Honeywell YTHX9421 User Manual

System Installation Guide
2-wire Prestige® IAQ and RF EIM
With wireless accessories
Control for up to 4 Heat/2 Cool heat pump systems or up to 3 Heat/2 Cool conventional systems.
Installation guide for:
• THX9000 Prestige IAQ thermostat
• Equipment Interface Module
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical shock or equipment damage.
MERCURY NOTICE: If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
Must be installed by a trained, experienced technician. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502
® U.S. Registered Trademark. Copyright © 2011 Honeywell International Inc. All rights reserved.
• Portable Comfort Control
• Wireless Outdoor Air Sensor
69-2445EFS-03
2-wire Prestige® IAQ and RF EIM
Mount and wire thermostat
1
Pull wiring through hole in wall plate and install as shown below. Strip 1/4" insulation and connect wires to screw terminals as shown.
Wall anchor
Drywall: 3/16" hole Plaster: 7/32" hole
Mounting
screw
MCR29241
MCR32386
MCR32387
Connect the two wires from the thermostat to the Equipment Interface Module R and C terminals or to a separate 24 volt transformer (not pro­vided).
Wiring must comply with local electrical codes.
Mount and wire Equipment Interface Module
2
Use screws & anchors (not included) as appropriate for mounting surface. Mount Equipment Interface Module on wall near HVAC equipment, or on the equipment itself.
Do not install inside HVAC equipment.
Strip 1/4” insulation, then insert wires as shown.
R C
W
O/B
W2
AUX1
W3
AUX2
Y Y2 G L
69-2445EFS—03
MCR32389
MCR32388
2
2-wire Prestige® IAQ and RF EIM
Wiring guide
Typical hookup of conventional system with up to three-stage heat and two-stage cool with single transformer.
FURNACE
TO THERMOSTAT
TRANSFORMER
R
24
C
VAC
120
VAC
STATUS
LEDS
POWER
HEAT
COOL
FAN
U1 U2 U3
SENSORS
CONV
W W2 W3
G
Y
Y2
1
3
RETURN AIR SENSOR
2
DISHARGE AIR SENSOR
INDOOR SENSOR
OUTDOOR SENSOR
RETURN AIR SENSOR
DISHARGE AIR SENSOR
INDOOR SENSOR
2
OUTDOOR SENSOR
STAGE 1 HEAT
STAGE 2 HEAT
STAGE 3 HEAT
FAN
COMPRESSOR
(STAGE 1)
COMPRESSOR
(STAGE 2)
JUMPERS
1
SEE WIRING GUIDE—EQUIPMENT SECTION FOR IAQ EQUIPMENT WIRING.
WIRE A MAXIMUM OF TWO SENSORS USING THE S1, S1, S2, S2
2
TERMINALS.
REMOVE JUMPER(S) FOR SEPARATE TRANSFORMERS.
3
3
69-2445EFS—03
M32390
2-wire Prestige® IAQ and RF EIM
Wiring guide
Typical hookup of heat pump system with up to four-stage heat and two-stage cool with single transformer.
TO THERMOSTAT
O/B
AUX1 AUX2
Y
Y2
G
L
CHANGEOVER VALVE
BACKUP HEAT
STAGE 1
BACKUP HEAT
STAGE 2
COMPRESSOR
(STAGE 1)
COMPRESSOR
(STAGE 2)
FAN RELAY
COMPRESSOR
MONITOR OR
ZONE PANEL
STATUS
LEDS
POWER
HEAT
COOL
FAN
U1 U2 U3
HEAT PUMP
O/B AUX1 AUX2
3
1
69-2445EFS—03
JUMPERS
AIR HANDLER
TRANSFORMER
R
24
C
VAC
RETURN AIR SENSOR
2
DISHARGE AIR SENSOR
SENSORS
1
SEE WIRING GUIDE—EQUIPMENT SECTION FOR IAQ EQUIPMENT WIRING.
WIRE AT MAXIMUM OF TWO SENSORS USING THE S1, S1, S2, S2
2
TERMINALS.
L TERMINAL SENDS CONTINUOUS OUTPUT WHEN THERMOSTAT IS SET TO
3
EM. HEAT MODE.
OUTDOOR SENSOR
RETURN AIR SENSOR
DISHARGE AIR SENSOR
2
OUTDOOR SENSOR
120
VAC
INDOOR SENSOR
INDOOR SENSOR
4
M32391
2-wire Prestige® IAQ and RF EIM
VA
24
VA
Wiring guide—equipment
Any combination of Universal relays (U1, U2, U3) can be used.
With power supply Without power supply
Typical hookup of non-powered humidifier.Typical hookup of powered humidifier.
U3
U3 U2
U2 U1
POWERED
HUMIDIFIER
U1
RH RC R
24
C
C
VAC
24
VAC
24
120
VAC
120
VAC
Typical hookup of powered ventilation.
U3
U3 U2
U2 U1
POWERED
VENTILATOR
U1
RH RC R
24
C
C
VAC
24
VAC
24
VAC
120
120 VAC
Typical hookup of powered dehumidifier (whole house dehumidifier).
U3
U3 U2
U2
24
VAC
U1
U1
RH RC R C
POWERED
DEHUMIDIFIER
VAC
24
VAC
24
120
VAC
VAC
120
M32393
M32396
M32398
U3
U3 U2
U2
NON-POWERED
U1
HUMIDIFIER
VAC
U1
RH RC R C
24
VAC
120
VAC
FIELD INSTALLED JUMPER BETWEEN R AND U1
M32394
Typical hookup of non-powered ventilation.
U3
U3 U2
U2
NON-POWERED
U1
VENTILATOR
24 VAC
U1
RH RC R
24
VAC
C
120 VAC
FIELD INSTALLED JUMPER BETWEEN R AND U1
M32397
Typical hookup of variable speed blower for dehumidification in low speed.
U3
1
U3
OR
24 VAC
U2
U2 U1
U1
RH RC R C
2
DEHUMIDIFICATION
WITH LOW SPEED FAN
120
24
VAC
VAC
FIELD INSTALLED JUMPER BETWEEN R AND U1
M32392
ANY COMBINATION OF UNIVERSAL RELAYS (U1, U2, U3) CAN BE USED. THEY ARE SET IN THE THERMOSTAT
1
INSTALLER SETUP.
WIRE THE EIM’S UNIVERSAL RELAY TO THE LOW SPEED FAN FOR DEHUMIDIFICATION CONTROL AT THE
2
EQUIPMENT. THE EIM’S RELAY CAN BE SET TO NORMALLY OPEN OR NORMALLY CLOSED IN THE THERMOSTAT INSTALLER SEUP.
= NORMALLY OPEN, DRY CONTACTS
= NORMALLY CLOSED, DRY CONTACTS
KEY
5
M32409
69-2445EFS—03
2-wire Prestige® IAQ and RF EIM
CONNECT
Link all devices to wireless network
3
The following instructions detail the connection process of the Prestige IAQ thermostat, Equipment Interface Module (EIM), and wireless RedLINK™ accessories.
NOTE: If the system is zoned using a TrueZONE™ panel with RedLINK™, the thermostat and accessories are connected to the Wireless Adapter. For more information, follow the connection process in the TrueZONE™ instructions.
Connection of Prestige IAQ Thermostat to the Equipment Interface Module
1. Connect 24 V power to the Prestige IAQ and EIM.
2. Select language and press NEXT.
Next
MCR32400
3. If zoned, select zone number and press NEXT; If not zoned, select Not Zoned and press NEXT.
CONNECTED
CONNECT
69-2445EFS—03
Next
MCR32401
4. Name thermostat and press NEXT.
Next
MCR32402
LED
S2
CONNECT
S2 S1
BUTTON
S1
5. Press and release the CONNECT button at the Equipment Interface Module (EIM). The CONNECT LED on EIM will flash green.
M32399
6
2-wire Prestige® IAQ and RF EIM
6. Press NEXT to connect the Prestige IAQ thermostat to the Equipment Interface Module (EIM).
Next
MCR32403
7. Press Done. Thermostat will advance to the Home Screen.
Done
MCR32404
Install batteries in wireless accessories
If no wireless accessories are being connected, skip to step 13.
Outdoor air sensor (optional; steps 8–9)
Install 2 fresh AA lithium batteries
M28800
Portable Comfort Control (optional; steps 10–12)
Install 3 fresh AA batteries
M29863
Connect Wireless Accessories: Outdoor Sensor and Portable Comfort Control
8. Press and release the CONNECT button on the Wireless Outdoor Sensor.
9. Check thermostat to verify that the outdoor sensor is working. After about 15 seconds, the thermostat should display outdoor temperature and humidity.
MCR28847A
7
69-2445EFS—03
2-wire Prestige® IAQ and RF EIM
M28846
CONNECT
CONNECT
CONNECT
WIRELESS SETUP
10. Press the CONNECT button on the Portable Comfort Control.
11. When the screen displays "Connected," press DONE.
Press to link to another thermostat
Press to save and exit
NOYES
CONNECT MORE?
CONNECTED
CONNECT
Install outdoor sensor
4
S2 S2 S1 S1
M28481
M28482
LED
BUTTON
M32399
12. Press NO at the next screen to save and exit. (Or press YES and repeat steps 3-5 to link another thermostat.)
The linking procedure at the Portable Comfort Control may time out if there is no keypress within 30 minutes. To begin again, press and hold the blank space (or arrow, if present) in the lower right corner of the screen until the display changes (about 3 seconds).
13. Press and release the CONNECT button at the EIM to exit (CONNECT LED on Equipment Interface Module [EIM] will be steady green). NOTE: The connection will time out automatically in 15 minutes.
69-2445EFS—03
M28491
1. Mount the sensor on a vertical exterior wall, at least 6 inches below any overhang. Choose a location protected from direct sunlight.
2. Place sensor securely in bracket, facing away from wall.
M28849A
8
Customize thermostat (installer options)
MCR28998
5
2-wire Prestige® IAQ and RF EIM
Installer Options
MENU
HELP
HELP
Note: Press HELP for more information on these and other options.
MENU
MCR29794
MCR28799
Press MENU.
Press t to scroll down, then press INSTALLER OPTIONS. Enter security code when prompted.
Security code is the thermostat date code (printed on back of thermostat). Or press MENU > EQUIPMENT STATUS to find code.
Press CREATE SETUP to set all system settings one by one.
Press VIEW/EDIT to select a specific function and make quick changes. (See complete list of system settings on pages 10-11.)
Press INSTALLER TEST to run system tests. You should always test the sys­tem after making changes to settings.
9
69-2445EFS—03
2-wire Prestige® IAQ and RF EIM
Installer setup tables
Setup functions (factory default setting listed, other options available)
100 Language English 110 Zone Number Not Zoned 112 Device name Thermostat 130 Date Month, Date, Year 160 Schedule options Programmable 172 System selection Conventional 173 Heat Pump Type Air To Air 174 Stages 1 Heat/1 Cool 175 Series 20 Control No 180 Fan operation System (gas/oil/heat) 190 Reversing valve O/B on Cool 200 Backup heat Electric 210 External fossil fuel Yes 220 Compressor cycle rate(s) 3 240 Heat stage cycle rate(s) 5 300 Changeover Manual 310 Deadband 2° F 320 Temperature display Fahrenheit 330 Daylight savings time Auto change: On 1350 Configurable S1 Sensor Input None 1355 Configurable S2 Sensor Input None 342 Outdoor temperature sensor? No 346 Upstage timer Off 347 Droop Temperature 2 349 Backup Heat Control Comfort 350 Compressor lockout (balance point) Off 360 Auxiliary lockout Off 365 Discharge Air Temperature Sensor No 1400 Configurable U1 Relay None 1405 Configurable U2 Relay None 1410 Configurable U3 Relay None 371 Humidification equipment None 372 Indoor humidity control Off 374 Humidifier fan action Humidify only with fan 379 Dehumidification equipment None 1500 Low Speed Fan Position Normally Closed 383 Overcooling limit 3° F (1.5° C) 384 Dehumidification fan control Forces fan on 386 Whole house Dehumidification Lockout Off 390 Dehumidification away mode Off 391 Away mode fan operation Automatic 392 Away mode low temp. setting 76° F (24.5° C) 393 Away mode high temp. setting 85° F (29.5° C) 394 Away mode dehumidification 65% relative humidity 400 Ventilation Control Off 401 Number of Bedrooms/Size of home 2 (1000 sq. ft.) 403 Ventilation levels 160 cfm (50%) 405 Ventilation Fan Action Ventilation Forces Fan On 406 Ventilation in High Humidity On
69-2445EFS—03
10
2-wire Prestige® IAQ and RF EIM
Installer setup tables
Setup functions (factory default setting listed, other options available)
431 Ventilation Lockout Temperatures None 433 Ventilation Lockout High Outdoor Humidity Off; 75° dewpoint if On 450 A-Coil Low Temperature Cutoff None 500 Replacement reminders Off 502 Furnace filter runtime counter Count heat and cool 525 Installer Custom Reminders Add Customer Reminder 530 Adaptive Intelligent Recovery On 540 Number of schedule periods 4 580 Minimum compressor off time 5 minutes 600 Temperature range stops 90° F (32° C); 60° F (15.5° C) 640 Clock format 12-hour 650 Extended fan on time(s) Off 670 Keypad lock Unlocked 680 Temp. control (heat) Standard 690 Temp. control (cool) Standard 695 Finish on High Heat Stage No 696 Finish on High Cool Stage No 700 Indoor display offsets No offset
Customer contact information (optional, but recommended)
1100 Dealer name Your company name 1150 Dealer phone number Your telephone contact 1200 Dealer email address Your email address 1250 Dealer website Your web site 1300 Dealer Message Edit
Note: All installer options, including Dealer name, contact information and message can be set up as a file and downloaded via the USB port on the thermostat.
Restore Factory Defaults
Under the Menu, Installer Options and Advanced Options is a button to “restore factory defaults.”
If pressed, it will reset the program schedule and most installer setup options (exceptions: 1350, 1355, 1400, 1405, 1410, 1500 and 450) and disconnect the thermostat from the Equipment Interface Module.
11
69-2445EFS—03
2-wire Prestige® IAQ and RF EIM
Accessories
Wireless Outdoor Sensor – Displays outdoor temperature and outdoor humidity on other RedLINK devices. Use for temperature lockouts in heat pump applications, condensation protection with humidification control and temperature and/or dewpoint lockouts for ventilation control.
Portable Comfort Control – Senses temperature; use to change thermo­stat settings.
Discharge Air Temperature Sensor – Use for desert humidification con­trol to help prevent condensation in duct system. Also used to control coil freeze protection: it will cut off condenser and keep the blower fan running to prevent freezing the coil. If used with a Return Air Temperature Sensor the Delta T can be viewed in thermostat’s installer test.
Return Air Temperature Sensor – Use for backup control. If power is lost at thermostat, the Equipment Interface Module sets temperature to 62° F (16.7° C) in Heat and 82° F (27.8° C) in Cool until power is restored to the thermostat. If used with a Discharge Air Temperature Sensor the Delta T can be viewed in thermostat’s installer test.
Wired Indoor Temperature Sensor – Use to sense and control tempera­ture at remote location(s); can be averaged between the thermostat and sensor location(s). See sensor instructions for installation details.
Wired Outdoor Temperature Sensor – Sends outdoor temperature for display on thermostat. Use for temperature lockouts in heat pump appli­cations, condensation protection with humidification control and tempera­ture lockouts for ventilation systems.
69-2445EFS—03
12
2-wire Prestige® IAQ and RF EIM
Replacing system components
Equipment Interface Module
After installing a new Equipment Interface Module, you must re-link all devices to the new EIM, as described below:
1. Install and wire new Equipment Interface Module.
2. Disconnect thermostat from the old Equipment Interface Module.
Installer Options
Wireless Device
MENU
HELP
Manager
Remove Device
MENU
MCR28801
MCR28998
MCR28802
Press MENU.
Press t to scroll down, then press INSTALLER OPTIONS. Enter security code when prompted.
Security code is the thermostat date code (printed on back of wallplate). Or press MENU > EQUIPMENT STATUS to find code.
Press t to scroll down, then press WIRELESS DEVICE MANAGER.
Press REMOVE DEVICE.
Remove This
Thermostat
MCR32405
MCR32406
Press REMOVE THIS THERMOSTAT.
13
69-2445EFS—03
2-wire Prestige® IAQ and RF EIM
CONNECT
Replacing system components
Equipment Interface Module (Continued)
Press YES.
Yes
MCR32407
M32408
3. Link thermostat to the new Equipment Interface Module (see pages 6–7)
Thermostat
After installing a new thermostat, you must link the new thermostat to the Equipment Interface Module, as described below.
1. Install and wire new thermostat (see pages 3-7).
2. Link thermostat to Equipment Interface Module (see pages 6–7).
Portable Comfort Control
1. Press and hold the blank space (or arrow if present) in the lower right corner of the screen until the display changes (see page 8).
2. Press REMOVE, then yes to disconnect from old Equipment Interface Module.
3. Follow the procedure on pages 7–8 to link to new Equipment Interface Module.
Outdoor air sensor
1. Press the connect button to link to the new Equipment Interface Module (see page 7).
How to disconnect all devices from the wireless network at the same time
Press and hold the Connect button at the Equipment Interface Module until the LED flashes amber (about 10 seconds).
NOTE: To get the Portable Comfort Control back to the connect screen, follow the instructions
M32399
below.
CONNECTED
CONNECT
LED
S2
CONNECT
S2 S1
BUTTON
S1
M28846
69-2445EFS—03
Portable Comfort Control
Press and hold the blank space (or arrow, if present) in the lower right corner of the screen until the display changes (about 3 seconds).
14
2-wire Prestige® IAQ and RF EIM
Specifications & replacement parts
Operating Ambient Temperature
Thermostat: 32 to 120° F (0 to 48.9° C) Portable Comfort Control: 32 to 120° F (0 to 48.9° C) Wireless Outdoor Air Sensor: -40 to 140° F (-40 to 60° C) Equipment Interface Module: -40 to 165° F (-40 to 73.9° C) Return Air Sensor: 0 to 200° F (-17.8 to 93.3° C) Discharge Air Sensor: 0 to 200° F (-17.8 to 93.3° C)
Operating Relative Humidity
Thermostat: 5% to 90% (non-condensing) Portable Comfort Control: 5% to 90% (non-condensing) Wireless Outdoor Air Sensor: 0% to 100% (condensing) Equipment Interface Module: 5% to 95% (non-condensing)
Physical Dimensions (height, width, depth)
Thermostat: 3-9/16 x 5-13/16 x 1-1/2 inches (91 x 147 x 38 mm) Wireless Outdoor Air Sensor: 5 x 3-1/2 x 1-11/16 inches (127 x 89 x 43 mm) Equipment Interface Module: 9-5/16 x 4-13/16 x 1-19/32 inches (91 x 147 x 38 mm)
Electrical Ratings
Terminal Voltage (50/60 Hz) Max. Current Rating
W - O/B 18 to 30 VAC 1.00A Y (cooling) 18 to 30 VAC 1.00A G (fan) 18 to 30 VAC 0.60A W2 - Aux 1 (heating) 18 to 30 VAC 0.60A Y2 (cooling) 18 to 30 VAC 0.60A W3 - Aux 2 18 to 30 VAC 1.00A L (Output) 18 to 30 VAC 0.60A U1 30 VAC max. 0.50A U1 30 VAC max. 0.50A U2 30 VAC max. 0.50A U2 30 VAC max. 0.50A U3 30 VAC max. 0.50A U3 30 VAC max. 0.50A S1 30 VAC max. 0.50A S1 30 VAC max. 0.50A S2 30 VAC max. 0.50A S2 30 VAC max. 0.50A
Accessories & Replacement Parts
Item Part Number
Portable Comfort Control REM5000R1001 Wireless Outdoor Air Sensor C7089R1013 Cover Plate (covers marks left by old thermostats) 50028399-001 Wired Indoor Sensor C7089U1005 Discharge Air Sensor C7735A1000 Return Air Sensor C7735A1000 Wired Outdoor Temperature Sensor C7089U1006
15
69-2445EFS—03
Loading...
+ 33 hidden pages