Series 2000 Commercial
Microelectronic Thermostat
Contents
Features .................................................................. 3
Programming........................................................... 4
® U.S. Registered Trademark Copyright © 1996 Honeywell Inc. • All Rights Reserved
1 63-4356—1
63-4356-1
Page 2
ENTER OCCUPIED PROGRAM MODE
ENTER UNOCCUPIED PROGRAM MODE
SET CURRENT DAY OR PROGRAM DAY
SET OCCUPIED TEMPERATURE SETPOINTS
SET UNOCCUPIED TEMPERATURE SETPOINTS
AM
Mon
Occupied
System Fan
RETURNS TO NORMAL OPERATIONS
SET OVERRIDE TEMPERATURE OFFSET AND ACTIVATE TEMPORARY OVERRIDE
ENTER HOLD MODE
Run
Program
Temporary
Occupied
Continuous
Unoccupied
Occupied
Start Time
Set Current
Day/Time
SET CURRENT DAY AND TIME
Heat
Set Program Set Temperature Change
Unoccupied
Start Time Day
Clear
Start Time
Copy
CLEAR PROGRAM PERIOD
63-4356—1 2
Room
Auto
Occupied
Unoccupied
Temp
System Fan
SELECT SYSTEM
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
OPERATION
Temp
Heat/Cool
Settings
Time/Temp
SELECT FAN OPERATION
INCREASE TEMPERATURE OR TIME SETTING
DECREASE TEMPERATURE OR TIME SETTING
CHANGE BETWEEN HEATING AND COOLING SETPOINTS
M10256
Page 3
FEATURES
•Program up to two Occupied and two Unoccupied time periods for each daily schedule.
• Set different schedules for each day of the week.
•Temporary temperature overrides.
•Program copy key.
3 63-4356—1
Page 4
PROGRAMMING
The keyboard is located behind the thermostat cover. Sixteen keys are used to set, review and modify programmed times and temperature settings. The thermostat display shows day, time, program period and temperature.
The thermostat can be set for two Occupied and two Unoccupied times for each day of the week (28 independent time settings). Temporary Occupied
63-4356—1 4
key provides quick temporary temperature changes for increased occupant comfort. The Continuous Unoccupied key provides energy efficient operation for extend periods of time.
Before starting the program procedure, use the following chart to organize the program schedule.
Page 5
Day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Occupied
Period 1
Unoccupied
Period 1
5 63-4356—1
Occupied
Period 2
Unoccupied
Period 2
Page 6
The program has four temperature settings, Occupied and Unoccupied heat and cool. The thermostat will operate at the Unoccupied temperature setting unless the thermostat is programmed. The following chart shows the default temperature settings.
Occupied
Setpoint
Unoccupied
Setpoint
Control Default Desired Default Desired
Heating 70°F
(21°C)
Cooling 78°F
(25.5°C)
63-4356—1 6
55°F (13°C)
90°F (32°C)
Setting Current Day and Time
Press Set Current Day/Time.
NOTE: On initial power up or after an
extended power loss, 1:00 pm flashes on the LCD until a key is pressed.
Set Current
Day/Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
System Fan
Mon
Heat/Cool
Settings
Clear
Copy
Set Day/Time
PM
M4951B
Page 7
Press Day until the current day is displayed.
Press Run Program.
NOTE: Sun = Sunday, Mon = Monday, Tue =
Tuesday, Wed = Wednesday, Thu = Thursday, Fri = Friday, Sat = Saturday.
Day
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
System Fan
Set Day/Time
Tue
PM
M4952B
Press increase ▲ or decrease ▼ key until the
current time is displayed.
NOTE: Tapping the Set Current Day/Time
will change the time in one hour increments.
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Start Time Day
Clear Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Set Day/Time
Tue
PM
M4953B
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Start Time Day
Clear Start Time
Time/Temp
Unoccupied
Occupied
Temp
Temp
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
AM
Room
Auto
M4954A
Setting Program Times
Press Occupied Start Time.
NOTE: Anytime a start time is not required,
press the Clear Start Time.
Set Program
Start Time
Occupied
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
System Fan
Mon
Heat/Cool Settings
Occupied 1
Clear
Copy
7 63-4356—1
AM
M4955A
Page 8
Press Day until the desired day is displayed.
Set Program
Start Time
Day
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Occupied 1
AM
Wed
M4956A
Press Occupied Start Time a second time to
set a second Occupied Start Time.
Set Program
Occupied
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Wed
Occupied 2
Start Time
M4958B
Press increase ▲ or decrease ▼ key until the
desired start time is displayed.
NOTE: The program times are in fifteen
minute intervals. (Example: 8:00, 8:15, 8:30).
Set Program
Start Time
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Unoccupied Start Time Day
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
System Fan
Occupied 1
63-4356—1 8
AM
Wed
M4957A
Press increase ▲ or decrease key until the
desired start time is displayed.
Set Program
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
System Fan
Occupied 2
PM
Wed
M4959A
Press Unoccupied Start Time.
Set Program
Un
Occupied 1
Start Time
PM
Wed
M4960A
Unoccupied
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Set Current
Temporary
Day/Time
Start Time
Occupied
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Heat/Cool Settings
Copy
System Fan
Page 9
Press increase ▲ or decrease ▼ key until the
desired start time is displayed.
Set Program
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Occupied 1
Un
Start Time
PM
Wed
M4961A
Press Unoccupied Start Time a second time to
set a second Unoccupied Start Time.
Set Program
Un
Occupied 2
Start Time
Wed
M4962B
Unoccupied
Start Time
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Press increase ▲ or decrease key until the
desired start time is displayed.
Set Program
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
Un
System Fan
Occupied 2
PM
Wed
M4963A
Copying a Day
NOTE: The thermostat must be in the program
9 63-4356—1
mode to use the copy feature. Go to step 2 if the thermostat is already in the program mode.
Press Occupied Start Time.
Start Time
Occupied
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Continous Unoccupied
Copy
Occupied
Temp
System Fan
Set Program
Time/Temp
Unoccupied
Temp
Tue
Heat/Cool Settings
Occupied 1
AM
M10255
Page 10
Press Day to select the day to be copied if
different from the day displayed.
Set Program
Start Time
Day
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Occupied 1
AM
Wed
M4966A
Press Day until the day to be copied to is
displayed.
Day
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
System Fan
Wed Thu
M4968A
Press Copy.
Copy
63-4356—1 10
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Wed
M4967A
Press Copy.
NOTE: donE will be displayed for two
seconds and then the normal program display will be shown.
Copy
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool Settings
Copy
System Fan
M4969A
Page 11
Repeat steps through for all the days
desired.
Press Run Program.
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
AM
Setting Program Temperature Setpoints
NOTE: The setpoint temperature range is 40 to
90°F (7 to 31°C) for heating and 45 to 99°F (9 to 37°C) for cooling.
Press Occupied Temp.
Occupied
Temp
System Fan
Set Program
Time/Temp
Unoccupied
Temp
Heat/Cool
Occupied
Settings
Room
Auto
M4954A
Occupied
Temp
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Continous Unoccupied
Copy
Press increase ▲ or decrease key until the
desired temperature is displayed.
Occupied
Temp
System Fan
Set Program
Time/Temp
Unoccupied
Temp
Heat/Cool Settings
Occupied
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Copy
Occupied
Day/Time
Start Time
Continous Unoccupied
11 63-4356—1
Setting
Heat
M4970B
Setting
Heat
M4971B
Page 12
Press Heat/Cool Settings to change between
heat and cool settings.
Heat/Cool
Settings
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Set Program
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
System Fan
Occupied
Setting
Cool
M4972A
Press increase ▲ or decrease key until the
desired temperature is displayed.
Set Program
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Unoccupied Start Time Day
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
Settings
System Fan
Occupied
63-4356—1 12
Setting
Cool
M4973B
Press Unoccupied Temp.
Unoccupied
Temp
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Start Time Day
Clear
Set Program
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool Settings
Copy
System Fan
UnOccupied
Setting
Heat
M4974B
Press increase ▲ or decrease key until the
desired temperature is displayed.
Setting
Heat
M4975B
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Continous Unoccupied
Set Program
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
UnOccupied
System Fan
Page 13
Press Heat/Cool Settings to change between
heat and cool settings.
Heat/Cool
Settings
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Start Time Day
Clear Start Time
Set Program
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
Un
System Fan
Occupied
Setting
Cool
M4976B
Press increase ▲ or decrease key until the
desired temperature is displayed.
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Set Program
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
Un
System Fan
Occupied
Setting
Cool
M4977B
Press Run Program.
Clearing Program Start Times
Press Occupied Start Time or Unoccupied
Start Time until the start time to be cleared is displayed.
Set Program
Start Time
Start Time
AM
AM
Occupied
Start Time
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
System Fan
Mon
Heat/Cool Settings
Occupied 1
Clear
Copy
Press Day until the desired day is displayed.
Day
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Start Time Day
Clear
Copy
Occupied
Temp
System Fan
Set Program
Time/Temp
Unoccupied
Temp
Mon
Heat/Cool Settings
Occupied 1
M4955A
M4978A
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
AM
Room
Auto
M4954A
13 63-4356—1
Page 14
Press Clear Start Time.
Set Program
Clear
Start Time
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Mon
Occupied 1
Start Time
M4979B
Repeat steps through for all the start
times to be cleared.
Press Run Program.
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
63-4356—1 14
AM
Room
Auto
M4954A
Temporary Occupied Override
Setting Temperature Offset for Temporary Override
Press Occupied Temp.
Occupied
Temp
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
System Fan
Occupied
Settings
Press Temporary Occupied.
Temporary
Occupied
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Wed
Setting
Heat
M10231
M4980A
Page 15
Press increase ▲ or decrease key until the
desired temperature offset is displayed (range is 0° to 5°F).
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Start Time Day
Clear Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
M4981A
Press Run Program.
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
AM
Room
M4954A
Using Temporary Override
Press Temporary Occupied.
NOTE: The default temperature setting is the
Occupied setpoint.
Temporary
Occupied
Auto
Press increase ▲ or decrease ▼ key to
change the default setting by the offset (range is 0° to 5°F), if desired.
15 63-4356—1
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
System Fan
Settings
Override
Heat
Setting
M4982B
Page 16
NOTE: If the offset is zero, the default
setting changes in one degree incre­ments. If the offset is 1 through 5, the default setting changes by plus or minus the offset.
Temporary
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Unoccupied Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
System Fan
AM
Wed
Override
Auto
Room
Auto
M4983B
Press Run Program to cancel the override.
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
63-4356—1 16
AM
Room
Auto
M4954A
Using Continuous Unoccupied
Press Continuous Unoccupied.
NOTE: The default temperature setting is the
Unoccupied setpoint. The default appears for five seconds and then the display shows the room temperature.
Continuous
Unoccupied
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Set Current
Temporary
Day/Time
Occupied
Continous
Unoccupied
Start Time Day
Clear
Start Time
Time/Temp
Unoccupied
Occupied
Temp
Temp
Heat/Cool
Settings
Copy
System Fan
Press increase ▲ or decrease ▼ key to
change the default setting, if desired.
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous
Unoccupied
Clear
Time/Temp
Occupied
Unoccupied
Temp
Temp
Heat/Cool
Copy
Settings
System Fan
Setting
Heat
M4984B
Setting
Heat
M10232A
Page 17
Press Heat/Cool Setpoint to change between
heat and cool settings. Use increase ▲ or decrease ▼ key to adjust temperature settings.
Press Run Program again to cancel the Hold
and to return to the program.
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Temp
Temp
Clear
Copy
System Fan
Mon
Heat/Cool Settings
Occupied 1
System Fan
Heat
AM
M4954A
Room
NOTE: If or appear under the tempera-
ture display, it means that both the heating and cooling setpoints are being adjusted. Tapping the key will change both the heat and cool setpoints by one degree. Press Heat/Cool Settings after the desired setpoint is reached to review the settings.
Auto
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time Day
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Start Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Temp
Temp
Clear
Heat/Cool
Copy
System Fan
Occupied
Settings
Temporary Setting
Heat
M4987B
Changing Temperature Setpoint Until Next Program Period
Press increase ▲ or decrease key until the
desired temperature is displayed.
17 63-4356—1
Press Run Program to cancel the temporary
setpoint and to return to the program.
Run
Program
Set Program Set Temperature Change
Unoccupied
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous
Unoccupied
Start Time Day
Clear
Start Time
Time/Temp
Occupied
Unoccupied
Temp
Temp
Mon
Heat/Cool
Copy
Settings
Occupied 1
System Fan
System Fan
Heat
AM
M4954A
Room
Auto
Page 18
TROUBLESHOOTING GUIDE
Symptom Action
Display will not come on. • Check if the circuit breaker is tripped—reset the circuit breaker.
Temperature settings will not change (Example: cannot set the heating higher or the cooling lower).
Heating will not come on. • Check if the circuit breaker is tripped—reset the circuit breaker.
63-4356—1 18
• Check if the fuse is blown—replace the fuse.
• Check if the system switch at the equipment is in the Off position— set to the On position.
• Check wiring between thermostat and HVAC equipment—replace any broken wires.
• If 24 Vac is present, proceed with troubleshooting.
• Check that the temperature setpoints are:
- heating: 40 to 90°F (7 to 31°C)
- cooling: 45 to 99°F (9 to 37°C).
• Keyboard is locked. Contact the installer.
• Check if the fuse is blown—replace the fuse.
• Check if the system switch at the equipment is in the Off position— set to On position.
• If 24 Vac is present, proceed with troubleshooting.
• Wait five minutes for the system to respond.
• Set system selection to Heat.
(Continued)
Page 19
TROUBLESHOOTING GUIDE
Symptom Action
Cooling will not come on. • Check if the circuit breaker is tripped—reset the circuit breaker.
System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers.
(Continued)
• Check if the fuse is blown—replace the fuse.
• Check if the system switch at the equipment is in the Off position— set to On position.
• If 24 Vac is present, proceed with troubleshooting.
• Wait five minutes for the system to respond.
• Set system selection to Cool.
Wait a minute after seeing the flame or snowflake and then check the registers.
19 63-4356—1
Page 20
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9
Helping You Control Your World
®
63-4356—1 J.H. Rev. 12-96 Printed in Taiwan R.O.C.
63-4356—1 20