WARNING:
IF THE INFORMATION IN THESE INSTRUCTIONS ARE NOT FOLLOWED EXACTLY, A FIRE
OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS
OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR LICENSED GAS SUPPLIER.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCHES.
• DO NOT USE THE PHONE IN YOUR BUILDING.
IMMEDIATELY CALL YOUR GAS SUPPLIER
FROM A NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S
INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS
SUPPLIER, CALL THE FIRE DEPARTMENT.
Installation
and
Operation
Instructions
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DANS CETTE NOTICE POUR
REDUIRE AU MINIMUM LE RISQUE D’INCENDIE
OU POUR EVITER TOUT DOMMAGE MATERIEL,
TOUTE BLESSURE OU MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE
NI OU LIQUIDES INFLAMMABLES DANS LE
VOISINAGE DE CET APPAREIL OU DE TOUT
AUTRE APPAREIL.
L’INSTALLATION LE SERVICE DOIVENT
ETRE EXECUTES PAR UN INSTALLATEUR
QUALIFIE, AGENCE DE SERVICE OU LE
FOURNISSEUR DE GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE
GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES SE
TROUVANT DANS LE BATIMENT OU VOUS
VOUS TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE
FOURNISSEUR DE GAZ CHEZ UN VOISIN.
SUIVEZ LES INSTRUCTIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE
DES INCENDIES.
1
Welcome to Jøtul...
Congratulations on the purchase of your new
GF 600 DV Firelight Gas Heater.
We at Jøtul are glad you’ve made the decision to
warm your hearth with a Jøtul product.
Your new Firelight exemplifies over 150 years
experience as the world’s largest manufacturer of
solid fuel burning appliances. We’ve been
producing fine quality cast iron stoves and
fireplaces continuously since 1853.
In the Firelight, we’ve combined advanced gas
technology with the warm, traditional elements
of cast iron. With proper care and use, your Jøtul
stove will provide you with many years of safe,
dependable and satisfying service. We appreciate
your trust in welcoming our product into your
home and invite your comment and appraisal of
our efforts to provide you with the finest in home
hearth products.
Please take a few minutes to familiarize yourself
with this manual and the features of your
Firelight gas stove.
2
Table of Contents
Service Tools .............................................. 3
Replacement Parts List......................... 26
Lighting Instructions ............ Back Cover
Jøtul GF 600 DV Firelight
Direct Vent Gas Heater
Manufactured and Distributed by:
Jøtul A.S.A.
Fredrikstad, Norway
Jøtul North America
Portland, Maine
Test Standards
This appliance complies
with National Safety
standards and is tested
and listed by Intertek
Testing Services of
Middleton, Wisconsin to ANSI Z21.88-2002•CSA
2.33-M02 and CAN/CGA 2.17--M91, CSA P.4.-01.2
for Canada.
DO NOT ATTEMPT TO ALTER OR MODIFY THE
CONSTRUCTION OF THE APPLIANCE OR ITS
COMPONENTS. ANY MODIFICATION OR ALTERATION WILL VOID THE WARRANTY, CERTIFICATION AND LISTING OF THIS APPLIANCE.
www.nficertified.org
We at Jøtul North America are dedicated
to manufacturing the finest quality hearth
products you can be assured will give you
many years of safe, dependable service.
THIS PRODUCT MUST BE INSTALLED
BY A LICENSED PLUMBER OR
GAS-FITTER WHEN INSTALLED IN THE
COMMONWEALTH OF MASSACHUSETTS.
To ensure your confidence, we recommend that
whenever possible, our products be installed and
serviced by professionals who are certified by the
National Fireplace Institute (NFI) or, in Canada, by
Wood Energy Technical Training (WETT).
3
GF 600 DV Firelight
Specifications
Input Rates
Natural Gas
40,000 BTU/hr. maximum input
28,600 BTU/hr. minimum input
Propane
40,000 BTU/hr. maximum input
30,900 BTU/hr. minimum input
THIS FIREPLACE IS SHIPPED FROM THE
FACTORY FOR USE WITH
ONLY. IF USE WITH PROPANE IS DESIRED,
THE APPLIANCE MUST FIRST BE CONVERTED USING THE FUEL CONVERSION KIT
PROVIDED, #154391. CONVERSION SHOULD
BE MADE BEFORE THE APPLIANCE IS INSTALLED.
The installation and repair of this appliance must
be done by a qualified service person. Failure to
properly install and maintain this heater could
result in an unsafe or hazardous installation,
which may result in a fire, explosion, property
damage, personal injury or loss of life.
This appliance should be inspected before use
and at least annually. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative
that control compartments, burners, and circulating air passageways of the appliance be kept
clean.
Glass Front
Do not operate the Firelight gas stove with the glass
front removed, cracked, or broken. Replacement of
the glass should be done by a licensed or qualified
service person. Only remove glass for routine
service. Always handle glass carefully.
Optional Forced Air Blower Kit
This appliance must be electrically connected and
grounded in accordance with local codes or, in the
absence of local codes, with the current NFPA 70National Electric Code of CSA C22.1 - Canadian
Electrical Code.
(The blower must be plugged into a grounded
outlet).
THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE.
The installation must conform to local codes. Your
local Jøtul dealer can assist you in determining
what is required in your area for a safe and legal
installation. Some areas require a permit to
install a gas burning appliance. Always consult
your local building inspector, or authority having
jurisdiction, to determine what regulations apply
in your area.
REMEMBER: Your local officials have final author-
ity in determining if a proposed installation is
acceptable. Any requirement that is requested by
the local authority having jurisdiction, that is not
specifically addressed in THIS manual, defaults to
local code. In the absence of local codes, the
installation requirements must comply with the
current National codes. In the U.S., these requirements are established in the National Fuel Code,
ANSI Z223.1.(NFPA 54). In Canada, the codes have
been established in CAN/CGA B149 Fuel Installation Code.
Installer l’appareil selon les codes ou reglements
locaux, ou, en l’absence de tels reglements, selon
les Codes d’installation CAN/CGA-B149.
DO NOT OPERATE THIS STOVE IF ANY PART HAS
BEEN UNDER WATER. call a qualified service
technician to inspect the heater and to replace
any part of the control system and any gas
control which may have been under water.
Safety Information
During normal operation, the Firelight gas stove will
reach high surface temperatures. Therefore:
Due to the high operating temperatures, this
appliance should be located out of traffic areas
and away from furniture and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burns and/or clothing ignition.
Young children should be supervised while they
are in the same room as the Firelight gas stove.
Clothing or other flammable materials should not
be placed ON or NEAR the Firelight gas stove.
Surveiller les enfants. Garder les vetements, les
meubles, l’essence ou autres liquides a vapeur
inflammables loin de l’appareil.
NEVER store or use gasoline or any other flam-
mable vapors or liquids in the vicinity of the
Firelight gas stove.
Never burn any other materials in your Firelight
gas stove, it is strictly designed for use with
natural gas or propane fuel ONLY.
Any safety screen, glass or guard removed for
servicing the appliance must be replaced prior to
operating the appliance.
Ne pas se servir de cet appareil s’il a ete’ plonge
dans l’eau, completement ou en partie. Appeler
un technicien qualifie pour inspecter l’appareil et
remplacer toute partie du syste’me de controle et
toute commande qui ont ete plonges dans l’eau.
5
Installation
Requirements
Location
In selecting the location, the aesthetic and functional use of the appliance are primary concerns.
However, proper venting systems and access to the
fuel supply are also important issues. Due to the
high surface temperatures, you must also consider
the proximity of traffic areas, furniture, draperies,
etc.
This appliance may be located on or near
conventional construction materials. HOWEVER,
always maintain the proper clearances to combustibles, as this provides adequate ventilation air
around the appliance.
The following clearances and hearth requirements are the minimum requirements when
installing the Firelight gas stove near or on combustible surfaces. Always provide adequate access
around the appliance for servicing and proper
operation.
A combustible surface is anything that can burn
(i.e. sheet rock, wall paper, wood, fabrics etc.). These
surfaces are not limited to those that are visible and
also include materials that are behind non-combustibles.
If you are not sure of the combustible nature of
a material, consult your local fire officials. Remember, “Fire Resistant” materials are considered combustible: they are difficult to ignite, but will burn.
Also, “fire-rated” sheet rock is considered combustible.
Hearth Requirements
The Firelight gas stove CANNOT be installed directly
on carpeting, vinyl, linoleum or Pergo®.
If it is desired to install this appliance on any
combustible material OTHER THAN WOOD, a floor
pad must be installed that is either metal, wood or a
listed hearth pad. This floor protection must extend
the full width and depth of the appliance. It is not
necessary to remove the carpeting, vinyl or linoleum
from underneath the floor protection. See Fig. 1.
24”
(610 mm)
29”
(740 cm)
Figure 1. Minimum Hearth Protection
6
Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove to
Combustibles: See Figs. 2-4.
Rear:3” (75 mm)
Ceiling:33” (840 mm)
Corner:3” (75 mm)
Right Side: 4” (100 mm)
Left Side: 10” (254 mm) - for access to Lighting Instruction
plate
Minimum Clearances from the Vent Pipe
to Combustibles:
Horizontal Run:
Off the top of the pipe -2”(50mm)
Off the sides and bottom -1”(25mm)
Vertical Run:
All sides1”(25mm)
24” or greater depth of ceiling
REAR CLEARANCE = 3” (75 mm)
3” (7.5 cm)
10”
(25.5 cm)
Left Side*Right Side
* Allow 10” on left side of the appliance for
complete access to the lighting instructions
and control valve.
Figure 3. Parallel Installation Clearances
4”
(10 cm)
10” or less in depth
33”
84 cm
29”
74 cm
Figure 2. Mantel and Trim Clearances.
3 ”
(7.5 cm)
3”
7.5 cm
Figure 4. Corner Installation Clearance.
ALCOVE:
MAXIMUM ALCOVE DEPTH: 24” (61 cm)
MINIMUM ALCOVE WIDTH: 44” (112 cm)
MINIMUM CEILING HEIGHT: 64” (163 mm)
7
Vent Requirements
There are three types of venting configurations
approved for use with the Firelight gas stove:
• Vertical Termination
• Hearthmount Co-Linear (Vertical Termination)
• Horizontal Termination
The GF600 Firelight is approved for use with the
vent systems listed below. Use parts of one manufacturer only - DO NOT MIX VENT COMPONENTS
FROM DIFFERENT MANUFACTURERS IN THE SAME
SYSTEM.
• Simpson Dura-Vent GS
• Amerivent Corporation
• Security Vent Ltd.
• Selkirk Metalbestos
Installation of any components not manufactured or approved by Jøtul or failure to meet all
clearance requirements will void all warranties and
could result in property damage or bodily injury.
The approved vent configurations described in
this manual are derived from extensive testing
under controlled laboratory conditions. Gas appliance performance can be negatively affected by
variables present in the installation environment, i.e:
atmospheric pressure, strong prevailing winds,
adjacent structures and trees, snow accumulation,
etc. These conditions should be taken into consideration by the installer and stove owner when planning the vent system design.
IMPORTANT
• JOINT SEALING REQUIREMENT:
Apply a 1/8” bead of hightemperature (750°F) sealant to
the male section of the inner
vent pipe. See Fig. 9. The
cement should form a seal
between the inner and
outer pipes.
• NEVER modify any
venting component or
use a damaged venting
component.
• The gas appliance and vent system must be
vented directly to the outside of the building and
never attached to a chimney serving a solid fuel
or other gas appliance. Each direct vent gas
appliance must have its own separate vent
system. Common vent systems are prohibited.
• If the venting system is disassembled for any
reason, re-install according to the manufacturer’s
installation instructions.
SEALANT
Vent Restriction
The GF 600 DV Firelight includes two rectangular
Exhaust Restrictor plates and one square Air Inlet
Restrictor Plate as shown in Figure 5. These are
located in the parts bag. The plates are used to
compensate for draft characteristics that would
otherwise interfere with proper burner performance such as low heat output, weak flame
picture, or inefficient combustion.
Exhaust Restrictor Plate Installation
• Both Exhaust Restrictor Plates (#129642) MUST
be installed in all Co-linear vent systems and any
vertically terminated vent run exceeding 7 feet
(210 cm) in length.
1. Remove the Glass Panel and Log Set.
2. Using a 1/4” nut driver, remove the two sheet
metal screws in the rear wall of the firebox
ABOVE EACH exhaust outlet. See Figure 5.
3. Install a restrictor plate over the upper half of
each exhaust hole and secure the plate using the
same screws that were just removed.
4. Reinstall logs and glass.
Restrictor
Plate
Exhaust
Outlet
Figure 5. Exhaust Restrictor Plate installation.
Air Inlet Restrictor Plate Installation
• The Air Inlet Restrictor (#129347) MUST be installed with any Co-linear Vent system.
1. Remove the Glass Panel and Log Set.
2. Using a 1/4” nut driver, remove the two sheet
metal screws (A) and Rear Log Shelf from the back
of the firebox. See Figure 6.
3. Using the right hand sheet metal screw, reinstall
the Log Shelf with the restrictor plate between
the Shelf and the Back Wall. The plate should
cover the lower right air inlet.
4. Reinstall logs and glass.
8
Right Air Inlet
Restrictor
Plate
A
A
Rear Log Shelf
Figure 6. Air Inlet Restrictor Plate installation.
Co-linear Hearthmount Installation
The GF 600 DV Firelight can be installed using a
Hearthmount Co-linear Flexible Vent System,
designed for installation into a solid fuel burning
masonry fireplace. See Figures 7 and 8.
Refer to the vent manufacturer’s instructions for
venting components and installation details.
EXHAUST RESTRICTORS REQUIRED ON ALL
CO-LINEAR INSTALLATIONS.
ALWAYS MAINTAIN THE PROPER
CLEARANCES TO COMBUSTIBLES.
#991
High Wind Cap
#923GK
Top Kit
Installation of Simpson Dura-Vent Co-linear
adapter (#923GCL) directly off the rear of the
stove. (No length of pipe prior to the adaptor).
Use only 3” listed flexible gas vent liners may be
used in this installation.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE MAY RESULT IN
PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE
TO MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED IN THIS MANUAL AND IN THE
INSTRUCTIONS PROVIDED WITH EACH VENT COMPONENT.
IMPORTANT NOTICE:
THE USE OF AN EXISTING CHIMNEY AS
AN AIR INTAKE IS NOT COVERED
UNDER THE ANSI Z21.88-1999-CSA 2.33-
M99 TEST METHODS AND RESULTING
ITS/WHI PRODUCT CERTIFICATION. THE
CODE AUTHORITY HAVING
JURISDICTION MUST BE CONSULTED
PRIOR TO PROCEEDING WITH THIS
INSTALLATION METHOD.
Co-linear
Exhaust Height:
Maximum - 10 ft.
(3 m)
Maximum - 35 ft.
(10.5 m)
Chimney must
be sealed with
Block-off Plate
if Air Inlet does
not extend all
the way to
terminus.
Dual
3” Flex
Liners
Minimum
Co-linear
Air Inlet
Height:
6 feet
(180 cm)
#923GCL
Co-linear
Appliance
Adaptor
Figure 7. Co-linear Hearthmount Vent System
9
Simpson Dura-Vent Chimney
Conversion Kit
The GF 600 DV Firelight is approved for use
with Simpson Dura-vent Chimney Kits as
shown in Figure 8. These installation requirements must be followed:
In masonry chimney a fire-clay liner must be
present the entire length of the chimney.
Vertical Termination
Cap #991
(No t i ncl u d ed in ki t).
Simpson Dura-Vent
Termination Kit
GF 3 DV
ALLAGASH
Stove
The liner must have an inside dimension of
6” round or greater. (USE KIT #934)
Prefabricated chimneys must be listed for
the specific Simpson Dura-Vent Chimney
Conversion Kit or a UL 103 listing. (USE KIT
#931, #932, or #933)
When venting immediately off the rear of
the GF600 DV, the maximum horizontal
must be less than 14” (including thimble
depth). Any other horizontal run must be
less than 24“ in length.
The two Exhaust Restrictor Plates and the
Air Intake Restrictor Plate included with the
stove must be installed according to the
assembly instructions on page 8.
Simpson Dura-Vent
Thimbl e Adapter
(Included in kit)
Simpson Dura-Vent
#990 90º Elbow .
(Not included in kit)
Appropriate length of
Simpson
Dura-Vent Pipe for
vertical rise.
(No t i ncl u d ed in ki t).
A: Maximum
horizontal run when
venting immediately
off the rear of the
stove MUST BE LESS
THAN 14” (360 mm)
TOTAL!
.
A
Figure 8. Vertical Vent System through Masonry or
Prefabricated HT Chimney.
4 inch
(100 mm)
Flex Liner
(Not included in
kit)
Fire-clay
liner or U L
103 listed
prefabricated chimney pipe.
10
VERY IMPORTANT NOTICE:
THE USE OF AN EXISTING CHIMNEY AS
AN AIR INTAKE IS NOT COVERED
UNDER THE ANSI Z21.88-1999-CSA
2.33-M99 TEST METHODS AND
RESULTING ITS/WHI PRODUCT
CERTIFICATION. THE CODE
AUTHORITY HAVING JURISDICTION
MUST BE CONSULTED PRIOR TO
PROCEEDING WITH THIS
INSTALLATION METHOD.
Vertical Venting and Termination
The GF 600 DV Firelight can be vertically vented
through a roof or ceiling. Follow these guidelines
Steep roofs, nearby trees, or predominantly
windy conditions, can promote poor draft or
down draft conditions. In such cases, an increase to
the height of the vent may improve performance.
If an offset or elbow is necessary in the vertical
rise, the vent pipe must be supported every
three feet to avoid excessive stress on the
offsets. Use listed Wall Straps from any of the
approved vent suppliers.
Whenever possible, use 45° elbows instead of
90° elbows as they offer less restriction to the
flow of flue gases and intake air.
A firestop is required at every floor penetration.
The opening should be framed to 10" X 10"
inside dimension. A listed wall thimble is
required as a firestop.
Any venting that is exposed above the first floor must
be enclosed regardless of attic space or living space.
Always maintain the required 1" clearance from all
sides of the vertical vent system.
ANY VENTING WITH A VERTICAL RISE MUST TERMINATE (END) WITHIN THE SHADED AREA.
Restrictors required on:
• All Co-linear (flex pipe)
• All coaxial (rigid pipe) venting higher than 7
feet.
• Both restrictors must be used when restriction is
required.
• Always maintain the proper clearances to
combustibles.
35 Ft.
(10.67 m)
30 Ft.
(9.14 m)
25 Ft.
(7.62 m)
IT IS NECESSARY to add restriction to a vertical
vent installation to compensate for excessive
draft. See the Adding Draft Restriction section
on page 8.
GAS VENT HEIGHT: In no case shall any discharge
opening on the cap be less than 18” (457mm)
horizontally from the roof surface.
Horizontal Overhang
all
18.
min.
Termination
Cap
Figure 9. Vent height and clearance from adjacent
surfaces.
18.
min.
Vertical W
Lowest Discharge
Opening
18 min.
20 Ft.
(6.10 m)
VERTICAL RUN
15 Ft.
(4.57 m)
10 Ft.
(3.05 m)
7 Ft. (2.13 m)
Min. Height for
Vertical
Termination
5 Ft.
(1.52 m)
2 Ft.
(.61 cm)
Min. Vertical
Rise for 1 ft.
(30.4 cm)
Termination
5 Ft.
(1.52 m)
(3.05 m)
HORIZONTAL RUN
10 Ft.
11
Horizontal Termination
The horizontal termination cap must maintain a
3” clearance to any overhead combustible
projections that are 2 1/2” or less. It must also
maintain a 12” clearance from projections that
exceed 2 1/2”. See Figure 9.
Minimum vertical rise from the top exit position
is a 24” section vent pipe. See Fig. 10.
A horizontal vent run made directly off the rear
of the stove must terminate ONLY with a 36”
Snorkel Cap.
The maximum horizontal run shall include no
more than a single 24” section of pipe. See
Figure 11.
The termination cap must not be recessed into the
wall or siding. Do not fill air space in wall around
termination cap with any type of insulation.
A minimum 11” X 11” square hole is required for
the proper pipe clearance through a wall penetration. A 10” x 10” opening is suitable with use
of Simpson Dura-Vent Wall Thimble #942.
Any horizontal run of vent must be level or have
a 1/4” rise for every foot of run toward the
termination cap.
Maximum
horizontal with 2
90° Elbow
(#990B)
Minimum vertical
rise with horizontal
termination: 24”
ft. vertical is 12”
Standard Horizontal
termination cap
(#984, #985)
C
L
58 1/2”
(148.6 cm)
center line
with required
2ft. rise and
90° elbow
Figure 10. A vertical run in a horizontal termination
must be at least 2 feet (61 cm).
Prevent potential damage to vinyl siding with
installation of a Vinyl Siding Standoff between
the vent cap and the exterior wall.
Rear Exit
Position
24 ”
610 mm
36” Snorkel
Maximum horizontal
run into a 36” Snorkel:
24” (610 mm )
Figure 11. Rear Exit Horizontal Termination.
12
Figure 12. Horizontal Termination Clearance
A = Clearance above grade, veranda, porch , deck, or
balcony : *12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened: 9
inches (23 cm) minimum. We recommend 12 inches
(30 cm) minimum to help prevent condensation.
C = Recommended clearance to permanently closed
window: 9 inches (23 cm) minimum. We recommend
12 inches (30 cm) minimum to help prevent condensation on the window.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60
cm) from the centerline of the terminal: 18 inches
(46 cm) minimum.
E = Clearance to unventilated soffit: 12 inches (46 cm)
minimum.
F = Clearance to outside corner: 9 inches (23 cm) min.
Jøtul N.A. strongly recommends 12 inches (30 cm),
G = Clearance to inside corner: 6 inches (16 cm) mini-
mum. Jøtul N.A. strongly recommends 12 inches (30
cm), particularly where windy conditions are prevalent.
H = *Not to be installed above a meter/regulator assem-
bly within 3 feet (90 cm) horizontally from the
centerline of the regulator.
I = Clearance to service regulator vent outlet: U.S. - 3 feet
CAN. 6 feet (1.8 m) minimum.
J = Clearance to nonmechanical air supply inlet to
building or the combustion air inlet to any other
appliance: *12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet: *6 feet
(1.8 m) minimum.
L = ** Clearance above paved sidewalk or a paved driveway
located on public property: *7 feet (2.1 m) min.
M = Clearance under veranda, porch, deck, or balcony: *12
inches (30 cm) minimum.
1
particularly where windy conditions are prevalent.
* As specified in CGA B149 Installation Codes. Note: Local Codes and Regulations may require different clearances.
** A vent shall not terminate directly above a sidewalk or driveway which is located between two single family dwellings and serves both
dwellings.*
1
Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*
Figure 13.
Termination clearance to
overhangs.
12
305
mm
2 1/2
64 mm
3
76 mm
13
Mobile Home Installation
Fuel Conversion
The GF 600 DV Firelight can be installed for use in a
mobile home in the U.S. and Canada provided:
1. The stove is secured to the floor of the mobile
home. Use Jøtul Floor mounting kit #750304.
2. The stove is installed in accordance with Title 24
CFR, Part 3280- Manufactured Home Construction and Safety Standard, in the U.S. Comply with
CSA Z240.4, Gas Equipped Recreational Vehicles
and Mobile Housing, in Canada.
3. Always contact your local officials about installation restrictions and requirements in your area.
THIS APPLIANCE MAY BE INSTALLED AS AN
OEM INSTALLATION IN A MANUFACTURED
(MOBILE) HOME AND MUST BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER’S
INSTRUCTIONS AND THE MANUFACTURED
HOME CONSTRUCTION AND SAFETY
STANDARD, TITLE 24 CFR, PART 3280,
STANDARD FOR MANUFACTURED HOME
INSTALLATION, ANSI/NCBCS A255.1 OR
STANDARD FOR CANADA, CSA Z240.4.
THIS APPLIANCE IS ONLY FOR USE WITH THE
TYPE OF GAS THAT IS INDICATED ON THE
STOVE’S RATING PLATE. AN LPG GAS
CONVERSION KIT IS PROVIDED WITH THE
GF 600 DV FIRELIGHT GAS STOVE.
THIS APPLIANCE MAY BE INSTALLED IN AN
AFTERMARKET PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE NOT
PROHIBITED BY LOCAL CODE.
CET APPAREIL PEUT ETRE INSTALLE DANS UN
MAISON PREFABRIQUEE (MOBILE) DEJA
INSTALLEE A DEMEURE SI LES REGLEMENTS
LOCAUX LE PERMETTENT.
CET APPAREIL DOIT ETRE UTILISE
UNIQUEMENT AVEC LES TYPES DE GAS
INDIQUES SUR LA PLAQUE SIGNALETIQUE. NE
PAS L’UTILISER AVEC D’AUTRES GAS SAUF SI
UN KITDE CONVERSION CERTIFIE EST
INSTALLE.
The GF 600 DV Firelight gas stove is shipped from
the factory equipped as a NATURAL GAS unit.
However, the stove is shipped with the necessary
gas conversion kit to convert the stove to burn
propane gas. These kits contain all the necessary
components needed to complete the task and
ensure safe operation, including labels that must be
affixed to the stove.
WARNING:
THE CONVERSION KIT IS TO BE INSTALLED BY
AN AUTHORIZED JØTUL SERVICE TECHNICIAN
IN ACCORDANCE WITH THE MANUFACTURER’S
INSTRUCTIONS AND ALL CODES AND
REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN SERIOUS
INJURY OR PROPERTY DAMAGE. THE
QUALIFIED AGENCY PERFORMING THIS WORK
ASSUMES RESPONSIBILITY FOR THIS
CONVERSION.
Conversion Kit (LPG #154391, NG # 154392)
Tools required:
• 1/4” nut driver
• 1/2” & 13 mm open end wrench or deep-well
socket
• Torx T20 or slotted screwdriver
• 7/16” open end wrench
• 3mm allen wrench
• 4 mm allen wrench
Conversion Kit Contents:
• 1 regulator tower labeled for propane
• 3 regulator tower screws
• 1 burner orifice (3.3 mm for NG, #48 for LP)
• 1 pilot orifice (#51 for NG, #30 for LP)
• Label A - to be completed and applied to the back
of the stove
• Label B - apply to the rating plate
• Small valve label - apply to valve body
• Conversion instructions
IN CANADA:
THE CONVERSION SHALL BE CARRIED
OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND
IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 & .2 INSTALLATION CODE.
14
Gas Conversion Procedure
All numbers in ( ) refer to the exploded view on
page 25 of this manual.
1. Turn off gas supply to the stove.
2. Remove the top griddle (7).
3. Locate the two set screws near the top of each
side casting (3, 8). Using a 3mm allen wrench
thread the set screws out. Lift off the top panel
of the stove (6).
4. Open the front doors of the stove using the stove
tool.
5. Release the glass clips (17) atop the firebox (22)
and slowly lift glass assembly (16) up and out.
6. Remove the four logs (36) using care not to
scratch or damage the logs.
7. Using a 1/4” nut driver remove the two hex head
screws that secure the air divider (21) to the
front log support (18) and lift out of the firebox
(22). See Figure 12.
10. Adjust the air shutter on the burner tube (19) to
allow for the proper mixing of air and gas. See
Fig. 13.
1/2” open for natural
7/8” open for propane
AIR SHUTTER
BURNER TUBE
ATTENTION: Air shutter should never be
LESS than 1/8” open.
Figure 13. Air shutter adjustment.
11. Change the Pilot Orifice.
From within the
firebox, pull the pilot hood off the pilot assembly.
See Fig. 14. Using the 4 mm allen wrench included with the conversion kit, remove the
original pilot orifice (counterclockwise). Replace
with the appropriate orifice:
#51 for natural gas
#30 for propane
12. Tighten orifice into the base of the pilot assembly. Be sure the orifice is tightly secured toprevent bypass leakage. Replace pilot hood onto
the pilot assembly.
Burner
Tube
Front Log
Support
Air
Divider
Figure 12. Remove the Air Divider and Log Support.
8. Shift the burner tube (19) to the right and lift
out. Note: There are no screws securing the
burner tube to the floor of the firebox. Simply
lift the rear of the tube slightly and then lift the
entire tube.
9. Change the main burner orifice. Using a ½” open
ended wrench or deep-well socket remove the
burner orifice from the brass orifice holder.
Replace with the appropriate orifice supplied in
the kit.
3.3 mm for NG
#48 for LP
Pilot Head
Pilot Orifice
Figure 14. Remove pilot head and pilot orifice.
15
13. Replace the burner tube (19), front log support
(18) and air divider (21), be sure to secure with
the two 1/4” hex head screws.
14. Install the log set (36), embers and glass assembly (16). See page 18 for log set placement.
15. Reinstall the top panel (6) and top griddle (7).
Be sure to secure with set screws from step 3.
16. Locate the decorative cast iron skirt (4) between
the left front and rear legs. Use a 13 mm wrench
or socket to remove the bolt that secures the skirt
to the base of the stove to improve access to the
valve. See Fig. 15.
17. Replace the variable regulator. Using a Torx T-20
screwdriver, remove the three specialty screws
from the HI/LO regulator on the front of the
valve. Note: To help identify which screws to
remove, refer to the new regulator in the kit. See
Figure 16.
18. Remove the regulator tower and the gasket. Be
sure to remove the black rubber gasket from the
valve.
19. Install the new variable regulator tower from the
kit. Be sure that the gasket is properly positioned
and tighten screws securely.
20. Install the identification labels to the stove so
that they can be seen by any person that may be
servicing the stove.
Label A: Apply to back of stove.
Label B: Apply to the Rating Plate.
Small valve sticker: Apply to valve.
Decorative Skirt
Figure 15. Remove the valve skirt for better access.
VARIABLE
REGULATOR TOWER
BE SURE TO
REMOVE THE BLACK
RUBBER GASKET
FROM THE VALVE!
MAIN GAS VALVE
21. Reassemble the stove, apply gas to the system
and check for leaks using a soapy water solution.
NEVER USE AN OPEN FLAME TO CHECK
FOR GAS LEAKS.
It is important that the correct gas pressure be
established at the time of installation. For more
details see the Gas Pressure section of this manual
(page 17).
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON THE INSIDE BACK
COVER OF THIS MANUAL WHEN LIGHTING THE STOVE.
16
Figure 16. Regulator parts.
Gas Connection
NOTE: IF THE OPTIONAL BLOWER KIT (# 129161) IS
TO BE INSTALLED ON THE STOVE AT THE TIME OF THE
INSTALLATION OR IN THE FUTURE, THE GAS SUPPLY
LINE SHOULD BE INSTALLED AS CLOSE TO THE FLOOR
AS POSSIBLE. USE OF A 90° ELBOW DIRECTLY OFF THE
VALVE TO ALLOW FOR ADEQUATE CLEARANCE FOR
THE BLOWER. See Figure 15.
The gas supply line connection is made to the
valve just inside the left rear leg. The Gas supply line
should be 3/8" or 1/2" diameter, or the appropriate
size to provide sufficient gas pressure to the valve
regardless of the input setting.
The use of Flexible Gas Appliance Connectors is
acceptable in many areas in the U.S., however,
Canadian methods vary depending on local code.
ALL INSTALLATIONS MUST COMPLY WITH LOCAL
CODE OR IN THE ABSENCE OF LOCAL CODE, MUST
COMPLY WITH THE MOST RECENT EDITION OF THE
NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR
CAN-B149.
All codes require a gas shutoff valve (gas cock)
and union to be installed in the supply line and in
the same room as the appliance for servicing and
maintenance. See Figure 17.
T-handle gas cocks are required in Massachusetts in compliance with Code 248 CMR.
Secure all joints tightly using appropriate tools
and sealing compounds (for propane units be sure to
use compounds that are propane resistant). Turn on
gas supply and test for gas leaks using a soapy water
solution. Never use an open flame to check for
leaks.
Leak test:
1. Mix a 50-50 solution of water and dish soap.
2. Light appliance- see lighting instructions on page
22 of this manual or on the stove’s rating plate.
3. Brush or spray all joints and connections with the
soapy water solution.
4. If bubbles appear at any connection or seam or a
gas odor is detected immediately turn gas control
knob to the OFF position.
5. Tighten or reconnect the leaking joint and retest
for any gas leaks.
Gas Pressure
It is important that the correct pressure is established at the time of the installation. Proper gas
pressure provides a consistent flow of gas to the
appliance and is instrumental in checking for gas
leaks. The gas control valve on the stove is equipped
with pressure test points for gauge connections. The
gauge connections are located on the front of the
valve under the On/Off/Pilot- knob. See Fig. 18.
Gauge connections are identified by:
•E for inlet or supply pressure ( the amount of gas
coming to the valve.)
•A for manifold pressure (the amount of gas that
is coming out of the valve to the burner.)
ALWAYS TEST PRESSURES WITH VALVE CONTROL
KNOB SET ON HIGH.
Figure 17. Gas supply valve types and fittings.
Control Valve
EA
Figure 18. Inlet and Manifold pressure test points.
INLET GAS PRESSURES
(inches water column)
MIN MAX
NATURAL GAS5.0 WC7.0 WC
PROPANE11.0 WC13.5 WC
17
High Altitude Adjustment
The appliance and its main gas valve must be
disconnected from the gas supply piping system
during any pressure testing on that system at test
pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas
supply line by closing its individual manual gas
shut-off valve (gas cock) during any pressure
testing of the gas supply piping system that is
equal to or exceeds pressures of 1/2 psig (3.5kPa).
MANIFOLD PRESSURES
MIN MAX
NATURAL GAS1.7WC3.5 WC
PROPANE6.4 WC10.0 WC
ATTENTION:
NEVER ALLOW THE INLET GAS PRESSURE TO EXCEED 13.5” WC
(OR 1/2”PSIG) AS SERIOUS DAMAGE
TO THE VALVE CAN RESULT.
When installing the GF 600 DV Firelight gas stove in
high altitude situations (above 2500') it becomes
necessary to compensate for the thinner air (less
volume of oxygen per cubic foot). High altitudes
affect the atmospheric pressure and heat value of
gaseous fuels. Lower oxygen content in the air and
lower gas viscosity require the use of a different
orifice to achieve efficient, clean combustion at the
burner tube.
In the U.S.,
THE DERATING KIT MUST BE INSTALLED BY AN
AUTHORIZED SERVICE TECHNICIAN IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AND ALL CODES AND REQUIREMENTS OF
THE AUTHORITY HAVING JURISDICTION. THE
INFORMATION STICKER MUST BE FILLED OUT BY
THE INSTALLER AND ADHERED TO THE APPLIANCE
AT THE TIME OF THE CONVERSION. THE QUALIFIED
SERVICE AGENCY PERFORMING THIS WORK ASSUMES RESPONSIBILITY FOR THIS DERATING.
In Canada,
This unit has been tested for installation at high
altitudes in accordance with Canadian test standard CAN/CGA-2.17.
THE DERATING SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN
ACCORDANCE WITH THE REQUIREMENTS OF THE
CAN1-B-149.1 AND .2 INSTALLATION CODE.
For installations from 610 - 1370 meters (2,0004,500 ft.) the orifice size is 3.3 mm for natural gas
and #48 mm for propane.
18
SEE THE HIGH ALTITUDE ORIFICE CHART on the
page 19. For high altitude installations, consult your
local gas distributor or the authority having jurisdiction for proper rating methods. If the installer
must convert the unit to adjust for varying altitudes, the information sticker must be filled out by
the installer and applied to the appliance at the
time of the conversion.
Derating Procedure
To derate this unit, install the appropriate orifice per
the High Altitude chart.
1. Remove the two ¼” hex head screw that holds
the burner tube/log support to the bottom of the
stove.
2. Remove the burner tube/log support to expose
the main burner orifice.
3. Remove the orifice and replace with the appropriate one from the high altitude kit.
4. Be sure to attach the high altitude conversion
sticker provided with the kit to the rating plate on
the appliance.
THIS STOVE HAS BEEN CONVERTED FOR USE AT
AN ALTITUDE OF: ___________
Orifice Size: __________ Manifold Press. _____
Input Btu/Hr. _________ Fuel Type __________
Date of Conversion ___________
Figure 19. High Altitude Conversion Label. This sticker
is included in all high altitude kits and must be
applied to the stove when converted for high altitude.
HIGH ALTITUDE ORIFICE CHART
Gas Type
Natural Gas
Natural Gas
Propane
Propane
Orifice Size
3.3 mm
3.2 mm
#48
#48
Elevation
0-2000 ft.
(0-610 m)
2001-4500 ft.
(611-1370 m)
0-2000 ft.
(0-610 m)
2001-4500 ft.
(611-1370 m)
Part Number
129666
Orifice only
154393 Kit
129407
No Derate
Air Shutter Adjustment / Flame
Appearance
The GF 600 DV FIRELIGHT gas stove is shipped from
the factory equipped as a NATURAL GAS STOVE. If
the stove is converted for propane, it will be necessary to adjust the air shutter on the burner tube to
achieve the proper gas to air mixture. The proper air
shutter settings are:
1/2” open for natural
7/8” open for propane
The air shutter can also help achieve the desired
flame appearance. Generally, flame appearance is a
matter of preference, however most people enjoy a
warm yellowish flame.
Air Shutter Too Open - the appliance will
generate a flame that is blue and transparent, or an
“anemic” flame.
Air Shutter Too Closed - the appliance will
generate very long yellow flames resulting in soot.
Sooting produces black deposits on the logs, on the
inside walls of the appliance, and potentially on the
exterior termination cap.
Sooting is caused by incomplete combustion in
the flames and lack of combustion air entering the
air shutter opening.
To adjust the air shutter, remove the burner
tube and using a phillips head screwdriver loosen
the screw at the air shutter and adjust accordingly.
Be sure to retighten the screw that holds the air
shutter setting. Reassemble the stove and close the
door. Allow stove to burn 30 minutes on the HIGH
setting, observing the flame continuously. If the flame
appears weak, slow, or sooty, repeat the process
described above until the flame is as desired.
See Fig. 13.
WARNING:
AIR SHUTTER ADJUSTMENTS
SHOULD ONLY BE PERFORMED
ONLY BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN.
19
Install the Log Set
The four-piece log set is packaged in bubble wrap
inside the firebox.
Do not handle the log set with your bare
hands. Always wear gloves to prevent skin irritation from the ceramic fibers.
1. Remove the Grille and Top Plate from the stove.
Release the Glass Clips on top of the firebox. Lift
the Glass Panel straight up and out of the stove.
Remove the log set package.
2. Install the Rear Log, oriented as shown in Fig. 20.
Place the log on the shelf (Rear Log Support)
against the back wall of the firebox. Push it over
to the right rear corner.
3. Install the Front Log on the Log Support over the
center of the burner tube. The pins in the Front
Log Support will engage with holes in the
bottom of the Front Log.
4. Install the Cross-over Log and Left Log as shown
in Fig. 21. Engage the pins in the Front Log with
the corresponding holes in the bottoms of the
upper logs and position the other ends in the
notches on the Rear Log.
Cross-over
Log
Left Log
Rear
Log
Front
Log
Figure 20. GF 600 DV Log set parts.
Placement of the Embers
The package of Ember stones, located in the
hardware bag, will simulate glowing coals when
the burner is operating. For best results, spread the
stones evenly across the burner tube screen. “Pea”
size embers create the best appearance, while too
large a “chunk” can create long stringy yellow
flames. All of the embers do not have to be used.
See Fig. 21.
Pin
Pin
Ember Stones
Figure 21. Positioning the top logs and ember stones.
20
Optional Controls
1
(25mm)
3/8
(8mm)
Min.
1/8
(3mm)
Min.
System Check
Wall Thermostat
Use only a 750 millivolt DC two-wire circuit ther-
mostat, placed in the same room as the heater,
typically 5’ off the floor. Avoid drafty areas or any
area that may affect the accuracy of the thermo-
stat.
The thermostat should be connected to the
stove using a minimum of 16 gauge wire with a
maximum length of 35 feet of wire.
Connect the two thermostat wire leads to the
two lower terminals on the terminal block located
ont the valve. Do not overtighten the connections.
IT IS NOT NECESSARY TO DISCONNECT ANY OTHER
WIRES. See Fig. 22.
At the thermostat, the two wires should be
connected to the two connection screws on the
thermostat base plate per the manufacturer’s
instructions.
For thermostatic operation, the On/Off/T-Stat
switch must be in the T-stat position, and the pilot
light must be on.
Remote Control
When using a remote, the remote receiver should
be wired to the terminal block the same way the
thermostat would be. See the instructions above.
Follow the operating instructions included with
the Remote Control unit.
1. PURGING THE GAS LINE: When lighting the
appliance for the first time, it will take a few
moments to clear the gas line of air. Once this
purge is complete, the appliance will operate as
described in the lighting instructions. See the
inside back cover of this manual or the stove
Rating Plate attached the bottom of the stove. All
subsequent lightings of the stove will not require
purging the gas line unless the supply line is shut off.
2. PILOT FLAME: The pilot flame should be steady -
not lifting or floating. The flame should be blue in
color around the pilot hood, with traces of yellow
toward the outer edges.
The pilot flame should engulf the top 3/8” of the
thermopile (to generate millivolt current) and the
top 1/8” of the thermocouple. The pilot flame
should project out of the pilot hood 1” at all three
ports. See Figs. 23.
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION
WHEN SERVICING THE CONTROLS. WIRING
ERRORS CAN CAUSE IMPROPER OR DANGEROUS OPERATION. ALWAYS VERIFY PROPER
OPERATION AFTER SERVICING THE APPLIANCE.
ROCKER
SWITCH
OPTIONAL
THERMOSTAT
REMOTE
CONTROL
ON
OFF
STAT
or
TH
TP
TH
TP
VALV E
THERMOPILE
TERMINAL
BLOCK
Figure 22. Accessory wiring diagram.
Figure 23. Correct pilot flame appearance.
21
Optional Blower Kit Installation
3. BURNER ADJUSTMENT: The Jøtul GF 600 DV
Firelight gas stove is equipped with a variable
gas control valve that provides easy adjustment
of the flame height, appearance, and heat
output. To adjust the flame between the HI and
LOW setting, rotate the HI/LOW knob, located in
the center of the valve face. Flame height will
adjust approximately 1.0” to 1.5” between the
LOW and HIGH settings. See Fig. 24.
NO SMOKE OR SOOT SHOULD BE PRESENT.
CHECK LOG PLACEMENT IF ANY SOOT OR SMOKE IS
DETECTED. IF SOOT OR SMOKE PERSISTS, THE AIR
SHUTTER MAY NEED TO BE ADJUSTED.
See Air Shutter/Flame Appearance section of
this manual for proper air shutter settings and
adjustments. Note: the more offsets there are in
the vent system, the greater the need for an air
shutter adjustment. See page 19.
WARNING:
AIR SHUTTER ADJUSTMENTS SHOULD
ONLY BE PERFORMED BY A QUALIFIED
PROFESSIONAL SERVICE TECHNICIAN.
CAUTION:
DO NOT ATTEMPT TO ALTER THE FLAME
APPEARANCE BY POSITIONING THE GAS
VALVE IN ANY OTHER POSITION OTHER
THAN THE FULL “ON” POSITION.
1. Unpack the blower kit. Use a 10mm wrench to
remove the Mounting Bracket from the Blower.
Keep the nuts and tooth washers for reassembly.
2. Attach the Snapstat to the Snapstat Retainer
using two #7 x 3/8” phillips screws supplied. See
fig. 25.
3. Attach the Snapstat Retainer to the Mounting
Bracket using the remaining two #7 x 3/8”
phillips screws as in fig. 25.
4. Locate the two raised bosses on the bottom back
of the stove. The blower is mounted to the stove
using these two threaded holes.
5. Use the two M6 x12 mm hex head flange bolts to
attach the Mounting Bracket to the base of the
stove. Orient the bracket with the Snapstat toward
the front of the stove and align the two MIDDLE
mounting holes on the bracket with the two
threaded holes on the bottom back of the stove.
6. Position the blower with the junction box to theREAR of the stove and insert the two threaded
studs on the blower through the rear-most holes
in the blower bracket. Attach the blower to the
bracket using the nuts and washers previously
removed. See fig. 26.
7. Attach either black and white wire from the
blower to either Snapstat terminal.
5”
4”
4”
Figure 24. Flame appearance on the “high” setting
after approximately 15 to 20 minutes operation.
The blower is equipped with a three-prong (grounding) plug for protection against shock hazard and
must be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the
grounding prong from the plug.
22
Connect Black and White
wires to Snapstat
Front of stove
Figure 26. Blower orientation.
Use middle holes to
mount bracket to
stove bottom
Fan Ducts faces
to rear
Connect the Wiring Harness
1. Locate the switch bracket on the back of the
stove, below the burner control switch.
2. Remove the four 1/4” hex head screws that
secure the switch bracket to the left rear
shroud. Carefully pull the switch bracket away
from the stove.
3. Use pliers to remove the blank switch cover from
the bracket.
4. Insert the new HI/OFF/LO blower switch into the
bracket. Feed the wires up from the blower
within the left rear shroud of the unit.
5. Connect the insulated wires (from the blower) to
the three leads on the HI/OFF/LO switch. BLACK
wire to the HI position, WHITE wire to the OFF
position, and the RED wire to the LO position.
6. Reattach the switch bracket to the rear shroud.
NOTE:
THE BLOWER WILL ONLY OPERATE WHEN
THE SWITCH IS IN THE HI OR LOW POSITION AND ONLY WHEN THE SENSOR
(SNAPSTAT) HAS BEEN HEATED BY THE
STOVE AFTER THE BURNER HAS BEEN
OPERATING APPROXIMATELY 10-20 MINUTES.
Operation
Familiarize yourself with the controls of the GF600
Firelight. Make sure that anyone else using the
appliance is also familiar with the controls and
operation procedures. Always follow the Lighting
Instructions on the inside back cover of this manual
and also located on the Rating Plate attached to the
burner assembly.
1. Once the pilot is lit, burner operation is controlled
by the rocker switch located at the left rear
corner of the stove. Use the T-STAT position for
the optional thermostatic or remote control
functions.
2. During the first few fires, you may notice odor
and/or smoke from the stove. This is normal and
results from burn-off of manufacturing residue
and curing of materials. You may find it helpful to
provide additional ventilation and fresh air to
alleviate this condition.
3. Condensation may develop on the glass when the
burner is first lit. This “fog” will disappear as the
heater warms up.
4. Keep the controls and the area under the appli-
ance free of debris, vacuum this area frequently.
Always keep the appliance area clear and free
from combustible materials, gasoline and other
flammable liquids.
If a vacuum is used during any service on the
stove, ALWAYS be sure the stove is cold.
5. This appliance has a continuous burning pilot
flame. Exercise caution when using products
having combustible vapors. Always shut-off gas
supply while servicing the stove.
6. CAUTION: DO NOT OPERATE THIS APPLIANCE
WITH THE GLASS REMOVED CRACKED OR BROKEN. Replacement of the glass should be done by
a licensed or qualified service person. Use only
replacement glass provided by your authorized
Jøtul dealer. Never use any substitute materials.
WARNING: OBSERVE CAUTION WITH THE GLASS.
THE GLASS PANEL MAY SHATTER UNEXPECTEDLY
IF STRUCK WITH AN OBJECT. ALWAYS HANDLE
THE GLASS PANEL WITH CARE. WHEN SERVICING
THE STOVE ALWAYS PULL THE GLASS ASSEMBLY
STRAIGHT UP FOR REMOVAL.
7. Clean the glass only when necessary. Wipe
surface with a clean, damp soft cloth. Follow with
a dry, soft towel as desired. Take care not to
scratch the glass surface.
WARNING: DO NOT USE ABRASIVE CLEANERS ON THE
GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT.
23
Maintenance
The GF 600 DV Firelight gas stove and its venting
system should be inspected before use and at least
annually by a qualified service technician.
IMPORTANT:
ALWAYS TURN OFF THE GAS SUPPLY TO
THE STOVE BEFORE ANY SERVICE WORK
IS PERFORMED ON THE STOVE.
General cleaning: The firebox should be vacuumed
out annually to remove any surface build up. Be
sure to vacuum or wipe off the pilot assembly and
burner orifice and burner tube. Also, when vacuuming the log set, be sure to handle it carefully as it is
very fragile.
Gasket inspection: It is important that the glass
gasket be inspected at least annually. Examine the
rope gasket for signs of deterioration and make
sure the gasket has a positive seal. This is important to prevent combustion gases from escaping
into the room. Replace the gasket if necessary.
Refer to the replacement parts list on page 26.
Always replace any damaged or broken parts
on the GF 600 DV Firelight with JØTUL AUTHORIZED
PARTS ONLY. These are available through your Jøtul
dealer. Never use any substitute parts on your GF
600 DV Firelight gas stove.
Record the following information to help your
dealer determine what you will need should you
ever require parts and service.
FOR YOUR RECORDS
GF 600 DV Firelight
MODEL NAME:
SERIAL NUMBER:
DATE OF PURCHASE:
PURCHASED FROM:
NAME OF INSTALLER:
TYPE OF FUEL:
RETAIN THIS MANUAL FOR REFERENCE
AND MAKE IT AVAILABLE TO ANYONE
USING OR SERVICING THE STOVE.
FUEL CONVERSION:
BY:
24
3
2
4
5
20
19
18
26
17
15
16
14
21
6
24
7
22
23
1
11
13
25
32
30
27
29
31
28
33
34
35
36
8
37
10
38
4
9
Firelight GF 600 DV
Parts Identification
25
Jøtul GF 600 DV Firelight Replacement Parts
Cast Iron PartMatte BlackBlue BlackIvoryGreenIndigo
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
A. This appliance has a pilot which must be lit
by hand. When lighting the pilot, follow
these instructions exactly.
B. BEFORE LIGHTING, smell all around the
appliance area for gas. Be sure to smell
next to the floor because some gas is
heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS:
• Extinguish any open flame.
• Open windows.
• Do not light any appliance.
• Do not touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Access the lower controls.
3. Turn the stove ON/OFF switch to “OFF”, or set the
thermostat to lowest setting (if used).
4. Confirm that the gas supply line shut-off valve is open.
Control
Knob
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
NOTE: Knob cannot be turned from “PILOT” to “OFF”
unless the knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow “B” in the safety information
above on this page. If you do not smell gas, go to the
next step.
ON
OFF
PILOT
CONTROL VALVE
• If your gas supplier cannot be reached, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, do not try to repair
it. Call a qualified technician. Force or
attempted repair may result in a fire or
explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
7. Push in gas control knob slightly and turn counter-
clockwiseto “PILOT”.
8. Push in control knob all the way and hold in.
Immediately light the pilot by triggering the spark
ignitor (push the red button repeatedly) until pilot
lights. Continue to hold the control knob in for
about one minute after the pilot lights. Release
knob and it should
spring back. The
pilot should remain
lit. If it goes out,
repeat Steps 5
through 8.
• If knob does not
return when released, stop and immediately call your service
technician or gas supplier.
• If pilot will not stay lit after several tries, turn the
control knob to OFF and call your service
technician or gas supplier.
9. Turn gas control knob counterclockwise
to “ON”.
10.Turn the stove ON/OFF switch to “ON”, or set
thermostat (if used) to desired temperature.
PILOT ASSEMBLY
TO TURN OFF GAS TO THE APPLIANCE:
1. Turn ON/OFF switch to” OFF”. The pilot will remain lit
for normal service.
2. For complete shutdown, turn ON/OFF switch to “OFF”.
3. Access the lower controls.
4. Depress gas control knob slightly and turn
clockwise to “OFF”. Do not force.
27
notes:
This appliance must be installed in conformance with local and national
building regulations. It is important that the these instructions be read
and understood before beginning the installation.
Jøtul pursues a policy of continual product development. Consequently,
products may differ in specification, color or type of accessories from
those illustrated or described in various publications.
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve
le droit de modifier les specifications, couleurs et equipement sans avis
prelable.
Jøtul North America
400 Riverside Street
Portland, ME 04104
28
Jøtul ASA,
P.O. Box 1411
N-1602 Fredrikstad,
Norway
10.03 PN. 129674-C
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.