• Drill and bit (3/16” for drywall, 7/32”
for plaster)
Must be installed by a trained, experienced technician
Read these instructions carefully. Failure to follow these instructions
can damage the product or cause a hazardous condition.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
1. Pull wires through wire
hole. Position coverplate
on wall, level and mark hole
positions.
2. Drill holes (3/16” for drywall,
7/32” for plaster) and tap in
supplied wall anchors.
3. Pull wire through coverplate
and subbase, position over
anchors, then insert and
tighten mounting screws.
Check level if desired.
4. Apply the large-print labels
to the coverplate, matching
the labels on the subbase.
Wiring
1. Loosen screw terminals, insert wires
into terminal block, then re-tighten
screws.
2. Push excess wire back into the wall
opening.
3. Plug the wall opening with
nonflammable insulation to prevent
drafts from affecting thermostat
operation.
Large-print
subbase switch
labels
Subbase
Coverplate
Terminal Designations
W Heat relay.
Y Compressor contactor.
G Fan relay.
O Heat pump changeover valve
energized in cooling.
Rc Cooling power. Connect to
secondary side of cooling system
transformer.
R Heating power. Connect to
B Heat pump changeover valve
secondary side of heating system
transformer.
energized in heating.
NOTES
R & Rc terminals
In single-transformer system, leave metal
jumper in place between R & Rc. Remove
metal jumper if two-transformer system.
Heat pump systems
If wiring to a heat pump, use a small piece
of wire (not supplied) to connect terminals W
and Y.
Wire specifications
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
3
T87N Easy-To-SeeTM • Owner's Manual
E
F
Fan operation settings
Fan operation settings:
F: For gas or oil heating systems, leave
the fan operation switch in this factory-set
position (for systems that control the fan in
a call for heat).
E: Change the switch to this setting for heat
pump or electric heat systems. (This setting
is for systems that allow the thermostat
to control the fan in a call for heat, if a fan
wire is connected to the G terminal.)
Cycle rate settings
Move the cycle rate switches
to the proper setting for your
system (see table below).
Heating System Switch 1 Switch 2
Steam or gravity (1 CPH) On On
High efficiency warm air Off On
(90%+), hot water, or
heat pump (3 CPH)
Gas or oil warm air Off Off
(factory setting) (5 CPH)
Electric warm air (9 CPH) On Off
Thermostat mounting
Coverplate
and subbase
Thermostat
Align the slots on the base with tabs on the
thermostat, then push gently until the
thermostat snaps into place.
Enlarged,
raised
numbers
indicate
temperature
range by
touch or
sight. The
large 5, 6, 7
and 8 mean 50,
60, 70 and 80°F,
respectively.
Fan switch
• On: Fan runs
continuously.
• Auto: Fan runs only
when heating or cooling
system is on.
Temperature
setting
Rotate to
set, a click is
heard every
two degrees
as the
temperature
is adjusted.
Temperature
Current indoor
temperature.
CAUTION: EQUIPMENT DAMAGE HAZARD
Do not operate cooling system when outdoor temperature is below 50°F (10°C).
Limited 5-year warranty
Honeywell warrants this product, excluding battery, to be
free from defects in the workmanship or materials, under
normal use and service, for a period of ve (5) years from
the date of purchase by the consumer. If at any time during
the warranty period the product is determined to be defective or malfunctions, Honeywell shall repair or replace it (at
Honeywell's option).
If the product is defective,
(i) return it, with a bill of sale or other dated proof of pur-
chase, to the place from which you purchased it; or
(ii) call Honeywell Customer Care at 1-800-468-1502. Cus-
tomer Care will make the determination whether the product
should be returned to the following address: Honeywell
Return Goods, Dock 4 MN10-3860, 1885 Douglas Dr. N.,
Golden Valley, MN 55422, or whether a replacement product
can be sent to you.
This warranty does not cover removal or reinstallation costs.
This warranty shall not apply if it is shown by Honeywell
that the defect or malfunction was caused by damage which
occurred while the product was in the possession of a
consumer.
Honeywell's sole responsibility shall be to repair or replace
the product within the terms stated above. HONEYWELL
SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF
ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY,
FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR
IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT.
Some states do not allow the exclusion or limitation of
incidental or consequential damages, so this limitation may
not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY
HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE FIVEYEAR DURATION OF THIS WARRANTY. Some states do not
allow limitations on how long an implied warranty lasts, so
the above limitation may not apply to you.
This warranty gives you specic legal rights, and you may
have other rights which vary from state to state.
If you have any questions concerning this warranty, please
write Honeywell Customer Relations, 1985 Douglas Dr.,
Golden Valley, MN 55422 or call 1-800-468-1502. In Canada,
write Retail Products ON15-02H, Honeywell Limited/
Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario
M1V 4Z9.
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.