IF THE INFORMATION IN THESE INSTRUCTIONS ARE NOT FOLLOWED EXACTLY, A FIRE
OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS
OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR LICENSED GAS SUPPLIER.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL
SWITCHES.
• DO NOT USE THE PHONE IN YOUR
BUILDING. IMMEDIATELY CALL YOUR GAS
SUPPLIER FROM A NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S
INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS
SUPPLIER, CALL THE FIRE DEPARTMENT.
Installation
and
Operation
Instructions
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DANS CETTE NOTICE POUR
REDUIRE AU MINIMUM LE RISQUE D’INCENDIE
OU POUR EVITER TOUT DOMMAGE MATERIEL,
TOUTE BLESSURE OU MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE
NI OU LIQUIDES INFLAMMABLES DANS LE
VOISINAGE DE CET APPAREIL OU DE TOUT
AUTRE APPAREIL.
L’INSTALLATION LE SERVICE DOIVENT
ETRE EXECUTES PAR UN INSTALLATEUR
QUALIFIE, AGENCE DE SERVICE OU LE
FOURNISSEUR DE GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE
GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES
SE TROUVANT DANS LE BATIMENT OU
VOUS VOUS TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE
FOURNISSEUR DE GAZ CHEZ UN VOISIN.
SUIVEZ LES INSTRUCTIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE DES INCENDIES.
Welcome to Jøtul...
Congratulations on the purchase of your new
Jøtul GI 425 DV Camden Classic Gas Fireplace.
We at Jøtul are glad you’ve made the decision to
warm your hearth with one of our products. We’ve
been making fine quality cast iron stoves and
fireplaces continuously since 1853. Your new
Camden fireplace is the result of our experience
as the world’s largest manufacturer of solid fuel
burning appliances for over 150 years.
In the GI 425 DV Camden Classic, we’ve combined
advanced gas technology with the warm,
traditional elements of cast iron. With proper care
and use, your Jøtul fireplace will provide you with
many years of safe, dependable and satisfying
service.
The GI 425 DV Camden Classic is a direct vented
gas heater designed and approved for installation
into an existing masonry fireplace. Please take a
few minutes to familiarize yourself with this
manual and the features of your new gas
fireplace.
PLEASE READ THESE INSTRUCTIONS IN THEIR
ENTIRETY AND MAKE THEM AVAILABLE TO
ANYONE USING OR SERVICING THIS
APPLIANCE.
THIS PRODUCT MUST BE INSTALLED BY A
LICENSED MASTER OR JOURNEYMAN PLUMBER
OR GAS-FITTER WHEN INSTALLED IN THE
COMMONWEALTH OF MASSACHUSETTS.
2. Lift the shipping carton off of the fireplace
cabinet.
3. Unpack the Firebox. The Logset is packaged inside
the firebox. Remove the Glass Panel Frame to
unpack the firebox:
• Locate the right and left spring latches on the
underside of the firebox floor. Release each latch
by pulling them forward to disengage the Frame
from the Firebox body.
• Pull the Glass Frame away from the Firebox and
lift to disengage it from the three steel retainer
tabs located at the top of the firebox. Set the
glass out of the way.
Do not unpack the log parts until you are ready
to install them.
4. Install the Levelling Bolts. Five round head
carriage bolts are included in the Hardware Bag.
Tilt the insert cabinet back on the pallet to allow
clearance for installation of these bolts into the
Cabinet Base, one at each corner and one in the
center.
Spring Latch
Replacement Parts List ............. 29
Service Log ................................ 30
Lighting Instructions ................ 31
Pull each Spring Latch to disengage them from the
Glass Frame.
3
Jøtul GI 425 Camden
Direct Vent Gas Fireplace
Manufactured and Distributed by:
Jøtul A.S.A.
Fredrikstad, Norway
Jøtul North America
Gorham, Maine
MEA No. 369-04-E
Test Standards
This appliance complies with
National Safety standards and
is tested and listed by Intertek
Testing Services of Middleton,
Wisconsin.
In addition, the Jøtul GI 425 DV gas fireplace
insert has been tested and listed as a direct vent gas
fireplace heater and listed to ANSI Z21.88-1998
(NFPA 54) and CSA 2.33-M98 for Canada.
Specifications
Input Rates
Natural Gas
26,000 BTU/hr. maximum input
13,000 BTU/hr. minimum input
Propane
26,000 BTU/hr. maximum input
13,000 BTU/hr. minimum input
GAS GAS
PANE IS DESIRED, THE FIREPLACE MUST BE
CONVERTED TO USE WITH PROPANE. FOR
YOUR CONVENIENCE THIS FIREPLACE IS
SHIPPED WITH A PROPANE CONVERSION
KIT.
Matte Black ................................................... #155314
Arched Frame w/ Screen,
Matte Black ................................................... #155315
Double Doors, Cast Iron -
Matte Black ................................................... #350565
Double Doors, Cast Iron -
Blue Black Enamel ....................................... #350566
Suggested Tools for
Installation and Service
• External regulator (for Propane only)
• Piping which complies with local code
• Manual shutoff valve - T-Handle in Massachusetts
• Sediment trap - if required by code
• Tee joint
• Pipe wrench
• Pipe sealant
• 10mm open end wrench
• 1/2”, 7/16” open end wrench
• Phillips head screwdriver
• Flat head screwdriver
• 1/4” nut driver
• Gloves
• Safety glasses
• Torx T20 screwdriver
• Leak test solution
• Power Drill
4
General Information
IMPORTANT:
SAVE THESE INSTRUCTIONS.
THIS HEATER MUST BE INSTALLED AND
MAINTAINED BY A QUALIFIED SERVICE
AGENCY.
DO NOT ATTEMPT TO ALTER OR
MODIFY THE CONSTRUCTION OF THIS
APPLIANCE OR ITS COMPONENTS. ANY
MODIFICATION OR ALTERATION WILL
VOID THE WARRANTY, CERTIFICATION
AND LISTING OF THIS APPLIANCE.
1. The installation and repair of this appliance must
be done by a qualified service person. Failure to
properly install and maintain this heater could
result in an unsafe or hazardous installation,
which may result in a fire, explosion, property
damage, personal injury or loss of life.
2. This appliance should be inspected before use
and at least annually. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative
that control compartments, burners and circulating air passageways of the appliance be kept
clean.
`S’assurer que le bruleur et le compartiment des
commandes sont propres. Voir les instructions
d’installation et d’utilisation qui accompagnent
l’appareil.
3. The installation must conform to local codes. Your
local Jøtul authorized dealer can assist you in
determining what is required in your area for a
safe and legal installation. Some areas require a
permit to install a gas burning appliance. Always
consult your local building inspector or authority
having jurisdiction to determine what regulations
apply in your area.
In the absence of local codes, the installation
requirements must comply with the current
National codes. In the U.S., these requirements
are established in the National Fuel Code, ANSI
Z223.1.(NFPA 54). In Canada, the codes have been
established in CAN/CGA B149 Fuel Installation
Code.
Installer l’appareil selon les codes ou reglements
locaux, ou, en l’absence de tels reglements, selon
les Codes d’installation CAN/CGA-B149.
4. DO NOT OPERATE THIS FIREPLACE IF ANY PART HAS
BEEN UNDER WATER.
Immediately call a qualified service technician to
inspect the heater and to replace any part of the
control system and any gas control which has
been under water.
Ne pas se servir de cet appareil s’il a ete’ plonge
dans l’eau, completement ou en partie. Appeler
un technicien qualifie pour inspecter l’appareil et
remplacer toute partie du syste’me de controle et
toute commande qui ont ete plonges dans l’eau.
5. Do not operate the fireplace with the glass front
removed, cracked or broken. Replacement of the
glass should be done by a licensed or qualified
service person. Only remove glass for routine
service. Always handle glass carefully.
Pour utilisation avec les portes en verre cerifiers
aved l’appareil seulemend ou. Ne pas utiliser avec
des portes on verre.
6. Notify your insurance company before proceding
with installation of this fireplace.
5
Safety Information
Installation
Due to the high operating temperatures this
appliance should be located out of traffic and
away from furniture, draperies, etc. Maintain
proper clearance to combustible mantels and
fireplace trim.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burns or clothing ignition.
Young children should be supervised while they
are in the same room as the GI425 gas fireplace.
Surveiller les enfants. Garder les vetements, les
meubles, l’essence ou autres liquides a vapeur
inflammables loin de l’appareil.
Clothing or other flammable materials should
not be placed ON or NEAR the GI425 gas fireplace.
Never allow any to use the fireplace if they are
unfamiliar with its operation.
NEVER store or use gasoline or any other flam-
mable vapors or liquids in the vicinity of the
GI425 gas fireplace.
Never burn any solid materials (wood, cardboard,
paper, coal, etc.) in this gas fireplace. Use with
natural gas or propane fuel ONLY.
Any safety screen, glass or guard removed for
servicing the appliance must be replaced prior to
operating the appliance.
Do not slam or strike the glass panel.
Were gloves and safety glases while performing
maintenance procedures.
Electrical Hazard
Be aware of electrical wiring locations when
cutting holes in walls and ceilings for termination.
The GI425 Blower must be electrically grounded
in accordance with local codes or, in the absence
of local codes, with the current ANSI/NFPA 70,
National Electrical Code or CSA C22.1-Canadian
Electrical Code.
The GI425 Blower is supplied with a three-prong
(grounding) plug for protection against shock
hazard and should be plugged directly into a
properly grounded three-prong receptacle. DO
NOT CUT OR REMOVE THE GROUNDING PRONG
FROM THE PLUG.
Always disconect the power supply when per-
6
forming routine service on the fireplace.
Requirements
The GI425 DV Camden Gas Insert can be installed in
most solid fuel burning fireplaces of either masonry
construction or a prefabricated factory built fireplace.
Prior to any installation of the GI425 DV Camden
the existing chimney exhaust flue must be thoroughly cleaned and completely inspected by a
qualified chimney sweep or fireplace service person.
Do not install this insert into a chimney that is
damaged. Any repairs must be made prior to installing the insert. If you are unsure of the condition of
your fireplace and chimney, contact a professional
fireplace technician or your local authorized Jøtul
dealer for professional assistance.
DO NOT REMOVE BRICKS OR MORTAR FROM THE
FIREPLACE OR CHIMNEY STRUCTURE. However,
masonry or steel may be removed from the smoke
shelf and adjacent damper frame area to accommodate installation of a chimney liner, provided that
their removal will not weaken the structure of the
fireplace or chimney, and will not reduce protection
for combustible materials.
If the fireplace has been modified to accommodate installation, use anchors or masonry nails to
attach the metal Fireplace Conversion Notice Plate to
the back wall of the masonry fireplace firebox where
it will be readily seen should the insert be removed.
THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE
OF ANY KIND.
All venting components must be installed in
accordance with the terms of their listing and
manufacturer’s instructions. Refer to the pipe
manufacturer’s instructions for proper pipe clearances.
This fireplace insert is specifically designed for
use with 3” Type B vent pipe components or a Listed
Flexible gas liner.
Do not modify or alter the construction of the
gas insert or any of its components to enable it to fit
into a fireplace. Any modification of the insert will
void the warranty, certifications and approvals of
the unit and could be dangerous.
25
E
C
D
A
B
635 mm
20
508 mm
7 1/2
191 mm
Exhaust
Outlet
1016 mm
Figure 1. GI 425 DV dimensions.
40
Air
Intake
11
289 mm
1 1/2
38mm
13
330 mm
8 1/2 (216 mm)
30 1/4
768 mm
127 mm
Air
Intake
2
50 mm
22
559 mm
17
432 mm
Exhaust
Outlet
5
21 1/2
546 mm
Minimum Fireplace Requirements
The GI425 DV CAMDEN gas insert has been specifically designed to be installed into a solid fuel burning
factory built fireplace OR a code approved solid fuel burning masonry fireplace with a tile flue liner. An
acceptable fireplace cavity must have the minimum dimensions specified below.
Two cast iron surround styles are available for the
GI 425 Camden fireplace insert.
Standard Classic Surround
The GI425 Camden includes Surround Panels
that will overlap a maximum fireplace opening
39” Wide x 29 1/2” High.
The actual standard surround dimensions are
40” Wide x 30 1/4” High.
Optional Lattice Classic Surround
The Lattice Surround Kit shares the same dimensions
as the standard Classic Surround described above.
#350557 - Matte Black
#350558 - Blue Black.
#350559 - Jøtul Iron
Optional Wide Surround
#155323 - Matte Black
#155324 - Blue Black.
#155354 - Jøtul Iron
These optional panels can be used to extend the Classic
or Lattice surround panels to cover oversize fireplace
openings up to a maximum 47” Wide x 33 1/2” High.
The actual wide surround dimensions are 48” Wide x
34” High.
NOTE: The additional weight of the Wide Surround
may necessitate use of the Anchor Bracket which is
included with this fireplace. The anchor will ensure
that the surround assembly aligns properly against
the fireplace face. Use the installation instructions
included in the Hardware bag.
48
1219 mm
The following clearances and hearth requirements
are the minimum requirements when installing the
Camden gas insert into a solid fuel burning appliance. These dimensions are measured from the
firebox cabinet to the combustible material. See
figures 5 and 6.
A combustible surface is anything that can
burn (i.e. sheet rock, wallpaper, wood, fabrics etc.).
These surfaces are not limited to those that are
visible and also include materials that are behind
non-combustibles.
If you are not sure of the combustible nature of
a material, consult your local fire officials. Remember, “Fire Resistant” materials are considered
combustible: they are difficult to ignite, but will
burn. Also, “fire-rated” sheet rock is considered
combustible.
Always maintain the proper clearances to the
appliance for the proper flow of ventilation air
around the insert.
Figure 5. Clearance to Adjacent Combustible
Material - measured from the fireplace centerline or
hearth.
F
E
Figure 4. Wide Surround Dimensions.
SEE PAGE 21 FOR SURROUND PANEL
ASSEMBLY INSTRUCTIONS.
8
34
864 mm
B
A
A: Hearth Protection Width - None required
B: Hearth Protection Depth - None required
C: Side Trim Clearance, 1” thick (25 mm) = 21 3/4 in. (552 mm)
D: Side Room Wall Clearance = 39 3/4 in. (1010mm)
E: Top Trim Clearance = 39 1/2 in. (1003 mm)
F: Mantel Clearance at 9 in. max. depth = 47 in. (1194 mm)
Mantel Clearance at 3.5 in. max. depth = 41 1/2 in. (1054 mm)
C
D
Mantel and Trim Clearance
9
228 mm
8
6 1/2
5
3 1/2
UPPER
TRIM
1 Max.
27 1/2
736 mm
21 1/2
622 mm
Depth
25 1/2
698 mm
23 1/2
660 mm
TOP OF FIREBOX
19 1/2
508 mm
17 1/2
394 mm
CABINET
22
559 mm
Figure 6. Minimum Mantel Clearances. Measure
clearances from the top and sides of the fireplace
cabinet before installation of the cast iron surround
panels.
Hearth Requirements
The Jøtul GI425 Camden does not require special
hearth protection. Combustible flooring materials
may be present directly in front of the fireplace
insert.
9
Vent Guidelines
• All vent components must be installed in accordance with the listing terms and manufacturer’s
instructions.
• Vent Height: Measured from the top of the insert
to the top of the termination cap.
Minimum: no less than 10'
Maximum: no greater than 35'. See figures 9 and 10.
The minimum vent height above the roof or
adjacent walls is specified by building codes. As a
general guide, follow the Gas Vent Rule on page
12.
• HORIZONTAL RUNS ARE NOT PERMITTED ANY-
WHERE IN THE VENTING SYSTEM.
• Venting liners used on this appliance may not be
less than 3” in diameter or greater than 3” in
diameter.
• Any unused flue or masonry enclosure can be used
as a passageway for venting provided the flue is
relined using 3” Listed flexible gas liner.
• The remaining space around the liner in a masonry or zero-clearance flue CANNOT be used to
vent any other appliance.
• Flexible liner components may not be exposed in
any living space.
• Installation of any components not manufactured
or approved by Jøtul or failure to meet all clearance requirements will void all warranties and
could result in property damage, bodily injury, or
serious fire.
• Never modify any venting component, or use any
damaged venting product.
• THE GAS APPLIANCE AND VENT SYSTEM MUST BE
VENTED DIRECTLY TO THE OUTSIDE OF THE BUILDING, AND NEVER ATTACHED TO A CHIMNEY
SERVING A SOLID FUEL OR GAS BURNING APPLIANCE.
• Variable Vent Restriction: See the System Check
section on pages 22-23 for specific instructions.
IMPORTANT NOTICE:
THE USE OF AN EXISTING CHIMNEY AS
AN AIR INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-1999-CSA 2.33M99 TEST METHODS AND RESULTING
ITS/WHI PRODUCT CERTIFICATION.
THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR
TO PROCEEDING WITH THIS INSTALLATION METHOD.
Masonry Fireplace Installation
When installing a GI425 DV Camden gas insert into
a masonry fireplace the insert will be vented
through dual 3” flexible gas aluminum liners.
This co-linear installation includes a pair of 3”
flex ducts that run from the insert completely
through the existing chimney to the termination
cap.
One liner is attached to the Exhaust Outlet on
the back of the unit and will carry the exhaust gases
to the outside of the house. This exhaust liner must
be directly connected to the unit and run the full
length of the chimney. See figure 7.
The other 3” liner will be attached to the Air
Intake Collar on the back of the unit to provide fresh
air for combustion. The Intake Collar is labeled for
easy identification. The liner must extend a mini-mum of 6’ off the back of the unit and extend
through the damper area of the fireplace into the
tile liner of the chimney. This liner can also extend
the full length of the chimney and connect to the
termination cap.
IMPORTANT
If the intake flex does not extend the full length
of the chimney, forming a direct connection between
the unit and the termination cap, A METAL BLOCK
OFF PLATE MUST BE INSTALLED to seal the air intake
from room air. Normally this sealing plate will be
installed within the existing fireplace damper area.
See figure 7. The sealing plate is not necessary if a
direct connection is made between the cap and the
fireplace.
WARNING! Avoid cross venting the insert. Before
installation, label both ends of the exhaust flex pipe
to ensure connection to the appropriate collars on
the fireplace unit and vent termination cap.
CANADA REQUIREMENT: Both the Intake and
the Exhaust liners must extend the full
length of the chimney and be securely
connected to both the unit and the termina-
tion kit.
If the fireplace has been modified to accom-
modate installation, use anchors or masonry
nails to attach the metal Fireplace Conver-
sion Notice Plate supplied with this unit to
the back wall of the masonry fireplace
firebox where it will be readily seen should
the insert be removed.