Honeywell Sensepoint XCD Data sheet

Sensepoint XCD
Flammable, toxic and oxygen gas detector for industrial applications
Use 3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from flammable, toxic and
Electrical
Current Output Sink or source Relays 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energized/de-energised (programmable)
Communication RS485, MODBUS RTU
Construction
Material Housing: Epoxy painted aluminium alloy ADC12 or 316 stainless steel Sensor: 316 stainless steel
Weight (approx) Aluminium Alloy LM25: 4.4lbs 316 Stainless Steel: 11lbs
Mounting Integral mounting plate with 4 x mounting holes suitable for M8 bolts. Optional pipe mounting kit for horizontal or vertical pipe Ø1.5 to 3" (2" nominal)
Cable Entries UL\cUL versions: 2 x ¾”NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating; ATEX/IECEx versions: 2 x M20 cable entries
Environmental
IP Rating IP66 in accordance with EN60529:1992
Certified Temperature Range 40ºF to +149ºF (-40ºC to +65ºC)
Detectable Gases and XCD Sensor Performance
Gas User Selectable
Electrochemical Sensors
Oxygen 25.0%Vol. only 25.0%Vol. n/a 20.9%Vol. (Fixed) 20.9%Vol. <30 <±0.5%Vol. -20°C / -4°F 55°C / 131°F 19.5%Vol.
Hydrogen Sulfide* 10.0 to 100.0ppm 50.0ppm 0.1ppm
Carbon Monoxide** 100 to 1,000ppm 300ppm 100ppm 100ppm <30 <±6ppm -20°C / -4°F 55°C / 131°F 30ppm p 100ppm p
Hydrogen 1,000ppm only 1,000ppm n/a 500ppm <65 <±25ppm -20°C / -4°F 55°C / 131°F 200ppm p 400ppm p
Nitrogen Dioxide*** 10.0 to 50.0ppm 10.0ppm 5.0ppm 5.0ppm <40 <±3ppm -20°C / -4°F 55°C / 131°F 5.0ppm p 10.0ppm p
* Lowest Alarm Limit = 1ppm; Lowest Detection Limit = .5ppm ** Lowest Alarm Limit = 15 ppm; Lowest Detection Limit = 10ppm *** Lowest Alarm Limit = 0.6 ppm; Lowest Detection Limit = 0.3ppm
Catalytic Bead Sensors
Flammable 1 to 8 20.0 to 100.0%LEL 100%LEL 10%LEL 50%LEL <25 <±1.5%LEL -20°C / -4°F 55°C / 131°F 20%LEL
Infrared Sensors
Methane 20.0 to 100.0%LEL 100%LEL 10%LEL 50%LEL <30 <±1.5%LEL -20°C / -4°F 50°C / 122°F 20%LEL
Propane 20 to 100%LEL 100%LEL 10%LEL 50%LEL <30 <±1%LEL -20°C / -4°F 50°C / 122°F 20%LEL p 40%LEL p
Carbon Dioxide 2%Vol. only 2%Vol. n/a 1%Vol. <30 <±0.04%Vol. -20°C / -4°F 50°C / 122°F 0.4%Vol. p 0.8%Vol. p
NOTE: For Cat Bead and Infrared sensors, Lowest Detectable Limit is 5% LEL and Lowest Alarm Level is 10% LEL.
Certification
US, Latin America, Canada UL/c-UL - Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II, Division 1, Groups E, F & G, Class II, Division 2, Groups F & G. -40°C to +65°C European ATEX Ex II 2 GD Ex d IIC Gb T6 (Ta -40ºC to +65ºC) Ex tb IIIC T85°C Db IP66 International IEC Ex d IIC Gb T6 (Ta -40ºC to +65ºC) Ex tb IIIC T85°C Db IP66
EMC CE: EN50270:2006 EN6100-6-4:2007
Performance UL508; CSA 22.2 No. 152 (flammable gasses, excludes infrared sensors); ATEX, IEC/EN60079-29-1:2007, EN45544, EN50104, EN50271; China: PA Pattern
Oxygen hazards. Incorporates a transmitter with local display and fully configurable via non-intrusive magnetic switch interface.
and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC
Alarm relays default normally open/de-energized. Fault relay default normally open/energized
Full Scale Range
Measurement (for transmitter and toxic gas sensors) “CCCF” Shenyang for Flammable (fire dept approval)
Default
Range
Steps User Selectable
Cal Gas Range
30 to 70% of selected
full scale range
Point
Response Time
(T90) Secs
Default Cal
25ppm <50 <±1ppm -20°C / -4°F 55°C / 131°F 10ppm p 20ppm p
Accuracy Operating Temperature
Min Max
Default Alarm Points
A1 A2
p - Rising Alarm q - Falling Alarm
Find out more
www.honeywellanalytics.com Toll-free: 800.538.0363
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract.
SS01082_v4 3/14 © 2014 Honeywell Analytics
q 23.5%Vol. p
p 40%LEL p
p 40%LEL p
Loading...