Interlogix NX-488 User Manual

ShatterPro
e
e
®
Glass Break Sensor
Document Number 466-1841 Rev B April 2001
Sentrol/Caddx Part Number NX-488
ITI Part Number 60-873-95
Installation Instructions
The ShatterPro® omnidirectional glassbreak sensor provides 360 degree coverage. It can be mounted on the ceiling, or on the opposite wall, or on adjoining walls. It has a range of up to 20 feet for glass panes 1 x 2 (0.3m x
0.6 m) or larger.
4.24"
10.8 cm
3.13"
8.0 cm
Figure 1. The ShatterPro Glass Break Sensor
The maximum detection range is 20 (6 m) for plate, tempered, laminated and wired glass. For armor-coated glass, the maximum detection range is 12 (3.65 m). Coverage is measured from the sensor to the point on the glass farthest from the sensor (see D and D in Figure 2). See Specifications for recommended glass thickness.
DD
D' 20'
Maximum distance (D) from the ShatterPro to the glass must not exceed 20'
Wireless ShatterPro
Figure 2. Optimum performance zone
Not
ShatterPro may not consistently detect cracks in glass, or bullets that break through the glass. Glassbreak sensors should always be backed up by interior protection.
D
is distance from glass The optimum performance zone is distance D in either direction on the glass.
1.70"
4.3 cm
Installation Guidelines
For best detection, avoid installing in rooms with
lined, insulating, or sound deadening drapes or rooms with closed wooden window shutters inside.
Dont use near an air compressor. A blast of
compressed air may cause a false alarm.
Avoid stairwells, glass booths, and all rooms smaller
that 10 x 10 (3 m x 3 m).
The Pattern Recognition Technology of the
ShatterPro ignores most false alarm sounds. Some sounds can duplicate the glass break pattern the ShatterPro detects, however, so the ShatterPro works best in rooms with only moderate noise. Avoid rooms where white noise, such as a fan, is present. Avoid rooms with noisy areas or multiple noise sources such as small kitchens or bathrooms, garages, etc.
Not
For glass break protection in these applications (where ShatterPro is not appropriate), use shock sensors on the windows or window frames.
Avoid adding (learning) the sensor into 24-hour sensor
groups, where the sensor will be armed even when the room is in use. Like a motion detector, a glass break sensor may be tripped when occupants are in the protected area. Adding the ShatterPro to a perimeter sensor group, which is armed only when the perimeter doors and windows are armed, will help prevent false alarms.
Do not install in humid rooms. The ShatterPro is not
hermetically sealed. Excess moisture on the circuit board can eventually cause an electrical short and possibly a false alarm.
The sensor can be mounted as close as 3.3 (1 m) from
the glass.
Tools Needed
Phillips screwdriver Sentrol 5709C hand-held tester
Installation
Use the following procedure to install the ShatterPro.
1. Choose a mounting location. Since the sound of breaking glass travels straight out from the broken window, the best location for mounting the sensor is the wall opposite the window--assuming the glass to be protected is within the sensor range and line of sight. The ceiling and adjoining (side) walls are also good sensor locations. A ceiling mounted sensor will have better detection if located 6-10 (2-3 m) back from the glass rather than directly above the glass.
Important !
DO NOT EXCEED THE 20’ MAXIMUM DETECTION RANGE OF THE SHATTERPRO. While the sensor may function beyond the 20’ range, it could miss a minimum output glassbreak. Furthermore, changing conditions in the room, such as rearranging furniture, could reduce the range of the sensor back to 20’.
2. Remove the cover from the ShatterPro base. Hold the base against the wall or ceiling at the desired mounting location. Insert screws through the two mounting holes in the base to attach it to the mounting surface.
Cover
3V Batteries
Base
Figure 4. Battery installation
Testing the ShatterPro
CAUTION
You must be free of all static electricity before handling the transmitter circuit board. Touch a grounded, bare metal surface before touching the circuit board, or wear a grounding strap.
Mounting holes
Figure 3. Mounting holes (back view of the ShatterPro)
3. Insert two 3V batteries as shown in Figure 4 and replace the cover.
4 Use the procedures in the following sections, Testing
the ShatterPro and Testing the System, to make sure the sensor is working properly with the panel.
Pattern Recognition Technology of the ShatterPro ignores most false alarm sounds, including glassbreak testers, so the ShatterPro must be set to test mode during
Figure 5. Testing the ShatterPro
the following procedure (see step 2). When the sensor is in test mode, processing of the glassbreak pattern in the upper and lower frequencies is disabled. The ShatterPro is then listening only for the mid-range frequencies, which the tester reproduces. It is these frequencies that determine the sensor detection range.
2
Loading...
+ 2 hidden pages