Honeywell W8735G Installation Instructions Manual

Page 1
W8735G Communication Gateway
INSTALLATION INSTRUCTIONS

FEATURES

• Monitors the bus for critical events and updates the server.
• Monitors system power and generates power failure alarms.
• Battery backup.
• Monitor up to four separate appliances.
• Updates via phone line or network.
• Auxiliary I/O.
• Remote firmware updates.

When Installing This Product…

1. Read these instructions carefully. Failure to follow the
manual could damage the product.
2. Installer must be a trained, experienced service techni­cian.
3. Complete all wiring connections to the gateway before powering up the 24Vac system transformer and plug-

APPLICATION

For use with Remote Access applications monitoring EnviraCOM™ enabled controls and sensors. Communicates with up to four EnviraCOM™ buses for multiple appliance installations.
ging in the gateway power supply into an outlet.
4. All wiring must comply with applicable local electrical codes, ordinances and regulations.

INSTALLATION

• R7184 Oil Primary
• R7284 Oil Primary
• L7224 Aquastat®
• L7248 Aquastat®
• TH9421C VisionPRO® IAQ
• W8735S1016 Indoor Temperature Module for temperature indication and alerting.
Mount the W8735G in the equipment room near the indoor HVAC equipment. Position the W8735G vertically so that the power and telephone plugs are situated towards the bottom or horizontally so that all wiring terminations face the floor, depending on the space available. See Fig. 1.
IMPORTANT
Turn OFF all power to heating and cooling equip­ment.
1. Position the W8735G on a wall near the indoor HVAC equipment. Level the module for appearances only; the module functions properly even when not level.
2. Use a pencil to mark the mounting holes to be used. The W8735G has two external mounting holes and two external flanges. See Fig. 2.
3. Use a minimum of one hole and one flange to mount the W8735G.
69-2432-01
Page 2
W8735G COMMUNICATION GATEWAY
CAUTION
4. Remove the W8735G from the wall and drill a minimum
of two 3/16-in. holes in the wall (if drywall) as marked. For firmer material such as plaster, drill a minimum of two 7/32-in. holes.
5. When mounting to the wall, gently tap provided anchors into the drilled holes until flush with the wall.
6. Position the W8735G over the drilled holes. Insert the provided mounting screws in the holes and tighten.
W8735G
10
(254)
EnviraCOM™
Enabled
Status
FURNACE OR BOILER
WATER HEATER
M29960
Fig. 1. Locating the W8735G in the Equipment Room.

WIRING

Voltage Hazard. Can cause electrical shock or equipment damage.
Disconnect power before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be involved.
IMPORTANT
All wiring must comply with local electrical codes and ordinances or NEC codes.
IMPORTANT
Use 18 to 20 gauge color-coded cable for proper wir­ing. Shielded cable is typically not required. Keep this wiring at least one foot away from large inductive loads such as electronic air cleaners, motors, line starters, lighting ballasts, and large distribution pan­els. Failure to follow these wiring practices may intro­duce electrical interference (noise) which can cause erratic system operation. All unused wire is to be grounded at controller end only. The bus wire to ter­minal 1/D must not exceed 1,000 feet (305 M).
5 (127)
2
(51)
12V DC
M29958
Fig. 2. W8735G Dimensions in inches (mm).

General Wiring Directions

Refer to Fig. 3 and Table 1 for the location and function of each terminal.
IMPORTANT
Wire the W8735G with the plug-in 12V power supply disconnected.
1. Remove power from all devices to be connected to the W8735G (Channels and Auxiliary Input and Output).
2. Remove the cover from the W8735G by gently pulling the cover plate outward to disengage the friction latches, which are on the side opposite of the wiring connections.
3. Identify the terminal block to be connected and loosen the terminal screws using a 3.5 mm slotted screw driver See Fig. 3 and Fig. 4.
4. Insert wire end through the rubber grommet, which is supplied in the bag assembly.
5. Place each of the three cables into its proper terminal and securely tighten each screw.
6. As needed, adjust the position of the grommet and press it into place in the slot on the base. See Fig. 3.
7. Replace the cover.
69-2432—01 2
Page 3
8. Bundle the wires and tie-off using the two wire tie-offs molded into the base. See Fig. 3.
W8735G COMMUNICATION GATEWAY
SIDE VIEW SHOWING CHANNEL AND AUXILIARY PORTS
WIRE
TIE-OFF
CHANNEL 1
CHANNEL 2
AUXILIARY
OUTPUT
AUXILIARY
INPUT
CHANNEL 3
CHANNEL 4
WIRE
TIE-OFF
TELEPHONE
NETWORK
W8735G Terminal Designation Function
Channel 1
1/D (channel 1) To EnviraCOM channel 1 network; DATA
2/R (channel 1) To EnviraCOM channel 1 network; 24 Vac Hot
3/B (channel 1) To EnviraCOM channel 1 network; 24 Vac Common
Channel 2
1/D (channel 2) To EnviraCOM channel 2 network; DATA
2/R (channel 2) To EnviraCOM channel 2 network; 24 Vac Hot
3/B (channel 2) To EnviraCOM channel 2 network; 24 Vac Common
Auxiliary
Auxiliary Output (DO) Connect to N.O. contact; alarm input
Auxiliary Output (DO) Connect to N.O. contact; alarm input
Auxiliary Input (DI) Connect to N.C. sensor contact; 18–30 Vac/Vdc
Auxiliary Input (DI) Connect to N.C. sensor contact; 18–30 Vac/Vdc
Channel 3 (Model 1018 only)
1/D (channel 3) To EnviraCOM channel 3 network; DATA
2/R (channel 3) To EnviraCOM channel 3 network; 24 Vac Hot
3/B (channel 3) To EnviraCOM channel 3 network; 24 Vac Common
Channel 4 (Model 1018 only)
1/D (channel 4) To EnviraCOM channel 4 network; DATA
2/R (channel 4) To EnviraCOM channel 4 network; 24 Vac Hot
3/B (channel 4) To EnviraCOM channel 4 network; 24 Vac Common
See Fig. 5 for a typical W8735G application.
WIRE TIE-OFF
POWER
RUBBER GROMMET (X5)
TERMINAL BLOCK
WIRE
Fig. 3. Wiring Connections (4-Channel).
Table 1. W8735G Terminal Designations.
SCREW DRIVER
M29956
3 69-2432—01
Page 4
W8735G COMMUNICATION GATEWAY
CHANNEL TERMINAL
1/D
2/R
3/B
M29957
Fig. 4. Communication Bus Terminals (4-channel).
VISIONPRO IAQ
2
TO OPTIONAL ENVIRACOM CONTROLS AND SENSORS
R7184U OIL PRIMARY CONTROL
THERMOSTAT OPTIONAL.
1
2
REVIEW COMPONENTS AND ACCESSORIES SECTION FOR COMPATIBLE DEVICES.
1 2 3
1
2 3
1
TELEPHONE
NETWORK
W8735G COMMUNICATION GATEWAY
1/D 2/R 3/B
EnviraCOM™
Enabled
Status
POWER
M29961
Fig. 5. W8735G with EnviraCOM oil primary and
VisionPRO IAQ.

W8735G GATEWAY LED CODES

The multipurpose LED is used to indicate battery life, gateway functionality, and abnormal (alarm) conditions. In case of multiple events, only the event with the highest priority will be displayed.
Battery good LOWEST Normal Operation. Green (Solid)
Battery low Replace the battery. Green/Off
Battery dead No backup battery. Risk of data loss during power outage. Green/Red
Time not available Gateway has not connected to the server yet. Red/Amber/Green
Attempting to connect to server
Connected to server Gateway is connected to server and data transfer is in
Server NACK No account set up for the gateway on server. Amber/Red
License expired One or more of the active channels have expired license. Red (Solid)
EnviraCOM communication loss
Auxiliary alarm Power lost to the Auxiliary Input. Amber/Off
Critical alarm HIGHEST One or more of the active channels have active critical

Wiring the Auxiliary Input/Output Term inals

The Auxiliary contacts are available to integrate non­EnviraCOM sensors and switches to the W8735G and to allow the W8735G to interface with non-EnviraCOM monitoring devices in case an alert condition is detected. See Fig. 6 for AUX-IN and AUX-OUT wiring connections.
Table 2. LED Diagnostic Blink Code.
Event Priority Description LED Color Flashes
Gateway is trying to contact the server, data transfer not
Amber/Green
started yet.
Amber (Solid)
progress.
One or more of the active channels have stopped working
Red/Off/Amber/Off
(no data received for five minutes).
Red/Off
alarm, or a critical global alarm is active.
AUXILIARY INPUT (AUX-IN)
Generic devices such as flood sensors, temperature controllers (for attic or outdoor temperature sensing) and basic 24 Vac/Vdc thermostats can be connected to the Auxiliary Input contacts to integrate non-EnviraCOM devices to the W8735G.
69-2432—01 4
Page 5
W8735G COMMUNICATION GATEWAY
M29962
AUXILIARY TERMINALS
AUX-IN
AUX-OUT
The Auxiliary Input port is labeled DI on the side of the case. Power for the Auxiliary Input (AUX-IN) may be drawn from an active communication channel (terminals 2 and 3) or a separate 24Vac transformer if no communications channel is used. See Fig. 7 and 8.
Connect the AUX-IN terminal to an optional normally closed (N.C.) sensor contact that fulfills the desired function. The Auxiliary Input terminals accept a voltage input of 18-30 Vac/ dc. Power to the Auxiliary Input represents a normal, non­alarm condition, while a loss of power to the contacts represents an alarm condition.
The Auxiliary Input accepts up to 30 Vac or Vdc presenting no more than a 10 mA load.
AUXILIARY OUTPUT (AUX-OUT)
The Auxiliary Output closes in the event an alert condition is detected from the W8735G or from the Auxiliary Input. The Auxiliary Output (dry) contacts remain closed until the alert condition is cleared. Use the Auxiliary Output terminals to interface with a lamp or buzzer to locally indicate an alert condition (see Fig. 13) or connect to a residential security panel in order to integrate the HVAC alerts to the home security system (see Fig. 12).
The Auxiliary Output is a normally open, dry contact that supports a load current of up to 1 A. A closed output indicates an alert condition. The auxiliary output port is labeled DO on the side of the case.
NOTE: The Auxiliary Output is “made” on all alert conditions
and is deactivated when the alert is cleared from the communication bus.

Auxiliary Input and Output Applications

AUXILIARY INPUT (AUX-IN) TERMINAL
• Connect the Auxiliary Input (AUX-IN) terminals to a normally closed dry contact sensor, drawing power from an active EnviraCOM channel or external transformer. See Fig. 7.
• Connect the Auxiliary Input (AUX-IN) terminals to a normally closed contact sensor, drawing 24 V power from an external power supply. See Fig. 8.
• For multiple sensors, connect in series to enunciate any condition on the AUX-IN loop. See Fig. 9.
• For multiple sensors, connect in parallel to annunciate an “AND” condition on the AUX-IN loop. See Fig. 10.
• Connect a 24 Vac/dc sensor. See Fig. 11.
AUXILIARY OUTPUT (AUX-OUT) TERMINAL
• Connect the N.O. Auxiliary Output terminals to an optional home alarm system or other local alert enunciation device. See Fig. 12.
• Use a 24 Vac relay if the enunciating device operates at line voltage. See Fig. 13.
1
1/D 2/R
CHANNEL 1
3/B
IMPORTANT
Make sure the current draw through the Auxiliary Output terminals does not exceed specifications. Use relays or contactors to integrate to line voltage devices.
Fig. 6. AUX-IN and AUX-OUT Terminals (located on the
main circuit board).
1/D 2/R
AUXILIARY SENSOR
(DRY CONTACTS)
1
POWER FROM THE AUXILIARY INPUT MAY BE DRAWN FROM AN ACTIVE COMMUNICATION CHANNEL AS SHOWN (2/R AND 3/B).
CHANNEL 2
3/B
OUTPUT
AUXILIA RY
INPUT
M23752
Fig. 7. Wiring Normally Closed Contact Sensor to the
AUX-IN Terminal Block (Channel Powered).
5 69-2432—01
Page 6
W8735G COMMUNICATION GATEWAY
CHANNEL 1
CHANNEL 2
OUTPUT
INPUT
AUXILIA RY
POWER FROM THE AUXILIARY INPUT SUPPLIED BY TRANSFORMER.
1
T87 OR SIMILAR
1
M23753
1/D 2/R 3/B
1/D 2/R 3/B
COMBINATION OF DEVICES CONNECTED IN SERIES TO ANNUNCIATE ON ANY EVENT ON THE AUX-IN LOOP.
1
CHANNEL 1
CHANNEL 2
OUTPUT
INPUT
AUXILIA RY
1
M23754
1/D 2/R 3/B
1/D 2/R 3/B
N.C. N.C.
1/D
CHANNEL 1
2/R 3/B
1/D 2/R
CHANNEL 2
3/B
1
N.C.
OUTPUT
N.C.
INPUT
1
COMBINATION OF DEVICES CONNECTED IN PARALLEL TO ANNUNCIATE ON AN “AND” EVENT ON THE AUX-IN LOOP.
AUXILIA RY
M23755
Fig. 8. Wiring Normally Closed Contact Sensor to the
AUX-IN Terminal Block (External Power Supply).
Fig. 9. Wiring the AUX-IN Terminal Block with devices in
series (External Power Supply).
Fig. 10. Wiring the AUX-IN Terminal Block with devices in
parallel (External Power Supply).
1/D 2/R
CHANNEL 1
3/B
1/D
CHANNEL 2
2/R 3/B
OUTPUT
24 VAC/VDC
SENSOR
INPUT
AUXILIA RY
M23756
Fig. 11. Wiring the AUX-IN Terminal Block to a 24 Vac/dc
Sensor.
69-2432—01 6
Page 7
Fig. 12. Wiring the AUX-OUT Terminal Block to a Home
HOME SECURITY
PANEL
AUXILIARY
CHANNEL 1
CHANNEL 2
OUTPUT
INPUT
AUXILIA RY
M23757
1/D 2/R 3/B
1/D 2/R 3/B
Security Panel.
NOTE: For the wiring in Fig. 12, be sure to check the exact
connections with the Home Security Panel Installa­tion Instructions-Auxiliary Devices.
W8735G COMMUNICATION GATEWAY
condition, it queues up the alarm report to the server. If the alarm message is active on the bus for a period exceeding 5 minutes, the gateway connects to the server and delivers its alarm report. If the gateway fails to connect while attempting to deliver an alarm report, it will retry at five minute intervals until successful.
The W8735G also reports a runtime data log for the bus or busses it is monitoring. During a 24 hour period, a W8735G communicating via a phone connection will dial out once between midnight and 4:00
AM local time to deliver the
previous day's log. Broadband gateways update the server every 30 minutes. Applications requiring closer monitoring and faster updates should be connected to a network connection.
Upon power-up, the gateway will conduct a self test which includes a broadband or dial-up attempt using a pre­programmed 800 number. Dial-up connections are only used in cases where Broadband connections are unavailable. For best performance, connect to both Network and Telephone connections. See Fig. 14.
W8735G COMMUNICATION GATEWAY
ENVIRACOM BUS
1/D 2/R 3/B
EnviraCOM™
Enabled
1/D
CHANNEL 1
2/R 3/B
1/D 2/R
CHANNEL 2
3/B
L1
24 VAC
TRANSFORMER
L2
BUZZER
N.O. 24 VAC
RELAY
Fig. 13. Wiring the AUX-OUT Terminal Block to Line
Voltage Annunciating Device (Buzzer).
OUTPUT
AUXILIA RY
INPUT
M23758

Phone/Network Communication

The W8735G Communication Gateway can update the Application server using either a dial-up or broadband connection. See Fig. 14. When the W8735G detects an alarm
Status
TELEPHONE JACK
TELEPHONE
NETWORK
POWER
ROUTER
CABLE/DSL MODEM
M29954
Fig. 14. Connecting the gateway to a network or phone
line.
IMPORTANT
— A phone line filter will be required if the gateway is
sharing the line with a DSL modem.
— The gateway will not attempt to dial out if the tele-
phone line is in use.
— Use only with analog telephone lines.
IMPORTANT
If the phone line is needed while the gateway is con­nected, simply picking up a phone off the hook will cause the gateway to release the line. Other instances/phone systems may require pressing the Flash button on the telephone.
7 69-2432—01
Page 8
W8735G COMMUNICATION GATEWAY
PREFIX 9
Some installations may require a 9 prefix be dialed in order to gain a dial tone. The W8735G supports this feature by way of the preset jumper. See Fig. 15. When this jumper is in place, a “9” will be added to the programmed dial-out number. Removing the jumper removes the 9 from the dial-out sequence.
PREFIX 9 JUMPER
M29955
Fig. 15. Prefix 9 Jumper.
MULTIPLE DIAL-OUT ATTEMPTS:
The normal communication procedure is for the gateway to first attempt a network connection. If this is unavailable, the gateway will attempt to dial out via the modem. Multiple numbers may be programmed into the gateway as backups (check Web App features). Thirty minute periods are allotted to each programmed dial-out number, with dial-out attempts occurring at approximately five minute intervals. At the end of a 30 minute period, the next access number in the queue is attempted. This routine is repeated between midnight and 4:00
AM local time at which point dial-out attempts cease. The
routine is repeated during the next reporting time of midnight­4:00 AM.
Battery Replacement
IMPORTANT
The battery backup will ensure that if the power to the gateway is out for a period exceeding one hour, the gateway will attempt to access the server to announce the outage.
Battery health is monitored constantly. Once a battery is replaced, the LED may take a few seconds to reflect the new battery.
For best performance replace the 9V battery yearly or as indicated by the LED (as described in Table 2).
Battery Installation
1. Press the latch on the top of the battery cover and pull it
away from the gateway. See Fig. 16.
2. Connect 9 Vdc battery to the connector leads.
3. Insert the battery in the battery compartment.
4. Insert the bottom tabs of the battery cover into the slots
on the case, then swing the battery cover until the latch engages.
BATTERY COVER LATCH
BATTERY COVER
9V BATTERY LEADS
BATTERY INSTALLED
IMPORTANT
For best gateway performance, connect to both the network and phone.
Gateway Updates
Periodically, the gateway may require a firmware upgrade to enable new features supported by the web application. This will occur automatically on a schedule determined by the web application administrators.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2010 Honeywell International Inc. 69-2432—01 M.S. 06-10 Printed in U.S.A.
M23760
Fig. 16. Battery Installation.
Loading...