Honeywell T874D, Q674E User Manual

!
SUPER TRADELINE
Thermostat and Q674 Subbase
T874 Multistage
Application
The T874D Thermostat and Q674E Subbase provide 24 to 30 Vac control of standard 2 stage heating and 2 stage cooling systems.
The Y594D includes the TG504 Thermostat Guard, field-adjustable range stops and field-adjustable locking levers.
Operation
The stages of heat make sequentially as the temperature drops. Make refers to the mercury switch initiating a call for heat or cool.
There are about 2° F [1° C] between stages so that the second stage makes only when the first stage cannot handle the load. This is the interstage differential.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mount­ing screws, because damage to subbase threads can result.
4. Do not short across coil terminals on relay. This
can burn out the thermostat heat anticipator.
Do not install thermostat where it may be affected by: — drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas behind the thermostat,
such as an outside wall.
MOUNT SUBBASE
The thermostat subbase can be mounted on a vertical
outlet box, horizontal outlet box or directly on the wall.
1. If you must mount the subbase on a vertical outlet box, order Honeywell part no. 193121A Adapter Assem­bly. See Fig. 1. The assembly includes an adapter ring, two screws and a cover plate to conceal any holes or blemishes on the wall. Install the ring and cover plate on the vertical outlet box.
Fig. 1—Installation of Q674 Subbase on outlet box.
VERTICAL  OUTLET
1
BOX
ADAPTER RING
MOUNTING SCREWS (2)
SUBBASE
HORIZONTAL OUTLET BOX
1
SUBBASE
1 NOT INCLUDED WITH UNIT.  2 ACCESSORY PARTS AVAILABLE (193121A).
MOUNTING SCREWS (2)
COVER  PLATE
2
2
MOUNTING SCREWS (2)
M925
IMPORTANT: An incorrectly leveled subbase will cause
the temperature control to deviate from setpoint. It is not a calibration problem.
LOCATION
Install the thermostat about 5 ft [1.5 m] above the floor
in an area with good air circulation at average temperature.
For a wall installation, hold subbase in position and mark holes for anchors. See Fig. 2. Wall anchors must be obtained from local hardware store. Be careful that the wires do not fall back into the wall opening. Set aside subbase. Drill four 3/16 in. [4.6 mm] holes and gently tap anchors into the holes until flush with the wall.
1 69-0753J. H. • 11-92 • ©Honeywell Inc. 1992 • Form Number 69-0753
2. Pull electrical wires through the cover plate (if
(2)
used) and subbase cable opening. See Fig. 3.
3. Secure the cover plate (if used) and subbase with the
screws provided. Do not fully tighten the subbase screws.
4. Level the subbase using a spirit level, see Fig. 3, and firmly tighten subbase mounting screws. The subbase mount­ing holes provide for minor out-of-level adjustments.
IMPORTANT: An incorrectly leveled subbase will cause
the temperature control to deviate from setpoint. It is not a calibration problem.
Fig. 2—Installation of Q674 Subbase on wall.
Fig. 3—Subbase components and leveling procedure.
SPIRIT LEVEL
TOP MOUNTING HOLES (2)
WIRING TERMINAL
THERMOSTAT CABLE OPENING
WALL
WIRES THROUGH WALL OPENING
WALL ANCHORS (2)
SUBBASE
M926
WIRING THE SUBBASE
All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instruc­tions when available. To wire subbase, proceed as follows:
1. Connect the system wires to the subbase as shown in
Figs. 5 through 8. A letter code is located near each terminal
MOUNTING HOLES
MOUNTING SCREWS
TO SPRING FINGER CONTACTS  ON THE THERMOSTAT (UP TO 12)
for identification. The terminal barrier permits straight or conventional wraparound wiring connection. See Fig. 4.
2. Firmly tighten each terminal screw.
3. Fit wires as close as possible to the subbase. Push
excess wire back into hole.
4. Plug hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
Fig. 4—Barrier configuration.
FOR STRAIGHT INSERTION– STRIP 5/16 in. [8 mm]
SUBBASE TERMINAL SCREW
Fig. 5—Schematic and hookup for T874D Thermostat with Q674E Subbase.
FALL H2
RISE
C2
FALL H1
RISE C1
H1 ANTICIPATOR
H2 ANTICIPATOR
FAN SWITCH
AUTO
ON
SYSTEM SWITCH
OFF
C1 ANTICIPATOR
C2 ANTICIPATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC AND RH FOR A SINGLE TRANSFORMER SYSTEM.
HEAT AUTO COOL
MOUNTING HOLES (2)
BARRIER
W1
HEAT RELAY 1
W2
HEAT RELAY 2
B
CHANGEOVER RELAY (HEAT)
RH
RC
O
CHANGEOVER RELAY (COOL)
G
FAN RELAY
Y2
COMPRESSOR CONTACTOR 2
Y1
COMPRESSOR CONTACTOR 1
POST (2) FOR MOUNTING THERMOSTAT
FOR WRAPAROUND– STRIP 7/16 in. [11 mm]
2
M927
M928
1
1
L2
L1 (HOT)
L1 (HOT)
L2
M3203
2
Loading...
+ 4 hidden pages