideal installation factor of an EEx unit is much higher than of a standard system due
to Zener barriers and clamping diodes the EEx system consumes more power during
running. The high installation factor does not mean a lower accuracy.
• The installation factor should have a value as indicated in the following table.
Meter SizeInstallation factorMFM 2081 K/FMFM 2081 K/F ExMFM 3081 K/FMFM 3081 K/F Ex
< 50< 100< 20< 60
The correct operation of the Zener barriers inside the converter are only guaranteed with a
robust and safe connection of the converter housing with potential earth (potential
compensation PA). Please use the outer earthing connector at the square flange of the
converter housing for earthing.
In case the converter housing has a pressure tight termination compartment, make sure the
connected cable glands / adapters have an Ex certification.
2 Electrical installation
2.1 Location and connecting cables
LocationDo not expose the compact flow meter to direct sunlight. Install a sunshade if necessary.
Connecting cablesTo conform to protection category requirements, observe the following recommendations:
• Fit blanking plug PG 16 and apply sealant to unused cable entries.
• In case if the terminal area is EEd, please use approved blanking plug.
• Do not kink cables directly at cable entries.
• Provide water drip point (U bend in cable).
• Do not connect rigid conduit to cable entries.
• If cables are a tight fit, enlarge inside diameter of cable gland by removing the
appropriate ring(s) from the seal.
2.2 Electrical Connection on converter without intrinsically safe
outputs
Please ensure that the information about power given on the dataplate corresponds to the
locally available mains voltage.
• Note information given on the instrument dataplate (voltage, frequency)!
• Electrical connection in conformity with IEC 364 or equivalent national standard.
• Special regulations apply to installation in hazardous areas. Please refer to separate
"Ex" installation instructions.
6 Additional Instruction for Ex version MFM 2081 / 3081
Page 7
• The PE protective ground conductor must be connected to the separate U-clamp
terminal in the terminal box of the signal converter.
• Do not cross or loop the cables in the terminal box of the signal converter. Use
separate (PG or NPT) cable glands for power and output cables.
• Ensure that the screw thread of the round cover on the terminal box is well greased at
all times.
NOTE: The grease used must be non-corrosive to aluminium; it must be resin- and acidfree.
• Protect sealing ring from damage.
5 6 4 4.1 4.2 11 12
N L AC
Output- - + DC
Connection PE
s. table
Fig. 2: Power and signal connections for MFC 081 K/F without intrinsically safe outputs
The tables below show the possible input output connection for the converter. The exact
configuration depends on which optional output modules were fitted in the factory.
Table of input/output connections
Nr.Option 1 (Current, pulse, alarm
and input)
Common (-)Common (-)
5
Current output (+)Current output 1 (+)
6
Control inputControl input
4
Pulse outputCurrent output 2 (+)
4.1
Status output (active)Status output (passive)
4.2
* The inputs/outputs share a common signal ground which is galvanically isolated from the
ground (PE)
In addition, the signal may need protection from external interferences. The use of screened
cables and a filter capacitor next to any counter is recommended (Fig. 3).
It is possible to connect the pulse output without an external voltage supply. However to do
this the function of the status output must be sacrificed. (Fig. 4)
If the alarm output is used to power the pulse signal then the following settings must be
made in the menus:
(i)Fct. 3.5.1 ALARM FUNCTION must be set to OFF.(ii)Fct. 3.5.2 ALARM ACTIVE LEVEL must be set to ACTIVE LOW.
Option 2* (2x current, not
galvanically isolated)
Additional Instruction for Ex version MFM 2081 / 30817
Page 8
(Max. 24 V DC)
V
ext
≥ 150 mA
R
ext
Fig. 3: Preferred connections to an external counter with separate power supply
(Example). For correct wiring see tables of input/output connections
(>1200 Ohm)
Fig. 4: Connection without external voltage source (Example). For correct wiring see tables
of input/output connections
Additional input/output options
No.Option 4*Option 5*Option 6
(Current and RS 485)(Current and Modbus)(1 Current, 1 Dual phase pulse