Interlogix NX-4-FP-12 User Manual

6000 Series PIR
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Model PI6000 - with 30 lb. pet immunity Model 6000 - with high density (HD) performance lens
Installation Instructions
266
266
267
T T + Ð NC C
Back housing
Circuit board
Shield
Lens
Front housing
Note
Use a screwdriver to undo the latch on the bottom of the detector.
Figure 1. Detector (Exploded)
Description
The 6000 Series Passive Infrared Detectors are designed for use in residential applications. These detectors utilize dual pyroelectric sensors with jumper selectable pulse count (two- or three-pulse mode). Advanced signal processing provides high immunity to false trips - RFI, lightning, vibration, and rapid temperature changes.
An interchangeable, opaque Fresnel lens blocks visible light and provides the ability to select the best coverage pattern for the site. The lens is part of a sealed optic enclosure which isolates the pyroelectric sensor from drafts and insects, common sources of false trips.
The 6000 series comes with a closed loop alarm contact and a closed loop tamper switch.
.Selecting a Location
Mount the detector at a height of 7 to 9 feet (2.1 to 2.7m) . See
Mounting Height Settings.
Mount the detector either flat on the wall or in a corner and at least 3/8” (0.95cm) from the ceiling. See Figure 2.
Do not locate the detector where it may be exposed to false alarm sources, such as:
- heat sources in the field of view
- direct or reflected sunlight
- strong air drafts (fans, air conditioners, etc.) on unit
Flat Wall
3/8”
0.95cm
Figure 2. Mounting
Corner
3/8”
0.95cm
Do not aim the detector at windows or glass doors.
Mount the detector on a rigid, vibration-free surface.
Do not locate the detector on a surface exposed to moisture.
Do not locate the detector where the ambient temperature is below 14°F (-10°C) or above 122°F (50°C).
PIRs require a clear line of sight. Inform end-users not to block the coverage pattern with inventory, furniture, decorations etc.
6000 Series PIR
E
Wire entry hole for
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
surface wire runs
Primary wire entry hole for corner
Primary mounting hole for flat wall mounting
Locking tab
Center wire entry hole
Cable strain relief
Additional wire entry hole
Secondary mounting hole used to lock down when flat wall mounting
Figure 3. Back Housing
Mounting holes for corner mounting
Installing the Detector
1. Select an appropriate mounting location.
2. Route wiring to the detector’s location.
3. Open the detector and, after selecting appropriate mounting and wire entry options, remove the knockouts by depressing from the inside of the detector in the center of desired knockout (see Figure
3). The circuit board may be removed to facilitate mounting and removal of knockouts if desired.
A B
Setting the Jumpers
J3 Pulse Count -
Jumpers J3 J4
3 2
PULS
J3
J4LED
PET
7/8' 8/9'
TT
Figure 4 . Circuit Board
+NCCOM
ON = Three-pulse mode
OFF = Two-pulse mode (factory default)
Note
Use two-pulse mode for all residential applications including pet applications.
Power In 10 to 16 VDC
J4 LED -
CAUTION
ON = LED enabled (factory default)
Y ou must be free of all electricity before handling sensor circuit boards. T ouch a grounded bare metal surface before touching
OFF = LED disabled circuit boards or wear a grounding strap. Promptly reinstall the circuit board when finished with knockout removal and mounting the back housing.
4. Pull cable through the appropriate knockout and fasten the detector to the wall.
5. Strip back the outer jacket and individual wires of the cable and connect the conductors to the proper terminals (see Figure 4). The alarm contacts are not polarity sensitive.
Note
Use caution not to strip more insulation than needed, approxi­mately 1/4” (0.6cm), so that bare wires do not touch and cause a short.
Pet Applications
A. For pet applications, the detector should be installed at the standard 7 to 8 feet (2.1 to 2.4m) mounting height. Verify that the circuit board is properly positioned in the back housing (see Mounting Height Settings).
B. Place the pulse count selection jumper in two-pulse mode (see
Setting the Jumpers).
C. Make sure animals cannot get within 6 feet (1.8m) of the detector’s line of sight or climb on furniture within 6 feet (1.8m) of the detector.
Note
6. Route the cable through the strain relief located on the far left side of the back housing (see Figure 3). Snap on the front housing.
7. W alk test the detector and check for desired coverage.
False alarm immunity from any number of small pets and rodents can be expected as long as the total combined weight does not exceed 30 lbs. and room temperature does not fall below 50° F (10° C).
Note
Most units walk test more accurately if the person testing waits 10 seconds between tripping the unit and walking again. This allows the detector to stabilize between trips.
Mounting Height Settings
The factory setting of the detector is for mounting heights of 7 to 8 feet (2.1 to 2.4m). For this setting, the locking tab on the back housing is in the notch by the 7-8’ arrow on the circuit board (position A in Figure 4).
For proper operation at mounting heights above 8 feet (2.4m), the locking tab must be in the notch by the 8-9’ arrow (position B in Figure 4).
Long Hair Short Hair Not Recommmended Up to 50 lbs Up to 30 lbs
Cocker Spaniel Basenji Doberman Eskimo Border T errier Greyhound Husky French Bulldog Mastiff Pekinese W elsh Corgi Shepherd Sheepdog Cats St. Bernard
The pet immunity feature has not been tested by Underwriters Laboratories Inc.
6000 Series PIR
Loading...
+ 2 hidden pages