Installation Instructions for the Trained Service Technician.
Application
These T874A,D Zone Thermostats and Q674B,D,E
Subbases provide 24 to 30 Vac temperature control in
Honeywell Trol-A-Temp heating/cooling zone systems.
TABLE 1—THERMOSTAT/SUBBASE AND SYSTEM COMPATIBILITY.
Thermostat/Application
Subbase Model
T874A/Q674B Zone 1; conventionalZone 1; conventionalAny zone; conventional heat-cool. Single-stage
T874A/Q674D Zones other than zone 1; Zones other than zone 1; Not applicableSingle-stage
T874A/Q674E Not applicableNot applicableAny zone; conventional heat-cool. Single-stage
T874D/Q674B Not applicableZone 1; conventionalAny zone; conventional heat-cool. Multistage
T874D/Q674D Not applicableZones other than zone 1; Not applicableMultistage
T874D/Q674E Not applicableNot applicableAny zone; conventional heat-cool. Multistage
a
Subbase not included with thermostat; order separately.
T874A1465/Q674B1471 HEAT-OFF-COOLON-AUTO White/GrayStg. 1—Stg. 1—
T874A1465/Q674D1123 NoneNoneWhite/Gray0.1 to 1.20 to 1.5
T874A1465/Q674E1379 HEAT-OFF-COOL-AUTO ON-AUTO White/Gray
T874D1801/Q674B1463 HEAT-OFF-COOLON-AUTO Beige/BrownStg. 1—Stg. 1—
T874D1827/Q674B1471 HEAT-OFF-COOLON-AUTO White/Gray0.1 to 1.2;0 to 1.2;
T874D1801/Q674D1115 NoneNoneBeige/BrownStg. 2—Stg. 2—
T874D1827/Q674D1123 NoneNoneWhite/Gray0.1 to 1.0.0 to 1.0.
T874D1827/Q674E1379 HEAT-OFF-COOL-AUTO ON-AUTO White/Gray
a
Subbase not included with thermostat; order separately.
See Table 1 for thermostat/subbase and system compatibility; see Table 2 for thermostat specifications. For complete
Honeywell Trol-A-Temp System specification and application information, refer to the system specification included with the control panel.
Thermostat/Anticipator Range (A)
Operation
On a 2-heat thermostat, the two stages of heat make
sequentially as the temperature drops. Make refers to the
mercury switch initiating a call for heat or cool.
There are about 2° F [1° C] between stages so that the
second stage makes only when the first stage cannot
handle the load. This is the interstage differential.
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury
in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.
If you have questions, call Honeywell at 1-800-468-1502.
M3375
Installation
M3703
SUBBASE
HORIZONTAL
OUTLET
BOX
1
NOT INCLUDED WITH UNIT.
1
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
!
1. Disconnect power supply to prevent electrical
shock or equipment damage.
2. To prevent interference with the thermostat
linkage, keep wire length to a minimum and
run wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mounting screws, because damage to subbase threads
can result.
4. Do not short across terminals of systems controls. This can burn out the thermostat heat
anticipator.
IMPORTANT: Thermostats are calibrated at the factory by
using subbases mounted at true level. Inaccurate subbase leveling will cause thermostat control deviation.
LOCATION
Locate the subbase about 5 ft [1.5 m] above the floor in
an area with good air circulation at average temperature.
Do not mount the subbase where the thermostat may be
affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun, appliances or fireplace.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
MOUNTING THE SUBBASE
The thermostat subbase can be mounted on a horizontal
outlet box or directly on the wall.
1. To mount on a horizontal outlet box, install the sub-
base on the outlet box as shown in Fig. 1.
For a wall installation, hold the subbase in position and
mark holes for the anchors (Fig. 2). Obtain wall anchors
locally. Take care that the wires do not fall back into the
wall opening. Set aside subbase. Drill two 3/16 in. [4.8 mm]
holes and gently tap anchors into the holes until flush with the
wall.
2. Pull electrical wires through the cover plate (if used)
and subbase cable opening (Fig. 3). See Wiring the Subbase section before pulling any wires.
IMPORTANT: Use 18 gauge, color-coded thermostat
cable for proper wiring.
3. Secure the subbase with the screws provided. Do not
fully tighten the subbase screws.
Fig. 1—Installation of subbase on outlet box.
Fig. 2—Installation of subbase on wall.
WALL
WIRES THROUGH
WALL OPENING
WALL
ANCHORS
(2)
M926
Fig. 3—Subbase components and leveling
procedure.
SPIRIT LEVEL
MOUNTING
HOLES (2)
TOP
MOUNTING
HOLES (2)
SUBBASE
WIRING
TERMINAL
POST (2) FOR
MOUNTING
THERMOSTAT
MOUNTING
HOLES
MOUNTING
SCREWS (2)
THERMOSTAT
CABLE OPENING
TO SPRING FINGER
CONTACTS ON THE
THERMOSTAT
(UP TO 12)
M927
4. Level the subbase using a spirit level, as shown in
Fig. 3, and firmly tighten the subbase mounting screws.
The subbase mounting holes allow minor out-of-level
adjustments.
IMPORTANT: An incorrectly leveled subbase will cause
the temperature control to deviate from set point.
WIRING THE SUBBASE
All wiring must comply with local electrical codes and
ordinances. Follow equipment manufacturer wiring instructions when available. To wire subbase:
1. Connect wires to the subbase terminals. Refer to
Figs. 6-10 for wiring diagrams of typical zone systems. A
2
letter code is located near each subbase terminal for identification. The terminal barrier permits straight or conventional wraparound wiring connection (Fig. 4).
2. Some Q674 Subbases have RC and RH terminals
for isolated heating and cooling transformers. For zoning
systems, jumper RC and RH terminals as shown in Fig. 5
and wire as single R terminal.
3. Firmly tighten each terminal screw.
4. Fit wires as close as possible to the subbase. Push
excess wire back into hole.
5. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
Fig. 4—Wiring connections.
FOR STRAIGHT
INSERTION–
STRIP 5/16 in. [8 mm]
FOR WRAPAROUND–
STRIP 7/16 in. [11 mm]
Fig. 5—Jumper RC and RH terminals for single
transformer system. Strip wire 3/4 in. [19 mm].
RCR
H
W2
ZONE 1
RELAY
4
Y2
ZONE 2
RELAY
ZONE 2ZONE 1
M6
M4
T6
T5
T4
M1
RCR
H
T874A THERMOSTAT/
Q674D SUBBASE
4
3
Y1 Y2
RC
4 56Z
DAMPER
ACTUATOR
123X
RH W2
M1633
M929
W1
SUBBASE TERMINAL SCREW
Fig. 6—Typical hookup for MM-2 Mini-zone Control Panel with T874A Thermostat/Q674B,D Subbase in
single-stage heating-cooling two-zone system.
BARRIER
MINIZONE
(MM-2)
CONTROL
PANEL
Y2
Y1
O
TO SINGLESTAGE
HEATING/
COOLING
EQUIPMENT
G2
G1
RC
RH
B
W2
W1
E
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION.
2
JUMPER RC AND RH TERMINALS TOGETHER AND WIRE AS SINGLE R TERMINAL.
3
DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL.
4
TRANSFORMER
L2
1
L1
(HOT)
M928
T874A THERMOSTAT/Q674B SUBBASE
2
OG B
HEAT
COOL
RELAY
RELAY
CHANGEOVER
CONTROL
O1
COOL
G1
FAN
B1
HEAT
B
2
24 V, 40 VA
1
3
RC RH W1
Y1
T6
T5
T4
M6
M4
M1
4 56Z
DAMPER
ACTUATOR
123X
369-0580—2
MOUNTING THE THERMOSTAT
1. Remove the thermostat cover by pulling the bottom
edge of the cover outward away from the base until it snaps
free from the cover clip.
spring fingers are not bent flat, preventing proper electrical contact with the subbase.
4. Set the heat anticipator indicator(s) to 0.1A for
proper system operation (Fig. 11).
5. Note the two tabs on the top inside edge of the
NOTE: The cover is hinged at the top and is removed by
pulling out at the bottom.
thermostat base. The tabs fit into the corresponding slots
on the top of the subbase. Mount the thermostat on the
subbase. See Fig. 12.
2. Carefully remove and discard the polystyrene packing
insert that protects the mercury switches during shipment.
3. Turn over the thermostat base and note the spring
fingers that engage the subbase contacts. Make sure the
Fig. 7—Typical hookup for MABS II and MABS II-L Control Panels with T874A Thermostat/Q674B,D
Subbases in single-stage heating-cooling zone system. MABS II Control Panel shown; MABS II-L Control
Panel hookup is the same.
6. Align the two captive mounting screws in the thermostat base with the posts on the subbase (Fig. 12). Tighten
both screws. Do not overtighten the screws or damage to
the subbase posts can result.
TO SINGLESTAGE
HEATING/
COOLING
EQUIPMENT
MABS II
CONTROL PANEL
SECOND
EM. HEAT
STAGE
RELAY
RELAY
Y
2
Y
1
O
G
2
G
1
R
C
R
H
B
W
2
W
1
E
T874A THERMOSTAT/Q674B SUBBASE
344
OGB
FAN
RELAY
ADD-A-
ZONE
A
4
A
EM. HEAT
3
A
24 V, 40 VA
2
A
TRANSFORMER
1
1
L2
L1
(HOT)
2
Y1 RC RH W1 W2 Y2
HEAT
COOL
RELAY
RELAY
CHANGEOVER
CONTROL
O
COOL
1
G
FAN
1
B
HEAT
1
E
1
2
1
Y1 Y2 RC RH W2 W1
CAC
RELAY
ZONE 1
T
8
T
7
T
6
T
5
T
4
M
6
M
4
M
1
456Z
DAMPER
ACTUATOR
123X
T874A THERMOSTAT/
Q674D SUBBASE
2
ZONE 1
ZONE 2
RELAY
RELAY
ZONE 2
T
8
T
7
T
6
T
5
T
4
M
6
M
4
M
1
456Z
DAMPER
ACTUATOR
123X
T874A THERMOSTAT/
Q674D SUBBASE
Y1 Y2 RC RH W2 W1
ZONE 3
RELAY
ZONE 3
T
8
T
7
T
6
T
5
T
4
M
6
M
4
M
1
2
4
456Z
DAMPER
ACTUATOR
123X
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC, RH TOGETHER AND WIRE AS SINGLE R TERMINAL.
3
ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION.
4
DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL.
4
M1634
Fig. 8—Typical hookup for MABS II and MABS II-L Control Panels with T874D Thermostat/Q674B,D
Subbases in multistage heating-cooling zone system. MABS II Control Panel shown; MABS II-L Control
Panel hookup is the same.
TO SINGLESTAGE
HEATING/
COOLING
EQUIPMENT
MABS II
CONTROL PANEL
SECOND
EM. HEAT
STAGE
RELAY
RELAY
Y2
Y1
O
G2
G1
RC
RH
ADD-A-ZONE
B
W2
W1
E
T874D THERMOSTAT/Q674B SUBBASE
2
3
RC
OG
BY2W2Y1RH W1
FAN
HEAT
RELAY
COOL
FAN
HEAT
EM. HEAT
COOL
RELAY
CHANGEOVER
CONTROL
O1
G1
B1
E1
2
1
RELAY
A4
A3
A2
A1
TRANSFORMER
1
L2
L1
(HOT)
24 V, 40 VA
ZONE 3
RELAY
ZONE 3
T8
T7
T6
T5
T4
M6
M4
M1
T874D THERMOSTAT/
Q674D SUBBASE
2
RC
Y2 W2 Y1
456Z
DAMPER
ACTUATOR
123X
RH W1
T874D THERMOSTAT/
Q674D SUBBASE
RC
ZONE 1
RELAY
2
Y2 W2 Y1
ZONE 2
RELAY
ZONE 2
T8
T7
T6
T5
T4
M6
M4
M1
RH W1
456Z
DAMPER
ACTUATOR
123X
444
CAC
RELAY
ZONE 1
T8
T7
T6
T5
T4
M6
M4
M1
456Z
DAMPER
ACTUATOR
23X
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
JUMPER RC, RH TOGETHER AND WIRE AS SINGLE R TERMINAL.
3
ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION.
4
IF SINGLE-STAGE COOLING, DO NOT CONNECT Y2; IF SINGLE-STAGE HEATING, DO NOT CONNECT W2.
569-0580—2
M1393A
Fig. 9—Typical hookup for MABS XX Control Panel with T874A Thermostat/Q674B,E Subbases in singlestage heating-cooling zone system.
MABS XX
CONTROL PANEL
ZONE 1
HEATFANCOOLHEATFANCOOLHEATFANCOOL
ZONE 2ZONE 3
TO SINGLESTAGE
HEATING/
COOLING
EQUIPMENT
L2
L1
(HOT)
MCM
ZONE 1
FANFANFAN
ZONE SYS
DAMPER
YWGGh
12 GYR W
1
2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
WIRE ONLY THE TERMINAL CONNECTIONS SHOWN. SOME TERMINALS NOT AVAILABLE ON ALL THERMOSTATS. IF THERMOSTAT HAS
2
R/RC/RH TERMINALS, JUMPER TOGETHER AND WIRE AS SINGLE R TERMINAL. DO NOT CONNECT THERMOSTAT O AND B TERMINALS
TO CONTROL PANEL.
O B RC RH
ZONE 1
M6 M4 M1 VO VC
G
Y1
Y1
Y2
R
W1
W2
O
BBB
T874A
THERMOSTAT/
Q674B OR E
SUBBASE
456Z
DAMPER
ACTUATOR
12
3X
W1
2
W2
T874A
THERMOSTAT/
Q674B OR E
SUBBASE
G
G
Y2
R
O
OPEN CLOSE
YRW
ZONE 2
M6 M4 M1 VO VC
456Z
DAMPER
ACTUATOR
123X
ZONE 2
ZONE SYS
DAMPER
OPEN CLOSE
CACFC
ZONE 3
ZONE SYS
DAMPER
OPEN CLOSE
GYRWM6
G
Y1
Y2
R
W1
2
W2
O
T874A
THERMOSTAT
Q674B OR E
SUBBASE
ZONE 3
M4
456Z
123X
M1 VO VC
DAMPER
ACTUATOR
ZONE
ADD-A-
M1636
1
2
3
4
5
6
7
8
9
6
r
Settings
Checkout
Before beginning checkout of thermostat operation,
set switches on the control panel for the desired system
operation. See instructions provided with the control panel.
TABLE 5—SYSTEM SET-UP FOR THERMOSTAT CHECKOUT.
HeatingCooling
ControlZones OtherZones Other
PanelZone 1Than Zone 1Zone 1Than Zone 1
Mini-zoneSet thermostatMove the heating setSet thermostatMove the cooling set
MABS IIsystem switch topoint lever 10° Fsystem switch topoint lever 10° F
MABS II-LHEAT; set fan switch[6° C] below roomCOOL; set fan[6° C] above room
to AUTO. Move thetemperature.switch to AUTO.temperature.
heating set pointMove the cooling
lever 10° F [6° C]set point lever 10° F
below room[6° C] above room
temperature.temperature.
MABS XXOn all zone thermostats, set the systemOn all zone thermostats, set the system
switch to HEAT; set the fan switch to AUTO.switch to COOL; set the fan switch to AUTO.
Move the heating set point lever 10° F [6° C]Move the cooling set point lever 10° F [6° C]
below room temperature.above room temperature.
NOTE: The control panel provides a three-NOTE: The control panel provides a three-
minute time delay when 24V is applied tominute time delay when 24V is applied to
the control panel and at the end of eachthe control panel and at the end of each
equipment cycle. The high-speed fan runsequipment cycle. The high-speed fan runs
during this time delay.during this time delay.
HEATING
NOTE: If a plenum fan control is used in the heating
system, there will be a short delay on a call for heat to
allow the furnace to heat the plenum. The fan starts
immediately in electric heat systems. Allow 30 seconds
for the damper to open or close completely.
Make sure all zone thermostats are set as instructed in
the Heating column in Table 5. Check each zone thermostat as follows:
1. If thermostat has a fan switch, set it to ON. See
Fig. 13. After 30 seconds, place your hand in front of an
air register in that zone to check for air flow at the register.
2. Reset fan switch, if provided, to AUTO. After 30 seconds, make sure air flow at register has stopped.
3. Move heating set point lever on zone thermostat
10° F [6° C] above room temperature to call for heat.
4. After 30 seconds (longer, if necessary, for time delay
on plenum fan control), check for warm air at the register.
5. Move heating set point lever on the zone thermostat
10° F [6° C] below room temperature to end a call for heat.
After 30 seconds (longer, if necessary, for time delay on
plenum fan control or control panel), check that air flow at
the register has stopped.
6. Repeat steps 1-5 for each zone thermostat.
To set up the system for thermostat checkout, adjust
each thermostat settings as shown in Table 5.
COOLING
CA UTION
!
Do not operate cooling equipment if outdoor
temperature is below 50° F [10° C]. Refer to
manufacturer recommendations.
Make sure all zone thermostats are set as instructed in
the Cooling column in Table 5. Check each zone thermostat as follows:
1. Move cooling set point lever on the zone thermostat
10° F [6° C] below room temperature to call for cooling.
2. After 30 seconds, place your hand in front of an air
register in that zone to check for cool air at the register.
3. Move the cooling set point lever on the zone thermo-
stat 10° F [6° C] above room temperature to end the call for
cooling. After 30 seconds (longer, if necessary, for time
delay on control panel), check that air flow at the register
has stopped.
4. Repeat steps 1-3 for each zone thermostat.
When system checkout is complete, return all thermo-
stats to the desired settings for normal system operation.
969-0580—2
Calibration
THERMOSTAT
T874 thermostats are accurately calibrated at the
factory. They do not have provision for field calibration.
THERMOMETER
The thermometer in your thermostat has been accurately calibrated at the factory. The thermometer should
only need adjustment if it has been dropped or shifted due
to mishandling.
If the set point lever and the thermometer reading do
not agree:
1. Remove the thermostat cover by pulling up from the
bottom of cover until it clears the mounting slots.
2. Set the thermostat cover on a table near an accurate
thermometer.
3. Allow ten minutes for the cover thermometer to
sense the area temperature; compare the readings. Be careful not to touch the thermometer or breathe on it.
4. If the readings are the same, replace the cover and put
the system into operation.
5. If the readings are different, insert a small screwdriver in the thermometer slot (Fig. 14) and turn it until the
thermometers have the same reading.
6. Replace the thermostat cover and put the system into
operation.
NOTE: Hand heat will offset the thermometer reading.
After making each adjustment, wait ten minutes for
the thermometer to stabilize before comparing.
Fig. 14—Thermometer calibration.
M5070
Home and Building ControlHome and Building ControlHelping You Control Your World
Honeywell Inc.Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North740 Ellesmere Road
Golden Valley, Minnesota 55422Scarborough, Ontario
M1P 2V9
Printed in U.S.A.
QUALITY IS KEY
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.