Jotul Wood Stove User Manual

Jøtul F 602 USA
Jøtul F 602 USA
Installation and Operating Instructions for the USA and Canada
Kindly save these instructions for future reference. Ce document doit être conservé pendant toute la vie de l'appareil.
USA
Table of contents
General information
Possible hazards to avoid
when using the Jøtul F 602 USA ..................................... 2
Installation
Safety notice .......................................................................... 3
Top Exit or Rear Exit............................................................. 3
Fasten the Legs ..................................................................... 3
Plan Ahead
Chimney connector ............................................................. 3
Wall Pass-Through................................................................ 4
Chimneys................................................................................ 4
Masonry Chimneys .............................................................. 5
Listed Metal Prefabricated Chimneys ............................. 5
Connection to the Chimney
Masonry Chimneys .............................................................. 5
Prefabricated Chimneys ..................................................... 5
Clearances to Combustibles
Floor Protection .................................................................... 6
Alternate Floor Protection .................................................. 6
Clearances to Adjacent Combustible Materials .......... 6
Using a Rear Heat Shield .................................................... 6
to Reduce Clearance in Alcove Installations ................. 6
Using Wall Protectors
to Reduce Clearances in Alcove Installations ............... 6
Alcove Installation ................................................................ 6
Operation
Wood Storage ........................................................................ 8
Creosote and Soot Formation and
the Need for Removal......................................................... 8
Breaking in Your Stove ....................................................... 8
Controls
Front Door Latch ...................................................................8
Air Control .............................................................................. 9
Building a Fire ....................................................................... 9
Reloading ............................................................................... 9
Reloading Procedure ........................................................... 9
Ash Removal .......................................................................... 9
Maintenance
General .................................................................................. 10
Glass Replacement ............................................................ 10
Glass Cleaning ..................................................................... 10
Jøtul F 602 Woodstove Clearances ......... 7
Figures and Diagrams ..................... 21-26
General Information
The Owner's Manual describes the installation and operation of the Jøtul F 602 USA non-catalytic wood heater. This heater meets the U.S. Environmental Protection Agency's emission limits for wood heaters sold after July 1, 1990. Under specific test conditions, this heater has shown heat output at rates ranging from 9,600 to 42,000 BTU's per hour.
When installing, operating, and maintaining your Jøtul F 602 USA, follow the guidelines given in these instructions. Save these instructions, and make them available to anyone using the stove.
A number of areas of the U.S. and Canada require a building permit to install a solid-fuel burning appliance. NFPA 211 (National Fire Protection Association, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances) or CAN/CSA B-365 (Installation Code for Solid­Fuel Burning Appliances and Equipment) may apply to the installation of solid fuel burning appliances in your area. Your Jøtul dealer has knowledge of your local codes and can provide assistance in making sure your installation is safe and legal. Also contact your insurance representative, building inspector, or fire officials to determine what regulations apply in your area.
The Jøtul F 602 USA has been tested and listed to ANSI-UL 1482, and ULC S627 by Intertek Testing Services­Warnock Hersey of Middelton, Wisconsin.
Possible Hazards to Avoid When Using the Jøtul F 602 USA
Any use of fire in a house represents a certain danger. With intense overfiring, temperatures on the surface of the Jøtul F 602 USA can exceed 1 000 0F (536 0C).
Comply with the following guidelines:
• Never overfire the stove. If any part of the stove or chimney glows, you are overfiring, and a house fire or serious damage to the stove or chimney could result. Immediately close down the air control if you notice this condition.
• Teach children that the stove is hot and must not be touched.
• Never use gasoline, gasoline-type lantern fuel,
• Never use kerosene, charcoal lighter fluid or similar liquids to start or "freshen up" a fire in this heater. They can ignite with explosive force, causing bodily injury or death. Keep all such liquids far away from the heater while it is in use.
• Never use the stove if there are combustible gases in the house. The fumes from certain cleaning fluids,
2
USA
adhesives, and paints are a few examples of combustible gases. Remember, the operating woodstove is a source of "open flame".
• Avoid creating a "low pressure" condition in the room where the stove is operating, such as by operating an exhaust fan or a clothes dryer. A low-pressure condition could cause poisonous gases to be drawn out of the stove into the room. Some fuel will during combustion separate carbon monoxide and generate it in the burnchamber. Carbon monoxide is toxic, so please follow the guidelines in this manual to avoid smoke "roll out" from the burnchamber. You can prevent a low-pressure condition by providing adequate outside combustion air within 24" of the stove.
• Never operate the Jøtul F 602 USA if it has cracked or broken glass. Replace damaged glass only with the proper glass panel available from your Jøtul dealer.
• Never burn trash of any kind in the stove.
• Keep combustible materials far away from the stove.
• Never modify the stove in any way.
• Do not dry clothes over the stove, since they could fall and ignite.
• Use only seasoned wood in your stove. Never use fireplace coal or synthetic logs that have not been approved for the stove.
• Always wear protective gloves when adding fuel to the fire.
• If you for some reason experience smoke "roll out" from the fireplace, it might activate smoke detectors (if installed).
• Do not connect this heater to any air distribution duct.
Note! This stove is not approved for use in mobile homes.
Top Exit or Rear Exit
The Jøtul F 602 USA has two flue outlet positions. If you wish to top-exit the stove, place the cover plate in the rear position and secure it with the screws and nuts, then secure the flue collar to the top with the two remaining screws.
To rear -exit the stove, secure the cover plate in the top position with the two screws, then secure the flue collar to the rear with the two remaining screws and two nuts.
When fastening the plate or flue collar to the rear, it may be necessary to reach in through the top opening and hold the nuts with a wrench.
Attaching the Legs
The Jøtul F 602 USA has four tapped leg bolt holes in the bottom plate. Fasten each leg to the bottom with a bolt and with a washer between the bolt head and the leg.
Plan Ahead
A safe stove installation involves several elements, including: (A) the chimney connector, (B) the chimney itself, (C) the connection between the chimney connector and chimney, and (D) protection of combustible materials in the vicinity of the stove. Each of these elements is equally important for a safe stove installation.
Installation
Safety Notice
If this solid fuel room heater is not properly installed a house fire may result. For your safety, follow the installation directions. Contact local building or fire officials about restrictions and installation inspection requirements in your area.
Please read this entire manual before you install and use your new stove. Failure to follow instructions may result in property damage, bodily injury, or even death.
We recommend that you have your Jøtul F 602 USA installed by a professional installer of solid fuel room heaters.
A. Chimney Connector (Stove Pipe)
Chimney connector is also sometimes called stove pipe or flue pipe, and it is used to connect the stove to the chimney. The chimney connector should be 6" diameter black steel, with a minimum thickness of 24 gauge.
Do not use aluminium or galvanized steel pipe as a chimney connector. These materials cannot withstand the extreme temperatures of a wood fire and can give off toxic fumes when heated.
Matching enamel pipe is available for your Jøtul F 602 USA. Contact your Authorised Jøtul dealer for more information.
Do not use chimney connector pipe as a chimney.
The factory-supplied adapter must be used for fitting the stove's flue collar to the chimney connector.
Chimney connector sections must be attached to the
3
USA
stove's flue collar adapter and to each other with the crimped end toward the stove (fig. 2, page 20). The space between the flue collar adapter and the chimney connector should be sealed with stove cement or an appropriately size piece of gasket. This allows any small amounts of condensed creosote to run into the stove rather then onto the outside of the pipe or the stove top. All joints, including the adapter to the flue collar, should be secured with three sheet metal screws to ensure that the sections will not separate.
For proper operation the chimney connector should be as short as possible. Horizontal lengths should have an upward slope from the stove of 1/4" per foot. Avoid using more than two 90 degree elbows or total runs of pipe greater than 1 0'.
No part of the chimney connector may pass through an attic or roof space, closet or other concealed space, or through a floor or ceiling. Whenever possible, avoid passing the chimney connector through a combustible wall.
Wall Pass-Through
When your installation unavoidably requires that the chimney connector pass through a combustible wall to reach the chimney, extreme care must be taken. In the U.S., the National Fire Protection Association's publication NFPA 21 1, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, permits four methods for passing through a combustible wall. In Canada, refer to CAN/CGA B356. Before beginning the installation, contact local building officials to make sure the proposed pass­through method meets local building code requirements.
An approved installation that uses a section of listed solid fuel insulated factory-built chimney as a pass- through for the chimney connector, must have an inside diameter which is 2" larger than the chimney connector- a minimum length of 12" -and at least 1" of insulation thickness. The chimney section is installed with at least 2" of air space between the outer chimney wall and adjacent combustible materials.
Sheet steel support plates are used on both ends of the chimney section to keep the connector centred. The opening around the chimney section is closed on both sides of the wall with sheet steel plates and the chimney section is securely fastened to the plates. Fasteners used to support the chimney section should never penetrate the inner flue liner.
See NFPA-211 for other approved wall passthrough methods.
B. Chimneys
There are two types of chimneys suitable for the Jøtul F 602 USA. An approved masonry chimney, or a listed residential-type building heating appliance chimney.
When selecting a chimney type and the location for the chimney in the house, keep this in mind: it is the chimney that makes the stove work, not the stove that makes the chimney work. This is because a chimney actually creates suction, called draft, which pulls air through the stove.
Several factors affect draft: the height, cross-sectional area, and temperature of the chimney, as well as the proximity of surrounding trees or buildings.
A commonly used method to pass through a wall directly to a masonry chimney requires removal of all combustible material from at least 12" around the entire chimney connector. The space is then filled with at least 12" of brick around a fireclay liner. Be sure to locate it so that the top of the chimney connector will be at least 18" below the ceiling. To construct the brick pass-through, you will need an opening of 30" x 30" minimum. It will be necessary to cut wall studs, install headers, and construct a sill frame to maintain proper dimensions and to hold the weight of the brick. Minimum 3-1/2" (4" nominal) thick solid bricks are to be used. The fireclay liner (ASTM C35 or equivalent), minimum 5/8" wall thickness, must not penetrate into the chimney beyond the inner surface of the chimney flue liner and must be firmly cemented in place. If it is necessary to cut a hole in the chimney liner, use extreme care to keep it from shattering. Refractory mortar must be used at the junction to the chimney liner. (See figure 3, page 21)
4
In general, a short masonry chimney on the exterior of the house will give the poorest performance. This is because it can be very difficult to warm up, and in extremely cold northern areas it may not work at all.
A tall masonry chimney inside the house is easier to keep warm and will work best.
This guideline gives the necessary chimney requirements based on the U.S. national code (NFPA-211). However, many local codes differ from the national code to take into account climate, altitude, or other factors. It is important that you check with your local building officials to find out what codes apply in your area before constructing a chimney.
USA
Masonry Chimneys
The minimum requirements for a properly constructed chimney include the following:
• The foundation must be large enough to support the intended chimney without settling.
• The masonry wall of the chimney, if brick or modular block, must be a minimum of 4" nominal thickness. A mountain- or rubble-stone wall must be at least 12" thick.
• The chimney must have a fireclay flue liner (or equivalent with a minimum thickness of 5/8" and must be installed with refractory mortar. There must be at1/ 2" air space between the flue liner and chimney wall.
• The preferred fireclay flue liner size has a nominal size of 8" x 8", and should not be larger than 8" x12". lf round fireclay liners are used, the inside diameter should be 6" and not larger than 8". lf an existing chimney with larger tiles is used it should be relined with an appropriate liner.
• No other appliance can be vented into the same flue.
• An airtight cleanout door should be located at the base of the chimney.
A chimney inside the house must have at least 2" of clearance to the combustible structure. A chimney outside the house must have at least 1" clearance to the combustible structure. Fire stops must be installed at the spaces where the chimney passes through floors and/or ceilings. Remember that there must be air space around the chimney, and that insulation must be 2" or more from the chimney.
A chimney, wether masonry or prefabricated metal, must be the required height above the roof or other obstruction for safety and for proper draft operation. The requirement is that the chimney must at least 3' higher than the highest point where it passes through the roof and at least 2' higher than the be at least and highest part of the roof or structure that is within 10' of the chimney, measured horizontally (fig. 4, page 21).
Chimneys shorter than 14' may not provide adequate draft. This could result in smoke spilling the room from the door or joints in the stove or pipe. In addition, inadequate draft can cause puffing. A too-strong draft, on the other hand, cause excessive temperatures and can shorten burn times. Excessive drafts can be corrected by having your dealer install a barometric damper at 0.1 " of water column. lf you suspect you have draft problem, consult your dealer.
Listed Metal Prefabricated Chimneys
The heater must be connected to a listed Type HT per UL 103 or ULC S629 prefabricated chimney. When a metal prefabricated chimney is used, the manufacturer's installation instructions must be followed precisely. You must also purchase (from the same manufacturer) and install the ceiling support package or wall pass through, the "T" section package, the firestops (when needed), the insulation shield, the roof flashing, the chimney cap, etc. Maintain the proper clearance to the structure as recommended by the manufacturer. This clearance is usually a minimum of 2", although it may vary by manufacturer or for certain components.
There are basically two methods of metal chimney installation. One method is to install the chimney inside the residence through the ceiling and the roof (fig. 5, page 22).
The other method is to install an exterior chimney that runs up the outside of the residence.
C. Connection to the Chimney
Masonry Chimneys
When connecting to a masonry chimney, the chimney connector must slide completely inside the chimney thimble (or breach) to the inner surface of flue liner, make sure the connector does not protrude past the inside of the flue liner as that will reduce the flow area available for the smoke and ultimately cause problems with your chimney system. The chimney connector should be sealed into the thimble with refractory cement and the connector should also be mechanically fastened to the chimney.
See fig. 6, page 22.
Prefabricated Chimneys
Always follow the chimney manufacturer's instructions and use all the components required by the manufacturer. Do not take shortcuts or use make shift methods for securing the chimney connector to the chimney.
Note: The clearances expressed in inches are those approved for installations in the United States. The clearances in parentheses that are expressed in centimeters are those approved for installations in Canada. Different test standards for the respective countries may result in differences in the clearance requirements.
5
USA
Clearances to Combustibles
Floor Protection
A bottom heat shield is required in all installations. In addition, your stove must be placed on a noncombustible surface that extends 8" beyond the sides and back of the stove and 16" in the front of the stove. This will result in an overall base that is 28 1/2" wide x 45- 1/2" deep . This is the minimum floor protector size. Floor protection must also be used under the stove pipe and must extend 2" beyond either side of the pipe (fig. 7, page
22).
The floor protection must have a minimum R value of D. 45. Warning! Never put any type of floor protection on top of carpeting.
Alternate Floor Protection
All floor protection materials must be non-combustible (i.e., metals, brick, stone, mineral fiber boards, etc.). Any organic materials (i.e., plastics, wood, paper products, etc.) are combustible and must not be used. The floor protector specified may include some form of thermal designation such as R-value (thermal resistance), k-factor (thermal conductivity), or C-factor (thermal conductance).
The easiest means of determining if a proposed alternate floor material meets requirements listed in the appliance manual is to follow the procedure: See page 26.
hearth in it that you plan to use, it is extremely important that the entire system be examined for safety. Many older homes may have faulty chimneys, or previous owners may have covered combustible walls or studs with brick veneers. Heat is conducted readily through brick and could ignite unseen combustibles behind it.
Contact local building or fire official about restrictions and installation requirements in your area.
Using a Rear Heat Shield to Reduce Clearance in Alcove lnstallations
The Jøtul F 602 USA optional rear heat shield, PN HS50,may be used only in top-exiting parallel installations to reduce clearance as shown in figures 11,12,13, page 23.
Using Wall Protectors to Reduce Clearances
The wall protector must be non-combustible, such as a minimum 24 gauge galvanized steel or its equivalent. The wall protector must be elevated 1" from the floor to provide an air space of at least 1" between the shield and the combustible wall. See figures 16, 17, and 18 on pages 23
and 24 for approved sizing specifications.
Alcove installation
When installed with a listed double wall pipe and with wall protection, the Jøtul F 602 USA can be placed in an alcove that has a minimum height of 96”1 and a maximum depth of 48", and a minimum width of 41". The clearances for this installation are shown in figure 14-15, page 23.
Clearance to Adjacent Combustible Materials
The diagrams in figures 8-9-10 - page 22, give the required clearances you must maintain from unprotected combustible materials or objects.
A combustible is anything that can burn, and in the case of stove installations, these combustibles may not be visible. lf you are not sure of the combustible nature of any material in the vicinity of your planned stove installation, you should check with your local fire off icials. Remember that "fire resistant" materials are considered combustible; they are difficult to ignite, but they will burn.
lf you have recently purchased a home that has a stove
6
When installed with a listed double wall pipe and with a stove heat shield, the Jøtul F 602 USA can be placed in an alcove that has a minimum height of 96”1 and a maximum depth of 24”2, and a minimum width of 55". The clearances for this installation are shown in fig. 12-13, page 23.
In an alcove, the height of the wall protector, including the air space at the bottom, must be at least 41" (104 cm) (see fig. 15, page 23). Both side walls and the rear wall must be protected by the wall protector (fig. 14, page 22).
(1See NFPA 211 for ceiling clearance reductions with protection.)
Jøtul F 602 Woodstove Clearances
Stove clearances Unprotected surfaces Protected surfaces (NFPA 211) Top vent/vertical
Side Rear Corner Side Rear Corner
Single wall pipe 21" 13.5" 13" 13" 11" 9" W/out rear heatshield 535mm 345mm 330mm 330mm 280mm 230mm
Single wall pipe 21" 11" 11" 13" 11" 9" With rear heatshield 535mm 280mm 280mm 330mm 280mm 230mm
Shielded single wall pipe 21" 9" 9" 13" 8" 8" With rear heatshield 535mm 230mm 230mm 330mm 205mm 205mm
Double wall pipe 24" 9" 9" 13" 8" 8" With rear heatshield 610mm 230mm 230mm 300mm 205mm 205mm
Double wall pipe 24" 15" 15" 12" 8" 8" W/out rear heatshield 610mm 380mm 380mm 305mm 205mm 205mm
USA
Connector Unprotected surface Protected surface (NFPA 211) clearances (pipe) Vertical installation Vertical installation
Single wall pipe 18" 6"
460mm 150mm
Double wall pipe pipe mfgr.listing pipe mfgr.listing
Connector Unprotected surface Protected surface (NFPA 211) clearances (pipe) Horizontal installation Horizontal installation
Single wall pipe 18" 9"
460mm 230mm
Double wall pipe pipe mfgr.listing pipe mfgr.listing
Very Important:
Top vent/vertical - assumes the connector pipe is exiting off the top of the stove and traveling vertically. If top vented to any horizontal runs - the stove’s position is dictated by the connector pipe clearances.
Rear vent/horizontal - assumes the connector pipe exits from the rear of the stove and runs horizontally to the chimney. If rear vented to vertical run - the stove position is dictated by the connector pipe clearances.
Minimum alcove dimensions:
Unprotected surface Protected surface (NFPA 211) Vertical venting. Vertical venting Assumes top exit: Assumes top exit:
Minimum alcove width 55” (1400mm) 41” (1040 mm) Maximum alcove depth 48” (1220mm) 48” (1220 mm) Height above the top of the stove 71” (1805mm) 71” (1805 mm)
7
USA
Operation
Before building a fire in your new stove, please read the following section carefully.
The stove is designed to burn natural wood only. Higher efficiencies and lower emissions generally result when burning air-dried seasoned hardwoods, as compared to softwoods or to green or freshly-cut hardwoods.
Do not burn:
• Coal
• Garbage
• Cardboard
• Treated or painted Wood Solvents
• Treated or painted Wood
• Chemical Chimney Cleaners
• Colored Paper
• Any syntethic fuel or logs that have not been approved for wood stoves.
Burning treated wood, garbage, solvents, colored paper, chemical chimney cleaners, or trash may result in release of toxic fumes.
will depend on how you operate your stove, but it is important to inspect the flue after every two weeks of use. An accumulation of 1/4" or more on the sides of the flue or connector is considered hazardous and should be removed.
In the event that creosote in your chimney or flue connector ignites, the resulting fire is often accompanied by a roaring noise and a crackling sound as flakes of burned creosote break loose. lf you suspect you are having a chimney fire, immediately close the draft regulator and make sure the stove door is closed. Call the fire department and get everyone safely out of the house.
Trying to extinguish the fire in the stove will not help. In fact it can make the matter worse by allowing oxygen through the door, which then supports the fire in the chimney. When the roaring and crackling has stopped, you should resist the temptation to open the door and look at the fire. The fire may have suffocated, but could rekindle when you open the door. After a chimney fire, do not use your stove until the chimney and the flue connector has been cleaned and inspected to ensure that no damage has been sustained.
Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or "freshen up" a fire in this heater. Keep all such liquids far away from the heater while it is in use.
Wood Storage
When storing wood outside, it should be covered and stored off the ground to protect it from the elements. Make certain that the woodpile has good air circulation through it in order to promote drying to aid in the seasoning process.
To obtain the best performance from your stove, we recommend using seasoned hardwood that has been dried and stored under cover for at least one year. Burning unseasoned or wet wood causes the rapid development of creosote and reduces the heat value of the wood.
Creosote and Soot Formation and the Need for Removal
When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form creosote. These creosote vapors condense in the relatively cool chimney flue of a slow burning fire. The creosote that accumulates in the flue is highly flammable and is the fuel of chimney fires. To prevent a chimney fire, the creosote needs to be removed by sweeping the chimney and flue connector. The frequency of sweeping
Breaking in Your Stove
A cast iron stove should be "broken in" gradually. Five consecutive small fires must be built in the stove prior to operating the stove continuously. Each fire should be a little larger than the previous one, and the last fire should be a full-sized load. Allow the stove to cool completely between fires.
It is normal for new painted stoves to emit a smell or even some smoke during the first few fires. This is caused by the seasoning of the high temperature paint, and the odor will diminish with each fire and eventually disappear. Opening a window or door near the stove will help provide additional ventilation and reduce the odor.
Controls
Front Door Latch
The latch for the front door is conveniently located to the left of the door's center. To open the door, simply raise the latch and pull the door toward you. To shut the door, raise the latch, push the door tightly against the stove front, and lower the latch. See fig. 19 A, page 24.
8
USA
Air Control
The sliding air control (See fig. 19 B, page 24) is located in the bottom center of the front door.
Sliding the control to the right opens the air control and increases the heat output; sliding it to the left closes the control and decreases the heat output. Slide the control fully to the right when first starting or reviving a fire, or when maximum heat is required. Position the control in the middle or left of the middle when less heat is needed and when longer burn times are desired. You will determine the best settings for your particular needs as you gain experience with your stove.
Hot while in operation. Keep children, clothing and furniture away. Do not store fuel within the clearances listed previously.
Building a Fire
A good fire will efficiently utilize your fuel, keep the glass in the door clean, keep emissions and creosote to an absolute minimum, require less work, and be very predictable.
A Good Foundation
Reloading
Reload the stove while it is still hot and there are plenty of hot to ignite the fresh fuel load. It is a good idea to include a smaller piece or two of wood at the base of the new load to help the stove recover more quickly to its operating temperature.
Reloading Procedure
• Always wear gloves when tending your stove.
• Push the air control to the right to the full open position.
• Wait a few seconds and open the door.
• Use a stove shovel or similar tool to break up any remaining charcoal and to drag some live embers toward the front where combustion air enters.
• Load the fuel (Smaller pieces first).
• Close the door.
• Wait 5-10 minutes and adjust the air control to desired setting.
Note: lf the charcoal bed present at reloading time is relatively deep (2"-3") and your wood is well seasoned, it is possible to add the fresh fuel load, close the door and reset the air control for the desired heat output rate within 5 minutes.
• Make sure the air control handle is fully to the right. Open the front door and cover the bottom of the stove with tightly crupled newspaper. Criss-cross a generous double handful of dry kindling, such as split pieces of scrap lumber, on top of the paper. lf you don't have scrap lumber, split some of your best dry wood down to finger-sized pieces and use that. Place three or four 1 " -2" split pieces of dry wood on top of the kindling.
• Light the paper evenly across the front and close the door.
• Continue to add 1" - 2" pieces of split dry wood until a healthy bed of glowing coals has formed.
• You can now add three or four small-to-medium pieces of wood. Allow this wood to burn for several minutes. Once you are sure the wood is burning well, adjust the air control to your desired heat output level. Moving it to the right increases the heat; moving it to the left decreases the heat. Avoid operating the stove with the air control closed completely.
• In order for secondary combustion to occur, the fire must be well established with temperatures above
1.0000F (6000C) in the firebox.
• lf the fire dies out, this cause is most likely either an insufficient bed of coals, reducing the air supply too soon, or using wood that is either too large or not dry enough.
Ash Removal
Ash removal will be required every day or two during normal operation, and is most easily done when the fire has burned down to coals. Use a shovel to push or rake any hot coals first to one side. Shovel out the exposed ash, and push or rake the hot coal to the other side. Remove the ash from the second side as well, and then spread the hot coals evenly across the firebox. Wood may now be added to start a new fire.
When removing ash from a stove that is in operation, close and latch the door before taking the ashes outside for safe disposal. It is always a good idea to wear heavy protective gloves while removing and disposing of the ashes from your stove. Ashes should be placed in a metal container used exclusively for ashes, with a tight fitting lid. The closed container of ashes should be placed outdoors, well away from all combustible materials, pending final disposal. lf ashes are disposed of by burisl in soil or otherwise dispersed, they should be retained in the closed container until all cinders have thoroughly cooled.
Overfiring will result if the stove is operated with the door open. This could cause damage to the stove, void the
warranty or lead to a house fire.
9
Loading...
+ 19 hidden pages