Jotul GF 400 DV User Manual

Jøtul GF 400 DV Sebago Gas Heater
WARNING:
ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICIN­ITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PER­FORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR LICENSED GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS-FITTER WHEN INSTALLED IN THE COMMONWEALTH OF MASSACHUSETTS.
A CARBON MONOXIDE (CO) DETECTOR SHALL BE INSTALLED IN THE SAME ROOM AS THE APPLIANCE.
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCHES.
• DO NOT USE THE PHONE IN YOUR BUILDING. IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
Installation and Operation Instructions
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUC­TIONS DANS CETTE NOTICE POUR REDUIRE AU MINIMUM LE RISQUE D’INCENDIE OU POUR EVITER TOUT DOMMAGE MATERIEL, TOUTE BLESSURE OU MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE NI OU LIQUIDES INFLAMMABLES DANS LE VOISINAGE DE CET APPAREIL OU DE TOUT AUTRE APPAREIL.
L’INSTALLATION LE SERVICE DOIVENT ETRE EXECUTES PAR UN INSTALLATEUR QUALIFIE, AGENCE DE SERVICE OU LE FOURNISSEUR DE GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES SE TROUVANT DANS LE BATIMENT OU VOUS VOUS TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE FOURNISSEUR DE GAZ CHEZ UN VOISIN. SUIVEZ LES INSTRUC­TIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE FOURNISSEUR DE GAZ, APPELEZ LE SERVICE DES INCENDIES.
1
Welcome to Jøtul...
Congratulations on the purchase of your new
Jøtul GF 400 DV Sebago Gas Heater.
We at Jøtul are glad you’ve made the decision to
warm your hearth with a Jøtul product.
Your new GF 400 DV Sebago benefits from our
experience gained over 150 years as the world’s
largest manufacturer of solid fuel burning appliances.
We’ve been making fine quality cast iron wood and
coal stoves and fireplaces continuously since 1853.
In the Sebago, we’ve combined advanced gas
technology with the warm, traditional elements of
cast iron. With proper care and use, your Jøtul stove
will provide you with many years of safe, dependable
and satisfying service.
The Jøtul GF 400 DV Sebago is a direct vented gas
heater designed and approved for installation into a
variety of configurations where close clearance to
combustible material is required. Please take a few
minutes to familiarize yourself with this manual and
the features of your new Jøtul stove.
2
Table of Contents
Service Tools .............................................. 3
Specifications ........................................... 4
General Information............................... 5
Safety Information .................................. 6
Installation Requirements
Location ................................................. 6
Hearth Protection .............................. 6
Clearances ............................................ 7
Mantel & Trim ..................................... 7
Alcove..................................................... 7
Vent Requirements ................................. 8
Adding Restriction.............................. 8
Vertical Termination .......................... 9
Co-linear Termination .................. 12
Coaxial Chimney Conversion.....13
Horizontal Termination................... 14
Vent Terminal Clearances ...............15
Mobile Home Installation ................... 16
Fuel Conversion...................................... 16
Gas Connection ...................................... 18
Gas Pressure............................................19
High Altitude Adjustment .................. 19
Air Shutter Adjustment .......................20
Wall Thermostat .................................... 20
Remote Control ......................................20
Log Set Installation ............................... 21
System Check..........................................22
Operation.................................................23
Maintenance........................................... 24
Glass Replacement............................ 24
Jøtul GF 400 DV
Sebago
Direct Vent Gas Heater
Manufactured and Distributed by:
Jøtul A.S.A.
Fredrikstad, Norway
Jøtul North America
55 Hutcherson Dr.
Gorham, Maine 04038-2634
M.E.A. 369-04-E
Test Standards
This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton, Wisconsin to ANSI Z21.88-2002 • CSA 2.33-M02 and CAN/CGA 2.17--M91, CSA P.4 -01.2 for Canada.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTER­ATION WILL VOID THE WARRANTY, CERTIFICA­TION AND LISTING OF THIS APPLIANCE.
Optional Blower Installation .............. 25
Optional Brick Kit Installation ........... 27
Illustrated Parts Breakdown ............... 28
Replacement Parts List.........................29
Lighting Instructions ............ Back Cover
THIS PRODUCT MUST BE INSTALLED
BY A LICENSED PLUMBER OR
GAS-FITTER WHEN INSTALLED IN THE
COMMONWEALTH OF MASSACHUSETTS.
3
GF 400 DV Sebago Specifications
Input Rates
Natural Gas
32,000 BTU/hr. maximum input 18,000 BTU/hr. minimum input
Propane
32,000 BTU/hr. maximum input 16,000 BTU/hr. minimum input
Specifications
26 1/2”
673 mm
28 1/2”
724 mm
Inlet Pressure: MIN MAX
Natural Gas: 5.0 WC (1.24 kPa) 7.0 WC (1.74 kPa) Propane: 12.0 WC (2.99 kPa) 14.9 WC (3.71 kPa)
Manifold Pressure: MIN MAX
Natural Gas: 1.2 WC (.30 kPa) 3.8 WC (.95 kPa) Propane: 2.9 WC (.722 kPa) 11.0 WC (2.74 kPa)
Piezo Ignitor / Standing Pilot
Suggested Tools for Installation and Service
• External regulator (for Propane only)
• Piping which complies with local code
• Manual shutoff valve (T-Handle in Massachusetts)
• Sediment trap - if required by code
• Tee joint
• Pipe wrench
• Pipe sealant
• 10 mm open end wrench
• 1/2”, 7/16” open end wrench or deep socket
• Phillips head screwdriver
• Flat head screwdriver
• 1/4” nut driver
• 4 mm allen wrench
• Gloves
• Safety glasses
• Torx T20 screwdriver
• Leak test solution
• Reciprocating Saw
• Power Drill
13”
330 mm
19 5/8”
500 mm
19 1/2”
495 mm
26 1/2”
673 mm
C
L
25 1/2”* 647 mm
29”
737 mm
28 1/2”* 724 mm
*For height with 6” Legs, subtract 2 1/4”
4
General Information
THIS HEATER MUST BE INSTALLED AND MAINTAINED
BY A QUALIFIED SERVICE AGENCY.
The installation and repair of this appliance must be
done by a qualified service person. Failure to properly install and maintain this heater could result in an unsafe or hazardous installation, which may result in a fire, explosion, property damage, personal injury or loss of life.
This appliance should be inspected before use and at
least annually. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners, and circulating air passage­ways of the appliance be kept clean.
THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE.
The installation must conform to local codes. Your
local Jøtul dealer can assist you in determining what is required in your area for a safe and legal installa­tion. Some areas require a permit to install a gas burning appliance. Always consult your local building inspector, or authority having jurisdiction, to determine what regulations apply in your area.
Glass Panel
Do not operate this appliance with the glass front removed, cracked, or broken. Replacement of the glass should be done by a licensed or qualified service person. Only remove glass for routine service. Always handle glass carefully.
Unpacking your stove
1. Remove the Top Plate of the stove by simply lifting it straight off of the stove body.
2. To open the firebox, disengage the two Glass Frame Latches located on top of the firebox. Pull each handle forward to clear the latch from the notch in the frame.
Glass Frame
Latch
CODE COMPLIANCE : Your local officials have final
authority in determining if a proposed installation is acceptable. Any requirement that is requested by the local authority having jurisdiction, that is not specifically addressed in this manual, defaults to local code. In the absence of local codes, the installa­tion requirements must comply with the current National codes. In the U.S., these requirements are established in the National Fuel Code, ANSI Z223.1.(NFPA 54). In Canada, the codes have been established in CAN/CGA B149 Fuel Installation Code.
Installer l’appareil selon les codes ou reglements
locaux, ou, en l’absence de tels reglements, selon les Codes d’installation CAN/CGA-B149.
DO NOT OPERATE THIS STOVE IF ANY PART HAS BEEN
UNDER WATER. Call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which may have been under water.
Ne pas se servir de cet appareil s’il a ete’ plonge dans
l’eau, completement ou en partie. Appeler un technicien qualifie pour inspecter l’appareil et remplacer toute partie du syste’me de controle et toute commande qui ont ete plonges dans l’eau.
3. Familiarize yourself with the installation require­ments specified in this manual, before beginning the installation.
Hardware Bag Contents
• Fuel Conversion Kit - LP................................ 155351
• Ember Bag , 4 oz. ............................................ 129123
THIS FIREPLACE IS SHIPPED FROM THE FACTORY FOR USE WITH NN
AA
TURAL GASTURAL GAS
N
A
TURAL GAS ONLY. IF USE WITH
NN
AA
TURAL GASTURAL GAS PROPANE IS DESIRED, THE APPLIANCE MUST FIRST BE CONVERTED USING THE FUEL CONVERSION KIT PROVIDED, #155351. CONVERSION SHOULD BE MADE BEFORE THE APPLIANCE IS INSTALLED. SEE PG. 16.
5
Safety Information
Location
During normal operation, the GF 400 DV Sebago gas stove will reach high surface temperatures. Therefore:
Due to the high operating temperatures, this appli-
ance should be located out of traffic areas and away from furniture and draperies.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to avoid burns and/or clothing ignition.
Young children should be supervised while they are in
the same room as the GF 400 DV Sebago gas stove.
Clothing or other flammable materials should not be
placed ON or NEAR the GF 400 DV Sebago gas stove. Surveiller les enfants. Garder les vetements, les meubles, l’essence ou autres liquides a vapeur inflammables loin de l’appareil.
NEVER store or use gasoline or any other flammable
vapors or liquids in the vicinity of the GF 400 DV Sebago gas stove.
In selecting a location for the stove, consider the following points:
1) Heat distribution
2) Vent termination requirements
3) Gas supply line routing
4) Traffic areas, furniture, draperies, etc.
The GF 400 DV Sebago may be located on or near conventional construction materials, however, proper clearance to combustibles must be maintained in order to provide adequate air circulation around the appliance. Also, it is important to provide adequate access around the stove for servicing and proper operation.
The clearance and hearth specifications listed in this manual are the minimum requirements for combustible material. A combustible material is anything that can burn (i.e. sheet rock, wall paper, wood, fabrics etc.). These surfaces are not limited to those that are visible and also include materials that may be located behind non­combustibles.
If you are not sure of the combustible nature of a material, consult your local fire officials. Remember, “Fire Resistant” materials are considered combustible: they are difficult to ignite, but will burn. Also, “fire-rated” sheet rock is considered combustible.
Hearth Requirements
Never burn any other materials in your GF 400 DV
Sebago gas stove, it is strictly designed for use with natural gas or propane fuel ONLY.
·Any safety screen, glass or guard removed for servic-
ing the appliance must be replaced prior to operating the appliance.
The GF 400 DV Sebago gas stove CANNOT be installed directly on carpeting, vinyl, linoleum or Pergo®.
If this appliance will be installed on any combustible material OTHER THAN WOOD, a floor pad must be installed that is either metal or wood, or a listed hearth pad. This floor protection must extend the full width and depth of the appliance. It is not necessary to remove carpeting, vinyl or linoleum from underneath the floor protection. See fig. 1.
Figure 1. Minimum Hearth Protection.
14”
(356 mm)
27”
(686 mm)
6
Stove and Vent Clearance Requirements
Minimum Clearances from the Stove to Combustibles:
Rear: 2” (51 mm)
Ceiling: 32 1/4” (819 mm)
Corner: 2” (51 mm)
Sides: 3” (76 mm)
See figs. 2-4.
2”
(51 mm)
To Rear Wall
Minimum Clearances from the Vent Pipe to Combustibles:
Horizontal Run:
Off the top of the pipe 2” (51 mm)
Off the sides and bottom 1” (25 mm)
Vertical Run:
All sides 1” (25 mm)
Minimum Ceiling or Alcove Height
Max. Mantel Depth
12.5
10.25 8
5.75
61
155 cm
43 3/4
111 cm
Min. Mantel Depth
Max. Top Trim Depth = 1
3.5
2 (5.1cm)
3”
(76 mm)
3”
(76 mm)
Figure 3. Parallel Installation Clearances.
2”
51 mm
51 mm
Figure 4. Corner Clearances.
2”
45 1/8
114.6 cm
42 5/8
108.3 cm
40 1/4
102.2 cm
46 1/2
118 cm
Figure 2. Mantel and Trim Clearance specifications. Back of bottom plate is flush with the fireplace face. Subtract 2 1/4” with Short Legs.
28 1/2
72.3 cm
Alcove Installation
Maximum Alcove Depth: 24” (61 cm)
Minimum Alcove Width: 31 3/4” (80.6 cm)
Minimum Ceiling Height: 61” (155 cm) With Short Legs (6”) : 59” (150 cm)
Alcove dimensions result from test configurations, not stove clearance specifications.
7
Venting Requirements
Vent Restriction
The Jøtul GF 400 DV Sebago gas stove may be installed with a vertical or horizontal termination and must conform to the configuration requirements described below.
This appliance is approved for use with vent systems
from the following manufacturers:
Simpson Dura-Vent GS
• Amerivent Corporation
• Security Vent Ltd.
• Selkirk Metalbestos
Use parts of one manufacturer only - DO NOT MIX VENT COMPONENTS FROM DIFFERENT MANUFACTURERS IN THE SAME SYSTEM.
Installation of any components not manufactured or approved by Jøtul or failure to meet all clearance require­ments will void all warranties and could result in prop­erty damage, bodily injury, or serious fire.
The approved vent configurations described in this manual are derived from extensive testing under con­trolled laboratory conditions. Gas appliance performance can be negatively affected by variables present in the installation environment, i.e: atmospheric pressure, strong prevailing winds, adjacent structures and trees, snow accumulation, etc. These conditions should be taken into consideration by the installer and stove owner when planning the vent system design.
IMPORTANT
• JOINT SEALING REQUIREMENT: APPLY A 1/8” BEAD OF
HIGH­TEMPERATURE (750°F) SEALANT TO THE MALE SEC­TION OF THE INNER VENT PIPE. THE CEMENT SHOULD FORM A SEAL BETWEEN THE INNER AND OUTER PIPES.
• NEVER MODIFY ANY VENTING
COMPONENT, OR USE ANY DAM­AGED VENTING PRODUCT.
• THE GAS APPLIANCE AND VENT
SYSTEM MUST BE VENTED DIRECTLY TO THE OUTSIDE OF
S
E
A
L
A
N
T
THE BUILDING AND NEVER ATTACHED TO A CHIMNEY SERVING A SOLID FUEL OR
Fig. 5.
GAS BURNING APPLIANCE. EACH DIRECT VENT GAS APPLIANCE MUST HAVE ITS OWN SEPARATE VENT SYSTEM. COMMON VENT SYSTEMS ARE PROHIBITED.
• IF VENTING SYSTEM IS DISASSEMBLED FOR ANY
REASON, REINSTALL PER THE INSTRUCTIONS PROVIDED FOR THE INITIAL INSTALLATION.
The GF 400 DV Sebago is equipped with Restrictor Plates which enable you to regulate the flow of incoming combustion air and exhaust gas. The plates prevent overly strong draft that can cause poor combustion and weak flame picture. Follow the guidelines below, and on
the following pages, to determine the correct restrictor plate setting for your particular installation configura­tion.
Intake Air Restrictor
This plate is located at the rear of the firebox behind the burner plate. It is set in a CLOSED position at the factory and should be left there for most vent configurations. It should be opened only for snorkel terminations and some short run horizontal terminations as specified on the following pages. To adjust the Air Restrictor to the OPEN position, locate and loosen the wing nut under the burner and push it back as far as it will go. See Fig. 6.
Exhaust Restrictor
The Exhaust Restrictor is an adjustable shutter located at the top of the firebox. It is adjusted by moving a pivot pin into one of four positions. It is set in the FULLY OPEN position at the factory. See Fig. 7.
Use the chart in Table 1 to determine the correct position for your installation and follow the instructions below to adjust it if necessary.
Additional restriction may be needed depending the overall vent height. Use Simpson Dura-Vent Restrictor Disk #929.
Adjusting Exhaust Restrictor Plate:
1. Remove the Top Plate.
2. Locate the pivot pin at the left side of the firebox top.
Loosen the wing nut on the pivot pin and push the pin to the left to disengage it from the current setting position. Move the pin toward the rear and then right to engage it in the appropriate position indicated on the firebox. See fig. 7.
3. Tighten the lock nut and replace the Top Plate.
8
A
B
C
D
FRONT
Horizontal Overhang
Vertical W
all
Termination
Cap
18. min.
Lowest Discharge
Opening
18 min.
18. min.
LEG
BACK
LEG
Fully Closed
Fully Open
Figure 6. Adjusting the Air Inlet Restrictor plate - View is from the right side of the stove.
Vertical Vent Termination
The Jøtul GF 400 DV Sebago can be vertically vented
through a ceiling or to a roof termination with the following guidelines:
The termination should fall within the shaded areas
of the grids depicted in the Vent Window diagrams on the pages 10-11.
Maximum Vertical run should not exceed 35 ft. (10.66 m).
Push the
Pivot Pin into
the slot
Default Factory
Setting is
“D”
A
B
C D
Front of
Stove
Minimum Vertical run must be at least 8 ft. (2.43 m).
Max. Colinear Horizontal run is 2 ft. (61 cm).
Vent Terminus Clearance: In no case shall any dis-
charge opening on the cap be less than 18 in. (610 mm) horizontally from the roof surface.
Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or promote down-draft occurances. Increasing the height of the vent may alleviate these conditions.
Use Wall Straps to support an offset pipe run at three
feet intervals to avoid excessive stress on the offsets.
Elbows: Four 45°, or two 90° elbows may be used. Do
not include the 45° elbow attached to the stove. Whenever possible use 45° elbows instead of 90° elbows as they are less restrictive to exhaust gas and intake air flow.
A firestop is required at every floor. The opening
should be framed to 10" X 10" inside dimension.
Any venting that is exposed above the first floor,
regardless of attic space or living space, must be enclosed. Always maintain the required 1" clearance from all sides of the vertical vent system.
Figure 7. Adjusting the Exhaust Restrictor plate - Top Plate removed. Viewed from front of stove.
Figure 8. Vertical vent termination height above roof.
9
HORIZONTAL RUN
35 Ft.
(10.67 m)
25 Ft.
(7.62 m)
2 Ft.
(16 cm)
VERTICAL RUN
Minimum
Vertical
Termination
8 Ft.
(2.43 m)
35 Ft.
(10.67 m)
25 Ft.
(7.62 m)
2 Ft.
(16 cm)
VERTICAL RUN
Minimum
Vertical
Termination
8 Ft.
(2.43 m)
45°
Elbow
Up
B
Vent Termination Zones - Natural Gas
35 Ft.
(10.67 m)
Horizontal and Vertical
30 Ft.
(9.14 m)
25 Ft.
(7.62 m)
20 Ft.
(6.10 m)
VERTICAL RUN
15 Ft.
(4.57 m)
A
Terminations for COAXIAL VENT
Up to four 45° or
two 90° elbows
permitted in
addition to the
starter elbow.
A
B
Vertical
Termination for
COLINEAR VENT
(3.65 m)
(2.43 m)
Min. Rise
12 Ft.
C
B
Min. Vertical
8 Ft.
5 Ft.
(1.52 m)
2 Ft.
(.60 m)
Termination
5 Ft.
(1.52 m)
10 Ft.
(3.05 m)
HORIZONTAL RUN
15 Ft.
(4.57 m)
• ALL VENTING MUST TERMINATE (END) WITHIN ONE OF THE SHADED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRESPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES.
The circled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting on the stove. First, determine which vent termination zone is appropriate for your installation and fuel type, then adjust the restrictor to the corresponding position as shown in Figure 7, page 9.
D
(6.09 m)
20 Ft.
27 Ft.
(8.22m)
• VENTING MUST TERMI­NATE (END) WITHIN THE SHADED AREA.
• Adjust the Exhaust Restrictor to position B
for any NG colinear termination.
Figure 9. Coaxial Vent Termination Window / NG
10
Figure 10 . Colinear Termination / NG
Vent Termination Zones - Propane
35 Ft.
(10.67 m)
Vertical Termination for COLINEAR VENT
30 Ft.
(9.14 m)
25 Ft.
(7.62 m)
20 Ft.
(6.10 m)
VERTICAL RUN
15 Ft.
(4.57 m)
12 Ft.
(3.65 m)
8 Ft.
(2.43 m)
5 Ft.
(1.52 m)
Min. Rise
2 Ft.
(.60 m)
A
B
Horizontal and Vertical
Terminations for COAXIAL VENT
Up to four 45° or
two 90° elbows
permitted in
addition to the
starter elbow.
B
D
OPEN AIR INLET
RESTRICTOR
35 Ft.
(10.67 m)
25 Ft.
(7.62 m)
VERTICAL RUN
VERTICAL RUN
Minimum
Minimum
Vertical
Vertical
Termination
Termination
8 Ft.
8 Ft.
(2.43 m)
(2.43 m)
C
D
5 Ft.
(1.52 m)
10 Ft.
(3.05 m)
HORIZONTAL RUN
15 Ft.
(4.57 m)
20 Ft.
(6.09 m)
27 Ft.
(8.22m)
2 Ft.
2 Ft.
(16 cm)
(16 cm)
• VENTING MUST TERMINATE (END) WITHIN ONE OF THE DESIG­NATED AREAS. ZONE “A” IS FOR VERTICAL TEMINATIONS ONLY.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRE­SPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE.
• OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND UNDER. SEE FIG. 6, PAGE 9.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES.
• VENTING MUST TERMINATE (END) WITHIN THE SHADED AREA.
• Adjust the Exhaust Restrictor to position C
for a straight vertical colinear termination.
The circled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting on the stove. First, determine which vent termination zone is appropriate for your installa­tion and fuel type, then adjust the stove restrictor plate to the corresponding position as shown in Figure 7, page 9.
• Adjust the Exhaust Restrictor to position D
for a vertical colinear termination with maximum 2 ft. offset.
Figure 11. Coaxial Vent Termination Window / LP Figure 12 . Colinear Termination / LP
11
Exhaust Gas
High Wind Cap
Co-linear Vent Installation
The GF 400 DV Sebago may be vented through a ma­sonry or Class A prefabricated chimney using a Co-linear Flexible Vent system approved for use with a solid-fuel burning fireplace. When installed in the manner de­scribed below, this system can improve the performance of the appliance in cold climate situations, as well as simplify the vent installation. See fig. 13.
These installation requirements must be followed:
1. Use the guidelines for Co-linear Vent Termination appropriate for your gas type on pages 10 - 11.
1. Prior to the installation the chimney flue must be
thoroughly cleaned and inspected by a qualified chimney service person.
2. In a masonry chimney, a fireclay liner must be present the entire length of the chimney.
3. Prefabricated chimneys must be UL 103 or ULC S-629 listed and have a minimum INSIDE diameter of 6 inches, (150 mm).
4. No appliance can be installed into a chimney flue serving any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET BEYOND THE DAMPER AREA OF THE FIREPLACE.
6. If the intake flex duct does not extend the full length
of the chimney and connect to both the unit and the termination cap, A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM.
Max. Co-linear Height - 35 ft. (10.66 m)
Min. Co-linear Height - 10 ft. (3.05 m)
The chimney must be sealed off from the room by a steel plate at the damper area.
Dual 3”Flex
Liners
Max. offset
24”
(609 mm)
Intake Air
The Air
Intake Flex
pipe must
extend
beyond the
damper.
Consult with the local code authority having juris-
diction before proceeding with this type of installation.
Refer to the vent manufacturer’s instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED FOR USE WITH THIS APPLIANCE MAY RESULT IN PROP­ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES AS DEFINED IN THIS MANUAL AND IN THE INSTRUC­TIONS PROVIDED WITH EACH VENT COMPONENT.
12
Figure 13. Co-linear Adaptor installed through a masonry chimney. Components shown may differ somewhat from manufacturer to manufacturer.
29”
to top of
25 1/2”
to center
of flue collar
Co-linear
Adapter.
Figure 14. Simpson Dura-Vent #923GCL Co-linear Adaptor is shown - other manufacturer’s components may differ. Subtract 2 1/4” for Short Legs.
Masonry or Prefabricated Chimney
Conversion
The GF 400 DV Sebago is approved for use with listed
chimney conversion kits from any of the manufacturers
listed on page 8. These kits are for use in a masonry
chimney or a prefabricated solid fuel listed chimney. See
fig. 15.
These installation requirements must be followed:
1. Use the guidelines for Coaxial Vent Termination appropriate for your gas type on pages 11 - 12.
2. In masonry chimney, a fireclay liner or listed steel
liner, must be present the entire length of the chim­ney.
3. Chimney height should not exceed 35 ft. (10.66 m).
4. The liner must have an inside dimension of 6” round
or greater.
5. Prefabricated chimneys must be UL 103 or ULC S-629 listed and have a minimum INSIDE diameter of 6 inches, (150 mm). Prefabricated chimneys must be listed for the specific Chimney Conversion Kit you choose.
Cap Adaptor-
included in
#934 Kit
4” Flex Pipe
not included
in kit
Support/Wall
Thimble Cover
Exhaust
Gas
Vertical
Termination
Cap
Intake Air
Use standard
vent pipe from
stove to
thimble from
the same
manufacturer
IMPORTANT NOTICE
THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-1999-CSA
2.33-M99 TEST METHODS AND RE­SULTING ITS/WHI PRODUCT CERTIFI­CATION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD.
Figure 15. Vent System through a masonry chimney using a chimney conversion kit. May also be used in listed prefabricated chimneys. Drawing is for illustrative purposes only - DO NOT VENT TWO APPLIANCES INTO A SINGLE CHIMNEY.
13
Horizontal Termination
Any horizontal termination must fall within the
shaded portion of the vent window graph illustrated in figs. 9 or 11. For Snorkel Terminations, see below.
Any horizontal termination except a snorkel termination,
must include:
1) Minimum rise of 2 ft.
2) Minimum horizontal run of 12 in. when vertical run is less than 8 ft.
2) Maximum rise of 35 ft.
3) Maximum horizontal run of 27 ft.
4) No more than four 45° or two 90° Elbows
Follow all termination clearance guidelines as speci-
fied in fig. 19.
The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections 2 1/2" or less. It must also maintain 12" clearance from projections exceeding 2 1/2". See fig. 20.
Wall Cut-out Opening: A minimum 10" X 10" (250 mm x
250 mm) square hole is required for proper pipe clear­ances through a combustible wall. Use a listed wall
thimble for the wall penetration.
DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.
Any horizontal run of vent must have a 1/4" rise for
every foot of run toward the termination cap. NEVER ALLOW THE VENTING TO RUN DOWNWARD FROM STOVE TO TERMINATION; DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE.
12 in.
(305 mm)
C
L
24 in.
Snorkel
(305 mm)
14”
355 mm
Max.
12”
Ven t
Pipe or
less
(1448 mm)
25 1/2 in.
Snorkel
(648 mm)
57”
Figure 16.
• Minimum vent for horizontal termination.
• 14” Maximum horizontal run directly off rear of stove with 14” Snorkel termination.
36 in.
Max.
6 ft.
183 cm
Snorkel
(915 mm)
Install a Vinyl Siding Standoff between the vent
termination and an exterior wall covered by vinyl siding material to prevent potential heat damage to the siding.
Do not recess the termination cap into a wall or
siding.
Snorkel Terminations
THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN
FOR ANY SNORKEL TERMINATION. See Fig. 6, pg. 9.
With a 14” Snorkel:
The horizontal run made directly off the rear of the stove into a 14” snorkel cap should include no more than a single 12” straight section as shown in fig. 17. One 45° Elbow may be used for a corner installation as shown in fig. 18.
With a 36” Snorkel:
The maximum horizontal run may be no more than 6 ft. (182 cm.)
14
Figure 17. Maximum Horizontal and Vertical Run with 36” Snorkel Termination.
Max.
45° Elbow
14”
355 mm
See Note F
Fig. 20
12 in. Straight Pipe
Wall Thimble and Trim Collar
Figure 18. Corner Installation with 14” Snorkel Termination.
Horizontal Termination Clearance
Figure 19. Vent Terminal Clearances - National Fuel Gas Code.
A = Clearance above grade, veranda, porch , deck, or
balcony : 12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensa­tion on the window.
C = Clearance to permanently closed window:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12 in. minimum to prevent condensa­tion on the window.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm) from the centerline of the terminal: 18 inches
(46 cm) minimum.
E = Clearance to unventilated soffit: 12 inches (46 cm)
minimum.
F = Clearance to outside corner: **Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H = *Not to be installed within 15 feet (4.5 m) above a
meter/regulator assembly within 3 feet (90 cm) horizontally from the center-line of the regulator.
I = Clearance to service regulator vent outlet:
3 feet (91 cm) minimum.
J = Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet:
**Min. 3 feet (91 cm) above if within 10 feet horizon­tally, U.S. / *6 feet (1.83 m) minimum / CAN
L = 1 Clearance above paved sidewalk or a paved driveway
located on public property: 7 feet (2.1 m) min.
M = Clearance under veranda, porch, deck, or balcony:
12 inches (30 cm) minimum.
* In accordance with CSA B149 Installation Codes.
** In accordance with the current ANSI Z223.1/NFFPA 54, National Fuel Gas Code. Note: Local Codes and Regulations may require different clearances.
1
A vent shall not terminate directly above a sidewalk or driveway which is located between two single family dwellings and serves both dwellings.
2
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*
2
2 1/2 12  305 mm
Figure 20. Termination Clearance to overhangs
64 mm
3
76 mm
15
Mobile Home Installation
Fuel Conversion
The GF 400 DV Sebago can be installed for use in a mobile home in the U.S. and Canada provided:
1. The stove is secured to the floor of the mobile home.
Use Jøtul Floor Bracket Kit #154388.
2. Provision must be made to secure an electrical ground
between the stove and the mobile home chassis.
3. The stove is installed in accordance with Title 24 CFR,
Part 3280- Manufactured Home Construction and Safety Standard, in the U.S. In Canada, comply with CSA Z240.4, Gas Equipped Recreational Vehicles and Mobile Housing.
4. Always contact your local officials about installation
restrictions and requirements in your area.
THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET PERMANENTLY LOCATED, MANUFACTURED (MOBILE) HOME, WHERE NOT PROHIBITED BY LOCAL CODES. THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE’S RATING PLATE. A GAS CONVERSION KIT IS PROVIDED WITH THE GF 400 SEBAGO DIRECT VENT GAS STOVE.
CET APPAREIL PEUT ETRE INSTALLE DANS UN MAISON PREFABRIQUEE (MOBILE) DEJA INSTALLEE A DEMEURE SI LES REGLEMENTS LOCAUX LE PERMETTENT. CET APPAREIL DOIT ETRE UTILISE UNIQUEMENT AVEC LES TYPES DE GAS INDIQUES SUR LA PLAQUE SIGNALETIQUE. NE PAS L’UTILISER AVEC D’AUTRES GAS SAUF SI UN KITDE CONVER­SION CERTIFIE EST INSTALLE.
The GF 400 DV Sebago gas stove is shipped from the factory equipped to burn NATURAL GAS only. If PROPANE gas is to be used as fuel, the appliance must first be converted for use with propane. Use Propane Conversion Kit 155351, supplied with the appliance.
Order and install NG Conversion Kit 155352 to
change back to use with natural gas.
WARNING:
THE CONVERSION KIT IS TO BE INSTALLED BY AN AUTHORIZED JØTUL SERVICE TECHNICIAN IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTION AND ALL CODES AND REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR PROPERTY DAMAGE. THE QUALIFIED AGENCY PERFORMING THIS WORK ASSUMES RESPONSIBILITY FOR THIS CONVERSION.
IN CANADA:
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE RE­QUIREMENTS OF THE PROVINCIAL AU­THORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIRE­MENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
Tools required:
• 1/2” open ended wrench or deep-well socket, Torx T20 or slotted screwdriver, 4 mm allen wrench.
16
Conversion Kit Contents:
• 1, regulator tower labeled for propane
• 3, regulator tower screws
• 1, burner orifice (#33 for NG, 1.65 mm for LPG)
• 1, pilot orifice (#51 for NG, #30 for LPG)
• Label A - to be completed and applied to
the back of the stove
• Label B - apply to the stove’s Rating Plate
• Small valve label - apply to valve body
Conversion instructions are also shipped in the stove with the conversion kit.
Fuel Conversion Procedure
Refer to fig. 47, Illustrated Parts Breakdown, to identify
part numbers below.
1. Turn off gas supply to stove.
2. Remove the stove Top Plate (41).
3. Disengage the two Glass Frame Latches at the top of
the firebox. See illustration on page 5. Carefully lift the glass panel up and out of the stove.
4. If installed, remove the Embers and Log Set using care
not to damage the fragile log parts.
5. Lift out the Burner Skirt (33). Tilt the skirt at an angle
to clear the firebox sides and front.
6. Reach under the stove and remove the Air Shutter wingnut from its stud. As you face the right side, it is the one closest to you. See fig. 21.
7. Lift out the Burner Plate: NOTE: There are no screws securing the Burner to the floor of the firebox. Pull the Air Shutter forward and lift the burner together with shutter up and out of the stove as a unit. See fig. 22.
8. Change the Main Burner Orifice. See fig. 23. Using a ½” open ended wrench or deep-well socket remove the burner orifice from its brass elbow housing and replace with the appropriate orifice supplied in the kit.
#33 for NG
1.65 mm for LPG
9. Replace the Air Shutter with its gasket and push it all
the way back to allow replacement of the Burner Plate.
10. Replace the Burner Plate. Engage the Air Inlet Tube with the Air Shutter and burner orifice. Properly seated, the burner plate will be engaged at its front corners with the two support brackets located at the front of the firebox.
• Replace the wingnut loosely on the air shutter stem under the stove. Air shutter adjustment will be done last.
11. CHANGE THE PILOT ORIFICE: From within the firebox, remove the Pilot Head by pulling it straight up from the pilot base. See fig. 25.
Using the 4 mm allen wrench that is included with the conversion kit, unscrew the pilot orifice (counter­clockwise). Replace with the appropriate orifice:
# 51 for natural gas #30 for propane gas
12. Tighten orifice into the base of the pilot assembly. To prevent bypass leaks, be sure the orifice is secured tightly and flush with the base. Replace pilot head by pushing it down onto the pilot base.
13. Replace the Variable Regulator. Using a Torx T-20 screwdriver, remove the three screws from the front of the valve regulator. See fig. 26.
Air Shutter Wingnut
FRONT
LEG
Open
Close
BACK
LEG
Figure 21. Locate and remove the Air Shutter wingnut from under the right side of the stove.
Air Shutter
Burner Plate
Figure 22. Remove the Air Shutter and Burner as a unit.
Brass Elbow
Burner Orifice
Figure 23. Change the Burner Orifice.
Air Shutter
Air Inlet
Tube
Opening
Dimension
Burner Plate
Figure 24. Air Shutter Setting
17
14. Remove the Regulator Tower, Gasket, white plastic
disk, and Spring.
15. Install the new regulator: Be sure the new gasket is
properly positioned and tighten screws securely.
16. Install the identification labels to the stove so that they
can be seen by any person that may be servicing the stove. Label A: apply to back of stove. Label B: apply to stove’s rating plate. Small valve Label: apply to valve.
17. Reassemble the stove, apply gas to the system and
check for leaks using a soapy water solution.
18. Adjust the Air Shutter: CAUTION! USE WORKGLOVES. SURFACES MAY BE HOT!
You will need to adjust the shutter to the position that supplies the correct amount of air mixture to achieve the best flame picture with your particular installation. Start with the shutter stem at the midway position in the slot in the bottom of the stove. See fig. 21. Pushing the stem back will restrict air, while pushing it forward will open the shutter. Too much air will produce a lighter flame, while too little will promote long, dark flames and may pro­mote sooting. Make adjustments in small incre­ments. With some experimentation, you will find the shutter position that works best for your installation.
Pilot Head
Orifice
Retainer
Clip
NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.
Correct gas pressure is essential for efficient and safe operation of this appliance. Correct gas pressure must be established at the time of installation. For more details, see the Gas Pressure section of this manual (page 19).
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON THE
INSIDE BACK COVER OF THIS MANUAL WHEN LIGHT­ING YOUR STOVE.
Gas Supply Connection
Connect the gas supply line to the stove, before installing the optional Blower.
If the blower will be installed, use a 45° elbow off the control valve to create clearance required for the blower
installation.
The gas supply line connection is made to the left side of the valve. The gas supply line should be 3/8" npt with a 1/2" diameter supply, or the appropriate size to provide sufficient gas pressure to the valve regardless of the input setting.
The use of Flexible Gas Appliance Connectors is acceptable in many areas in the U.S. However, Canadian methods vary depending on local code.
ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY WITH THE MOST RECENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR CAN-B149.
All codes require a gas shut-off valve (gas cock) and union, to be installed in the supply line, and in the same room as the appliance. This allows for the disconnection of the stove for servicing and maintenance. See fig. 27.
Pilot Base
Figure 25. Pilot orifice removal and replacement.
Regulator
Tower
Figure 26. Regulator assembly.
Remove black
gasket
Apply small
18
label here
Figure 27. Supply valve coupling.
A T-HANDLE GAS COCK IS REQUIRED IN MASSACHUSETTS TO COMPLY WITH CODE 248CMR.
Secure all joints tightly using appropriate tools and sealing compounds. For propane units be sure to use compounds that are propane resistant. Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open flame to check for leaks.
A
E
Leak test:
1. Mix a 50-50 solution of water and dish soap.
2. Light appliance- see lighting instructions on the inside back cover of this manual or on the stove’s rating plate.
3. Brush or spray all joints and connections with the soapy water solution.
4. If bubbles appear at any connection or seam or a gas odor is detected, immedi­ately turn gas control knob to the OFF position.
5. Tighten or reconnect the leaking joint and retest for any gas leaks.
Gas Pressure
Correct gas pressure is essential for efficient and safe operation of the GF 400 DV Sebago gas stove. It is important that the correct pressure is established at the time of the installation. Proper gas pressure provides a consistent flow of gas to the appliance and is instrumental in checking for gas leaks.
Pressure Test: Attach a manometer to the appro-
priate test point on the valve. See fig. 28. The gauge connections are located on the front of the valve under the On/Off/Pilot- knob. Gauge connections are identified by:
E - for Inlet or Supply Pressure (the amount of
gas coming to the valve.)
A - for Manifold Pressure (the amount of gas that
is coming out of the valve to the burner.)
ALWAYS TEST PRESSURES WITH VALVE CONTROL
KNOB SET ON HIGH.
Figure 28. Pressure test points.
INLET GAS PRESSURES
(inches water column)
MIN MAX
NATURAL GAS 5.0 7.0 PROPANE 12.0 14.9
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply line by closing its individual manual gas shut-off valve (gas cock) during any pressure testing of the gas supply piping system that is equal to or exceeds pressures of 1/2 psig (3.5 kPa).
MANIFOLD PRESSURES (inches water column)
MIN MAX
NATURAL GAS 1.2 3.8 PROPANE 2.9 11.0
High Altitude Adjustment
Installations located at altitudes from 2000 - 4500 ft.
(610 m -1370 m) DO NOT require adjustment for alti­tude. DO NOT DERATE THIS APPLIANCE FOR ALTITUDE.
19
Flame Appearance / Air Shutter
Optional Wall Thermostat or
Adjustment
The GF 400 DV Sebago gas stove is shipped from the factory equipped to burn Natural gas with the air shutter set at the halfway position. Please be aware, however, that this initial setting may not provide the optimal flame picture in your particular installation. No single setting will be appropriate for all vent configurations, fuel types, or installation environments. The air shutter setting can also be adjusted to achieve the desired flame appearance. Flame appearance is a matter of individual preference, however, most people enjoy a warm yellowish flame.
Too much air - the appliance will generate a flame
that is blue and transparent, or an “anemic” flame.
Too little air - the appliance may generate very long
yellow flames resulting in soot. Sooting produces black deposits on the logs, on the inside walls of the appliance, and potentially, on the exterior termination cap. Sooting is caused by incomplete combustion and lack of combus­tion air entering the air shutter opening.
To adjust the air shutter: CAUTION! USE WORKGLOVES.
SURFACES MAY BE HOT!
1. Reach under the right side of the stove and loosen the
wingnut located closest to you. See fig. 29. Slide the wingnut stem forward to open the air shutter and increase air. Slide the shutter stem back to decrease the air supply.
2. Tighten the wingnut to secure the shutter at the
desired setting.
3. Operate the burner for 30 minutes on the HIGH setting,
observing the flame continuously. If the flame appears weak, slow, or sooty, adjust the air shutter to a more open position as described above until the flame is as desired. Make adjustments in small increments and allow the burner to settle in before making further adjustment
WARNING: AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN.
FRONT
LEG
Open
Close
BACK
LEG
Remote Control
Use only a 750 millivolt DC two-wire circuit thermostat with this appliance. The thermostat should be placed in the same room as the heater, typically 5 feet off the floor. Avoid drafty areas or any area that may affect the accuracy of the thermostat.
The thermostat should be connected to the GF 400 DV Sebago using a minimum of 16 gauge wire with a maximum length of 25 feet of wire.
Connect the two thermostat wire leads to the two lower terminals on the terminal block located directly above the ignitor button. Do not overtighten the connections. IT IS NOT NECESSARY TO DISCONNECT ANY OTHER WIRES. See Fig. 30.
For thermostatic operation, the On/Off/T-Stat switch on the back of the stove must be in the T-stat position, and the pilot light must be running, as it is the power source for the thermostat.
At the thermostat, the two wires should be con­nected to the two connection screws on the thermostat base plate per the manufacturer’s instructions.
Remote Control
When using a remote, the remote receiver should be wired to the terminal block the same way the thermo­stat would be. See the instructions above.
Follow the operating instructions included with the Remote Control unit.
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING THE CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER OR DANGEROUS OPERATION. ALWAYS VERIFY PROPER OPERA­TION AFTER SERVICING THE APPLIANCE.
ROCKER
SWITCH
OPTIONAL
THERMOSTAT
REMOTE
CONTROL
ON
OFF
STAT
or
TH
TP
TH TP
VALV E
THERMOPILE
TERMINAL
BLOCK
Figure 29. Loosen the wingnut to adjust the air shutter stem.
20
Figure 30. Accessory wiring diagram.
Log Set Installation
NOTE: If appropriate, install the optional Antique Brick Panel Kit before assembling the logset.
The GF 400 DV Sebago logset must be installed before operating the burner. The logset includes five log pieces, packaged inside the firebox, and a quantity of ember stones packaged in the Miscellaneous Parts bag. To install the log set, remove the packaging and place the parts inside the firebox as illustrated in figs 32-37. Do
not handle the log set with your bare hands. Always wear gloves to prevent skin irritation from the ceramic fibers.
The ember stones realistically simulate glowing coals
when the burner is operating. These should be spread evenly over the burner plate and around the logs. DO NOT
OBSTRUCT THE PILOT ASSEMBLY OPENING. See fig. 37.
NOTE: You do not need to use all the ember stones.
With experimentation, you will find the arrangement and quantity of embers that works best with your stove. Depending upon the characteristics of your installation, it is possible that too many ember stones can promote sooting on the logs. Adjust the quantity of ember stones as appropriate to maintain the best overall flame picture.
THE CERAMIC FIBER LOGS AND GLOWING EMBERS CAN IRRITATE YOUR SKIN. GENTLY WASH YOUR HANDS WITH WARM SOAPY WATER AFTER HANDLING THE LOGS.
Figure 34. Install Left Log
Figure 35. Install Middle Log
Figure 32. Install Right Log
Figure 33. Install Rear Log
Figure 36. Install Crossover Log
Figure 37. Install Ember Stones
Pilot
Opening
DO NOT
OBSTRUCT
21
System Check
1. PURGING THE GAS LINE: When lighting the appli-
ance for the first time, it will take a few moments to clear the gas line of air. Once this purge is complete, the appliance will operate as described in the lighting instructions. See the inside back cover of this manual or the stove Rating Plate attached the bottom of the stove. Subsequent burner starts will not require purging the gas line unless the supply line is shut off.
2. PILOT FLAME: You can monitor the pilot flame
through the view port located at the rear of the Right Log. See fig. 36. The pilot flame should be steady - not lifting or floating. The flame should be blue in color around the pilot hood, with traces of yellow toward the outer edges.
The pilot flame should engulf the top 3/8” of the thermopile (to generate millivolt current) and the top 1/8” of the thermocouple. The pilot flame should project out of the pilot hood 1” at all three ports. See fig. 37.
3. BURNER ADJUSTMENT: This stove is equipped with a
variable gas control valve that allows easy adjust­ment of the flame height appearance and heat output. To adjust the flame between the HI and LOW setting, rotate the HI/LOW knob, located in the center of the valve face. Flame height will adjust
approximately 1” to 2” between the LOW and HIGH settings. See fig. 38.
NO SMOKE OR SOOT SHOULD BE PRESENT. CHECK LOG PLACEMENT IF ANY SOOT OR SMOKE IS PRESENT. IF SOOT OR SMOKE PERSISTS, THE AIR SHUTTER MAY NEED TO BE ADJUSTED.
See Air Shutter/Flame Appearance section of this manual for proper air shutter settings and adjust­ments. Note: the more offsets there are in the vent system, the greater the need for an air shutter adjustment. See page 20.
1
(25mm)
1/8
(3mm)
Min.
Figure 37. Proper pilot flame appearance.
CAUTION:
DO NOT ATTEMPT TO ALTER THE FLAME APPEARANCE BY POSITIONING THE GAS VALVE CONTROL IN ANY OTHER POSITION OTHER THAN THE FULL “ON” POSITION.
3/8
(8mm)
Min.
22
WARNING:
AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE
PERFORMED BY A QUALIFIED PROFESSIONAL
SERVICE TECHNICIAN.
Figure 38. Flame appearance on the “high” setting after approximately 15 to 20 minutes burning.
Operation
Familiarize yourself with the controls of the GF 400 DV Sebago. Make sure that anyone else using the appliance is also familiar with the controls and operation proce­dures. Always follow the Lighting Instructions on the inside back cover of this manual and also located on the Rating Plate attached to the back of the stove.
1. Once the pilot is lit, burner operation is controlled by
the rocker switch located at the left rear corner of the stove. Use the T-STAT position for the optional thermo­static or remote control functions. See fig. 39.
2. During the first few fires, you may notice odor and/or
smoke from the stove. This is normal and results from burn-off of manufacturing residue and curing of materials. You may find it helpful to provide addi­tional ventilation and fresh air to alleviate this condi­tion.
3. Condensation may occur on the glass upon each
lighting of the appliance. This “fog” will disappear as the appliance heats up.
4. Keep the controls and the area under the appliance
free of debris, vacuum this area frequently. Always keep the appliance area clear and free from combus­tible materials, gasoline and other flammable liquids.
If a vacuum is used during any service on the stove, ALWAYS be sure the stove is cold and there are NO hot embers.
5. Remember, this appliance has a continuous burning
pilot flame. Exercise caution when using products having combustible vapors. Always shut-off gas supply while servicing the stove.
6. CAUTION: DO NOT OPERATE THIS APPLIANCE WITH THE GLASS REMOVED CRACKED OR BROKEN.
Replacement of the glass should be done by a licensed or qualified service person. Use only replacement glass provided by your authorized Jøtul dealer. Never use any substitute materials.
WARNING: OBSERVE CAUTION WITH THE GLASS. THE GLASS PANEL MAY SHATTER UNEXPECTEDLY IF STRUCK WITH AN OBJECT. ALWAYS HANDLE THE GLASS PANEL WITH CARE. WHEN SERVICING THE STOVE ALWAYS PULL THE GLASS ASSEMBLY STRAIGHT UP FOR RE­MOVAL.
7. Clean the glass only when necessary. Wipe surface
with a clean, damp soft cloth. Follow with a dry, soft towel as desired. Take care not to scratch the glass surface.
WARNING: DO NOT USE ABRASIVE CLEANERS ON THE GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT.
Figure 39. Burner Switch and Optional Blower Controls
23
Maintenance
Your Jøtul GF 400 DV Sebago and its venting system should be inspected before use and at least annually by a qualified service technician.
Use the form on page 30 to keep a maintenance
history of your stove.
IMPORTANT:
ALWAYS TURN OFF THE GAS SUPPLY TO THE FIREPLACE AND UNPLUG THE FORCED AIR BLOWER BEFORE ANY SERVICE WORK IS PERFORMED ON THE FIREPLACE.
Annual Cleaning
Vent System
The entire vent system, including the chimney, should be inspected and cleaned every year. If the intake and exhaust venting is disassembled for any reason, it should be reassembled and sealed according to the manufacturer’s instructions provided at the initial installation.
FOR REPLACEMENT, USE ONLY JØTUL CERAMIC GLASS PANEL 220089. DO NOT USE ANY OTHER TYPE OF GLASS WITH THIS APPLIANCE.
Glass Panel or Gasket Removal
1. Lift the Top Plate off of the stove.
2. Release the two Glass Frame Latches. Pull each latch handle forward forward to disengage the latch from the notches in the glass frame.
3. Lift the glass frame all the way up and out of the top of the stove. Lay this assembly on a flat surface, protecting the frame from scratches using a blanket or towel.
3. The glass panel is held in place by four compression clips. Use a screwdriver or small pliers to pry these up off the edge of the glass retaining walls. See fig. 40.
4. Remove the old gasket material. See fig. 41.
Glass Clips
Burner and Logset
Periodically inspect the Firebox, Valve Compartment, Convection Airways and optional Blower to BE CERTAIN THAT THE FLOW OF COMBUSTION AND VENTILATION AIR IS UNOBSTRUCTED.
The firebox should be vacuumed annually to remove any surface build up. Use a soft brush attachment and handle the logs carefully as they are fragile. Be sure to vacuum or wipe off the pilot assembly and burner surfaces.
Glass Care
Clean the glass only when necessary. Wipe the surface with a clean, dampened, soft cloth. Follow with a dry, soft towel. Take care not to scratch the glass surface.
WARNING: DO NOT USE ABRASIVE CLEANERS ON THE
GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT.
Gasket Inspection
It is important that the glass gasket be inspected at least annually. Examine the ribbon gasket for signs of deterioration and make sure the gasket has a positive seal. Replace the gasket if necessary. Refer to the replacement parts list on page 29.
Figure 40. Use small pliers to pry the clips off of the glass panel frame.
Glass Panel or Gasket Replacement
1. Wrap the new gasketing material evenly around the edge of the glass, peeling back the protective strip to expose the adhesive as you go. Press the adhesive side down onto the glass surface. Do not stretch the gasket.
2. Place the gasketed glass within the frame and press each of the retainer clips back into place on the retainer walls.
Figure 41. Wrap the gasket around the glass panel.
24
Optional Blower # 156000
Connect the gas supply line to the stove, before installing the Blower.
Use a 90° Elbow off the control valve to create clearance required for the blower installation.
1. Unpack and check the contents of the blower kit.
Contact your dealer if any damage is evident or parts are missing. See fig. 42.
2. Attach the Snapstat Bracket to the studs located in
the middle of the firebox floor using the two M6 hex nuts and a 10 mm wrench. See fig. 43.
3. Attach the Blower Bracket to the stove using the
two M6 flange head hex bolts as shown in fig. 43.
4. Attach the Duct Deflectors using the two #7 x 1/2”
screws together with the finger guard mounting screws already in place. See #7 and #11 in fig. 42.
5. Install the Blower with the duct openings oriented
up and forward. See fig. 44. Feed the wire harness through the bracket opening and secure the blower to the bracket with the wingscrew.
6. Attach either Snapstat wire connector to either
Snapstat terminal. See fig. 44.
7. Install the Snapstat by sliding it all the way into the
slot in the bottom of the Snapstat Bracket as shown in figs. 42 and 44.
8. Connect the male wire harness connector to the
female wire harness connector already installed in the stove. See fig. 44.
9. Connect power cord to outlet.
7
5
11
1
3
Contents
1. Blower
2. Mounting Bracket
3. Snapstat Wire Harness
4. Control Switch Wire Harness
5. Snapstat
6. Snapstat Bracket
7. Blower Duct Deflector (2)
8. M6 Hex Head Flange Nuts (2)
9. M6 x 12 Hex Head Flange Bolts (2)
10. M6 x 12 Wingscrew
11. #7 x 1/2” phillips screw (2)
Tools Required
• 10 mm wrench
* short phillips screwdriver * Safety Glasses * Work Gloves
Figure 42. Blower Kit Components
6
8
2
9
4
7
10

THIS BLOWER MUST BE ELECTRICALLY

GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE CURRENT ANSI/NFPA 70, NATIONAL ELECTRICAL CODE OR CSA C22.1-CANADIAN ELECTRICAL CODE.

THIS UNIT IS SUPPLIED WITH A

THREE-PRONG (GROUNDING) PLUG FOR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THE PLUG.

ALWAYS DISCONECT THE POWER

SUPPLY WHEN PERFORMING ANY SERVICE ON THE FIREPLACE INSERT.
Hex Head
Flange Bolts
Hex Head
Flange Nuts
Blower Bracket
Figure 43. Attach Snapstat and Blower Brackets.
Snapstat
Bracket
25
Figure 44. Attach Blower to the Mounting Bracket with the wingscrew and connect wires to Snapstat and female control quickconnect.
Blower Operation
Wingscrew
Snapstat
Connectors
Male
Quickconnector
to Female
Quickconnector
The optional variable-speed blower will enhance heat circulation around the firebox and out into the room. The blower is controlled by a heat activated switch (snapstat) that will ONLY function when the control switch is in AUTO setting. After the fire has been burning for a time, the snapstat will react to the heat and activate the blower. Fan speed may be manually adjusted with the rheostat knob. If the burner turns off, the blower will be shut off automatically when the stove cools down.
If automatic blower circulation is not desired, place
the blower control switch in the MANUAL position.
Figure 45. Blower Controls
G
W
G
BL BK
POWER
BK
SUPPLY
BL
GY
P
P
GY
BLOWER
W
BK
SNAPSTAT
P
BR
BR
P = QuickConnector Pin
Blower Speed
Control
BK
BK
BK
P
BK
P
RHEOSTAT
26
SWITCH
MANUAL OFF AUTO
Figure 46. Blower Wiring Diagram
Optional Antique Brick Panel Kit 155375
Tools Required: Safety glasses and gloves
Left Panel
220601
Rear Panel 220599
Right Panel
220600
1. Remove the Top Plate. Simply lift if up off of the
stove body. It is not fastened.
2. Remove the Glass Frame. Disengage the two
compression latches located at the top of the firebox and lift the glass frame up and off of the stove. See Fig. 1.
3. Remove the Logset.
These parts are not fastened. Simply lift them out of the firebox. You do not have to remove the embers.
4. Install the Rear Panel.
Tilt the Rear Panel top first to slide behind the exhaust baffle and position it up against the back wall.
5. Install the Side Panels. Tilt each panel, bottom
edge first, into position against the side walls. The panels will stand on their own against the wall. Push them back against the Rear Panel.
6. Reinstall the Logset. See page 21. BE CERTAIN THAT NO EMBERS ARE BLOCKING THE PILOT ASSEMBLY OPENING.
7. Replace the Glass Frame.
Slide the frame down the slot in the front of the firebox. Be sure to push the frame into the slot in the bottom to ensure it is fully seated. The gasket at the top of the frame should be flush with the top of the firebox.
Pull the compression latches out to engage with the top lip of the glass frame.
8. Replace the Top Plate.
Figure 47. Brick Kit Contents
Glass Frame
Latch
Figure 48. Release the glass frame latches.
Exhaust Baffle
Figure 49. Install the Rear Panel to fit behind baffle.
Figure 50. Install the Side Panels.
27
GF 400 DV Sebago Illustrated Parts Breakdown
1
2
3
4
51
52
53
5
6
7
8
57
9
45 44
54
43
42
41
25
40
64
49
39
38
56
37
56
36
35
34
33
32
31
30
29
28
27
55
26
24
23
22
63
58
10
11
46
47
Figure 51. Illustrated Parts Breakdown - GF400 DV Sebago
Side-mount Valve shown. Center-mounted valve uses same components.
141312
28
15
16
48
17
18
19
20
50
59
60
61
62
21
GF 400 DV Sebago Parts List
Cast Iron Parts Matte Black Blue Black Enamel Ivory Enamel Green Enamel Jøtul Iron Jøtul Iron Enamel
7. Left Side Plate 10391892 10391827 10391829 10391832 10391885 10391846
9. Bottom Plate 10396392 10396327 10396329 10396332 10396385 10396346
14. Legs, (4) 10192592 10192527 10192529 1092532 10192585 10192546
19. Front, Complete 15565492 155660 155672 155666 15565485 15565446
23. Right Door 10421692 10421627 10421629 10421632 10421685 10421646
25. Right Side Plate 10391992 10391927 10391929 10391932 10391985 10391946
41. Top Plate 10396292 10396227 10396229 10396232 10396285 10396246
50. Left Door 10421592 10421527 10421529 10421532 10421585 10421546
1. Air Divider ................................................................... 220624
2. Simpson DuraVent Collar ....................................... 129126
3. Collar Gasket .............................................................. 129118
4. Wire Harness Assembly .......................................... 155397
5. Rating Plate ................................................................ 220613
6. Lanyard ........................................................................ 129159
8. Rear Shroud ................................................................ 220558
10. Valve Bracket .............................................................. 220352
11. Valve - NG ................................................................... 220520
12. Elbow, 3/8” Brass ...................................................... 129129
13. Terminal Block ........................................................... 129154
15. Bracket, Terminal Block ........................................... 220614
16. Gas Line, 5/16” Flex .................................................. 129390
17. Orifice Holder Assembly ......................................... 129668
18. Glass Frame Assembly .............................................155398
Glass Panel Replacement Kit ................................. 155553
Glass Pane, Ceramic ................................................. 220567
Glass Gasket, 7/16” Tadpole .................................. 129124
Glass Frame ........................................................... 12972592
Glass Clips, (4) ............................................................220042
20. Keeper, Door Latch ....................................................220604
21. Control Door............................................................... 221188
22. Door Latch .................................................................. 220603
24. Log Set ......................................................................... 155378
26. Air Intake Gasket....................................................... 220642
27. Air Intake Restrictor ................................................. 220602
28. Air Shutter Gasket .................................................... 220734
29. Pilot Assembly Gasket ............................................. 129670
30. Pilot Assembly Spacer ............................................. 220546
31. Pilot Assembly, w/NG orifice ................................. 129471
Pilot Orifice NG #51 ................................................. 129472
Pilot Orifice LP #30 .................................................. 129473
Jam Nut - Orifice Holder ......................................... 129152
Ferrule (2) .................................................................... 129463
Nut (2) ..........................................................................129464
Pilot Line w/ Fitting .................................................. 129446
Thermocouple ........................................................... 129766
Electrode ..................................................................... 129765
Thermopile .............................................................. 3094527
32. Burner Assembly ....................................................... 155336
33. Burner Skirt ................................................................ 220582
34. Exhaust Baffle ............................................................220565
35. Exhaust Restrictor .................................................... 220563
36. Exhaust Restrctor Gasket ....................................... 220583
37. Firebox Assembly ...................................................... 221194
38. Latch Assembly ..........................................................220091
39. Relief Door Gasket .................................................... 129319
40. Relief Door .................................................................. 129640
42. Relief Door Guide ...................................................... 129499
43. Heat Fins, (4)............................................................... 155653
44. Inner Shroud, Right .................................................. 220596
45. Inner Shroud, Left ..................................................... 220597
46. Ignitor Bracket ........................................................ 3902576
47. Ignitor ....................................................................... 3902573
48. Burner Orifice, NG #33 ............................................ 220641
Burner Orifice, LP 1.65mm .................................... 220638
49. Primary Air Shutter .................................................. 220790
51. Rheostat Knob ........................................................... 220709
52. Rocker Switch, (2) ...................................................... 220703
53. Rheostat ...................................................................... 220970
54. Retaining Collar ........................................................ 220717
55. Fender Washer ........................................................... 118023
56. Wingnut, (3) ............................................................... 117975
57. Wire Harness.............................................................. 156001
58. Control Door Hinge .................................................. 221176
59. Bolt, M6 x 20 Blk Hex Hd ........................................ 117117
60. Spacer, .375 o.d. x 3.172 ..........................................118040
61. Washer, Fender .250 x 1.500 dia. ..........................118029
62. Bolt, M6x100 Hex ..................................................... 117955
63. Spacer, .250 x .50 x .250 Alum,.............................. 117994
64. Spacer, .250 x .50 x .125 Alum,............................. 118009
*Wire Harness Retainer........................................... 220733
Accessories
Variable Speed Blower .................................. 156000
Brick Panel Kit.................................................. 155375
Wall Thermostat ............................................. 750003
Remote Control ............................................... 750002
Floor Bracket Kit ............................................. 750304
Fuel Conversion Kit to Propane .................. 156003
Fuel Conversion Kit to Natural Gas ........... 156004
ALWAYS USE REPLACEMENTS PARTS
PROVIDED BY AN AUTHORIZED JØTUL
DEALER ONLY.
* Parts not illustrated
29
Record the following information to help your dealer determine what you will need for parts and service.
MODEL NAME: ________________________
SERIAL NUMBER: ______________________
DATE OF PURCHASE: ___________________
PURCHASED FROM: ____________________
NAME OF INSTALLER: ___________________
TYPE OF FUEL: ________________________
WAS STOVE CONVERTED? _______________
NOTES:
GF 400 DV Sebago
30
RETAIN THIS MANUAL FOR REFERENCE
AND MAKE IT AVAILABLE TO ANYONE
USING OR SERVICING THE STOVE.
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY, READ BEFORE LIGHTING.
WARNING:
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
A. This appliance has a pilot which must be lit
by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING, smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS:
• Extinguish any open flame.
• Open windows.
• Do not light any appliance.
• Do not touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Access the lower controls.
3. Turn the stove ON/OFF switch to “OFF”, or set the
thermostat to lowest setting (if used).
4. Confirm that the gas supply line shut-off valve is open.
Control
Knob
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
NOTE: Knob cannot be turned from “PILOT” to “OFF” unless the knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow “B” in the safety information above on this page. If you do not smell gas, go to the next step.
ON
OFF
PILOT
Control Valve
• If your gas supplier cannot be reached, call the fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it. Call a qualified technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
7. Push in gas control knob slightly and turn counter-
clockwise to “PILOT”.
8. Push in control knob all the way and hold in.
Immediately light the pilot by triggering the spark ignitor (push the red button repeatedly) until pilot lights. Continue to hold the control knob in for about one minute after the pilot lights. Release knob and it should spring back. The pilot should remain lit. If it goes out, repeat Steps 5 through 8.
• If knob does not return when released, stop and immediately call your service technician or gas supplier.
• If pilot will not stay lit after several tries, turn the control knob to OFF and call your service technician or gas supplier.
9. Turn gas control knob counterclockwise to “ON”.
10. Turn the stove ON/OFF switch to “ON”, or set
thermostat (if used) to desired temperature.
Pilot Assembly
TO TURN OFF GAS TO THE APPLIANCE:
1. Turn ON/OFF switch to” OFF”. The pilot will remain lit for
normal service.
2. For complete shutdown, turn ON/OFF switch to “OFF”.
3. Access the lower controls.
4. Depress gas control knob slightly and turn clock-
wise to “OFF”. Do not force.
31
November 2005
137750-E
This appliance must be installed in conformance with local and national building regulations. Before beginning the installation, it is important that the these instructions be carefully read and understood. Jøtul maintains a policy of continual product development. Consequently, products may differ in specification, color or type of accessories from those illustrated or described in various publications.
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve le droit de modifier les specifications, couleurs etequipement sans avis prelable.
32
Jøtul AS
P.O. Box 1411 N-1602 Fredrikstad
Norway
Jøtul North America
55 Hutcherson Dr. Gorham, ME 04038-2634
Loading...