NetworX NX–208E
2-Wire Smoke Expander Module
©2004 GE Security
KA-0104
GE Security
g
2266 Second Street North
North Saint Paul, MN 55109
Phone: 651-777-2690
USA & Canada: 800-777-5484
Technical Service: 800-777-2624
www.GE-Security.com 12345 SW Leveton Drive
Tualatin, OR 97062
Phone: 503-692-4052
USA & Canada: 800-547-2556
Technical Service: 800-648-7424
Faxback: 800-483-2495
Ordering Information
Model Description
UL Listings
Residential and Commercial UL Burglary ratings
UL 609 Commercial Burglary
UL 864 Commercial Fire
UL 985 Residential Fire
UL 1023 Residential Burglary
UL 1610 Grade B & C Central Station Burglar Alarm
CAN/ULC Listings S304
CAN/ULC Listings S545
Tw o-wire smoke loop expander
3.3K End-of-Line Resistor device
NX-8 Commercial Fire Kit: Includes NX-8-CF Control Panel, (2) NX-148E-CF LCD Keypads, NX-870E Fire Supervision & 16.5V,
50VA Transformer
NX-8E Commercial Fire Kit: Includes NX-8E-CF Control Panel, (2) NX-148E-CF LCD Keypads, NX-870E Fire Supervision & 16.5V,
50VA Transformer
16-zone expander module
Smart power supply and buss extender
Seven relay module
NX-208E
EOL33
NX-8-CF-KIT
NX-8E-CF-KIT
Other available NetworX modules
NX-216E
NX-320E
NX-507E
Specifications
Operating Power 12V DC
Supplied from
NetworX models* NX-6, NX-8, NX-8-CF, NX-8E, NX-8E-CF or NX-320E
Auxiliary Power Current limited to 100mA
Supplied from
NetworX models NX-6, NX-8, NX-8-CF, NX-8E, NX-8E-CF or NX-320E
Current Draw 30mA
DCIN Current Draw 31mA max @ 12V DC
62mA max @ 24V DC
Aux+ Rating 13mA @ 12V DC in Normal Standby
53mA @ 12V DC in Alarm
3.84 Amps max (with 8 detectors per loop)
Loop Resistance 12V Loop = 20Ω max
24V Loop = 50Ω max
Loop Response 180mS
Operating Temperature 32°F to 120°F
Dimensions 9.5” W x 3.5” H x 1.0” D
Shipping Weight 2 lbs.
* IMPORTANT: Supplied power from external supplies must be UL listed for
Commercial Fire or Burglary.
NetworX Technical Support: 800-727-2339