14. UL & CE NOTICES ................................................................................................................................... 44
These instructions do not purport to cover all details or variations in equipment nor to provide ev ery possible contingency to be met during
installation, operation, and maintenance. If further information is desired or if particular problems arise that are not covered sufficiently for the
purchaser’s purpose, the matter should be referred to GE Security, Gladewater, Texas, USA.
This document contains proprietary information of GE Security, USA and is furnished to its customer solely to assist that customer in the installation,
testing, operations, and/or maintenance of the equipment described. This document shall not be reproduced in whole or in part nor shall its contents
be disclosed to any third party without the written approval of GE Security. Please refer to the current GE Sec urity produc t c atalog for detailed
warranty information.
™
is a trademark of the GE Security companies.
Main
800-727-2339 Technical Support 800-727-2339
Outside the US 903-845-6941 Tech Support Fax 903-845-8409
Main Fax 903-845-6811 Sales & Literature 800-547-2556
Web: www.caddx.com
1420 N. Main
Gladewater, TX 75647
www.ge-security.com
1. GENERAL DESCRIPTION
The NX-2192E is a microprocessor-controlled point ID bus interface module for the NX-8E control panel. The PinPoint System provides
two-wire bidirectional communications with up to 255 individually addressed devices. The total number of devices in a system is limited by
the I/O capability of the panel. The NX-8E can support a maximum of 192 zones mapped to 192 input device addresses and an additional
48 addresses for output devices. Warranty information is provided in the Interlogix product catalog.
2. INSTALLATION
The NX-2192E is installed in the NX-8E control panel enclosure. Three loop outputs are provided for interface with the point ID devices. A
single loop output can support the full 255 point ID devices as long as the wire run limits are not exceeded. The total number of devices
can be distributed across the three loop outputs to meet wire run limit requirements.
3. DEVICE ADDRESS CONFIGURATION
Each device on the PinPoint System must be configured for a unique address with the range of 0 through 254. Address 255 is reserved.
Setting the address switches at the time that each device is installed will determine the address selection. Please refer to the worksheet
in Appendix1 on page 40.
4. TERMINAL DESCRIPTIONS
TERMINAL DESCRIPTION
PANEL-
PANEL+
COM
EARTH
AC
AC
DATA
DCOUT-
DCOUT+
DCOUTDCOUT+
LOOPA+
LOOPALOOPB+
LOOPBLOOPC+
LOOPC-
For UL certified installations, the NX-2192E must be powered by the NX-8E control panel.
Supply Common terminal.
DC supply terminal for powering the NX-2192E.
Common terminal.
Earth Ground.
AC Input. Connect to a 16.5V 25, 40, or 50VA Class II UL approved transformer.
AC Input. Connect to a 16.5V 25, 40, or 50VA Class II UL approved transformer.
Connect to the NX8 / NX-8E control panel DATA terminal. This terminal is the incoming data-signaling
terminal to the NX-2192E. The maximum total wire run from the control panel to all devices including the
NX-2192E is 2500 feet.
WARNING
connecting.
Connect to the NX-8 / NX-8E control panel COMMON terminal. This terminal supplies the common side
of the power to the NX-2192E.
Not used at this time.
Supply Common terminal.
Used only when supplied by UL approved transformer in 12V mode.
Rating: 600mA when using 12V transformer
Loop A Point ID bus supply terminal.
Loop A Point ID bus return terminal.
Loop B Point ID bus supply terminal.
Loop B Point ID bus return terminal.
Loop C Point ID bus supply terminal.
Loop C Point ID bus return terminal.
: This terminal is not protected from damage by mis-connection. Observe caution when
2
NX-2192E PINPOINT SYSTEM
5. WIRING DIAGRAM
NX-2192E PINPOINT SYSTEM
3
6. MAXIMUM NUMBER OF DEVICES PER WIRE RUN
The number of devices on an individual wire run must not exceed the number listed in the following table. If a star configuration is used,
the total wire length must not exceed 10000 feet per loop output.
The NX-8E has the ability to automatically find and store in its memory the presence of all keypads, zone expanders, wireless receivers
and any other modules connected to the data terminal. This allows these modules to be supervised by the control panel. To enroll the
modules enter the Program Mode of the NX-8E control panel, and when the Program Mode is exited, it will automatically enroll the
devices. The enrolling process takes about 12 seconds, during which time the “Service” LED will illuminate. User codes will not be
accepted during the enrolling process. Once a module is enrolled, if it is not detected by the control, the “Service” LED will illuminate.
8. PROGRAMMING THE MODULE
To enter the program mode, press []-[8]. All of the function key LEDs will begin to flash.
Enter the "Go To Program" code (default is [9]-[7]-[1]-[3]). If the code was valid, the Service LED will flash, and the function
LEDs will illuminate steady, indicating the device to program should be entered.
Press [4] [4] [#] for the fixed address of the PinPoint module. The Armed LED will illuminate while it is waiting for a
programming location to be entered.
Enter the desired programming location. The Armed LED will begin to flash while a programming location is being entered.
Press [#]. If this is a valid location, the Armed LED will extinguish, the Ready LED will illuminate, and the binary data for the
first segment of this location will be shown on the zone LEDS.
To change the data, enter the data followed by []. The data will be entered, and the location will automatically increment to
the next segment. The data for that segment will be displayed. This procedure is repeated until the last segment is reached.
Pressing the [#] key will exit from this location. To review the data, repeat the above procedure, pressing the [] key without
entering data first. Each time the [] key is pressed the next segment is displayed.
Programming data is always one of two types of data. The first type is numerical, and can take on values from 0-255 or 0-15 depending
on the segment size. The second type is a feature selection type. Feature selection data is used to turn features on or off. LCD Keypad Users Note: All steps required for programming are the same as the aforementioned LED keypad. The LCD keypad display will
prompt you for the data required. While in the programming mode, and not in a location, the number in parenthesis is the location you
were previously changing. For example, if the display reads "Enter location, then # (5)", it is reminding you that location 5 was the last
location you programmed. In feature selection data, the numbers of the enabled features will be displayed. However, the features not
enabled will display a hyphen (-).
IMPORTANT NOTES
To program additional points after the Program Mode is exited:
1. Re-Enter the Program Mode using the instructions in Section 8, page 4 of this manual.
2. Enter Location 0 and press [1] to initialize the “Progam Mode Designation”
3. Program the desired location(s).
9. PROGRAMMING SEQUENCE EXAMPLE
The following example assumes the installation of a single input module on the bus as address number 5, with its input mapped to zone
number 9:
Enter system program mode on the NX-2192E as previously described.
Select the configuration location for zone number 9 by entering [9] [#].
Input for segment 1 is requested. Select the device address of 5 (b inary) by e ntering [2]-[4]-[5]-[6]-[7]-[8] so that the sequence
of (1_3_____) is displayed.
Press [] [#] to exit this location.
Select the PinPoint program mode location by entering [0] [#].
Input for segment 1 is requested. Enable PinPoint program mode by entering [1] [].
Wait for the keypad to sound a ding-dong. Press [EXIT] [EXIT] to exit the system program mode.
Refer to Location 0 description for troubleshooting if the keypad does not ding-dong after PinPoint program mode is complete.
4
NX-2192E PINPOINT SYSTEM
10. PROGRAMMING LOCATION GUIDE
LOCATION 0
Location 0 is used to communicate to the PID bus interface to enter PID Program Mode.
Segment 1 must be set to [1] to “learn” points. While in this mode, all nodes able to communicate will be enabled and mapped to pre-
programmed zones. With this in mind, prior to entering PID program mode, all zones must be either programmed with a serial number (for
devices without a dip switch) or a physical address (for devices with a dip switch). If programming is a success and no errors were
reported, a “0” will automatically be written into segment 1 of this location and the keypad will sound a ding-dong. Otherwise, the number
of errors will be written and the keypad will sound a triple beep, indicating that errors were found. If errors were found, segments 2-16 will
contain the locations of the first 15 zones with errors. Zone locations may then be examined to determine the type of error that occurred.
POINT ID PROGRAM MODE
DESIGNATION
16 segments of numerical data
NOTE: If the 8 on-board zones are enabled, then zones 1-8 are already used and may not have a PID address mapped to them.
If zone doubling is enabled, then zones 1-16 are already used and may not have a PID address mapped to them.
Segments 2-16 are “read only”.
LOCATIONS 1 – 192
Segment 1 is used to store the physical address of the corresponding node. Factory default is 255. Whether or not the device has a dip
switch, this location is programmed by the installer prior to entering PID Program Mode.
Segment 2 is used to store the input number for multiple input/output devices. Factory default is 1.
Segment 3 is used to display an error code if an error(s) occurred during the last PID program mode cycle. The following table prov ides
a description of the types of errors that may occur:
Table 10-1
PROGRAMMING NODE INFORMATION
ZONES 1 - 192
3 segments of binary data
ERROR CODE DESCRIPTION ERROR CODE DESCRIPTION
1 Node is missing. 5 Auto enroll error.
2 Multiple node responded. 6 Reserved.
3 Communication error. 7 Reserved.
4 Device type mismatch. 8 Zone programmed but node not enabled.
LOCATION 193 DEVICE OPTIONS 1 segment of feature selection data
Segment 1 selects the following options:
1 = Reserved.
2 = "On" if Loop A should be enabled; “Off” if disabled.
3 = "On" if Loop B should be enabled; “Off” if disabled.
4 = "On" if Loop C should be enabled; “Off” if disabled.
5 = “On”if 24V mode should be enabled; “Off” if 12V mode.
6 = “On” if the NX-2192E is powered from AUX + terminals of the control panel. Turning this option “On” disables NX-2192E power
monitoring.
7 = “On” if any AC Fail condition should be communicated to the central monitoring station. Option 6 overrides this condition
occurring on the NX-2192E, but not individual nodes.
8 = “On” if any Low Battery condition should be communicated to the central monitoring station. Option 6 overrides this condition
occurring on the NX-2192E, but not individual nodes.
LOCATIONS 194 - 241
Segment 1 is used to store the physical address of the corresponding node. Whether or not the device has a dip switch, this location is
programmed by the installer prior to entering PID Program Mode. This segment can also be used as an indicator that the corresponding
node had an error during the last PID Program Mode cycle, because any error causes this segment to be defaulted to address 255.
Segment 2 is used to store the output number for multiple input/output devices. Default is 1.
Segment 3 is used to display an error code if an error or errors occurred during the last PID Program Mode cycle. In the following Table
2.1, a description of the types of errors that may occur and the bit in the error code associated with the error is outlined.
NODE INFORMATION FOR
OUTPUTS 1 –48
3 segments of binary data
NX-2192E PINPOINT SYSTEM
5
Table 10-2
AC Fail (control or exp.) does not
ERROR CODE DESCRIPTION
1 Node is missing.
2 Multiple node responded.
3 Communication error.
4 Device type mismatch.
5 Auto enroll error.
6 Reserved.
7 Output programmed to non-output device.
8 Output programmed but node not enabled.
LOCATION 242 – 336 (EVEN LOC)
Segment 1 is used to select the particular event that will trigger the output. Refer to Table 10-3 for the specific events that can be
selected.
Segment 2 is used to select the amount of time an output will remain activated when an output triggers. If this lo cation is p rogrammed as
a zero, the output will follow the particular event.
Table 10-3
# Event # Event # Event
Always On
0
1
follow AC Fail delay time
Low Battery (control or exp.)
2
Dynamic Battery Test Time
3
Listen In
4
Line Seizure
5
Telephone Line Fault
6
Program Mode
7
Over-current (control or exp.)
8
Box Tamper (control or exp.)
9
Siren Tamper (control or exp.)
10
♦ If set to follow condition, these events will be one second.
LOCATION 243 – 337 (ODD LOC)
Segment 1 selects the following special conditions:
EVENT & TIME FOR
OUTPUTS 1 - 48
Smoke Power Reset
11
Yelping Siren
12
Steady Siren
13
Any Siren
14
Steady Siren (temporal)
15
Any Siren (temporal)
16
Alarm Memory
17
Entry
18
Exit
19
Entry or Exit
20
Armed
21
SPECIAL FEATURES FOR
OUTPUTS 1 - 48
2 segments of numerical data
Disarmed
22
Ready to Arm
23
Not Ready to Arm
24
Fire
25
Fire Trouble
26
Chime
27
Beeping Keypad
28
Aux 1 Keypad Function
29♦
Aux 2 Keypad Function
30♦
Panic Keypad Function
31♦
Code Entry (set in locs 338 - 481)
32♦
2 segments of feature selection data
1 = "On" if output should time in minutes; "Off" if output times in seconds.
2 = "On" if output should latch until a code is entered; “Off” for timed.
3 = "On" if output should stop time when a code is entered.
4 = “On” for inverted output.
5 = “On” disables output during listen-in (only events 12-16).
6 = Reserved.
7 = Reserved.
8 = Reserved.
Segment 2 selects the following partitions:
1 = "On" if the event should activate when it occurs in Partition 1.
2 = "On" if the event should activate when it occurs in Partition 2.
3 = "On" if the event should activate when it occurs in Partition 3.
4 = "On" if the event should activate when it occurs in Partition 4.
5 = "On" if the event should activate when it occurs in Partition 5.
6 = "On" if the event should activate when it occurs in Partition 6.
7 = "On" if the event should activate when it occurs in Partition 7.
8 = "On" if the event should activate when it occurs in Partition 8.
6
NX-2192E PINPOINT SYSTEM
Table 10-4
LED DESCRIPTION OUTPUTS
TABLE 10-4
IS USED TO
PROGRAM
LOCATIONS
338 - 481
1 "On" if code will activate output; "Off" if it will not.
2 "On" if code will activate output; "Off" if it will not.
3 "On" if code will activate output; "Off" if it will not.
4 "On" if code will activate output; "Off" if it will not.
5 "On" if code will activate output; "Off" if it will not.
6 "On" if code will activate output; "Off" if it will not.
7 "On" if code will activate output; "Off" if it will not.
8 "On" if code will activate output; "Off" if it will not.
When activating outputs with a user code (event #32), locations 338 - 361 can be used to restrict certain codes from activating certain
outputs. Each location contains 10 segments. Location 338 / segment 1 corresponds to user 1; segment 10 corresponds to user 10; and
finally location 361 / segment 1 corresponds to user 231; Segment 10 corresponds to user 240. The LEDs correspond to outputs 1 - 8.
Refer to Table 10-4 for descriptions.
LOCATIONS 362 - 385
CODES 1 – 240
OUTPUTS 9 - 16 ENABLE
10 segments of feature selection data
When activating outputs with a user code (event #32), locations 362 - 385 can be used to restrict certain codes from activating certain
outputs. Each location contains 10 segments. Location 362 / segment 1 corresponds to user 1; segment 10 corresponds to user 10; and
finally location 385 / segment 1 corresponds to user 231; Segment 10 corresponds to user 240. The LEDs correspond to outputs 9 - 16.
Refer to Table 10-4 for descriptions.
LOCATIONS 386 - 409
CODES 1 – 240
OUTPUTS 17 - 24 ENABLE
10 segments of feature selection data
When activating outputs with a user code (event #32), locations 386 - 409 can be used to restrict certain codes from activating certain
outputs. Each location contains 10 segments. Location 386 / segment 1 corresponds to user 1; segment 10 corresponds to user 10; and
finally location 409 / segment 1 corresponds to user 231; Segment 10 corresponds to user 240. The LEDs correspond to outputs 17 -
24. Refer to Table 10-4 for descriptions.
LOCATIONS 410 - 433
CODES 1 – 240
OUTPUTS 25 - 32 ENABLE
10 segments of feature selection data
When activating outputs with a user code (event #32), locations 410 - 433 can be used to restrict certain codes from activating certain
outputs. Each location contains 10 segments. Location 410 / segment 1 corresponds to user 1; segment 10 corresponds to user 10; and
finally location 433 / segment 1 corresponds to user 231; Segment 10 corresponds to user 240. The LEDs correspond to outputs 25 -
32. Refer to Table 10-4 for descriptions.
LOCATIONS 434 - 457
CODES 1 – 240
OUTPUTS 33 - 40 ENABLE
10 segments of feature selection data
When activating outputs with a user code (event #32), locations 434 - 457 can be used to restrict certain codes from activating certain
outputs. Each location contains 10 segments. Location 434 / segment 1 corresponds to user 1; segment 10 corresponds to user 10; and
finally location 457 / segment 1 corresponds to user 231; Segment 10 corresponds to user 240. The LEDs correspond to outputs 33 -
40. Refer to Table 10-4 for descriptions.
LOCATIONS 458 - 481
CODES 1 – 240
OUTPUTS 41 - 48 ENABLE
10 segments of feature selection data
When activating outputs with a user code (event #32), locations 458 - 481 can be used to restrict certain codes from activating certain
outputs. Each location contains 10 segments. Location 458 / segment 1 corresponds to user 1; segment 10 corresponds to user 10; and
finally location 481 / segment 1 corresponds to user 231; Segment 10 corresponds to user 240. The LEDs correspond to outputs 41 -
48. Refer to Table 10-4 for descriptions.
NX-2192E PINPOINT SYSTEM
7
11. BATTERY CALCULATION WORKSHEET
TOTAL STANDBY CURRENT
System Component Qty Standby Current TOTAL STANDBY CURRENT
NX-8E-CF 1 X 60mA
NX-870E 1 X 20mA
NX-148E X 75mA
NX-208E Aux+
NX-216E X 30mA
NX-320E X 10mA
NX-507E X 10mA
NX-1700E X 40mA
NX-2192E X 170mA
X
13mA
TOTAL
TOTAL ALARM CURRENT
System Component Qty Device Alarm Current TOTAL ALARM CURRENT
NX-8E-CF 1 X 210mA
NX-870E 1 X 110mA
NX-148E X 110mA
NX-208E Aux+
NX-216E X 60mA
NX-320E X 10mA
NX-507E X 310mA
NX-1700E X 110mA
NX-2192E X 170mA
2192E is powered from AUX + terminals of the control panel. Turning this option “On” disable s
tral monitoring station. Option 6 overrides
“On” if any Low Battery condition should be communicated to the central monitoring station. Option 6
5
DEVICE OPTIONS 193
1 = Reserved.
2 = "On" if Loop A should be enabled; “Off” if disabled.
3 = "On" if Loop B should be enabled; “Off” if disabled.
4 = "On" if Loop C should be enabled; “Off” if disabled.
5 = “On” if 24V mode; “Off” if 12V mode.
6 = “On” if the NX-
NX-2192E power monitoring.
7 = “On” if any AC Fail condition should be communicated to the cen
this condition occurring on the NX-2192E, but not individual nodes.
8 =
overrides this condition occurring on the NX-2192E, but not individual nodes.
not follow AC Fail delay time
2 Low Battery (control or exp.) 19 Exit
3 Dynamic Battery Test Time 20 Entry or Exit
4 Listen In 21 Armed
5 Line Seizure 22 Disarmed
6 Telephone Line Fault 23 Ready to Arm
7 Program Mode 24 Not Ready to Arm
8 Over-current (control or exp.) 25 Fire
9 Box Tamper (control or exp.) 26 Fire Trouble
10 Siren Tamper (control or exp.) 27 Chime
11 Smoke Power Reset 28 Beeping Keypad
12 Yelping Siren 29♦ Aux 1 Keypad Function
13 Steady Siren 30♦ Aux 2 Keypad Function
14 Any Siren 31♦ Panic Keypad Function
15 Steady Siren (temporal) 32♦ Code Entry ( locs 338 - 481)
16 Any Siren (temporal)
(EVENT / TIME)
18 Entry
SEG 1 DESCRIPTION SEG 2DESCRIPTION
1 = ON times in minutes
2 = ON to latch until a code is
3 = ON if output should stop time
4 = ON for inverted output 4 = On if event activates output in
5 = ON disables output during
6 = Reserved 6 =
7 = Reserved 7 =
8 = Reserved 8 =
USE THE FOLLOWING TABLE FOR
ODD NUMBERED LOCATIONS 243 – 337
(SPECIAL FEATURES)
OFF if times in seconds
entered; OFF for timed
when a code is entered
listen-in (only events 12-16)
1 = On if event activates output in
Partition 1
2 = On if event activates output in
Partition 2
3 = On if event activates output in
Partition 3
Partition 4
5 = On if event activates output in
Partition 5
On if event activates output in
Partition 6
On if event activates output in
Partition 7
On if event activates output in
Partition 8
LOC PAGE DESCRIPTION SEG 1 DEFAULT SEG 1 DATA SEG 2 DEFAULT SEG 2 DATA