KROHNE BM90 User Manual

Page 1
Level-Sonic Non contact level gauging using ultrasonic waves
Inst allation and operating instructions
BM90/BM90L BM90E/BM90LE
05/99
KROHNE S.A.
CERTIFIED
ISO 9001
C E
BM90 / L
BM 90 E / LE Panel mounted
Page 2
2
LEVEL-SONIC BM90 SERIES
Contents Page
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1. Level-Sonic BM90 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.2. Initial start up Level-Sonic BM90 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2.1. How to view parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2.2. How to change parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2.3. Programming example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.3. Program checking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.3.1. Program correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2. Inst allation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1. Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1.1. BM90 / L Wall mounted converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1.2. Transducer wiring for BM90 / L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.1.3 Transducer Cable Extensions for BM90 / L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.1.4. BM90 E/ LE Panel mounted converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1.5. Transducer wiring for BM90 E / LE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1.6 Tranducer Electrical Connections for BM90 E / LE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.1.7 Transducer Cable Extensions for BM90 E / LE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.2. Transducer mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.2.1. Alternativ mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.3. Temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3. Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.1. Keypad definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.2. Display descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.3. Security code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.4. Application programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.5. Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.5.1. Parameter index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.5.2. Parameter definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
4. Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.1. Level measurement mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
4.2. Measurement with volumetric conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
4.3. Pump control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
4.4. Differential level mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
4.6. Open channel flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
4.7. Open channel flowmeter with penstock control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5. Fault finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
5.1. Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
5.2. Programming sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
6. Technical data Level-Sonic . . . . . . . . . . . . . . . . . . . . . .37
6.1. Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
6.2. Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Appendix 1 : Vessel - Flume linearisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Appendix 2 : Serial Communications BM90 L only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Appendix 3 : Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Page 3
1. Introduction
1.1. Level-Sonic BM90
The KROHNE S.A. Level-Sonic BM90/BM90E is a multipurpose liquid level measurement and flow control instrument. The KROHNE S.A. Level-Sonic BM90L/BM90LE is also available for powder and granulate level.
It consists of two main elements, a microprocessor based transceiver and a high-efficiency transducer.
Ultrasonic pulses are transmitted by the transducer to the surface of the material to be monitored and, within millisec­onds, are reflected back to the transducer. The time period between transmission and reception of the pulses is directly proportional to the distance between the transducer and the material.
The Level-Sonic BM90 microprocessor computes this time period continuously for all echoes received and analyses which is the correct reflection from the surface being monitored. It uses this data as the basis for giving control outputs and displays, in useable engineering units.
Level-Sonic BM90 is capable of the following functions :
a) Level Measurement
b) Volume Measurement
c) Distance Measurement
d) Pump Control
e) Differential Level Measurement
f) Open Channel Flow Measurement
WARNING
DO NOT OPEN THE ELECTRICAL COVER WHEN THE POWER IS ON TO
THE SUPPLY OR RELAY TERMINALS.
NOTE : There is no need to remove the upper cover. If you need to access to the RS232 or RS485 terminal for the BM90L then you have to open it.
IN THIS EVENTUALLITY, PLEASE REMOVE IT GENTLY, A FLAT CABLE IS ATTACHED TO THE COVER. TAKE CARE NOT TO DESTROY IT.
3
Page 4
4
1.2. Initial st art up Level-Sonic
The Level-Sonic BM90 system requires programming by the operator to obtain the required measurements and control. To become familiar with the use of the system, it is suggested that the following Q UICK START G UIDE is used before the instrument is installed.
Quick Start Guide :
1. Connect power and transducer cables as defined on the instrument.
ac Power Supply Transducer dc Power Supply [ 1 ] [ 2 ] [ 3 ] Terminal Nos: [ 19 ] [ 20 ] [21 ] [27 ] [28]
E N L Black Blue Screen +ve -ve
2. The instrument is supplied factory set on initial power up to work in distance measurement up to 10 metres from the transducer on the Level-Sonic BM90/E and 15 metres on the Level-Sonic BM90L/LE.
3. Hold the transducer approximately 1.5 metres from a flat surface and switch on.
After a short period, the display will show the distance (e.g. 1.50) between the transducer and the surface.
If the transducer is now moved slowly towards the sur­face, the reading should decrease. This shows that the unit is correctly wired and is operating as expected in response to the reduction in distance.
If the reading increases as the transducer is moved towards the surface, it indicates that the unit has been previously programmed to read level not distance.
1.2.1. How to view parameters
The operational program for Level-Sonic BM90 is con­tained within the parameters listed on Page 17 . Each parameter instructs the unit to carry out a specific func ­tion. To look at the complete list of parameters, please refer to chapter 3 but as an intitial guide proceed as fol ­lows :
Press ’MODE’, the display will show ’PROG’. (there may be a delay of up to 6 seconds if the instrument is busy). Press ’1’ immediately to obtain a display of Pr.01 or the previous parameter number used.
It is now possible to key in any parameter number, via the keypad. To display its value press ’DSP’. To return to the parameter number press ’DSP’ again.
To view a sequence of parameter numbers, enter the first one that is of interest and then press ’ s’ to increase the parameter number or ’t’ to decrease the parameter number.
Similarly, if a parameter value is displayed then press­ing ’s’ or ’t ’ key will momentarily flash the next para­meter number and then display that parameter value.
If a key is not pressed for a period of 30 seconds the unit will automatically return to the run mode.
Press ’MODE’ to return Level-Sonic BM90 to the ’RUN’ mode.
1.2.2. How to change parameters
l Press ‘MODE‘ t o display ‘prog‘.
Whilst ’prog’ is displayed press ‘1‘ and the display will show either Pr.01 or previous Pr. number. If not Pr. 01 then press ‘1‘ to obtain display of Pr.01.
l Press ‘DSP‘ t o display the value of Pr.01.
l Press ‘ENT‘ and the display will show ‘COdE‘
requesting that a security code is entered.
l Press ‘9753‘ to enter the factory set security code.
(see page 16 to change code)
l Press ‘ENT‘ and the display will blink and show
either the default value of Pr.01 which is 2, or any other value previously programmed into it.
The unit is now ready to be programmed.
Note : Whenever ‘COdE‘ is displayed, re-enter the secu­rity code.
The display should now beshowing the value entered in ‘Pr.01‘ which is 2.
To change the value of this or any other parameter press the new number required and ‘ENT‘. For our example press 1 and ‘ENT‘ and the value of Pr.01 will change to 1 which means it is in level mode i.e. measuring liquid height above datum.
Then using the ‘
s‘ key move to the other parameters that
require changing.
To change the value of any other parameter either use the ’ s’ key to move to higher Pr numbers, or press ’DSP’ and then enter the Pr number required and press ’DSP’ again to display its value.
Page 5
5
1.2.3. Programming example
The following example shows how Level-Sonic BM90 should be programmed for a simple level application including setting a high alarm.
Having changed the value in Pr.01 to = 1 (level Press
‘s‘ Display Pr.02 = 2 (units in meters) ‘s‘ Change Pr.03 = 1.5 (empty distance) ‘s‘ Change Pr.04 = 1.0 (operational span) ‘s‘ Change Pr. 05 = 0.5 (blanking distance) ‘s‘ Display Pr.06 = 1 (rate of change of
level in metres)
Press Pr.08 Change Pr.08 = 1 (relay 1 designated
normally energised) ‘s‘ Change Pr.09 = 0.7 (relay 1 set) ‘s‘ Change Pr.10 = 0.5 (relay 1 re-set)
MODE to return to normal running
For a full description of parameter options, please refer to chapter 3.
Note : The display does not show the decimal point until the first decimal figure is keyed in.
1.3. Program checking
To check that the previous program functions properly,
hold the transducer approximately 1.5 m above a surface and press ‘MODE‘ to return to the run condition.
The display will read approximately zero.
If it displays LOST it is because the transducer is more than the 1.5 metre (distance to furthest point) from your target. Go closer and wait for LOST to change to 0.000 and then a level.
By slowly moving the transducer towards the surface, the display will increase simulating a rising level. When the display exceeds 0.7 the relay will switch, as indicated by the light on relay 1, and if the transducer is then raised, the display will decrease and the relay will reset below
0.5.
1.3.1. Program correction or resetting factory defaults
If at any time you feel that a mistake has been made, the following routine clears the program back to the known starting position of the factory set values shown on page 26. It is also advisable to return to the factory default values before building a program for a new appli­cation. This is achieved as follows :
Press
‘MODE‘ to display PROG .
1 immediately to display a Pr number
‘99 ‘ to display Pr.99.
D S P to show ==== ‘C E ‘ to clear the display. ‘E N T‘ to display COdE requesting the security
code. ‘9753‘ ‘E N T‘ the display will now show ‘t.rES‘
followed by ’P.rES’ and finally ‘====‘. ‘DSP‘ to display ‘Pr.99‘ and now the new
program can be entered.
The above is a brief introduction.
1.0 (Pr.4)
1.5
(Pr.3)
0.5 (Pr.5)
Relay 1 Reset
0.5 (Pr.10)
0.7 (Pr.9)
Nota : To understand programming completely it is necessary to read the detailed section describing Programming, Section 3, along with the parameter descriptions, Section 4, and the examples, Section 5, before continuing.
Page 6
6
2. Inst allation
The installation of the Level-Sonic BM90 unit is straight forward, providing the guidelines in this chapter are fol ­lowed.
2.1. Converter
The BM90 / L unit (Fig 1) must be mounted on a flat sur­face secured by the 3 mounting holes. For the BM90 E/LE, see panel cut out figure 5. When mounting the unit avoid vibration or close proximity to high voltage cables, contactors and drive controls. The unit should not be mounted in direct sunlight or in a con­fined space where temperatures may exceed the normal working temperature. If the unit is mounted outside it
must be protected from severe weather conditions. Note : Electrical Connection
Converter instrument has 2 covers, the bottom one with 2 screws is protecting terminals. See Fig. 6 for the wiring diagram. Replace cover after completion of wiring.
Note : Select the correct working voltages for AC On converter instrument the voltage selector switch is on
the left hand side of the bottom PCB.
Note : If DC power supply is required, instruments will be marked accordingly.
NOTE : There is no need to remove the upper cover. If you need to access to the RS232 or RS485 terminal for the BM90E then you have to open it.
IN THIS EVENTUALLITY, PLEASE REMOVE IT GEN­TLY, A FLAT CABLE IS ATTACHED TO THE COVER. TAKE CARE NOT TO DESTROY IT.
2.1.1 BM90 / L Wall mounted converter
Fig 1:
Page 7
7
Figure 2:
AC power supply - connected:
Earth to terminal 1 Neutral to terminal 2 Live to terminal 3
The instrument will automatically accept either 110V or 230V AC –10%, 50Hz or 60Hz, 12VA. A time lag fuse T160mA is fitted.
DC power supply - connected :
Positive +ve to terminal 27 Negative -ve t o terminal 28
The instrument will accept 24V DC + 25%, - 10%. 9W. A time lag fuse T315mA is fitted.
5 SPDT Relays - rated 8A/250V AC/30V DC resistive, with gold contacts for lower power switching, are connect­ed to terminals 4 to 18, for activating external alarms, contactors, pumps etc..
Transducer RZV15 - i s connected:
Black to terminal 19 Blue to terminal 20 Screen t o terminal 21
Temperature compensated transducer RZT15 ­is connected:
(Screen t o terminal 19
Must enable Pr.37 (Blue to terminal 20
(Black to terminal 22
Isolated Analogue - i s connected :
Screen t o terminal 24 Positive +ve to terminal 25 Negative -ve t o terminal 26.
Separate Temperature Compensation - when compen­sation is provided by a separate temperature sensor, the sensor should be connected with a shielded twisted pair and connected:-
(Screen to terminal 21
Must enable Pr.37 (Core* t o terminal 22
(Core* to terminal 23
* The polarity of the cores is unimportant, but it is impor ­tant that the screen is connected only at the instrument end and not at the temperature sensor end.
1 2 3
E N L L2 L1
AC POWER
110/230 VAC
+10%/-10%
50/60 HZ 12VA
19 20 21 22 23 24 25 26
27 28
+ -
DC Power
21.6-30VDC 9W
Isolated Analog Output
+
-
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
RELAY 1
RELAY
RELAY
RELAY 5
RELAY 2
2.1.2. Transducer Wiring for BM90 / L
The wall mount instrument has two-part screw terminals. It can be powered from either an AC or DC supply.
Simultaneous AC & DC powering can be done through an external relay which switch on the other power when the main one is off. The relay contact will be released when main power is off. Ask for scheme if necessary.
Page 8
8
2.1.3. Transducer Cable Extensions for BM90 / L
Transducer cables may be extended using junction boxes as shown below in Figure 3:
Junction
Screen - Term 19
Standard Transducer
Transceiver
Core - Term 20
Transducer
Black
Screen
Blue
RG62AU
Temperature Compensation Transducer
RG62AU
Blue
Junction
Core - Term.22 Screen - Term.19
Core - Term. 20
Screen - Term.19
Transceiver
Transducer
Black
Screen
Figure 4:Transducer Wiring for Differential Mode
UP & DOWNSTREAM SHIELD
Junction
Screen - Term 19 Transceiver
Core - Term 18
Upstream Transducer
Black
Screen
RG62AU Junction
Screen - Term 21
Transceiver Core - Term 16
Downstream Transducer
Black
Screen
Blue
RG62AU
Extend transducer cable if necessary
with RG62AU as shown.
1 2 3
E N L
L 2 L1
AC POWER
110/230 VAC
+10%/-10% 50/60 HZ 12VA
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
RELAY 1
RELAY 3
RELAY 2
27 28
+ -
DC POWER
21.6-30VDC
9W
19 20 21 22 23 24 25 26
ISOLATED
ANALOG
OUTPUT
-
SHIELD
HOT.BLUE
BLACK
+
TEMP
SENSOR TRANS-
DUCER
SHIELD
RELAY 4
RELAY 5
LINK
UPSTREAM - BLUE
DOWNSTREAM - BLUE
UP & DOWNSTREAM BLACK
Page 9
9
KROHNE
134
5
2
Level-Sonic
1
HI.TO
5
R1.HR
9 R1.ST
CE R5.HR
R5.ST
2 LO.TO
TEMP6R2.HR
0 R2.ST
#
3 HEAD
7
R3.HR.R3.ST
MODE
DSP
DIST
4
FLOW
8
R4.HR_R4.ST
TEST
GAIN
ENT
m
96 144
90-91 PANEL CUTOUT 150 BEHIND PANEL
2-20 PANEL WIDTH
10
8
FUSE 160mA ANTISURGE
ANALOGUE
6
5
9
4
3
7
TRANSDUCER
TCOMP
TRANSDUCER
HOT
1
2
N
E
L
MAINS SUPPLY
SER.NO.
FUSE
315mA ANTISURGE
RELAYS
18
17
19
RELAY 4
21
20
22
12
11
13
15 14
16
24
23
28
SHIELD
27
25
26
+
_
ANALOGUE OUTPUT
RELAY 4
RELAY 3
RELAY 2
RELAY 1
RELAY 5
0V
24V
DC SUPPLY
AC SUPPLY
2.1.4. BM90 E/LE Panel mounted converter
The panel mount instrument has two rear screw termi­nals. There is no serial commnucation connector even on the BM90 LE
2.1.5. Transducer wiring for BM90E / LE
fig 6
fig 5
Page 10
10
2.1.6 Transducer Electrical Connections For BM90 E /LE - Figure 7 below
The panel mount instrument has two-part screw termi­nals. It can be powered from either an AC or DC supply.
AC power supply - connected: Earth to terminal 1
Neutral to terminal 2
Live to terminal 3 The instrument will automatically accept either 110V or 230V AC –10%, 50Hz or 60Hz, 12VA. A time lag fuse T160mA is fitted.
DC power supply - connected :
Positive +ve to terminal 10
Negative -ve t o terminal 0v The instrument will accept 24V DC + 25%, - 10%. 9W. A time lag fuse T315mA is fitted.
5 SPDT Relays - rated 8A/250V AC/30V DC resistive, with gold contacts for lower power switching, are connect­ed to terminals 11 to 25, for activating external alarms, contactors, pumps etc..
Transducers: The Level-Sonic BM90 uses RZV15 series transducer. The Level-Sonic BM90L uses RXV15 series transducer.
Transducer RZV15 and RXV15 - are connected:
Black to terminal 4 Blue to terminal 5 Screen t o terminal 6
Temperature compensated transducer RZT15 and RXT15 - are connected:
(Screen t o terminal 4
Must enable Pr.37 (Blue to terminal 5
(Black to terminal 8
Isolated Analogue - i s connected :-
Screen t o terminal 26 Positive +ve to terminal 27 Negative -ve t o terminal 28
Separate Temperature Compensation - when compen­sation is provided by a separate temperature sensor, the sensor should be connected with a shielded twisted pair and connected:
(Screen to terminal 6
Must enable Pr.37 (Core* to terminal 7
(Core* to terminal 8 * The polarity of the cores is unimportant, but it is impor ­tant that the screen is connected only at the instrument end and not at the temperature sensor end.
2.1.7 Transducer Cable Extensions for BM90 E / LE
Junction Screen - Term 4
Standard Transducer
Transceiver
Core - Term 5
Transducer
Black
Screen
Blue
RG62AU
Temperature Compensation Transducer
RG62AU
Blue
Junction
Core -Term.7
Screen - Term.4 Core - Term.5
Screen - Term.4 Transceiver
Transducer Black
Junction
Screen - Term 4
Transceiver
Core - Term 25
Upstream Transducer
Black
Screen
Blue
RG62AU
Junction
Screen - Term 4
Transceiver
Core - Term 23
Downstream Transducer
Black
Screen
Blue
RG62AU
Transducer cables may be extended using junction boxes as shown in Figure 7 below
fig 7
Transducer wiring for Differential Mode - fig 8
Extend transducer cable if necessary
with RG62AU as
shown
Link terminals 5 and 24 together
4
23
6
5
24
25
Link
(Without extension cable)
Up & Downstream Sreens
Up & Downstream Blacks
Upstream Blue
Downstream Blue
8
Page 11
11
2.2. Transducer Mounting
The transducer can be supplied as ’standard’ or mounted in a Teflon faced flange for applications requiring chemical compatibility. The figure below shows the dimensions:
20
170
Isolation Kit
Fit as shown
20
2172100 10m cable
6.9 dia
50
M20 x 1.5
95
Dia to suit flange selected
No. & size of bolts
to suit flange selected
Bolt hole PCD to suit
flange selected
DIA
DIA
DIA
Standard
Flanged
An isolation kit is provided with each transducer to min­imise any ringing transmitted through the mounting struc ture.
The transducer must be mounted perpendicular to the monitored surface and, ideally, at least 0.5 metres above it.
The transducer has a 10 inclusive conical beam angle at 3dB and must be mounted with a clear unobstructed sight of the liquid to be measured over the complete measurement range.
The transducer is provided with integral cable which can be extended up to 300 metres using a suitable junction box and RG62AU cable. The temperature compensated transducer requires an additional single core screen extension. The extended cable should then be terminated directly into the instrument.
Transducer cables and temperature compensation cables can be run together but should be separated from power cables by at least 150mm and preferably installed in their own earthed steel conduit.
Page 12
12
2.2.1. Alternative mounting arrangements for transducer
FLEXIBLE OR RIGID
CONDUIT.
BRACKET.
UNDER FLANGE.
INTEGRAL FLANGE WITH PTFE FACE.
SLIP-ON FLANGE.
ISOLATION KIT.
ISOLATION KIT.
OPTIONAL
ISOLATION KIT
Do not mount transducers incorporating temperature compensation in direct sunlight.
Do not over-tighten the bolts on flange construction trans­ducers.
Flange transducers are not pressure rated and are suit­able only for atmospheric pressure.
CENELEC approved transducers must be mounted and
wired in accordance with the appropriate National Standards concerning installation in hazardous environ­ments.
For differential applications mount both transducers at the same height above the zero datum point.
For open channel flow applications the transducer must be mounted upstream of the flume or weir as detailed in BS3680 (usually 3 or 4 times maximum head).
Page 13
13
KEEP TRANSDUCER
PERPENDICULAR TO LIQUID.
KEEP TRANSDUCERS AND
TEMPERATURE COMPENSATION PROBES OUT OF DIRECT SUNLIGHT
DO NOT AIM THROUGH HOLES IN THE TANK
.
AVOID ROUGH EDGES
IN STANDPIPES
.
AVOID INFLOWS OR
OTHER OBSTRUCTIONS
.
CAUTION: AVOID THE FOLLOWING TRANSDUCER INSTALLATION FAULTS
Standpipe Installations
In many applications access to a vessel must be made via a standpipe. However, it is necessary to observe some basic rules when fitting transducers into stand­pipes.
BLANKING: Parameter 5 should always be set at
least 150 mm longer than the length of the standpipe.
STANDPIPE should be in accordance with the follo-
wing table
DIMENSIONS: Flange size and minimum Maximum length bore of Standpipe of Standpipe
3" ( 75mm) 300mm 4" (100mm) 300mm 6" (150mm) 400mm 8" (200mm) 600mm 12" (300mm) 600mm e.g. : Using a 4" flanged transducer would require the standpipe length to be no more than 300mm and Pr.5 set at 450 mm minimum.
The inside of the pipe and joint with vessel top must be clean and free of any obstructions, seams or welds.
Isolation kit
dia 95 (3.74")
M20 X 1.5
22 (0.86")
155 (6.10")
PVC flange
Page 14
14
2.3. Temperature Sensor
If a separate temperature sensor is to be used it must be mounted where it will monitor temperature changes of the air between the transducer and the liquid. This is usually adjacent to the transducer, but should not be in direct sunlight and should be protected from wind chill.
35
TEMPERATURE SENSOR RTS 2B
175
25
34 ref
3/4" BSPP
-
12
50 INTERNAL
EARTH
UNIMPORTANT
+
POLARITY
LOCK
SCREW
9 dia
33 HEX
HOUSING: CAST IRON BLACK EPOXY PAINT
CLASSIFICATION EEx e II T6/IP 65
PROBE: 316ST. STEEL
52 30 dia
EXTERNAL
EARTH
15
28 DIA
M20 x 1.5
10 DIA
202550
M20 x 1.5
BLUE
TERMINALS
(VIEWED ON TOP)
HOUSING: POLYCARBONATE
PROBE:316 SS
5 REF 150
TEMPERATURE SENSOR RTS 2
85 DIA
53
72 DIA
N/C
Page 15
15
3. Programming
The Level-Sonic BM90 has two modes :
a) RUN (normal operating) b) PROG (programming)
In the ‘RUN‘ mode, the instrument is monitoring the tar­get, displaying values and setting outputs as pro­grammed by the operator. In the ‘PROG‘ mode, the operator uses the keypad in conjunction with the display to adjust the settings and to test that the unit is programmed correctly.
3.1. Keypad definitions
The keypad consists of 20 keys which are used to con­trol the operation of the converter.These keys also have secondary functions indicated above them (See Figure
5) enabling the operator to view the results being obtained by the instrument during its normal ’RUN’ cycle.
3.2. Display Descriptions
The following display codes are used :
PROG
RUN
Pr.XX
COdE
====
FULL
-FUL
P.rES
t.rES
LOSt
tESt
gAIN
HEAd
FLO
HI.tO
LO.tO
deG.C
dISt
An.OP
Precedes program mode
Precedes run mode
Parameter number
Security code request
No value
Numerical overflow of display i.e. value too large to display Negative numerical overflow Check taht Pr.43 is correct
Resetting to factory parameters
Resetting totalizer
Loss of echo
System performing a requested test
Gain value being displayed
Head
Flow
Totaliser high 4 digits 9999 (----)
Totaliser low 4 digits (----) 9999
Temperature C
Distance
Analogue output
Primary Key Functions
Active Secondary Key Functions During normal ’RUN’ mode it is possible for an operator to obtain the data defined as secondary function without interrupting normal operation, by pressing the appropri­ate key, i.e.
Key 7 Key 8
CE Key 9 Key 0
.
_
’s’
Test
ENT
DSP
’t’
Relay 3. Hours energised. Relay 4. Hours energised. Relay 5. Hours energised. Relay 1. Number of times energised. Relay 2. Number of times energised. Relay 3. Number of times energised. Relay 4. Number of times energised. Relay 5. Number of times energised. Displays gain Displays mA output. Displays distance from the transducer face. Displays temperature.
Keys 1 - 4
Key 5 Key 6
Show high totaliser, low totaliser, head and flow when in the OCM mode. Head will always show level. Relay 1. Hours energised. Relay 2. Hours energised.
0 - 9
.
-
CE
#
MODE
TEST
’s’
’t’
DSP
ENT
Numerical Values Decimal Point Negative value (also used to slow down simulation) Clear Entry (also used to leave test func­tions Pr.75 to Pr.78.) Returns display to normal ’RUN’ mode after viewing secondary functions (also speeds up simulation Pr.78) Alternates between ’RUN’ and ’PROG’ mode. Displays gain in ’RUN’ mode and allows parameter interrogation and simulation hold in ’PROG’ mode. Increase parameter number (also control of simulation direction). Decrease parameter number (also control of simulation direction) Display parameter number/value alter­nately. Enter a new value or initiate a system test under Pr.75 to Pr.78
Page 16
16
3.3. Security code
The Level-Sonic BM90 programme includes security code protection. Any operator can display the value of a parameter, but any attempt to enter a new value or per­form a test will result in the security code being request ­ed. The security code is requested by the prompt of ’COdE’, if the code is not entered correctly this prompt is re-dis ­played. Once the code has been input correctly, it will not be required again whilst the system remains in the ’PROG’ mode. The factory set value is 9753. A new "customer’s" security code, comprising 4 numeri­cal digits, can be entered via Pr.96, providing the opera­tor is in programme mode. The range of acceptable values is 1000 to 9999. If an invalid code is entered, the instrument will default to a code number 9753. The code number is scrambled immediately on entry. If you forget your security code ring your supplier for advice quoting the number stored in Pr.96..
3.4. Application programming
The programming of Level Sonic BM90 is controlled by the parameters summarised and listed later in this chap­ter. Programming is easy to follow because the parame­ters available to the programmer fall into distinct groups:-
Pr. 1 - Pr.6 Basic set up Pr. 8 - Pr.22 Relays 1 to 5 designation and settings Pr.23 - Pr.29 Failsafe operation Pr.30 - Pr.34 Set the analogue output Pr.37 - Pr.39 Temperature compensation Pr.40 - Pr.44 Volume conversion Pr.45 - Pr.50 Open Channel Flow Metering Pr.51 - Pr.57 Specialised Pump Control Pr.68 - Pr.70 Select echo detection and processing Pr.71 - Pr.74 Miscellaneous Pr.75 - Pr.78 Test Parameters Pr.95 - Pr.96 Number Stores Pr.97 - Pr.99 Resets
It can be seen from the above which distinct groups of parameters need to be considered for a particular appli­cation. For instance, in an application to measure level, it may be necessary to consider only Pr.1 to Pr.29 which are relative to basic set-up, relays and failsafe.
It is good practice to carry out a programme reset on a new application before starting programming as this will return all parameters to factory defaults and any parame­ters which are not required for the new application will remain at default, ensuring that the programme runs cor­rectly.
Default values for each parameter are shown in the para­meter definition , Section 3, and in the Parameter Setting table, Page 43.
3.5. Programming
The following is the programming sequence to set up a unit for operation. If you have not done this before, refer back to chapter 1 "Initial start up Level-Sonic BM90".
1. Calculate the correct values
From the information contained within this manual and the knowledge of the application, produce on
paper the correct values for the parameters required (use page 36 P rogramming sheet). To help you with this, see the examples on pages 27 to 32. Details of all the parameter options are listed on pages18 to 26.
2. Sequence to enter a new program or modify the existing one
l
Press ‘MODE‘. When display shows "Prog" press ‘1‘ and then press ‘DSP‘ followed by ‘ENT‘.
l
Display will show COdE and security code must be entered (factory default is 9753. For a new code see chapter 3.3).
l
The display will now show the value of Pr.01 or the last Pr. number used indicating that the correct secu­rity code has been entered.
If the unit is being programmed for a n e w application it is recommended that all parameters are reset to the factory programmed values as follows :
l 1.
Display Pr.99
l
2. Press ‘DSP‘ to show ‘====‘
l
3. Press ‘CE‘ to obtain a clear display
l
4. Press ‘ ENT‘ and the display will show ‘P.rES‘, then ‘t.rES‘ and then ‘====‘
l
5. Press ‘DSP‘ and enter Pr.01
l
6. Press ‘DSP‘ to display the value of Pr.01.
If a modification is being made to an existing program then the sequence re-commences here.
l
The new values for any parameter should be input, checking that the value is stored correctly. The para­meters can be accessed in series using ‘s‘ and ‘ t keys or individually by entering the required parame­ter number.
l Before entering the ‘RUN‘ mode, the program can be
checked by pressing Pr.78, then DSP , then ‘ENT‘. Level-Sonic BM90 will now simulate the operating program providing display, analogue output and relay functions
.
CAUTION : All Level-Sonic BM90 outputs will work under simulation,
so ensure that external connections will not cause dam­age.
l Press ‘CE‘ to leave simulation. l Press ‘TEST‘ to freeze and unfreeze simulation. l When the program is complete and does not require
further modification press ‘MODE‘ to return to the ‘RUN‘ condition.
Page 17
17
3.5.1. Parameter index Level-Sonic BM90
Basic Set-up Open Channel Flow
Pr.1 Application Pr.45 Flow Exponent Pr.2 Units Pr.46 Max. Flow Rate Pr.3 Empty Distance Pr.47 Time Base for Flow Rate Pr.4 Operational Span Pr.48 Totalise Display Conversion Pr.5 Blanking Distance Pr.49 Control of Ext. Totaliser Pr.6 Rate of change Pr.50 Penstock Control
Relays Pump Controls
Pr.8 Relay 1 Pr.51 Pump Sequence Pr.9 Relay 1 Set Pr.52 Duty Standby Pr.10 Relay 1 Reset Pr.53 Pump Exerciser Pr.11 Relay 2 Pr.54 Pump Tolerance Pr.12 Relay 2 Set Pr.55 Pump Maintenance Pr.13 Relay 2 Reset Pr.56 Run-on-Interval Pr.14 Relay 3 Pr.57 Run-on-Time Pr.15 Relay 3 Set Pr.16 Relay 3 Reset Echo Detection Pr.17 Relay 4 Pr.68 Echo Selection Algorithm Pr.18 Relay 4 Set Pr.69 Check Search Pr.19 Relay 4 Reset Pr.70 Echo Velocity Pr.20 Relay 5 Pr.21 Relay 5 Set Pr.22 Relay 5 Reset
Failsafe Miscellaneous
Pr.23 Failsafe R1 Pr.71 Correction Value Pr.24 Failsafe R2 Pr.72 Parameter Display Pr.25 Failsafe R3 Pr.73 Software Revision Number Pr.26 Failsafe R4 Pr.74 Reset Counter Pr.27 Failsafe R5 Pr.28 Failsafe Analogue Pr.29 Failsafe Time Delay
Analogue Test Parameters
Pr.30 Analogue Output Pr.75 Digital Output Set Pr.31 Analogue Value Options Pr.76 HardwareTest Pr.32 Analogue Datum Pr.77 Transmitter Test Pr.33 Analogue Span Pr.78 Simulation Pr.34 Analogue Test
Temperature Number Store
Pr.37 Probe Enable Pr.95 Serial Number Store Pr.38 Temp. Compensation Pr.96 Security Code Store Pr.39 Probe Test
Volume Conversion
Reset
Pr.40 Vessel Shape Pr.97 Relay Hours/Starts Totaliser Reset Pr.41 Dimension ’H’ Pr.98 OCM Totaliser Reset Pr.42 Dimension ’L’ Pr.99 Full System Reset
Pr.43 Display Conversion Pr.44 Volume Linearisation
NOTE: All other parameters are unused and should not be changed.
Page 18
18
Pr. 7 Decimal Display (D=2)
3.5.2. Parameter definitions
The parameters define all the options that are available to the operator of a Level-Sonic BM90. It may be easier to read these in conjuction with the application examples on pages 27 to 32. Note : (D=) factory default entry for that parameter.
Enter
1 Liquid Level Measurement 2 Distance Measurement 3 Differential Level Measurement (DLD) 4 Open Channel Flow Metering (OCM)
Enter one of the following codes :
1 Feet 2 Metres To display in percent of 3 Inches span, set Pr. 40 to 1 4 Centimeters
The system will be set to work in the specified units but the display can be made to display a percentage, a con­verted value or a volume (Pr.40).
Pr. 1 Basic Application (D=2)
Pr. 2 Calibration / Display units (D=2)
Note : Any subsequent change of units in Pr.2 (i.e. Pr.2 = 1-4) will reset parameters Pr.3 to Pr.6 to new units and all other parameters will default to factory resets.
Pr. 3 Empty Distance (D=10.00) / BM90L (D=15.00) The distance from the face of transducer to the furthest
point away, usually the bottom of the container or chan­nel. Enter the distance in the units selected in Pr.2. NOTE:- We reccomend setting the unit to factory defaults and let it measure the empty distance. Enable Pr.37 if using temperature compensation.
Resolution is a function of this parameter.
The distance between the furthest and nearest points over which measurement is required. Enter distance in the units selected in Pr.2. For differential applications, the value required is the maximum difference in the levels to be measured.
Pr. 4 Operational Span (D=10.00) / BM90L (D=15.00)
Pr. 5 Blocking or blanking distance (D= 0.50)
The distance in front of the transducer, within which the liquid should not enter and within which no return echoes will be processed.
Enter in the units selected in Pr.2 (not %).
IMPORTANT : PLEASE D O N OT REDUCE THE FACTORY SET
VALUE WITHOUT REFERENCE T O
KROHNE S
.
A.
Pr. 6 Rate of Change (D=1.00) This value should be as small as possible but greater
than the maximum rate of change of level. Do not change this value unless you know that the rate of change is greater than 1.0m/min or that the system con­tinually ’tracks’ a level lower than the actual level.
If it is necessary to change the value, enter the new value in units per minute selected in Pr.2. The suggested range of values is 0.1 to 10 metres/min or the equivalent.
Relays The 5 relays can be assigned to various functions depending on the application, as shown below:
Hysteresis is fully adjustable, so for most functions it is necessary to enter both "set" and "reset" values.
The relay state under normal operating conditions is defined as:-
(e) = normally energised. De-energise when "set" value is reached. (d) = normally de-energised. Energise when "set" value is reached.
"Failsafe" functions are detailed in Pr.23 - 27.
The relays can be programmed to give both high and low alarm or control levels.
e.g. High alarm Set: 2.0m Low Alarm Reset: 0.5m
Reset: 1.8m Set: 0.2m
The system will automatically configure itself as high or low alarm depending on which of the set and reset entries has the higher value.
Note that on distance measurement only (Pr.1 = 2), the highest value is furthest from the transducer.
Defaults are 0 for relay designations 8, 11, 14, 17 and 20. Defaults are 0.00 for relay settings 9 & 10, 12 & 13, 15 & 16, 18 & 19, and 21 & 22.
The relays are controlled from parameters 8-22 as fol­lows:
Relay 1 Relay 2 Relay 3 Relay 4 Relay 5
Designation Pr. 8 Pr.11 Pr.14 Pr.17 Pr.20 Set (l.e.d. on) Pr. 9 Pr.12 Pr.15 Pr.18 Pr.21 Reset (l.e.d. off) Pr.10 Pr.13 Pr.16 Pr.19 Pr.22
0 = No decimal places allowed. 1 = Up to 1 decimal place allowed. 2 = Up to 2 decimal places allowed.
3.= Up to 3 decimal places allowed
Page 19
19
The application - relay function options are shown on the following tables : (D = 0 or 0.00 for all)
Pr. 9 Relay 1 Set Pr. 10 Relay 1 Reset
Pr. 11 Relay 2 Designation
Pr. 12 Relay 2 Set
Identical to Pr. 8.
Identical to Pr. 9.
Pr. 13 Relay 2 Reset
Identical to Pr. 10.
Pr. 8 Basic A pplication - Relay F unction 1 - 2
(e) normally energised ( d) normally de-energised
de-energised to alarm energise to start (motor)
Relay 1 Pr. 1 = 1 / Pr.1 = 2 Pr. 1 = 3 Pr. 1 = 4
Designation Level / Distance Differential Open Channel Flow
Enter 0 O ff Off Off
1 Level Alarm (e) Level Alarm on ( e) Level Alarm ( e)
either transducer
2 Level Control ( d) Differential Alarm (e) Level Control ( d)
3 Off Differential Control (d) Flow Alarm (e)
4 Of f Downstream Level (e) Off
Alarm
5 O f f Upstream Level Alarm ( e) Off
6 Temperature Alarm (e) Temperature Alarm (e) Temperature Alarm ( e)
7 Loss of Echo ( e) Loss of Echo ( e) Loss of Echo ( e)
8 Run / Prog ( e) Run / Prog ( e) Run / Prog ( e)
Level/Differential
Enter values in display unit as selected Pr. 2.
Flow Enter values in unit selected at
Pr.46
Temperature Enter values in C
(only valid if probe fitted)
Loss of Echo No set/Reset entries are required or run/prog
Pr. 15 Relay 3 Set
Pr. 16 Relay 3 Reset
Pr. 17 Relay 4 Designation
Identical to Pr. 8.
Pr. 18 Relay 4 Set
Identical to Pr.9.
Pr. 19 Relay 4 Reset
Identical to Pr.10.
Pr. 14 Relay 3 Designation
Identical to Pr. 8.
Identical to Pr. 9.
Identical to Pr. 10.
Page 20
20
Pr. 29 Failsafe Time Delay (D=120)
Enter value (in seconds) before unit goes to selected fail­safe positions.Minimum value is 30 seconds.
Pr. 23 Relay 1 Failsafe) Pr. 24 Relay 2 Failsafe ) Pr. 25 Relay 3 Failsafe ) Pr. 26 Relay 4 Failsafe ) Pr. 27 Relay 5 Failsafe )
Note : Relay designated LOSS-OF-ECHO will always de-energise. Relay 5 Failsafe is not applicable in differential or OCM mode.
Enter 1 Energise
2 De-energise 3 Hold-state
one option for each relay
Pr. 28 Analogue and Display Failsafe (D=3)
Enter 1 Low
2 High 3 Hold Value
Level/Differential
Enter values in display unit as selected Pr. 2.
Flow Enter values in unit selected at
Pr.46
Temperature Enter values in C
(only valid if probe fitted)
Sampler Enter value in hours
(no reset needed)
Totalizer Refer to Pr.49
Loss of Echo No set/Reset entries are required or run/prog
Pr. 20 Relay 5 Designation - Basic Application - Relay Function
Pr. 21 Relay 5 Set Pr. 22 Relay 5 Reset
Pr.23 to 27 Failsafe (D=3 for all) On loss of power all relays will de-energise.
For other fault conditions e.g. damaged transducer, the failsafe relay state (after time delay selected at Pr. 29) is selectable.
(e) normally energised ( d) normally de-energised
de-energised to alarm energise to start (motor)
Relay 5 Pr. 1 = 1 / Pr.1 = 2 Pr. 1 = 3 Pr. 1 = 4
Designation Level / Distance Differential Open Channel Flow
Enter 0 Off N / A Off
1 Level Alarm ( e) N / A Level Alarm (e)
2 Level Control (d) N / A Level Control (d)
3 O ff N / A Flow Alarm ( e)
4 Off N / A Off
5 Off N / A Totalizer Drive (d)
6 Temperature Alarm (e) N / A Temp. Alarm ( e)
7 Loss of Echo ( e) N / A Loss of Echo (e)
8 Run / Prog ( e) N / A Run / Prog (e)
Page 21
21
Pr. 31 Analogue Value Options (D=1)
Pr. 32 Analogue Datum (D=0.00)
Pr. 33 Analogue Span (D=100)
Pr. 34 Analogue Output Test (D=0)
Pr. 30 Analogue Output (D=1)
Enter 1 - 4-20mA )
2 - 20-4mA ) > related to span (Pr.4) 3 - 0-20mA ) or Pr.33 4 - 20-0mA ) 5 - 4-20mA ) > will over-range 0-24mA
if normal span
6 - 0-20mA ) (Pr.4) is exceeded
The output represents different variables depending on the application mode selected at Pr.1
Limits are defined by Pr.4
Pr. 1 Entry Application Output Proportional To
1.00 Liquid Level a) Liquid Level b) Liquid volume if Pr.40 is used
2.00 Distance a) Target distance b) Space volume if Pr.40 is used
3.00 Differential (DLD) Differential level. (The unit can differentiate between positive and negative differentials. (See Pr.31)
4.00 Open Channel Meter (OCM) a ) If Pr.31 = 1 output proportional to head b) If Pr.31 = 2 output proportional to flow
NOTE: Refer to Pr.34 for output test.
In differential mode (Pr.1 = 3) Enter 1 - difference of two levels
- Pr.4 represents maximum differential in levels
2 - upstream level
- Pr.4 represents the difference between upstream empty distance Pr.3 and maximum upstream level.
3 - downstream level
- Pr.4 represents the difference between downstream empty distance Pr.3 and maximum downstream level.
In OCM mode (Pr.1 = 4) Enter 1 - for measured head (depth of liquid)
2 - for calculated flow
If an analogue output is required with a zero different from the measurement zero (Pr.3) then an offset defined as a percentage of the measurement span/flow/volume etc., can be entered here.
If an analogue output is required with a span different to that defined for the measurement (Pr.4) then an alterna­tive value defined as a percentage of the measurement span/flow/volume etc., can be entered here. A value of zero is ignored.
This parameter can be used to examine the last analogue output value set up by the instrument. Also any value in the analogue output range can be entered for loading to the current output, and can be measured at the output terminals, to test the external analogue circuitry.
Pr. 37 Temperature Sensor Enable (D=1)
Pr. 38 Compensating Temperature (D=20 C)
Pr. 39 Temperature Probe test (D=0)
1 = No sensor attached 2 = Senor attached
If no probe is fitted the vessel temperature may b entered here.
Displays the sensor resistance in K Ohms. Typically 9.5 at 20 C. If value shows ’0.00’ after switching ’Off’ and ’On’ then either no sensor is connected, or there is a short circuit or open circuit in the system.
Page 22
22
Enter the required value for open channel flow device being used.
e.g. Flow Device Enter
Unity 1 Rect. flume 3/2 2 Rect. weir 3/2 2 V-notch weir 5/2 3 Special 4 (Refer to Pr.44) Parshall Flumes 5-14
The OCM flow exponent (Pr.45) has been expanded to include 10 Parshall flume profiles. The data for the selected flume is loaded into the flume mapping system (Pr.44) from tables held in memory.
Size Exponent
5 : 1,2,3,24 inches 1.550 6 :6 inches 1.580 7 : 9 inches 1.530 8 : 12 inches 1.522
9 : 18 inches 1.538 10 : 36 inches 1.566 11 : 48 inches 1.578 12 : 72 inches 1.595 13 : 96 inches 1.606 14 : 10,12,15,20,
25,30,40,50 feet 1.600
Maximum head is entered in Pr.4 and the associated maximum flow in Pr.46. If one of the values is known, the other can be found in the flume tables or by calculation from
Q = KHn GPM,
where H = Inches, Q = US GPM and
K = Constant for flume size
(for imperial gallon multiply K factor by 0.8).
Pr. 45 Flow exponent (D=1)
Pr. 40 Vessel Shape (D=0)
Enter 1
Flat bottom
Enter 2
Pyramid bottom
Enter 3
Conical bottom
Enter 4
Half sphere bottom
Enter 5
Parabolic bottom
Enter 6
Flat ends
Enter 7
parabolic ends
’0’ = no volume conversion 1 = flat bottomed vessel and percentage of span 2 - 7 = standard shapes as shown below 8 = vessel linearisation (see Pr.44)
Pr. 41 Vessel Dimension H (D=0)
Pr. 42 Vessel Dimension L (D=0)
Pr. 43 Display Conversion (D=1)
Pr. 44 Linearisation (D= ==== )
Enter H where indicated above in units selected at Pr.2.
Enter L where indicated above in units selected at Pr.2.
If Pr.40 entry is between 1 - 8 then enter - full scale dis ­play ¸ 100 e.g. if 100% = 2000 litres and display required in litres then set Pr.43 to 2000 ‚ 100 = 20.
To display in any unit enter any value from ’0.001’ to ’9999’
NOTE: Display cannot be more than 4 digits. If it is neces­sary to measure 20,000 gallons, then display in thou­sands of litres (or cubic metres) by dividing 20 by 100 = 0.2.
This function allows non-standard flumes and vessels to be characterised. For full details please refer to Appendix 1, pages 39 to 40.
Page 23
23
Pr. 46 Maximum Flow Rate (D=0)
Pr. 47 Time Base of Maximum Flow Rate (D=1)
Pr. 48 Totalizer Display Conversion (D=0)
Pr.49 Control External Counter (D=0.00)
Used to totalise on the display in flow units larger than those entered at Pr.46 (max. flow rate)
Enter
0 Multiples by 1 1 Multiples by 0.1 2 Multiples by 0.01 3 Multiples by 0.001 4 Multiples by 0.0001 5 Multiples by 0.00001 6 Multiples by 0.000001 7 Multiples by 0.0000001
e.g. If Pr.46 is entered as litres, at Pr.48 enter ‘3‘ to total ­ize the flow in cubic meters.
Enter the maximum flow rate in units per second, per minute, per hour or per day, corresponding to maximum head, set at Pr.4 and then define the time base at Pr.47.
Enter the value corresponding to the flow rate time base.
Enter 1 = units per second
2 = units per minute 3 = units per hour 4 = units per day
If Pr.20 is set to 5, "Totaliser Drive", then enter the amount which each relay trip is to represent in totalised units. See example 5 on page 39.
e.g. If "litres" entered at Pr.46 and Pr.48 is ’0’ then to totalise in cubic metres enter 1000.
If an entry is made at Pr.48 for the internal totaliser then to use the same unit for an external counter enter ’1’.
After making entries in Pr.49, go to Pr.98 to clear and ini ­tiate totaliser.
Flume K Factor Flume K Factor
Size-Inches for US GPM Size-Feet for US GPM
1 3.22 10 331.60 2 6.45 12 393.70 3 9.46 15 486.90 6 18.20 20 642.10
9 30.80 30 797.40 12 40.90 40 1263.00 18 58.90 50 1574.00 24 76.30 36 110.00 48 142.00 72 204.70 96 256.60
Pr. 50 Penstock Control (D=1)
Enter 1 - No drive
2 - Penstock control
The control system uses relays 1 and 2 to drive a pen­stock up and down respectively to maintain the flow in a channel within certain limits.
The designations for relays 1 and 2 are ignored, but the following values have to be set.
Pr.9 : Top flow limit ) In units defined by Pr.10 : Bottom flow limit ) Pr.46 entry Pr.12 : Width of drive pulse (seconds) Pr.13 : Time between drive pulses (seconds)
See example 4.6 on page 32.
The penstock drive consists of a pulse train of variable time base which drives the penstock up and down.
'a'
'b'
In order to even out the wear of pumps it is possible to alternate the sequence in which pumps are used. (Pr.52 must be set to 1). Enter
1 Sequence by set points (i.e. no alternation) 2 Alternate RL1 and RL2 3 Alternate RL1, RL2 and RL3 4 Alternate RL1, RL2, RL3 and RL4 5 Alternate RL1, RL2, RL3, RL4 and RL5
Pr. 51 Pump Sequencing (D=1)
The time ’a’ is set by Pr.12 and ’b’ is set by Pr.13 in sec ­onds, this allows any shape drive train to be defined.
The control will maintain the flow between two limits, a high limit set by Pr.9 and a low limit set by Pr.10.
If the flow exceeds the value in Pr.9 relay 2 drives the penstock down. If the flow is below the value in Pr.10 relay 1 drives the penstock up. See Example 6.
Page 24
24
Pr. 52 Duty/Assist/Standby Pump Control (D=1)
Pr.53 Pump Exerciser (D=1)
Pr. 62 BM90E Serial Communication Enable (D=1)
Pr. 57 Pump Run-On Time (D=0)
Pr. 54 Pump Tolerance (D=1)
Pr. 55 Pump Maintenance Dropout (D=0) The removal of one pump for maintenance can necessi-
tate a great deal of readjustment to ensure correct con­trol. Pr.55 removes this need by allowing one pump to be removed without affecting the control levels. Pumps are re-assigned downwards so that the highest level is not used, therefore, normal control levels are maintained for lower level setting.
Enter the pump running time in seconds. (max. 120 seconds). Only one run-on cycle occurs per interval as set by Pr.56.
Notes : a) Caution is required when choosing a value for pump run-on time, as extended pump run-on can lead to CAVI­TATION, causing AIR LOCK or PUMP DAMAGE. b) As overflow can occur, do not use pump run-on for pump up operation, set Pr.56 and Pr.57 to zero. c) Care should be taken if pump sequence and pump run­on are defined together. As pump run-on will be assigned to the last pump to turn off which could be any of those in the sequence.
Enter
0 All pumps in 3 drop out pump 3 1 drop out pump 1 4 drop out pump 4 2 drop out pump 2 5 drop out pump 5
To use this facility, first select alternating duty options 2 to 5 in Pr.51, depending on the number of pumps installed.
Enter the number of starts assigned to Pump 1 before the sequence switches to allow the other pumps to be exer­cised in turn.
In applications where a greasy topped liquid is being pumped, problems may occur due to build-up of grease at the levels where pumping starts. It is usually neces ­sary for this to be cleared manually. To avoid this, vary ­ing the "turn on" point for the pumps by – 10% of the set point value causes the build-up to occur over a larger area, significantly reducing the maintenance problem. Enter 1 - No tolerance applied to pumps
2 - Tolerance applied to all pumps
NOTE: The pump ’reset’ points must be outside the toler­ance band of the set points and blanking.
NOTE:
a. The system assumes that the lower numbered
pumps turn on first.
b. CAUTION - A PUMP NOT INCLUDED IN AN
ALTERNATING SEQUENCE BUT PROGRAMMED INTO THE FIXED PART OF THE SEQUENCE WILL BE SUBSTITUTED INTO THE ALTERNATING SEQUENCE TO REPLACE A PUMP DROPPED OUT.
c. This feature should not be used if the relays are being used for a mixture of pump control and alarm functions.
Duty assist is where pumps are switched on by set point, and kept on to assist earlier pumps. Duty standby is where only one of the pumps specified for duty can be on at a time, i.e. when the set point for the second pump is reached and it switches on, the first pump will switch off.
Enter 1 - Duty/assist operation
2 - Duty/standby on pumps 1 and 2 3 - Duty/standby on pumps 1, 2 and 3 4 - Duty/standby on pumps 1, 2, 3 and 4 5 - Duty/standby on pumps 1, 2, 3, 4, and 5
The turn-off points for the pumps can all be the same, or they can be different depending on the chosen "Set" and "Reset" values for each relay.
When submersible pumps are used, it may be necessary to pump down occasionally to clear the sludge from the bottom of the well. This feature is controlled by Pr.56 and Pr.57. Once in every interval defined by Pr.56, the pump will run-on for the time period defined by Pr.57.
Enter the time interval in hours between each run-on cycle.
Pr. 56 Pump Run-On Interval (D=0)
Pr. 58 to Pr. 61 Unspecified
(Channel 1-RS232)
Channel 1 (RS232) 1 = Comminssioning System (default)
2 = Polled data transfer
Channel 2 (RS485) Is permanently enabled for polled
data transfer
Pr. 63 BM90E Station Number (D=0) For plooed date transfer, the unit requires to have a sta-
tion number assigned to it in the range 1-31, which has to be unique to the unit.
NOTE : Pr.62 & Pr.63 are not available on BM90LE
Page 25
25
Pr. 64 to Pr. 67 Unspecified
Pr. 68 Echo Processing Algorithm
Pr. 70 Echo Velocity
Pr. 69 Check Search (D=1)
Pr. 71 Correction Value (D=0.00)
Each system has two echo extraction techniques, which are capable of determining the "true" echo for the majority of applications where an echo is present.
For Level-Sonic BM90: (D=2)
Enter 1 = All vessel viewing. This technique con ­tinuously looks for echoes over the complete vessel. It is suited to applications that have very rapid level changes but it is more sensitive to parasitic echoes.
Enter 2 = Windows. This technique positions a nar ­row ’window’ around the target it is tracking to enable it to ignore a large amount of spurious noise.
For Level-Sonic BM90E: (D=1)
Enter 1 = For solids applications. This technique looks for the highest level within the transducer view.
Enter 2 = For liquids. This technique positions a narrow ’window’ around the target it is tracking to enable it to ignore a large amount of spurious noise.
Only available if Pr.68 is set to 2. It enables the instru ­ment to look outside its window at intervals to check that there are no other relevant echoes within the transducers view. Enter 1 = Not used
2 = Included Check search should be used where fill rates can some­times be greater than that entered at Pr.6, or if the trans ­ducer is liable to be submerged.
(D=344.1 i.e. speed of sound in air at 20 C)
If operating through any medium other than air, enter the velocity of sound through that medium in metres per second.
2. It can be used to prevent loss-of-echo when the target can go further away from the transdu­cer than the desired span. e.g. a) When a channel floor is lower than the
zero point of a "V" notch weir. b) To set an elevated zero level in a ves sel which is not normally completely emptied.
Add the extra depth to Pr.3 and enter minus the extra depth at Pr.71 in the units selected at Pr.2.
Pr.72 Parameter Display (D=0) The system will display continually the value of:
Gain - by entering 67 Temperature - b y entering 38 Analogue output - by entering 34.
It can be used only for commissioning as it will be lost on power down. It cannot be used in OCM mode.
Displays the revision number of the software (e.g. LA.14).
Pr. 74 Reset Counter
This count value gives the number of times that the sys­tem has been powered down or reset since the last time the counter was zeroed. It is useful for checking if the power supply is erratic.
Pr. 73 Software revision number
Both negative and positive values can be input. This value must be entered in the units selected at Pr.2.
This parameter has two uses:
1. It can be used to correct minor reading errors
on the display
Pr. 75 Digital Outputs (D=0) To aid commissioning and the testing of external wiring, it
is possible to define the status of all five relays when in ’PROG’ mode.
Press ’DSP’ then: Enter 0 - To de-energise all relays ADD 1 - To energise relay 1 ADD 2 - To energise relay 2 ADD 4 - To energise relay 3 ADD 8 - To energise relay 4 ADD 16 - To energise relay 5 e.g. To energise relays 2 and 5 enter ’18’
The defined relay state will be maintained until over-writ ­ten or until ’PROG’ mode times out (6 minutes). The time period can be extended by pressing a key during this period to reset the time-out counter.
Page 26
26
Pr. 95 Serial Number (Viewable only)
Pr. 79 to Pr. 94 Unspecified
Pr. 76 Hardware Test
Pr. 77 Transmitter T est
Pr. 78 Simulation
Press ’DSP’ then ’ENT’ to test LED’s/LCD and relays. The LCD will flash all segments, and the LED’s will count up in binary. Press ’CE’ to end test, or let it time out.
CAUTION: DO NOT USE THIS TEST WHEN CON
NECTED TO PUMPS OR RELAYS. USING THIS PARAMETER WILL OPE­RATE ALL RELAYS AND MIGHT START PUMPS, ALARMS ETC.
Press ’DSP’ then ’ENT’, the transmitter should pulse con­tinuously, (made visible by the neon). By the use of an oscilloscope the return echo can be observed if required.
Also useful to ascertain if a transducer is correctly con ­nected, as it will ’click’ repeatedly. Press ’CE’ to end.
The value displayed will depend on the value set in Pr.01.
Press ’ENT’ to simulate the operation of the instrument as set up between Blanking and Empty distance. The dis­play will depend on mode set in Pr.01.
Mode = 1 (liquid level) LEVEL = 2 (distance measurement) DISTANCE = 3 (differential) N O SIMULATION AVAILABLE = 4 (OCM) - LEVEL
It will set all LED’s/relays and the current output as pro ­grammed. Therefore, care must be taken if the instru­ment is wired into other instruments or controls. The displayed value, on which all relays are operated, is that which is set by the operator. The initial speed of the simulation is that set into Rate of Change (Pr.6) this can be increased by a factor of 2 by pressing the ’#’ key and the key can be pressed 6 times (x64). To reduce the speed press the ’-’ key, the speed cannot be reduced below that defined by Rate of Change, Pr.6.
The direction of the simulation can be changed by using the ’ s ’ and ’ t’ keys, which one has to be pressed depends on the set up. The simulation can be stopped and re-started using the ’TEST’ key. Press ’CE’ to end.
Pr. 96 Security C ode Store
A new security code can be entered at this parameter, but after entry it is scrambled. Refer to factory if you for ­get the security code and quote the number displayed here.
This parameter displays the serial number of the Level­Sonic BM90 unit.
Pr.99 Return to Factory Default Parameter Settings
Pr. 97 Relay Hours/Starts Totaliser Reset (D= ==== )
The totalisers are cleared by entering: Pr.97 and ’DSP’ to show ==== Press CE t o clear the screen Press Enter to request ’COdE’ Enter 9753 Press Enter to show ’t.rES’ and ====
Pr. 98 Clear the OCM Totaliser i.e. HI.TO and LO.TO
(D= ==== )
The totalisers are cleared by entering: Pr.98 and ’DSP’ to show ==== Press CE t o clear the screen Press Enter to request ’COdE’ Enter 9753 Press Enter to show ’t.rES’ and ====
Press ’MODE’ t o display ’PROG’
’1’ immediately to display ’Pr.01’ or previous
Pr. number. ’99’ to display Pr.99 ’DSP’ t o display ’CE’ to clear the display ’ENT’ to display ’COdE’ requesting the security
code* (see note) ’9753’ and ’ENT’ to display P.rES followed by
t.rES, and then ==== ’DSP’ to display ’Pr.99’ and now the new pro
gramme can be entered.
NOTE * Enter your own security code number if you have changed it from factory setting of 9753.
Page 27
27
4. Examples
4.1 Level measurement mode (Pr. 1 = 1 )
Applications for this mode are Level Measurement, Contents Measurement and Pump Control.
The application :
lTo measure and display the level of liquid in meters lMaximum level 3 m, lFill rate 0.1 meter/min lAlarm if level exceeds 2.8 m l0-20 mA signal proportional to level
Pr. 1 = 1 Defines level measurement. Pr. 2 = 2 Programme units are meters. Pr. 3 = 4 Distance of transducer from the zero level. Pr. 4 = 3 The span, based on zero level. Pr. 5 = 0.5 Blanking zone into which level should not rise. Pr. 6 = 0.1 The maximum rate of change of liquid level in meters/min. Pr. 8 = 1 Relay 1 to alarm on level (normally energised). Pr. 9 = 2.8 Relay 1 de-energised at 2.8 m indicates high alarm. Pr.10 = 2.6 Relay 1 re-energised at 2.6 m to clear the high alarm. Pr.23 = 3 Hold alarm indication (relay 1) on failsafe. Pr.28 = 3 Analogue output holds on failsafe. Pr.30 = 3 0.20 mA output fixed to span (Pr.4). Pr.78 Simulate the program.
3.0m
(Pr.4)
4.0m (Pr.3)
Reset Alarm
2.8m (Pr.9)
Set Alarm
0.5m (Pr.5)
2.6m (Pr.10)
Page 28
28
4.2. Measurement with volumetric conversion (Pr. 1 = 1 )
The application :
lTo measure the level in a conical bottomed cylindrical tank. Dimensions as shown lTotal volume of tank = 120 m
3
when level is 8.5 m
lOutput display in m
3
lAnalogue output to be 0-20 mA proportional to volume in tank lHigh alarm at 90 m
3
, low alarm at 10 m
3
volume
Pr. 1 = 1 Defines level measurement. Pr. 2 = 1 0 Programme in meters, display/control in volume. Pr. 3 = 9 Transducer to zero level = 9.0 m Pr. 4 = 8.5 The span over which measurement is required. Pr. 5 = 0.5 Blanking zone into which the level should not rise. Pr. 6 = 1 0 The rate of change of level will not exceed 10.0 m/min Pr. 8 = 1 Relay 1 to alarm on volume (normally energised) Pr. 9 = 9 0 Relay 1 de-energises at 90 m3. High alarm on. Pr.10 = 85 Relay 1 energises at 85 m3to clear high alarm. Pr.11 = 1 Relay 2 to alarm on volume (normally energised) Pr.12 = 10 Relay 2 de-energises at 10 m3. Low alarm on. Pr.13 = 15 Relay 2 energises at 15 m3to clear low alarm. Pr.30 = 3 Analogue output to be 0-20 mA fixed to span. Pr.40 = 3 Define vessel as conical bottomed. Pr.41 = 2.0 Define the depth of cone as 2.0 m Pr.43 = 1.2 Define total capacity 120 m3. Pr.78 Simulate the program.
9.0m
(Pr.3)
0.5m (Pr.5)
Reset Low Alarm (Pr.13)
Set Low Alarm (Pr.12)
2.0m (Pr.41)
8.5m (Pr.4)
Reset High Alarm (Pr.10)
Set High Alarm (Pr.9)
Page 29
29
4.3. Pump control (Pr. 1 = 1)
The application :
l2 pump control, pump down in a wet-well, duty-assist operation lAlternate pump duty to reduce wear l4-20 mA to remote indicator lLoss-of-Echo indication to telemetry lDisplay actual level in meters
Pr. 1 = 1 Defines level measurement. Pr. 2 = 2 Programme in meters, display in meters. Pr. 3 = 5.4 Transducer to zero level = 5.4 m. Pr. 4 = 4.5 The span over which measurement is required. Pr. 5 = 0.5 Blanking into which the material will not rise. Pr. 6 = 1.5 Max. rate of level change 1.5 m/min. Pr. 8 = 2 Relay 1 control on level (normally de-energised). Pr. 9 = 3.75 Relay 1 energises at 3.75 m to turn pump 1 on. Pr.10 = 0.5 Relay 1 de-energises at 0.5 m to turn pump 1 off. Pr.11 = 2 Relay 2 to control on level (normally de-energised). Pr.12 = 4.0 Relay 2 energises at 4.00 m to turn pump 2 on. Pr.13 = 0.75 Relay 2 de-energises at 0.75 m to turn pump 2 off. Pr.17 = 7 Relay 4 assigned to indicate loss-of-echo to the telemetry system. Pr.23 = 2 Switch pump 1 off on failsafe. Pr.24 = 2 Switch pump 2 off on failsafe. Pr.28 = 1 Analogue output to 4 mA on failsafe. Pr.29 = 30 Failsafe delay 30 secs. Pr.30 = 2 Analogue output to be 4-20 mA fixed to Pr.4. Pr.51 = 2 Alternate pump duty. Pr.78 = Simulate the program.
0.5 (Pr.10)
5.4m (Pr.3)
0.5m (Pr.5)
4.5m (Pr.4)
Stop 1
Start 1
3.75 (Pr.9)
4.00 (Pr.12)
Start 2
Stop 2
0.75 (Pr.13)
Page 30
30
4.4. Differential level mode (Pr.1 = 3)
In the differential mode, the transceiver drives two transducers, to measure the difference in levels by subtracting the downstream level from the upstream level. Please refer to connection diagram Fig. 6 for transducer wiring.
The upstream transducer should be chosen to give a positive differential value.
The application :
lStart rake when differential reaches 0.15 m lStop rake when differential falls to 0.05 m lMaximum differential 0.3 m lAlarm if level on upstream side exceeds 0.6 m lLoss-of-Echo indication to telemetry system l4-20 mA signal proportional to differential
Pr. 1 = 3 To define differential level measurement. Pr. 2 = 4 As distances are small programme in cms. Pr. 3 = 1 2 0 The distance from bottom of channel to transducers in cms. Pr. 4 = 3 0 The maximum differential span in cms. Pr. 5 = 5 0 Blanking zone in cms. Pr. 6 = 1 0 0 The max. rate of change of level in cms. Pr. 8 = 3 Relay 1 designated for differential control. Pr. 9 = 1 5 Relay 1 energises at diff. 15 cm to start rake. Pr.10 = 5 Relay 1 de-energises at diff. 5 cm to stop rake. Pr.11 = 5 Relay 2 to alarm on an upstream level. Pr.12 = 60 Relay 2 de-energises at 60 cm high alarm. Pr.13 = 55 Relay 2 energises at 55cm to clear high alarm. Pr.17 = 7 Relay 4 assigned to indicate loss-of-echo to the telemetry system. Pr.23 = 2 Switch rake off on failsafe. Pr.24 = 3 Hold alarm level indication on failsafe. Pr.28 = 3 Analogue output holds on failsafe. Pr.29 = 120 Failsafe time is left at default of 120 s. Pr.30 = 1 4-20 mA output fixed to span (Pr. 4) Pr.97 = 2 This counts the number of times the rake is turned on, and how (optional) many hours it has been energised.
120cm (Pr.3)
30cm
(Pr.4)
RAKE CONTROL
50cm (Pr.5)
15cm (Pr.9)
Start rake
Stop rake
Flow
60cm (Pr.12)
55cm (Pr.13)
Page 31
31
4.5. Open channel Flowmeter (Pr. 1 = 4)
The application : lRectangular flume, with a max. flow of 150 l/s at head 0.3 m
lLoss-of-echo indication to telemetry system l4-20 mA signal proportional to flow lTotalise flow and provide pulsed output to external totalizer lDisplay flow reading
Pr. 1 = 4 To define open channel flow metering. Pr. 2 = 4 As distances are small, work in cms. Pr. 3 = 120 Distance of trans. from bottom of channel. Pr. 4 = 30 Level at which max. flow rate value is defined. Pr. 5 = 50 Blanking zone into which level will not rise.
It is suggested that this is above the top of the channel to allow
the system to continue reading up to that level. Pr. 6 = 5 0 Rate of Change of level 50 cm/min. Pr.17 = 7 Relay 4 assigned to indicate loss-of-echo to the telemetry unit. Pr.20 = 5 Relay 5 to operate as external totaliser switch. Pr.28 = 3 Analogue output "holds" on failsafe, as factory set. Pr.29 = 120 Failsafe time is left at default of 120 s. Pr.30 = 1 4-20 mA output fixed to span (Pr.4). Pr.31 = 2 Analogue output represents flow rate. Pr.37 = 2 Probe enable if Temperature Compensation is used Pr.45 = 2 To define that a rectangular flume is being used. Pr.46 = 39 Defines the max. flow is 39 l. Pr.47 = 1 Flow in Pr.46 is in litres per second. Pr.48 3 To avoid totalizer overflow, totalise in cubic meters rather than litres. Pr.49 = 1 Sets external totaliser to same as internal totaliser. Pr.78 = Simulate the program. Pr.98 Clear and initiate the totalizers.
Note : In normal ’RUN’ mode display will always show Flow. Instantaneous readings of "High total", "Low total", "Head" and "Flow" can be obtained by pressing keys 1 to 4. The display will revert back to Flow after 15 seconds.
120cm
(Pr.3)
120cm (Pr.3)
Transducer position
3-4 times max. head.
30cm
(Pr.4)
Flow
90-120cm
50cm (Pr.5)
Page 32
32
4.6. Open channel flowmeter (Pr. 1 = 4) with penstock control
The application : lAs chapter 4.5. but additionally to control a penstock via Relays 1 and 2 to modulate flow
between 25 and 30 l/s
ENTER: Pr.1 - Pr.6 as example 5, then go to Pr.9
Pr.9 = 30 Defines top flow limit 30 litres per second.
Pr.10 = 25 Defines low flow limit 25 litres per second.
Pr.12 = 8 Duration of penstock drive pulse is 8 seconds.
Pr.13 = 4 Time between drive pulses is 4 seconds.
ENTER: Pr.14 - Pr.48 as example 5, then go to Pr.50.
Pr.50 = 2 To initiate penstock control.
ENTER: Pr.78 and Pr.98 as example 5.
Page 33
33
5. Fault Finding
5.1. Fault finding - Hardware
A) The display is blank or frozen, the l.e.d’s are unlit and the neon does not fire:
1. Ensure that power is being supplied to the board, and that it is correctly wired. Refer to figure 6, on Page 9.
2. Check fuses.
3. Check that the supply voltage is within specified levels (See Section 2 Page 10). A large voltage drop can cause the unit to lock to show last distance or level reading.
B) The fuse blows continuously:
* In this case the system is drawing excessive current.
1. Power down and fit a new fuse - refer to Page 10 Disconnect all cabling from the unit except for the power lead. If the fuse does not blow on power up, there is a fault in the external wiring.
2. Check that the power supply is within specified limits ­refer to Page 10.
3. Check the enclosure for metal debris which may be under the lower PCB.
C) The system powers up, but displays ’8888’:
* In this case a connection in the PCB is giving a continu­ous or intermittent fault.
1. Check; with power off, that an Eprom is fitted at U7 and that the chip has not vibrated free from its socket.
D) The display shows ’LOSt’:
* In this case the instrument is not reciving a good signal grom the transducer.
1.Check the transducer wiring and connections to the instrument. Note that different connections are used if a temperature compensated transducer is connected. See Figure 6, Page 9.
2. Check whether the neon light adjacent to terminal 22 is flashing. If it is proceed to number 3, if it is not then :
a: Disconnect the transducer: If the neon now
lights then there is a short circuit in the cabling.
b: If the neon does not light the transmission fuse may have blown. Check F1 and F2 T80mA fuses on the bottom PCB.
c: If the unit still shows ’LOSt’ check that you can hear the transducer "clicking" when close to the ear.
d: If the transducer cable has been extended, dis -
connect and remove the transducer and connect it direct to the Liquiflex. If the unit now operates, recheck the extension cable connections and routing, avoiding power cables. Re-instal the transducer checking that its aim is perpendicular to the target surface.
e: If the transducer does not click proceed to 5.
3. Is there a target within the empty distance specified in Pr.3? This is particularly important if temperature variations are experienced and no compensation is applied.
4. Is the vessel empty with a conical, parabolic, sloping or spherical bottom? This commonly causes loss of echo if the transducer cannot be mounted over the centre of the vessel. When the vessel becomes empty the pulse from the transducer hits the sloping sides of the bottom section and the signal is not reflected back to the transducer. Under this condi­tion the display will indicate ’LOSt’ but the failsafe desig ­nation will operate until product returns and the system will automatically recover and track level. If the transduc ­er cannot be mounted centrally, the problem may be overcome by the installation of a target plate.
5. Connect a known good transducer to the instrument and check the operation. If the known transducer gives a good signal check the instruments gain by pressing the ’TEST’ key. The number displayed ranges from 1 - 100 and the lower the number the better the signal strength.
If the gain figure is 50 - 100 check the surface level for foam or other materials which may float in and out of the beam and cause poor echoes.
6. Check that the ST6 eprom is seated correctly at U6 on the bottom PCB
E ) The keypad fails to respond:
1. Check for correct alignment of connection from keypad to main board.
2. Check that key press sequence is valid; refer to Programming Section.
3. Power down unit and wait 5 seconds. Power up and immediately press ’MODE’. This should result in ’PROG’ being displayed. It is now advisable to reset to factory parameters; refer to Programming Section 3.
F) Analogue Output is Unstable:
1. Connect a test meter in series with your external wiring. Can the fault be seen on the test meter? If YES, then use Pr.34 to enter a stable value into the current loop. Suitable values range from 4 to 20. If the output is still unstable disconnect external wiring
Page 34
34
and connect a meter across terminals 25 and 26 and repeat Pr.34 test. If the output is now stable check wiring and meters
G) Analogue has no Output:
1. Check programme value at Pr.30 - Value 1-6.
2. Insert a test meter in series with the output. Under Pr.34 enter a fixed output. If still no output, connect a test meter directly across ter ­minals 25 and 26, repeat test under Pr.34. If no value is read at terminals 25 to 26 contact Krohne.
H) Analogue Output is less than 20 at maximum dis­play reading:
1. The load attached to the output may be too high. To check this disconnect all the external wiring and see if it know reads 20. The output is capable of driving 20mA into 750 Ohms.
I) Analogue Output does not correspond to applica­tion:
1. Checked that the correct options (Pr.30 to Pr.33) have been selected.
2. Check that the correct span (Pr.4) has been input, this is the value over which the analogue will be spanned unless a separate entry has been made at Pr.32 or Pr.33.
J) Reading on display and outputs stay high:
* This is usually caused by return echoes from close-in obstructions.
1. Check for obstructions. If the transducer is mounted on a standpipe, check for rough edges at the connection with the vessel, refer to the figure Page 12.
2. If there are no close-in obstructions ensure that the iso ­lation kit is fitted on the transducer and the transducer is mounted correctly. The isolation kit should enable the transducer to move slightly, it should not be solid. ( Not applicable to flanged transducers.)
3. Check the entry at P5, Blanking distance, and return to
0.5m if reduced from factory setting
4. May be caused by rate of change, Pr.6 being too small.
K) Reading is lower than expected: * This only occurs when the system is locked on to a mul­tiple of the true echo.
1. Check that Pr.3 and Pr.4 are correctfor the application
2. It can be caused when the level rises into the blanking zone. The system can then lock on to a multiple echo,
and may continue tracking the multiple when the level decreases. Using check search Pr. 69 should rectify this situation, but preventing the level entering the blanking zone is the preferred solution.
3. It can also be caused by the level moving at a much faster rate than is allowed for by the defined rate of change (Pr.6) . To solve the problem the rate of change value should be increased to more closely match the real rate.
L) Reading is unstable :
1. If a high rate of change (Pr.6) is defined the display will be more unstable. Therefore, an unnecessarily high value of Pr.6 should be avoid.
M) Reading changes in steps:
* This is usually caused by the rate of change value (Pr.6) being too small to keep up with the process.
1. To rectify, increase the value of Pr.6 to match the rate of change of level.
N) The display is inaccurate:
1. The empty distance (Pr.3) of the vessel may be incor­rectly set.
2. The dimensions of the vessel or flume may be incor­rect, as may the values of maximum flow, volume or mass conversion.
3. The system may require temperature compensation.
4. The application may include vapours that significantly change the speed of sound. Provided these are constant over the range the speed of sound can be adjusted through Pr.70.
O) Temperature is inaccurate :
1. The position of the transducer/temperature sen­sor is important to prevent heating by sunlight and con­vection currents. Also the sensor should be in a free-air vented position if possible to prevent hot-spots.
2. Check that temperature compensation is enabled at Pr.37.
3. Check the resistance of the temperature probe when disconnected against the value in Pr.39 when connected. If using a temperature compensated transducer, check this resistance value across the shield and black core when disconnected.
Page 35
35
NOTE: The sensor sensor compensates only for tem­perature variance, it is not expected to accurately measure the actual temperature.
P) The boards hums loudly:
* Usually vibration from the transformer.
1. Check the mounting screws for tightness.
Q) Relays not switching:
1. Check the programmed relay designations and settings at Pr.8 - Pr.22 Functions can be tested under simulation using Pr.78.
2. Test the actual relays using Pr.75 or Pr.76.
3. Check contact continuity at the terminals 4 - 18.
WARNING: It is reccomended that all external con­trols, alarms etc. are disconnected before performing the above tests.
Page 36
36
5.2. Programming sheet
Pr Description Factory User Eng Pr Description Factory User Eng
Default Default
Basic Set-up Open Channel Flow
1 Application 2.00 45 Flow Exponent 1.00 2 Units 2.00 46 Max. Flow Rate 0.00 3 Empty Distance 10.00 47 Time Base for Flow 1.00 4 Operational Span 10.00 48 Totalise Display Conv. 0.00 5 Blanking Distance 0.50 49 Contr. for Ext. Sampler 0.00 6 Rate of Change 1.00 50 Penstock Control 1.00
Relays Pump Controls
8 Relay 1 0.00 51 Pump Sequence 1.00
9 Relay 1 Set 0.00 52 Duty Standby 1.00 10 Relay 1 Reset 0.00 53 Pump Exerciser 1.00 11 Relay 2 0.00 54 Pump Tolerance 1.00 12 Relay 2 Set 0.00 55 Pump Maintenance 0.00 13 Relay 2 Reset 0.00 56 Run-on-Interval 0.00 14 Relay 3 0.00 57 Run-on-Time 0.00 15 Relay 3 Set 0.00 16 Relay 3 Reset 0.00 Echo Detection 17 Relay 4 0.00 68 Echo Selection 2.00 18 Relay 4 Set 0.00 69 Check Search 1.00 19 Relay 4 Reset 0.00 70 Echo Velocity 344.10 20 Relay 5 0.00 21 Relay 5 Set 0.00 22 Relay 5 Reset 0.00
Failsafe Miscellaneous
23 Failsafe R1 3.00 71 Correction Value 0.00 24 Failsafe R2 3.00 72 Parameter Display 0.00 25 Failsafe R3 3.00 73 Software Rev. No LA * 26 Failsafe R4 3.00 74 Reset Counter 0.00 27 Failsafe R5 3.00 28 Failsafe Analogue 3.00 29 Failsafe Time Delay 120.00
Analogue Test Parameters
30 Analogue Output 1.00 75 Digital Output Set 0.00 31 Analogue Options 1.00 76 Hardware Test 32 Analogue Datum 0.00 77 Transmitter Test 33 Analogue Span 100.00 78 Simulation 34 Analogue Test 0.00
Temperature Number Store
37 Probe Enable 1.00 95 Serial Number Store Ser.No. 38 Temp. Compensation 20.00 96 Security Code Store 15.02 39 Probe Test 0.00
Volume Conversion Reset
40 Vessel Shape 0.00 97 Relay Hrs/Starts Reset 41 Dimension H 0.00 98 OCM Totaliser Reset 42 Dimension L 0.00 99 Full System Reset 43 Display Conversion 1.00 44 Volume Linearisation
Page 37
37
Type BM90 / L RZV15 RZT15 RZV15T
BM90E/ LE RXV15 RXT15 RXV15T Temperature Uncompensated Compensated Uncompensated Compensation Frequency (in KHz) 41.50 41.50 41.50 Beam Angle at 3dB 10 degrees 10 degrees 10 degrees Body Material CPVC CPVC CPVC Face Material Urethane Urethane Teflon Process Temperature * -40 to + 90 deg C -40 to + 90 deg C -20 to +90 deg C Protection IP68 IP68 IP68 Weight (Kg) 2.00 2.00 3.00
6. Technical Data Level-Sonic
6.1. Converter
BM90 / BM90 L BM90 E / BM90 LE
Enclosure IP65 Aluminium NORYL DIN43700. IP55 to front of panel.
IP20 behind panel. Dimensions 206 (8.11") x 326 (12.83") x 123 (4.84") 144H X 96W X 140D (mm). Weight 4 Kg (8.8 lb) 1.75Kg Power Supply 110/230 V selectable, 50/60 Hz, 10 VA 110/230Vac + 10% selected automatically.
12 V or 24 VDC not selectable 6 W 50/60Hz, 12VA, 24Vdc + 25% Nominal voltages +/- 10 % - 10%, 9W. Separate terminals.
Fuse Rating 125 mA (slow blow) AC F2 T160mA for ac supply
250 mA @ 24 V DC F 1 T315mA for 24Vdc supply
500 mA @ 12 V DC F3 & F 4 T80mA Range U p t o 10 m (32.8 feet) and up to 15 metres liquids and solids with L. Accuracy +/- 0.25 % of measured distance at + 0.25% of measured distance from the
constant temperature transducer at constant temperature of 20 C. Ambient Temp. - 2 0 C to + 50 C (- 4 F t o + 122 F) -40 deg C to + 70 deg C. Calibration Integral keypad with security code 5 X 4 integral keypad with security code. Resolution 2 mm (0.08 ") or 0.1 % of range (set at Pr.3) 2mm or 0.1% of range, whichever is the
whichever is greater greater. Analogue Output Opto isolated 4-20 mA or 4-20mA into 750 Ohms. 16 bit. Short circuit
0-20 mA into 750 ohms protected and opto-isolated on ac powered
Short circuit protected units. Not opto-isolated on 24Vdc units.
Maximum allowable degradation of signal 2% under extremes of transient and constant con­ducted immunity tests to EN50082.
Relay Outputs 5 multifunction SPDT relays 5 multi-function SPDT relays rated
rated 5 A/230 V a.c resistive 8A/230Vac/30Vdc resistive, with gold con
tacts.
Indication Integral 4 digit LCD, 12 mm (0.47") high Integral, 4 digit LCD, 12mm high characters.
characters 5 red LED’s to indicate relay status 5 red LED’s to indicate relay status. Failsafe High, low, hold (Pr.23 to 29) High, Low, Hold Damping Fully adjustable (Pr.7) Fully adjustable Blanking Fully adjustable (Pr.5) min 0.3 m (11.82 ") Fully adjustable Optional Temp. Reduces ambient temperature errors from sensor 0.17 % / 1 C of measured distance to
0.01 % / 1 C (34 F)
6.2. Transducer
NOTE: *All the above transducers can be approved for use in Hazardous Areas, Zones 1 & 2 but Ambient
Temperature limited to: -20 to + 60 deg C. CENELEC: EExm II T6 CERTIFICATE NO: 93C.108.020X
CE approved - EMC tested in accordance with EN50081 & EN50082
Parts 1 & 2 Low voltage directive, EN61010
Page 38
38
APPENDIX 1 Vessel or Flume
linearisation
This feature allows volume conversion to be applied on irregular shaped vessels and flow measurements to be made on open channels providing that level/volume/flow relationships are known.
The system allows the entry of a volume or flow profile of up to 16 points into memory, that is then used to pro­duce the required flow or volume values when in ‘RUN‘ mode. The required profile is stored in parameter 35.
Before proceeding it is useful to write down the point numbers and ’A’/’b’ values to facilitate programming.
Note l% Head or Level designated ’A’
l% Flow or Volume designated ’b’
Flow
When using the facility for flow it is enabled by Pr.40 = 4. T he profile is stored as percentage of head, against per ­centage of flow.
Volume
When using the facility for volume, it is enabled by Pr.32 = 8. The profile is stored as percentage of level, against percentage of the total volume.
Procedure
The procedure uses a 16 point curve to map the profile, but all 16 points do not have to be used.
The profile data is input into Pr.35 which when accessed [Pr.35, ‘DSP‘, ‘ENT‘] will display ‘A1‘, which means the data pointer is at value 1 on ‘A‘ data. The values can be displayed and changed as required.
% Flow or Volume
Designated ’b’
% Head or Level Designated A
Pr.44 - Keyboard Controls
# Toggles the display between data blocks ‘A‘
and ‘b‘
s Increases and decreases the point number, t when either the point number or its value is
displayed
CE Clears the display when inputting a new value. DSP Toggles the display between the block and
point number and the value.
ENT Enters a new value. TEST Exits Pr.44 and returns the operator to the
normal program.
0-9 The number keys and decimal point are used
to input new values. Point numbers can only be changed by using the ‘s‘ and ‘t‘ keys.
Pr.44 - Inputting Values
When a new value is to be entered, first display the old
value and then input the new and press ‘ENT‘, the sys-
tem will display the value it has stored in memory. The values input have to be in a specific form.
1. Head or Level designated ‘ A‘
These values must be a whole number. Decimal places will be ignored.
i.e. 11 will be accepted as 11
22.3 will be accepted as 223.
The allowable range of values is 0-250 %, any unused data values must
be set to 255.
PARAMETER RESET LOADS 255 T O ALL DATA VALUES
2. Flow or Volume designated ‘b‘
These values are expected to contain one decimal place, therefore, it is not necessary to input the decimal place, but the procedure will display it.
i.e. 10 will be accepted as 1.0
100 or 10.0 will be accepted as 10.0
The allowable range of values is 0-500 %
PARAMETER RESET LOADS 0 T O ALL DATA VALUES.
Note :
1. As time is required to enter all the data, the standard
keypad timeouts are suspended.
2. We recommend that the required values are written in table form, as shown, before programming commences. Then enter all Block A values, before entering all block b values.
Page 39
39
Points ’A’’b’
Number % Head or Level % of Flow of volume
1 0 0.0 2 1 0 0.0 3 2 0 7.2 4 30 16.1 5 40 27.3 6 50 37.5 7 60 48.5 8 70 59.5
9 80 70.5 10 90 80.0 11 100 89.5 12 110 100.0 13 255 ­14 255 ­15 255 ­16 255 -
110
100
90
80
70
60
50
40
30
20
10
0
Vessel (or channel)
symmetrical
about c/1
Transducer
% of level
Point Head (cm) % Head ’A’ Value Flow litres/sec % Flow ’b’ Value
1.00 0.0 0.0 0.00 0.0 0.0 0
2.00 2.5 8.3 8.00 0.4 1.1 11
3.00 5.0 16.70 17.00 1.7 4.4 44
4.00 7.5 25.0 25.00 3.7 9.5 95
5.00 10.0 33.30 33.00 6.3 16.2 162
6.00 15.0 50.0 50.00 12.70 32.5 325
7.00 20 0 66.60 67.00 20.30 52.0 52 0
8.00 25.0 83.20 83.00 29.30 75.0 75 0
9.00 30.0 100.0 100.00 39.0 100.0 1000
10.00 Not used Not used 255.00 Not used Not used .0
11.00 Not used Not used 255.00 Not used Not used .0
12.00 Not used Not used 255.00 Not used Not used .0
13.00 Not used Not used 255.00 Not used Not used .0
14.00 Not used Not used 255.00 Not used Not used .0
15.00 Not used Not used 255.00 Not used Not used .0
16.00 Not used Not used 255.00 Not used Not used .0
NOTE: 1. Points 10 to 16 not used - leave at factory
default value.
2. ’A’ values must be whole numbers, no deci mals allowed.
3. ’b’ values must be entered as the tabulated value, the decimal will be automatically allocated.
Now continue programming the instrument as follows: Programme the instrument exactly as section 4.5 on Page 31, except:
Change Pr.45 from 2 to 4, which denotes
"Special Flow Device". Go to Pr.44 and proceed as follows: Press Pr.44 to display Pr.44: Press ’DSP’ to show Press ’ENT’ to show ’A1’ Press ’DSP’ to show value of ’A1’ (default = 255)
Key in the value ’O’ from Table 1 and press ’ENT’ Press ’DSP’ to show ’A1’ again Press ’s’ to show ’A2’ Press ’DSP’ to show value of ’A2’ (default = 255)
Key in the value ’8’ from Table 1 and press ’ENT’
Continue for all points which you need to use
(up to ’A16)’
Any points not used must be left at the default
of 255 Press ’DSP’ to display the last ’A’ number used, then Press ’t’ several times to return to ’A1’ Press # t o show ’b1’ Press ’DSP’ to show value of ’b1’ (default = .0)
Key in the value ’0’ from Table 1 and press ’ENT’ Press ’DSP’ to show ’b1’ again Press ’s’ to show ’b2’ Press ’DSP’ to show value of ’b2’ (default = .0)
Key in the value ’11’ from Table 1 (accepted as 1.1)
Continue for all points which you need to use (up to 16)
Any points not used must be left at the default of .0 Press ’TEST’ then ’DSP’ to show Pr.44
Leave the linearisation part of the programme by dis
playing any other parameter, or go into ’RUN’ mode.
Example: Flow - Special Flume Mapping Use Example 4.5 on Page 31, but substitute a special ’U’ throat flume with maximum flow
39 litres/second at 30 cm/hd. First, create the following table from the relationship of head and flow which must be given forthe special flume.
Page 40
40
APPENDIX 2 Serial Communications BM90 L ONLY
The Level-Sonic BM90E is fitted with two serial communi­cations channels as standard. Channel 1 has been built for RS232 and Channel 2 for RS485. The connector is TB5 on the top PCB.
RS232
1. RS232 : BM90E PL C COMPUTER
15M
CABLE - 3 CORE SCREENED
As only one BM90 L unit can be connected to each RS232 serial port on the computer, and the transmission distanc is limited, this is only likely to be used for commu ­nications within a control room.
RS485
2. RS485 : BM90E 01 BM90E 31
PLC
COMPUTER
1000M to further unit
CABLE - SINGLE PAIR SCREENED
This option allows up to 31 Level-Sonic BM90 L units to be daisy-chained on the same cable, connected to a single port on the computer. Therefore where multiple Level-Sonic BM90E units are being used this option should be used.
Converters / Repeaters To interface to the Level-Sonic BM90E a computer or PLC with the required serial port will be required. Usually the RS232 port will be fitted as standard, with the RS485 being available as an option.
If the required serial option cannot be fitted, then signal converters and repeaters are on the market. These will convert RS232 to RS485 and will extend greatly the transmission distances.
DATA COMMUNICATIONS There are at present two types of data communications available in the Level-Sonic BM90E Unit.
1. Commissioning System The commissioning system allows the echoes being received and processed by Level-Sonic BM90LE to be downloaded to an IBM or compatible computer (usually portable), so that they can be viewed easily. This system has made the use of an oscilloscope for on-site cimmis­sioning unnecessary. To use this option requires a software package and inter­face cables. These are detailed along with its operation in a separate bulletin.
2. Pleed Data Transfer This option allows an external computer to obtain data that can be used to produce any required display i.e. tables, mimics. The data is transmitted in a format that can be understood and processed by any programmable device using High or Low level languages.
The data obtained depends on the application pro­grammed.
LEVEL
a) Level b) Displayed value - %, volume, tonnage, etc. c) Rate of change of level d) Temperature e) Status of 4 relays f) Loss of transducer and loss of echo
DISTANCE
a) Distance b) Displayed value - % - ullage etc. c) Rate of change of level d) Temperature e) Status of 4 relays f) Loss of transducer and loss of echo
DIFFERENTIAL
a) Upstream level b) Downstream level c) Difference of levels d) Temperature e) Status of 4 relays f) Loss of transducer and loss of echo
OCM
a) Flow rate b) Head c) Totaliser value d) Temperature e) Status of 4 relays f) Loss of Transducer and loss of echo
To use this option will require software to be written for the PLC or computer that requests the data. Details of the transmission protocols and hardware connections are given in a sepatate bulletin.
RS 232
RS 485
TB5
Rx Tx GND SCN SCN - +
Page 41
41
APPENDIX 3 TECHNICAL DATA LEVEL-SONIC
Type BM90 / L RZV15 RZT15 RZV15T
BM90E/ LE RXV15 RXT15 RXV15T Temperature Uncompensated Compensated Uncompensated Compensation Frequency (in KHz) 41.50 41.50 41.50 Beam Angle at 3dB 10 degrees 10 degrees 10 degrees Body Material CPVC CPVC CPVC Face Material Urethane Urethane Teflon Process Temperature * -40 to + 90 deg C -40 to + 90 deg C -20 to +90 deg C Protection IP68 IP68 IP68 Weight (Kg) 2.00 2.00 3.00
Converter
BM90 / BM90 L BM90 E / BM90 LE
Enclosure IP65 Aluminium NORYL DIN43700. IP55 to front of panel.
IP20 behind panel. Dimensions 206 (8.11") x 326 (12.83") x 123 (4.84") 144H X 96W X 140D (mm). Weight 4 Kg (8.8 lb) 1.75Kg Power Supply 110/230 V selectable, 50/60 Hz, 10 VA 110/230Vac + 10% selected automatically.
12 V or 24 VDC not selectable 6 W 50/60Hz, 12VA, 24Vdc + 25% Nominal voltages +/- 10 % - 10%, 9W. Separate terminals.
Fuse Rating 125 mA (slow blow) AC F2 T160mA for ac supply
250 mA @ 24 V DC F 1 T315mA for 24Vdc supply
500 mA @ 12 V DC F3 & F 4 T80mA Range U p t o 10 m (32.8 feet) Up to 15 metres liquids and solids. Accuracy +/- 0.25 % of measured distance at + 0.25% of measured distance from the
constant temperature transducer at constant temperature of 20 C. Ambient Temp. - 2 0 C to + 50 C (- 4 F t o + 122 F) -40 deg C to + 70 deg C. Calibration Integral keypad with security code 5 X 4 integral keypad with security code. Resolution 2 mm (0.08 ") or 0.1 % of range (set at Pr.3) 2mm or 0.1% of range, whichever is the
whichever is greater greater. Analogue Output Opto isolated 4-20 mA or 4-20mA into 750 Ohms. 16 bit. Short circuit
0-20 mA into 750 ohms protected and opto-isolated on ac powered
Short circuit protected units. Not opto-isolated on 24Vdc units.
Maximum allowable degradation of signal 2% under extremes of transient and constant con­ducted immunity tests to EN50082.
Relay Outputs 5 multifunction SPDT relays 5 multi-function SPDT relays rated
rated 5 A/230 V a.c resistive 8A/230Vac/30Vdc resistive, with gold con
tacts.
Indication Integral 4 digit LCD, 12 mm (0.47") high Integral, 4 digit LCD, 12mm high characters.
characters 5 red LED’s to indicate relay status 5 red LED’s to indicate relay status. Failsafe High, low, hold (Pr.23 to 29) High, Low, Hold Damping Fully adjustable (Pr.7) Fully adjustable Blanking Fully adjustable (Pr.5) min 0.3 m (11.82 ") Fully adjustable Optional Temp. Reduces ambient temperature errors from sensor 0.17 % / 1 C of measured distance to
0.01 % / 1 C (34 F)
Transducer
NOTE: *All the above transducers can be approved for use in Hazardous Areas, Zones 1 & 2 but Ambient
Temperature limited to: -20 to + 60 deg C. CENELEC: EExm II T6 CERTIFICATE NO: 93C.108.020X
CE approved - EMC tested in accordance with EN50081 & EN50082
Parts 1 & 2 Low voltage directive, EN61010
Page 42
42
Pr Description Factory User Eng P r Description Factory User Eng
Default Default
Basic Set-up Open Channel Flow
1.00 Application 2.00 45.00 Flow Exponent 1.00
2.00 Units 2.00 46.00 Max. Flow Rate 0.00
3.00 Empty Distance 10(15) 47.00 Time Base for Flow 1.00
4.00 Operational Span 10(15) 48.00 Totalise Display Conv. 0.00
5.00 Blanking Distance 0.50 49.00 Contr. for Ext. Sampler 0.00
6.00 Rate of Change 1.00 50.00 Penstock Control 1.00
7.00 Decimal Display 2.00
Relays Pump Controls
8.00 Relay 1 0.00 51.00 Pump Sequence 1.00
9.00 Relay 1 Set 0.00 52.00 Duty Standby 1.00
10.00 Relay 1 Reset 0.00 53.00 Pump Exerciser 1.00
11.00 Relay 2 0.00 54.00 Pump Tolerance 1.00
12.00 Relay 2 Set 0.00 55.00 Pump Maintenance 0.00
13.00 Relay 2 Reset 0.00 56.00 Run-on-Interval 0.00
14.00 Relay 3 0.00 57.00 Run-on-Time 0.00
15.00 Relay 3 Set 0.00
16.00 Relay 3 Reset 0.00
17.00 Relay 4 0.00
18.00 Relay 4 Set 0.00
19.00 Relay 4 Reset 0.00 Echo Detection
20.00 Relay 5 0.00 68.00 Echo Selection 2(1)
21.00 Relay 5 Set 0.00 69.00 Check Search 1.00
22.00 Relay 5 Reset 0.00 70.00 Echo Velocity 344.1
Failsafe Miscellaneous
23.00 Failsafe R1 3.00 71.00 Correction Value 0.00
24.00 Failsafe R2 3.00 72.00 Parameter Display 0.00
25.00 Failsafe R3 3.00 73.00 Software Rev. No. S/Ware
26.00 Failsafe R4 3.00 74.00 Reset Counter 0.00
27.00 Failsafe R5 3.00
28.00 Failsafe Analogue 3.00
29.00 Failsafe Time Delay 120.00
Analogue Test Parameters
30.00 Analogue Output 1.00 75.00 Digital Output Set 0.00
31.00 Analogue Options 1.00 76.00 Hardware Test ====
32.00 Analogue Datum 0.00 77.00 Transmitter Test ====
33.00 Analogue Span 100.00 78.00 Simulation ====
34.00 Analogue Test 0.00
Temperature Number Store
37.00 Probe Enable 1.00 95.00 Serial Number Store Ser.No
38.00 Temp. Compensation 20.00 96.00 Security Code Store 15.02
39.00 Probe Test 0.00
Volume Conversion Reset
40.00 Vessel Shape 0.00 97.00 Relay Hrs/Starts Reset ====
41.00 Dimension H 0.00 98.00 OCM Totaliser Reset ====
42.00 Dimension L 0.00 99.00 Full System Reset ====
43.00 Display Conversion 1.00
44.00 Volume Linearisation ====
To scroll through parameters 1-74 press "MODE" followed by "1" followed by "TEST". To stop the scroll press "CE".
APPENDIX 4
PARAMETER SETTINGS BM90 / L ; (--) = BM90 E / LE SETTINGS
Loading...