IDEAL 61-085 User Manual

Vol-Con®XL (61-086) Voltage/Continuity Tester and Vol-Test™ (61-085) Voltage Tester
Instruction Manual
Read First: Safety Information
This tester complies with UL3111-1, Cat III-600 overvoltage protection, Pollution Degree 2. Use the tester only as specified in this manual; otherwise, the protection provided by the tester may be impaired.
In this manual, a Warning identifies con­ditions and actions that pose hazards to the user. A Caution identifies conditions and actions that may damage the meter or the equipment under test.
Warning
To avoid possible electric shock or person­al injury, follow these guidelines:
• Do not use tester if it is damaged. Visually inspect tester to ensure case is not cracked and battery cap is in place.
• Inspect and replace leads if insulation is damaged, metal is exposed, or probes are cracked. Pay particular attention to the insulation surrounding the connectors.
• Do not use tester if it operates abnor­mally as protection maybe impaired.
#61-085 #61-086
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 1
• Do not use during electrical storms or in wet weather.
• Do not use around explosive gas, dust, or vapor.
• Do not apply more than the rated volt­age to the tester. Voltage is not to exceed 600V.
• Always operate this solenoid-type tester within the specified duty cycle on the front of the tester. Duty cycle ratio is:
• 1:15 ON:OFF time.
• Maximum ON time is 15 seconds.
• Do not use without batteries and cap properly installed.
• Remove test leads prior to removing battery cap.
Caution
To protect yourself, think "Safety First":
• Voltages exceeding 30VAC or 60VDC pose a shock hazard so use caution.
• Never ground yourself when taking electrical measurements.
• Use appropriate personal protective equipment such as safety glasses, face shields, insulating gloves, insulating boots, and/or insulating mats.
• Use the 3-Step Testing Method. Before each use:
• Perform a continuity test by touching
the probe tips together, an audible sound should be heard and the con­tinuity LED should light. This test verifies the functionality of the batter­ies and test leads (61-086 only).
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 2
• Verify tester operation by measuring a
known voltage. Apply tester to circuit under test. And, then test on the known live voltage again to ensure proper operation.
• Connect the black common lead to ground before applying the red test lead to voltage. Disconnect the red test lead from the voltage first.
• Always work with a partner.
• When using the probes, keep fingers as far behind the probe tips as possible.
Features:
• Vibration Mode w/indicator movement
• Audible and LED Indication of Voltage Levels (61-085 has LED indication only).
• Auto-Switching Voltage/Continuity Technology (61-086 only)
• Independent solenoid and electronic cir­cuitry design provides back-up voltage indication for added safety.
• Low Impedance Measuring Device
• Replaceable Test Leads
• Shielded probe tips
• Ultrasonically welded and o-ring sealed for added durability
Accessories:
• TL-82 Resistor-fused test leads
• C-90 Soft-sided carrying case
To Measure AC Voltage:
• Ensure that the plug for the test leads is fully seated into the banana jacks.
• Connect the tester in parallel with the
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 3
load or circuit.
• The tester indicates both the voltage type and the voltage level. (See Tester Operation table)
To Measure DC Voltage:
• Ensure that the plug for the test leads is fully seated into the banana jacks.
• Connect the tester in parallel with the load or circuit.
• The tester indicates the voltage type, polarity, and the voltage level. (See Tester Operation table)
To Test for Continuity: (61-086 only)
• Ensure that the plug for the test leads is fully seated into the banana jacks.
• De-Energize circuit before performing continuity test. Note, if voltage is pres­ent in the circuit, the tester automatical­ly switches to voltage indication mode.
• Test for continuity by connecting the tester to the circuit.
• If circuit has 500kΩ or less resistance, an audible indication is heard and the Continuity LED lights. (See Tester Operation table)
• Reversing prods on the circuit under test verifies continuity versus low volt­age +DC.
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 4
61-086
Neon Bulb
Indicator
Left LED Right LED
Neon Bulb Left LED Right LED Indicator
Continuity Off On Off No movement.
Open Circuit No Voltage Off Off Off No movement.
6-65 AC Off On On No movement.
6-90 DC Off On if black On if red No movement.
prod is prod is on negative, on negative, off if it is on off if prod is positive. reversed.
65-110 AC On On On Little or no
movement.
90-110 DC On On if black On if red Little or no
prod is prod is movement. on negative, on negative off if it is on off if prod is positive. reversed.
110-600 AC On On On
Scale indicates relative magnitude.
110-600 DC On On if black On if red
Scale indicates
prod is prod is
relative voltage. on negative, on negative, off if it is on off if prod is positive. reversed.
Tester Operation Table
61-086 only
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 5
Applications:
• Locating Blown Fuses
With power off: Place tester across the sus­pected fuse to perform continuity check. If continuity LED turns “On,” the fuse is good. If the continuity LED does not turn “On,” the fuse is defective. (61-086 only)
With power on: Place tester across the “source” side of one fuse and the load side of an adjoining fuse. If no voltage is indicated, the fuse next to the load side prod is blown. If voltage is indi­cated, the fuse next to the load side prod is OK. Repeat the same test with the prods on the opposite side of the same two fuses to check the other fuse.
On a three phase circuit, repeat the same test as above. An indication of no voltage or lower than normal line volt­age indicates the blown fuse.
• Finding Grounded Side of Line (neutral)
Hold one test prod to the ground and touch the other test prod to each of the line terminals until one is found that does not give a voltage indication. The continuity LED should be “On.” This is the grounded side of the line.
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 6
• Testing for “Grounded” Side of Motor or Appliance
With power to motor or appliance “Off,” touch one test prod to the frame and the other prod to each of the terminal connec­tions. The terminal which turns the continuity LED “On” is the grounded side. With power to motor or appliance “On,” place tester across the frame and to each of the terminal connections. The terminal which does not give a volt­age indication, but does give a continu­ity indication, is the grounded side.
• Testing for 25 to 60 Cycle Frequency
Place tester between each side of AC line. A low frequency hum and slow vibrations indicate 25 cycle current. 60 cycle current is indicated by a higher frequency hum and more rapid vibra­tions.
• Checking Continuity of Cords, Motors, Appliances, etc. (61-086 only)
Remove power source and place tester across circuit to be tested. Continuity LED turns “On” and an audible beep is heard if resistance is less than 500K ohms.
• Locating Excessive Leakage to Ground
Place tester across the neutral terminal
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 7
and the ground, only the continuity light should turn “On,” indicating neutral and ground are connected. If the “ – DC” light also turns “On,” there is 6VAC or greater between neutral and ground indicating a high resistance leakage to ground. High resistance leakage is qualified since a low resistance (high current) leak to ground would open a circuit breaker or blow a fuse.
Battery Replacement: (61-086 only)
• Replace batteries when touching the leads together no longer lights the con­tinuity LED or produces an audible sound.
• Remove test leads from tester.
• Loosen the encapsulated screw from the bottom of the case.
• Remove battery cap.
• Replace the batteries with (4) new 1.5V button-type batteries (IDEAL# 61-201, IEC #LR44, or NEOA# 1166A).
• Replace battery cap and re-tighten the encapsulated screw.
Test Lead Replacement:
• Replace leads only with IDEAL test leads below.
• # TL-80 Standard Test Leads with
Shielded Probe Tips
• # TL-82 Resistor-fused Test Leads
with Shielded Probe Tips. Each probe tip contains a special, current­limiting resistor which acts like a fuse to limit short-circuit current and pre-
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 8
vents dangerous arcing during a shorted condition. The resistors are rated to 140Ω +/- 10%. Fusing cur­rent is 1A at 125V. Fusing time is 30-60ms at 125V, without causing dangerous conditions during opening of the fuse element. Leads need to be replaced when fuse has opened.
Note that TL-80 and TL-82 test leads can only be specifically used with the 61-085 and 61-086 testers.
Maintenance:
• Clean the case with a damp cloth and mild detergent. Do not use abrasives or solvents.
Service, and Replacement Parts:
For replacement parts or to inquire about service information contact
IDEAL INDUSTRIES, INC.
Attn: Repair Dept. 1000 Park Avenue Sycamore, IL 60178 Technical Support: 1-877-901-2005 or visit our website www.testersandmeters.com.
Specifications:
VAC Ranges: 120V, 240V, 480V, 600V AC. VAC Accuracy: Relative indication only
VDC Ranges: 120V, 240V, 600V DC VDC Accuracy: Relative indication only
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 9
Continuity (61-086 only): Continuous LED and audible indication at less than 500kΩ resistance. Response time of 100ms.
Operating Frequency: 25-60 Hz Input Impedance: Low Operating Environment: 32° F to 122° F (<70% humidity) Storage Temp.: -4° F to 140° F (<80% humidity) Altitude: 2000m Indoor Use Battery: (4) 1.5V (IDEAL# 61-201, IEC #LR44, or NEOA# 1166A).
Battery Life: 200 hours typical. Accessories included: Test Leads, (4)
1.5V "LR44" batteries, operating instructions
Dimensions: 6.0" (H), 2.3" (W), 1.2" (D) Weight: 8.0 oz Safety: EN61010, CAT III 600V, CE, UL,
(3111) cUL
n Double Insulation
Warranty Statement:
This tester is warranted to the original pur­chaser against defects in material and work­manship for five years after purchase. During this warranty period, IDEAL INDUS­TRIES, INC. will, at it’s option, replace or repair the defective unit, subject to verifica­tion of the defect or malfunction.
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 10
This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unrea­sonable use of the instrument.
Any implied warranties arising out of the sale of an IDEAL product, including but not limited to implied warranties of mer­chantability and fitness for a particular pur­pose, are limited to the above. The manu­facturer shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or eco­nomic loss, or for any claim or claims for such damage, expenses or economic loss. State laws vary, so the above limitations or exclusions mat not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary form state to state.
Cat III – 600V
ND 3401-1 61-085/086 Vol-Con In 1/9/07 4:29 PM Page 11