E-Z Check®Plus G.F.C.I. Tester
• Super-bright indicator lights
• Impact-resistant plastic construction
• Convenient “push-pull” shape
Tests For
• Open ground • Test for G.F.C.I.
• Hot on neutral and hot open • Open neutral*
• Hot and ground reversed • Open hot
• Reverse polarity
* May show as reverse polarity on some G.F.C.I. protected outlets.
Cautions
• Do not use tester in cardiac care areas.
• All corrective work must be made by a qualified electrician.
• When testing G.F.C.I. installed in two-wire systems (no ground wire available),
the tester may give a false indication that the G.F.C.I. is not functioning properly.
If this occurs, recheck the operation of the G.F.C.I. using the test and reset
buttons. The G.F.C.I. button test function will demonstrate proper operation.
Instructions for G.F.C.I.
1. Always test on a known live circuit before use to assure the unit is in operating
condition. Plug E-Z Check
®
Plus tester into receptacle. The combination of
bright lights indicates wiring sequence.
2. If the receptacle under test is G.F.C.I. protected, you have automatically tested
for nuisance tripping. (If insertion of the tester tripped the G.F.C.I., either there is
additional leakage to ground or the G.F.C.I. trip level is set too low.)
3. Consult the G.F.C.I. manufacturer’s instructions to determine that the G.F.C.I. is
installed in accordance with the manufacturer’s specifications.
4. Check for correct wiring of receptacle and all remotely connected receptacles on
the branch circuit.
5. Operate the test button on the G.F.C.I. installed in the circuit. The G.F.C.I. must
trip. If it does not — do not use the circuit — consult a qualified electrician. If
the G.F.C.I. does trip, reset the G.F.C.I. Then, insert the E-Z Check
®
Plus Circuit
Tester into the receptacle to be tested.
6. With the tester plugged into a G.F.C.I. receptacle and both outside lights lit, simply push the test button on top of the tester. The right light bulb should become
dark for an instant, the G.F.C.I. should trip and then both lights should go out
indicating a properly functioning G.F.C.I. If the right light becomes dark, it indicates a properly functioning tester. But if both lights do not go out and the
G.F.C.I. does not trip, it suggests a: (a.) wiring problem with a totally operable
G.F.C.I. or (b.) proper wiring with a faulty G.F.C.I. Consult with a qualified electrician to check the condition of the wiring and G.F.C.I.
Intermittent use only.
Warranty limited solely to repair or replacement; no warranty of merchantability, fitness for a particular purpose or consequential damages.
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A.
Ajax, Ontario, L1S 2E1, Canada
Warrington, Cheshire WA5 5TN,
England
800-304-3578
Customer Assistance
www.idealindustries.com
ND 252-2 Made in U.S.A.