Honeywell XS100T, XH100, XS100 User Manual

Thank you for purchasing this Honeywell smoke or heat alarm. The alarm is suitable for use in domestic premises (including static
holiday homes) and leisure accommodation vehicles (LAVs) This manual contains important safety information about the
installation and operation of the alarm. Please read the manual carefully and keep it in a safe place for future reference. Please also explain the alarm operation to all other occupants of the building.
You are advised to have a re evacuation plan, which you should
test every month. Everyone in the building should be familiar with the alarm signals, so that they react to them without delay.
Warnings
To avoid dust and debris contamination, the smoke or heat alarm should be removed from the mounting for the duration of any building work involving dust or debris. If this is not possible then the alarm vents must be fully covered with a plastic bag or tape whilst the work is in progress.
While covered, the alarm will not detect fires or smoke, so it is vital the covering is removed when work is completed each day, and replaced the following day if necessary.
The alarm is permanently sealed for safety, so do not attempt to open it.
If you are in any doubt regarding the cause of an alarm it should be assumed that the alarm is due to an actual fire and the dwelling should be evacuated.
1
XH100 XS100 XS100T
Honeywell offers three models of its battery powered smoke or heat alarms:
XH100 is a heat alarm approved to BS5446-2:2003.
XS100 is an optical smoke alarm approved to EN14604:2005 and
uses an optical detection technique only.
XS100T is a optical-thermal smoke alarm approved to
EN14604:2005, which uses dual detection techniques for quicker
response times, wider range of re types and fewer false alarms.
All have a sealed-in battery with a 10-year lifetime and warranty. They have clear visible status indications for Power (green), Fault (yellow) and three extra-large Alarm indicators (red).
In addition, all versions have an audible alarm and a TEST/HUSH button.
3. Smoke and Heat Alarm Operation
Clean front and user interface
Separate, labelled indicators for each power state
Power
Fault (e.g End of life)
Big, easy to press button
Fault Hush
Alarm Hush
Test with reduced
sound level
Indicators are only visible when used
Clear and big alarm indicators
Visible from all sides
Rounded shape gives
Power Fault Alarm
All alarms have three (four, if equipped with wireless module) status indicators and a TEST/HUSH button.
The green POWER light indicates that the unit is activated and working normally.
The red ALARM light indicates that a re has been detected. The yellow
FAULT light indicates that the unit is not working
properly. The TEST/HUSH button is used to test the unit, or to mute an
alarm or fault signal.
Normal operation
The green POWER light will ash once per minute, to indicate that your alarm is working*.
5 6 7 8
*Note: There is an option to disable the ashing power light during
initial setup e.g. for installation in bedrooms. Please see the installation instructions for further details.
Alarm
If a re is detected, the red ALARM indicators will ash and
the loud audible alarm will sound continuously. You should immediately evacuate the premises and then contact the emergency services. (Do not pause to collect property or to ring for help.)
However, if you are certain that it is a false alarm caused by steam, cooking fumes or burnt toast; you can press the
TEST/HUSH button to silence the alarm for 5 minutes while the
air clears.
Caution: If you cannot reach the alarm from oor level, use a
broom handle (or similar) to press the test button. Please do not climb on anything to help you reach.
Note: The Alarm
HUSH
after which the alarm will return to full sensitivity. The Alarm function can be operated repeatedly if required.
Faults
If the unit is in FAULT the YELLOW light will ash every minute with one short chirp. (The only exception is a wireless module fault, which is signalled with 3 chirps. In this case, refer to the wireless module manual for further details).
3. Smoke and Heat Alarm Operation continued
Status Lights and Sound Meaning
Alarm
NORMAL
OPERATION*
Flashes once every minute. *NB light can be switched off (see installation section)
(Red)
Power
(Green)
Fault
(Yellow)
Sound
No smoke and/or heat present
***
ALARM
3 chirps and ashes continuously for 60 minutes. Pattern is then repeated once every 30 seconds.
REMOTE SMOKE
OR HEAT ALARM or
REMOTE CARBON
MONOXIDE
ALARM**
REMOTE FAULT**
Smoke or heat ALARM: 3 chirps continuously / Carbon Monoxide ALARM: 4 chirps continuously.
Networked units – 4 chirps and 4 ashes every 4 hours. The fault will be broadcasted on the network
Fire detected by an interconnected smoke or heat alarm or Carbon monoxide
leak detected by an interconnected Carbon Monoxide alarm
A wireless connected unit is in fault
2 3
function will silence the alarm for 5 minutes
Normal operation
Smoke and/or heat detected
2. Description1. Welcome
HUSH
Each smoke or heat alarm has a dot on its side indicating which type of alarm it is.
Heat alarm
Optical
smoke alarm
Optical-thermal
smoke alarm
• • • • •
All Honeywell X-Series alarms (including optional X-Series Carbon
Monoxide alarms) can be wirelessly interconnected using an
optional plug-in module. This means that if one X-Series Alarm
triggers an alarm, all interconnected units will give a loud audible alarm (85dB) as well. This is especially useful, when living in a large or multi-story dwelling. The maximum number of devices that can be added to a network is 32. Some wireless module information is included in this manual for completeness. If equipped, the module will use the indicator for Wireless (blue) on
the smoke or heat alarms. The XH100 gives a re warning when
the temperature at the alarm reaches 58°C.
If there are other alarms connected to it in a network, they will
ash and chirp every four hours to show that an alarm somewhere
in the network has a fault, and that it needs to be investigated.
When an interconnected alarm is in fault or alarm, all the interconnected alarms will chirp. The alarm that is in fault or
has detected a threat will chirp and ash. Only the alarm that
is in fault or detected the threat can be silenced, silencing the interconnected alarms.
Once the alarm in the fault state is located, counting the number of chirps and ashes will establish whether it is a wireless module
fault or a smoke alarm fault. The chirps can be silenced for 24 hours by pressing the
TEST/HUSH button until the yellow LED blinks. Pressing the button
again will restore the chirps. The 24 hour period can be restarted by pressing the TEST/HUSH button twice. When a remote fault occurs, press the TEST/HUSH button on the alarm that is in the fault state as that will hush the other alarms in the network.
You must investigate and clear all faults without delay. When you
nd the faulty alarm:
• Check the ‘Replace by...’ date, and replace the alarm if it has expired.
• Check the dates on all of the other alarm modules if one module has passed its ‘Replace by...’ date.
5. Testing your alarm
Automatic self-test
Your smoke or heat alarm has a self-test function, which is performed automatically every 10 seconds.
Monthly Test
The smoke or heat alarm should be tested monthly to check that all visual and audible signals are working.
Press the TEST/HUSH button for 1 second to activate a full test cycle showing all lights/messages (green, yellow, red) and sound with the audible output at a reduced level
Hold the TEST/HUSH button for 10 seconds or more if you want to test the full 85dB sound level.
Test/Measuring mode overview
Press the button for
Unit mode Green Flash + chirp
1 s 2 s 3 s 4 s 5 s 6s 7s 8s 9s 10s 11s 12s 13s 14s 15s 16s 17s 18+s
Yellow Flash + chirp
Red Flash + chirp
Reduced volume alarm pattern Pause High volume alarm pattern Pause Remote Test* (see
Done even if button released Will go back to Normal mode as soon as button released Button may be
11 12
16
0333
DOP-RSA002
DOP-RSA003
EN 14604:2005/AC:2008
KM 634563
BS EN 14604:2005/AC:2008
KM 630857
BS 5446-2:2003
The CE mark afxed to the XS100 and XS100T conrms their
compliance with the European Directives which apply to the products and, in particular compliance with the harmonised
specications of standard EN 14604 relating to Construction
Products Regulation 305/2011.
The BSi Kitemark is a product or service certication mark that
shows it has been tested independently and audited to ensure it meets the appropriate standards of quality and safety.
4
Note: The fault signal could be caused by a low battery, or an electronics failure, or by dust entering the unit and obstructing the optical sensor.
A replace by date is also printed on the side of the unit to facilitate an advance replacement before the end-of-life signal is given. This date includes a 6 months shelf life, i.e. this is the latest date the unit should be replaced.
This package contains:
• An XS 100 optical smoke alarm which uses the light scattering principle
or
• An XS100T optical-heat alarm which uses the light
scattering principle in combination with a heat sensor or
• An XH100 Heat Alarm (certied by BSi only)
The alarm includes a non-servicable battery giving a
10 year life
Screws and wall plugs for mounting the alarm
Installation and maintenance instructions
Warning
If you cannot reach the alarm from oor level, use a broom
handle (or similar) to press the test button. Please do not climb on anything to help you reach.
Monthly Test with Wireless Function
To test your wireless alarm communication, press the test/hush
button on one alarm and keep it pressed. Once the alarm has
completed its full volume alarm test, it enters a Remote Test state
comprising one red LED ash with a chirp every 6 seconds. This
is repeated by all interconnected alarms, enabling each connected alarm to be checked at the same time. Pressing the test/hush button again returns the alarms back to the Normal Condition. Alternatively, the alarms will return to a normal condition after 10 minutes if the test/hush button isn’t pressed.
For more information, refer to the Wireless Module manual.
‘Monthly Test with Wireless Function
note below)
released
The wireless module is not working correctly. Refer to the wireless module
WIRELESS MODULE
FAULT
Unit with the fault – 3 chirps and 3 ashes every minute. This fault will not be broadcasted on the network
FAULT
1 chirp and 1 ash every minute
*unless the light is switched off during installation
**Only applicable when a wireless plug-in module is installed. Only silencing the alarm that is in fault or that detected the threat will silence the
interconnected alarms. See Warning in section 1 ***unless muted by pressing the TEST/HUSH button
***
***
The unit has reached its end of life and must be replaced
manual for further details
4. Precautions during use
The smoke or heat alarms do not require any maintenance other than to clean the outside case occasionally with a damp cloth and mild detergent.
For the smoke alarms (XS100T, XS100) ensure that the openings
on the side of the unit are not blocked with dust or dirt.
Dust and insect contamination can inhibit the operation of the smoke alarm. Use a vacuum cleaner to ensure that it is kept clean and free of dust and other contamination.
13 14
Do not paint the detector
Warning
Contact us
www.homesafety.honeywell.com www.honeywellanalytics.com www.honeywell.com
Honeywell Analytics Ltd.
4 Stinsford Road
Nufeld Industrial Estate
Poole, Dorset BH17 0RZ Tel: +44 (0)1202 645577 Fax: +44 (0)1202 665331
Acts for and on behalf of Life Safety Distribution GmbH, Javastrasse 2, 8604 Hegnau, Switzerland by its Authorised Representative Honeywell Inc.
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract. Please retain product documentation for the lifetime of the product.
I56-6200-002 MAN0982_Issue 1_01/15_EN © 2015 Honeywell Analytics
Operating and Installation Instructions
X-Series Battery Powered Smoke and Heat Alarms XS100T Optical-thermal smoke alarm XS100 Optical smoke alarm XH100 Heat alarm
6. Specication
7. Installation – Where to site the alarms
Reliability
Detection principle
XS100T: Optical with thermal assistance XS100: Optical XH100: Thermal
Approvals
XS100T, XS100: CE EN14604:2005/AC:2008
XH100:
BS5446-2:2003 BSi Kitemarked
Other
RoHS, REACh, R&TTE and EMC
compliances Self-test
Every 10 seconds
function Lifetime and
10 years
warranty
Operating environment
Temperature
Humidity
IP rating
Electrical and interconnection
Power supply Wireless
-10 °C to 55 °C
25-95% Relative Humidity (non-condensing)
IPX2D
17 18 19 20
Long-life lithium battery, 3V sealed-in A separately sold wireless plug-in module
XW100 is available
User interface
Visual indicator
Power: Green LED Alarm: 3 large red LEDs Fault: Yellow LED Wireless (if installed): Blue LED
Audible
>85 dB @ 3 m with distinct alarm sound (3 chirps)
Button
Test with reduced sound level Alarm hush Fault hush (24 hours)
Product
Size Weight
Ø 116 mm x 42 mm 185 g
Packaging
Type Dimension Scope of
supply
Carton Box with Euro-hole hanger 119 x 119 x 55 mm Smoke or heat alarm including sealed battery
Mounting kit: screws + plugs Instruction manual
21 22 23 24
10. Deactivating the power light ashes
Once fully mounted in the mounting plate, the green power light will ash every minute to show that the batteries are OK.
However, this might be annoying in bedrooms, so you have the option to stop this happening.
Warning
The optional power light de-activation can only be done during
the rst 30 seconds after pushing the alarm fully into the
mounting plate!
To deactivate the power light ashes, press the TEST/HUSH button ve times during the rst 30 seconds after pushing the alarm fully into its mounting. The power light will ash each time
the TEST/HUSH button is pressed. If deactivation is successful, the green POWER light will ash ve times in conjunction with short chirps
25 26 27 28
16. Troubleshooting and getting assistance
If you have carefully read all of these instructions and your alarm still fails to work, contact the nearest customer service centre
listed in the ‘Contact Us’ section. Our Customer Service advisors
may be able to resolve your problem quickly. Alternatively you can contact your local supplier.
To return the alarm for repair or replacement, please either use the original packaging or put it in a solid box or padded envelope with a letter describing the fault. To prevent inadvertent activation in transit, please switch off the alarm by removing it from the mounting plate.
Please notify your postal service that the package contains sealed batteries, as they might be restricted or forbidden postal items.
Proof of purchase must be provided if you want to claim repair under the warranty.
17. Recyclable packaging
The Green Dot logo signies that we are a
member of an organisation which collects and
recycles packaging. Our packaging is widely
recycled using local facilities.
This section provides general recommendations for the location of battery powered smoke or heat alarms in residential premises.
Please ensure that you also follow country specic regulations
and guidelines such as the British BS5839-6 or the German DIN14676. For example, certain countries require the installation of interconnected mains powered smoke or heat alarms.
The selection of the correct smoke or heat alarm model depends on the location it will protect.
Where to install Smoke Alarms (XS100T and XS100)
Ideally a smoke alarm should be installed in every room of a house, except kitchens, bathrooms and garages. As a minimum, one smoke alarm should be tted on every level of the house,
including stairways. While the XS100 smoke alarm is sufcient for this purpose, the XS100T optical-thermal re and smoke alarm is
specially recommended for use on exit routes and stairways as it has the potential to detect heat build-up in narrow or high areas where smoke may not reach the alarm.
Where to install Heat Alarms (XH100)
Heat alarms should be installed where smoke alarms can’t go, as
they are not affected by fumes, vapours or condensation. I.e. they can go in kitchens, bathrooms or garages.
7. Installation – Where to site the alarms continued
Using alarms in a network
Networked alarms can give advance warning of potential danger
from hidden res. They operate as shown below.
8. Installation – Where not to put the alarm
Where not to put the Smoke Alarms (XS100T and XS100)
A smoke alarm (XS100T, XS100) should not be installed in
bathrooms or kitchens where steam or cooking fumes could give rise to false alarms, or in a garage where it could react to exhaust fumes from your vehicle.
Where not to put the Heat Alarm (XH100)
Heat alarms should not be installed in locations where local
regulations require a Smoke alarm that satises EN14604. Check with your local re and rescue service if you are unsure.
11. First time switch on
First read the paragraph above and decide whether or not you
want the power light to ash.
To switch on the alarm:
1. Fit the alarm onto the ceiling mounting plate approximately 10 mm off centre
2. Press rmly against the mounting plate and slide the alarm
sideways until the locking tab clicks
3. The unit will automatically switch on
12. For Tamper Proof Ceiling Mounting
The alarm can be locked via use of a tamper-proof clip on the mounting plate. This should be removed before installation.
1. Break off the removable clip. Pliers can be used if required.
2. Fix the alarm in place on the ceiling.
3. The alarm can now only be removed (and turned off) by using a screwdriver
This product complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC.
Components or assemblies bearing this or similar symbols shall not be treated as household or municipal waste. Waste electrical products (end of life) shall be recovered and disposed of at specialist WEEE disposal facilities.
Please contact your local authority, your distributor,
or the manufacturer if you require more information
about recycling WEEE.
19. Disclaimer
Smoke and heat alarms are designed to alert you to the presence
of potentially dangerous smoke or re. They are not designed or intended to remedy a re or to locate or record a specic source of re. Honeywell shall therefore not be held liable to pay for any re
investigation or service call carried out or arranged in response to an alarm.
Dust and insect contamination is beyond our control, it is totally unpredictable and is considered normal wear and tear. For this reason, contamination is not covered by the warranty.
Preferred locations
The alarm should be tted on the ceiling, as close to the centre of
the room as possible but at least 50 cm (10 inches) from any wall or light tting. This is to avoid dead air in the corners of the room where smoke might not reach, or possible obstruction
by light ttings.
>70 cm
Optimal Satisfactory
The alarm should be tted where you can hear it when you are
asleep, for example in the hallway outside your bedrooms. This will also protect you from smoke rising up the stairs from a lower level.
9. Installation – Mounting the Alarm
The Alarm pack contains:
• 1 x Smoke or heat alarm
• 1 x Ceiling mounting plate
• Plugs and screws
• Instructions (this document)
Clip with a breakable part
The alarm must be xed horizontally and to the ceiling using the
enclosed mounting plate. The mounting plate can be screwed to the ceiling using either the central hole or the two slots in the ceiling mounting plate (see diagram).
Fitting the alarm to the plate will switch it on.
Note: In special circumstances an alarm may be mounted on a wall.
Locking / release tab (Removable)
Switch on operation
13. Switching off the Alarm
The alarm is switched off by removing it from the ceiling mounting plate. To remove the alarm, press on the tamper proof tab located at the edge of the alarm, and then slide the alarm to the side to remove it from the mounting plate. If the tamper proof option has been used, insert a small screwdriver carefully into the gap and apply slight pressure before sliding the alarm to the side.
‘Switch off’ operation
20. Warranty18. End of Life
Honeywell warrants your new smoke or heat alarm for ten years from the date of purchase by the end user or until the expiry date
on the side of the unit, whichever occurs rst, according to the specications as set out in this instruction manual.
We will, at our discretion, repair or replace, with the same or a similar product, any part of the smoke or heat alarm which is found to be defective in either materials or workmanship within the warranty period.
We shall be under no obligation to repair or replace units which are found to be defective in any way due to unreasonable use or neglect, improper storage, if not used or maintained in accordance with its user manual, or if the product has been tampered with or
found to have been dismantled (other than as specied in its user
manual).
The warranty supplied with this product does not replace your statutory rights, but our liability under the warranty is limited to the price of the faulty product.
In no event are we liable for (a) any direct, indirect, incidental, consequential loss; (b) any loss arising from business interruption;
(c) loss of prots; (d) loss of revenue; (e) loss of use of any property
or capital; (f) loss of anticipated savings or loss of data due to the use of this product.
Warning
It is the responsibility of the installer to ensure the product is installed in line with current regulations. If in doubt please consult a competent professional installer.
>50 cm
<7.6 m
15 - 30 cm
Note: National regulations differ with respect to quantity and placement of smoke detectors. If in doubt, please check, for example by contacting your local Fire Service.
Mounting the Alarm on a ceiling
The central hole may be used on its own or alternatively if
specic xed orientation is required, the two slots can be used
1. Place mounting plate where you want to mount the alarm.
2. With a pencil, mark the location of the screw holes.
3. Drill either one or two holes 5 mm in diameter and >25 mm in depth and then insert the provided plastic plugs.
4. Screw the mounting plate to the ceiling using supplied screws.
Mounting the Alarm on a wall
Sometimes it may be advisable to mount additional alarms on a wall instead of a ceiling. For example, this might be necessary in tall vertical spaces such as stairwells, because heat and smoke may rise rapidly and by-pass the ‘dead air’ areas that can form
beneath stair landings. Also, by visibly ashing above the stairs, it can warn occupants of danger on a lower oor before they
descend into it. If you do use this method, the alarm(s) should be placed where
they can be seen from above, and should be well away from any corners or obstructions.
The procedure for tting the alarm is the same as that used for
ceiling mounting, but you may want to put the locking tab at the bottom or side where it is more easily accessible.
14. Decorating and Building Work
You are advised to cover or remove the alarm during decoration and building work to protect the alarm from inadvertent operation, damage, or the ingress of dust or debris.
Please ensure that alternative safety arrangements are in place while the alarm is covered and inoperable, and ensure that the protection is removed when work has stopped for the day. Failure to do so could lead to loss of life.
15. Conformance
The XS100 and XS100T have been tested and approved to EN
14604 for compliance with Construction Products Regulation 305/2011.
The XW100 radio module complies with the R&TTE directive and
RED directive.
The XS100T, XS100 and XH100 comply with the current EMC and ROHS directives.
The XH100 has been tested and approved to BS 5446-2, re detection and re alarm devices for dwellings, specication for
heat alarms.
These declarations of conformity are available for download from homesafety.honeywell.com.
21. What to do in the case of a re alarm
• Raise the alarm by shouting Fire, Fire, Fire, or by banging
metal objects together.
• Get out straight away, using the nearest re exit.
• Do not stop to investigate the re or to collect valuables
or pets.
• Use your escape route to get everyone out and meet at an agreed point.
• Close any doors which are open, and only open the doors you need to go through. This will help to stop the re spreading so rapidly.
• Check doors and handles with the back of your hand. If they
feel warm, don’t open the door as the re is on the other side.
• If there is a lot of smoke, crawl along the oor as the air and
visibility will be better.
• Once you’ve got everyone out of the building, call the Fire
Brigade from any phone. Give the operator your name and address.
• Don’t go back into the building for anything. If there is still
someone inside, tell reghters when they arrive – they will be able to nd the person quicker and more safely than you.
• Find somewhere safe to wait for the Fire Brigade. When they arrive, try to give them as much information as possible about
the re and building.
29 30 31 32
Loading...