Searchpoint Optima Plus
Infrared Point Gas Detector
Page 2
MAN0551 Issue 07 - 09/08
2108M0501
TOTAL ENVIRONMENTAL SOLUTIONS
Ensure that you read and understand these Operating
Instructions BEFORE installing or operating any part of the
Searchpoint Optima Plus.
Please pay particular attention to the Safety Warnings.
WARNINGS
1. For installations in the UK, the Code of Practice
SELECTION, INSTALLATION AND MAINTENANCE
OF ELECTRICAL APPARATUS FOR USE IN
POTENTIALLY EXPLOSIVE ATMOSPHERES should
be strictly observed. General recommendations are
given in BS5345: Part 1: 1989. Specic requirements
for ameproof (Type 'd'), intrinsically safe (Type 'i')
and increased safety (Type 'e') protection are given
in BS 5345: Part 3: 1979, BS 5345: Part 4: 1977 and
BS5345: Part 6: 1978 respectively.
For installations in North America, the National
Electrical Code (NFPA 70 - 1990) or later issues
should be strictly observed.
Elsewhere the appropriate local or national
regulations should be used.
2. The Code of Practice regarding SELECTION,
INSTALLATION, USE AND MAINTENANCE
OF APPARATUS FOR THE DETECTION AND
MEASUREMENT OF COMBUSTIBLE GASES
(OTHER THAN FOR MINING APPLICATIONS OR
EXPLOSIVES PROCESSING AND MANUFACTURE)
must be complied with. Refer to BS6959:1988 in the
UK or the appropriate local or national regulations.
3. Operators must be fully aware of the action to be
taken if the gas concentration exceeds an alarm
level.
2
Page 3
MAN0551 Issue 07 - 09/08
2108M0501
TOTAL ENVIRONMENTAL SOLUTIONS
CAUTIONS
1. Use only approved parts and accessories with the
Searchpoint Optima equipment.
2. To maintain safety standards, a planned maintenance
programme is strongly recommended. This
maintenance programme should take account of all
operational conditions and requirements. Maintenance
and service operations should only be performed by
personnel qualied to work upon Searchpoint Optima
Plus.
3. In order to maintain electrical safety, the unit must
not be operated in atmospheres with more than 21%
oxygen.
IMPORTANT NOTICES
1. Honeywell Analytics Limited can take no responsibility
for installation and/or use of its equipment if this is not
done in accordance with the appropriate issue and/or
amendment of the manual.
2. The user of this manual should ensure that it is
appropriate in all details to the exact equipment to be
installed and/or operated. If in doubt, the user should
contact Honeywell Analytics Limited for advice.
3. If further details are required which do not appear in
this manual, contact Honeywell Analytics Limited or
one of their agents.
4. The Searchpoint Optima System is certied for and
intended for use in potentially hazardous areas.
Install and use the Searchpoint Optima System in
accordance with the latest regulations.
Honeywell Analytics Limited reserve the right to change
or revise the information supplied in this document
without notice and without obligation to notify any person
or organisation of such revision or change.
3
Page 4
MAN0551 Issue 07 - 09/08
2108M0501
HELP US TO HELP YOU
Every effort has been made to ensure the accuracy in the
contents of our documents, however, Honeywell Analytics
Limited can assume no responsibility for any errors or
omissions in our documents or their consequences.
Honeywell Analytics Limited would greatly appreciate being
informed of any errors or omissions that may be found in the
contents of any of our documents and to this end we include
the form opposite for you to photocopy, complete and return
to us so that we may take the appropriate action.
4
Page 5
MAN0551 Issue 07 - 09/08
2108M0501
5
Page 6
MAN0551 Issue 07 - 09/08
2108M0501
CONTENTS
Section Page
1. INTRODUCTION 10
1.1 General 10
2. INSTALLATION VARIATIONS 14
2.1 ATEX Units 14
2.2 UL and CSA Units Only 15
3. INSTALLATION 17
3.1 Unpacking 17
3.2 Siting and Orientation 17
3.3 Installation Guide 18
3.4 Attachments and Options 22
3.4.1 General 22
3.4.2 Standard Weather Protection 22
3.4.3 Sunshade/Deluge Protection 22
3.4.4 Storm Bafe 23
3.4.5 Dust Barrier 23
3.4.6 Calibration Cap 24
3.4.7 Gassing Cover 24
3.4.8 Flow Housing 25
3.4.9 Remote Gassing Cell 26
3.4.10 Junction Box Adaptor Plate 27
3.4.11 European Duct Mounting Kit 28
3.4.12 US Duct Mounting Kit 31
6
Page 7
MAN0551 Issue 07 - 09/08
2108M0501
CONTENTS
Section Page
4. ELECTRICAL CONNECTIONS 35
4.1 General 35
4.2 Analogue Connection 40
4.3 Digital Connection 40
4.4 +24V Power Connection 41
4.5 Earth Connection 41
5. COMMISSIONING 46
5.1 General 46
5.2 Commissioning Procedure using SHC-1
and Multimeter 47
5.2.1 Electrical Commissioning and Tests 47
5.2.2 Gas Response Testing 48
5.2.3 System Level Testing 49
5.2.4 Final Commissioning 51
5.3 Commissioning Procedure with Multimeter
Only 52
5.3.1 Electrical Commissioning and Tests
(Multimeter) Only 52
5.3.2 Gas Response Testing (Multimeter)
Only 54
5.3.3 System Level Testing 55
5.3.4 Final Commissioning (Multimeter) 56
5.4 Control System Setup 57
5.5 Functional Response Checking and
Calibration 57
7
Page 8
MAN0551 Issue 07 - 09/08
2108M0501
CONTENTS
Section Page
6. CALIBRATION 59
6.1 General 59
6.2 SHC-1 Hand-Held Interrogator 60
6.2.1 Connecting the Hand-Held
Interrogator 61
6.2.2 Hand-Held Interrogator Operating
Modes 62
6.2.3 Other Hand-Held Features 66
6.3 Calibrating the Controller 70
6.4 Calibrating the Sensor 73
7. ROUTINE CHECKS 81
7.1 General 81
7.2 Inspection and Functional Response Check
Procedure 81
7.2.1 Response Check Using Gassing Cover
and %LEL Concentration Gas 83
7.2.2 Response Check Using Remote
Gassing Cell & High %VV Gas 87
7.3 Inspection and Testing of Units Installed
in Ducts 92
7.4 Removal and Retting of Flow Housing 94
7.4.1 Removal of Flow Housing 94
7.4.2 Retting of Flow Housing 94
8
Page 9
MAN0551 Issue 07 - 09/08
2108M0501
CONTENTS
Section Page
8. FAULT FINDING 97
8.1 Troubleshooting 97
8.2 Diagnosis of Warning and Fault Messages 103
9. REPLACEMENT OF HAND-HELD
INTERROGATOR BATTERY 111
10. ORDERING DETAILS 113
11. SPECIFICATION 117
11.1 Searchpoint Optima Plus Specication 117
11.2 Cross Interference to Other Gases and
Vapours 124
11.3 Hand-Held Interrogator SHC-1
Specication 125
11.4 SHC Protection Device 126
11.5 Termination Unit DVC100 Specication 127
11.6 DX Termination Units Specication 128
12. CERTIFICATION DETAILS 130
13. WARRANTY 137
9
Page 10
MAN0551 Issue 07 - 09/08
Optical Block
WindowHeaterMirror
Heater
Gas Measuring Path
2108M0501
1. INTRODUCTION
1.1 GENERAL
Searchpoint Optima Plus is designed for use in potentially
hazardous areas where it provides gas and vapour
detection which is free from poisoning and independent
of the presence of oxygen. The gas measuring parts of
Searchpoint Optima Plus are illustrated below.
Searchpoint Optima Plus uses the dual wavelength infrared
absorption principle to detect hydrocarbon gases and
vapours in various concentration ranges. The instrument
measures the number of molecules of the target gas in the
light path, which depends on the concentration of the target
gas. In addition to the relatively long and open measuring
chamber, Searchpoint Optima Plus can be tted with a short
enclosed ow through-cell as part of the chassis.
This is tted with separate inlet and outlet ports and
allows the application of high concentrations of gas for
test purposes.
10
Page 11
MAN0551 Issue 07 - 09/08
2108M0501
1. INTRODUCTION
Searchpoint Optima Plus is a micro-processor controlled,
Infrared Gas Detector with comprehensive built-in self-
diagnostic and fault nding facilities. An analogue 4 to
20mA output and digital communications are provided as
standard. Full two way communication allows calibration
and advanced self checking procedures to be used. To take
advantage of these features a Hand-Held Interrogator unit
may be connected to a Termination Unit or via the SHC
Protection Device to other junction boxes.
There are several different types of termination unit available:
Termination UnitCertication Output
DVC Type Termination Units
DVC100 (I) MK2ATEXIsolated 4-20mA
DVC100 (M) MK2 ATEXIsolated 4-20mA and MODBUS
DX Type Termination Units
DVC100 (I)ULIsolated 4-20mA
DX100 (M)ULIsolated 4-20mA and MODBUS
Searchpoint Optima Plus contains no moving parts and
is available in a robust Stainless Steel explosion proof
enclosure which has a M25 (ATEX) or 3/4 NPT (UL and CSA)
mounting thread. The unit operates over a wide temperature
range and has a high degree of protection against dust
and water ingress. It is designed to operate in the most
arduous conditions and is supplied with a choice of weather
protection assemblies.
Searchpoint Optima Plus can be In-Duct Mounted, used
in Sampling Systems, is easily condence checked and
may easily replace an existing sensor. Provided that
existing cabling has three appropriately rated cores and the
installation is correctly screened and earthed, it should not
be necessary to replace the eld cables or junction boxes. (A
current to bridge converter may be required if the controller
cannot be congured to accept 4-20mA signals).
11
Page 12
MAN0551 Issue 07 - 09/08
2108M0501
1. INTRODUCTION
No special tools are required for installation. Correct
function of the detector as installed can be easily conrmed
using a Hand-Held Interrogator. Maintenance amounts to
occasional cleaning, zeroing and response checking for
condence.
12
Page 13
MAN0551 Issue 07 - 09/08
2108M0501
13
Page 14
MAN0551 Issue 07 - 09/08
Existing Junction Box
Existing Cable
Optima
2108M0501
2. INSTALLATION VARIATIONS
2.1 ATEX UNITS
Replacing existing Sensor
using existing Junction Box
and Cable (where suitable).
New Junction Box.
New Installations.
Optima
Optima
DVC Termination Unit
When used for calibration
and diagnostics purposes
the Hand-Held Interrogator
SHC-1 allows digital
communication with the
Optima. It is connected
to the Optima via the IS
Socket on the Termination
Unit DVC100 or via the
SHC Protection Device for
other junction boxes.
SHC-1
14
Page 15
MAN0551 Issue 07 - 09/08
3/4 NPT
Optima
2108M0501
2. INSTALLATION VARIATIONS
2.2 UL AND CSA UNITS ONLY
UL and CSA Installations using
Explosion Proof
Junction Box.
Note: The Junction Box must be suitable for the hazardous
location in which the Optima is installed, check with the
Junction Box manufacturers literature as to suitability of
the box.
Optima
15
Field
Cable /
Conduit
Top
DX
Termination
Unit
Handheld
Interrogator
Socket
Page 16
MAN0551 Issue 07 - 09/08
2108M0501
16
Page 17
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
WARNING
The Code of Practice regarding selection, installation
and maintenance of electrical apparatus for use in
potentially explosive atmospheres must be complied
with at all times.
Notes:1. The flying leads of the Searchpoint Optima Plus
must be mechanically protected and terminated
within a suitable terminal or junction facility.
2. When the detector is terminated in a hazardous
area a suitable UL listed enclosure must be used
(where appropriate).
3.1 UNPACKING
Carefully unpack the equipment, observing any instructions
that may be printed on or contained in the packaging, and
check the contents for transit damage.
3.2 SITING AND ORIENTATION
Searchpoint Optima Plus must
be mounted horizontally, as
this greatly reduces the risk of
obscuration due to build up of
dirt and moisture on the optical
surfaces.
Ensure the area immediately
surrounding the sensor is free
from objects that could hinder
the free ow of air around it.
17
Page 18
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
For monitoring lighter than air gases, Searchpoint Optima
Plus should be mounted above the area requiring protection.
For monitoring heavier than air gases it should be mounted
below the area to be protected.
When monitoring for heavier than air gases and mounting
the detector close to the oor, give consideration to the
potential of general site debris to build up on the detector.
Whether Searchpoint Optima Plus is installed in a
sheltered or an exposed location, it will require some form
of protection around the optics. The standard weather
protection combined with the sunshade/deluge protection
provides a high degree of protection of the detector, suitable
for many outdoor environments. Detectors operating in very
exposed locations where torrential rain or driven sea-spray
is routinely encountered can benet from the additional
protection provided by the Storm Bafe (2108D0280).
In areas where a high pressure jet may be used at close
range to wash down the surrounding location, it is advisable
to t some means of extra peripheral shielding,
Bafe or a shield plate.
eg. Storm
Accessories and attachments that can be used to improve
ease-of-use, performance and reliability in particular
installations are described in Section 3.4.
3.3 INSTALLATION GUIDE
Note: Installation of Searchpoint Optima Plus does not require
the unit to be opened. There are no user serviceable
parts inside the unit. Do not attempt to open or
dismantle the unit.
(1) Ensure that the correct attachments and accessories
for the application have been tted (see Section 3.4).
18
Page 19
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
(2) Check that the unit's 4-20mA current ouput is of the
correct type for the control card that it is connected to.
(Output type is on a label attached to white lead.)
Control card I/P: SINK Optima O/P: SOURCE
Control card I/P: SOURCE Optima O/P: SINK
(3) Secure the junction box onto the mounting surface,
using the Junction Box Adaptor Plate if required.
Searchpoint Optima Plus must be installed with it's
long axis horizontal in order for the standard weather
protection to operate correctly and to prevent water
from settling on the optical surfaces (see below).
The Optima unit should therefore only be screwed into
a threaded entry that is in a vertical wall of the junction
box.
37
(4) Feed the unit's wires carefully through the chosen
junction box entry and offer up it's threaded boss to
the entry. Screw the unit into the junction box until
it is secure and the semi-circular pattern of holes on
the front of the weather protection are on the bottom
(see below). For M25 entries, the boss should go right
through the wall and a locking nut should be tted;
whilst for 3/4 NPT entries, the boss should lock off on
the taper. If getting the holes in the right orientation
requires more rotation than is readily achievable,
remove the weather protection and rotate it through
180 degrees.
19
Page 20
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
(5) Using a multimeter, check that the voltages on the
+24V, and 4-20mA connections with respect to 0V are
less than +32V DC and that there is no 110V or 230V
AC around.
(6) Wire up the unit's electrical connections in
accordance with Section 4, taking note of the general
recommendations upon electrical installation.
(7)
Ensure that all cable entries are either used or plugged
in strict accordance with the relevant certication
requirements and local codes of practice.
(8) Verify the correct installation and operation of the unit
using the SHC-1 handheld interrogator. If a Termination
Unit has been used, testing can be performed without
the need for a hot work permit. Alternatively, if a basic
junction box has been used, electrical connections can
be made to the terminals inside the box using the SHC
adaptor. This will ordinarily require a hot work permit.
CAUTION
1. Searchpoint Optima Plus is certied and specied
for operation in ambient temperatures from -40°C
to +65°C. Operation of the unit outside of this
temperature range invalidates the certication and
the warranty. The unit records a non-erasable fault
log entry if it is operated at temperatures outside of
it's certied range.
If the ambient temperature that the unit could be
exposed to is likely to go outside of the certied
range it is recommended that the unit be located
elsewhere. The use of sampling systems can be
highly effective, especially in applications where
high temperatures are involved.
20
Page 21
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
2. Searchpoint Optima Plus is specied for operation
in environments where the rate of change of unit
temperature is less than 3°C / minute. Exceeding
this rate of change of temperature will cause the unit
to report a fault and may cause permanent damage.
If the conditions experienced by the unit are likely
to cause it to exceed this rate of change it is
recommended that additional preventative measures
are taken. The use of sampling systems is highly
effective; whilst shielding the unit from the prevailing
air ow can also be of benet.
3. Searchpoint Optima Plus has been vibration tested
to the levels specied in EN61779. If the vibration
levels on the installation exceed this, the unit's
reliability and integrity of operation will be degraded.
Do not install units in locations where the vibration
exceeds this level.
4. All optical gas detectors are eventually affected by
the build up of contaminants / condensation upon
their optical surfaces, normally resulting in faults
or warnings. In order to minimise the faults and
warnings caused by this it is recommended that
detectors are located as far away as is possible
from sources of airborne contaminants and steam /
condensation. Alternatively, the tting of shields or
the Storm Bafe (2108D0280) should be considered.
Sources of contamination / condensation that have
caused particular problems where appropriate
measures were not taken include generator / turbine
exhausts, steam lines / vents, drilling operation
(oilmist and mud spray) and unltered HVAC
installations. In dusty atmospheres, regularly check
for the build up of dust on the detector (refer to
section 7 Routine Checks).
21
Page 22
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
3.4 ATTACHMENTS AND OPTIONS
3.4.1 General
There are a number of attachments and accessories
available for use with Searchpoint Optima Plus. When
specifying Optima Plus for a particular application, it is
recommended that the user contacts Honeywell Analytics
or their representatives to determine the attachments and
accessories required. Covers, barriers and bafes provide
protection from a wide variety of environmental conditions.
Gassing covers, cells and ow housings provide the means
of applying gas to the detector. Mounting plates and remote
gassing kits enable the detector to be installed in ducts or in
places where obtaining routine access is difcult.
3.4.2 Standard Weather Protection (2108D0276)
Provides the best compromise
between response time and
protection. Suitable for indoor,
outdoor and duct mounting
applications.
3.4.3 Sunshade/Deluge Protection (2108D0275)
Supplied as standard
for all outside
applications. Provides
additional protection
against heavy rainfall,
wash downs and
direct sunlight.
22
Page 23
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
The Sunshade/
Deluge protection
should be clamped
around the base of
the Standard Bafe
Weather Housing with
the longer overhang
extending beyond
the Standard Bafe.
Ensure the clamp
does not cover the
gas venting slot of the
Standard Bafe.
3.4.4StormBafe(2108D0280,NotIllustrated)
The storm bafe provides increased protection against
a variety of environmental conditions and effects. It is
particularly effective against torrential rain and driven
sea-spray and is recommended for exposed installations
in maritime locations or areas where monsoon or tropical
rain conditions are experienced. The storm bafe can be
benecial in installations where steam drifting over the
detector from nearby plant is a problem. The storm bafe
can also be useful in some duct applications where the
inlets are not ltered and where high ow rates result in dirt
build-up or excessive cooling / condensation effects. This
accessory will reduce the detector’s speed of response.
3.4.5DustBarrier(2108D0259,NotIllustrated)
Fits under the standard bafe weather housing to prevent
the ingress of dust or oil mist which could contaminate the
optical surfaces. It also protects the optics in very wet or
exposed locations. This accessory will reduce the detector’s
speed of response.
23
Page 24
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
3.4.6 Calibration Cap (2108D0272)
Used to achieve accurate
calibration of Optima Plus on the
bench. Requires all protective
covers and attachments to be
removed from the measurement
chamber except for the
dust barrier. The calibration
procedures are described in
Section 6.
CAUTION
The Calibration Cap is designed for temporary use on
Optima whilst performing calibration. If the calibration
cap is left tted it will prevent ambient gas from reaching
the detector's measurement chamber. Ensure that
operators are aware that calibration caps must not be
left tted. In order to reduce the likelihood of this mistake
going un-noticed, the calibration caps are coloured red.
3.4.7 Gassing Cover (2108D0258)
Provides a convenient means
of applying gas to Optima Plus
units in the eld. Suitable for
functional test and calibration
purposes. Fits over the standard
weather protection, covering the
gas inlet slots. Gas is introduced
into the weather protection via
an injection tube on the gassing
cover. Injected gas diffuses
through the dust barrier into the
measurement chamber.
The response check procedure
is described in Section 5.4.
24
Page 25
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
CAUTION
The Gassing Cover is designed for eld testing and
calibration operations. If the cover is left tted it will
prevent ambient gas from reaching the detector's
measurement chamber. Ensure that operators are aware
that gassing covers must not be left on detectors.
Gassing covers are coloured red to reduce the likelihood
of this mistake.
3.4.8 Flow Housing (2108D0282)
For use in sampling system
applications.
The Flow Housing is fabricated
from solvent resistant Anodised
Aluminium.
The nozzles on the Flow Housing
are stainless steel with an outside
diameter of 6mm.
It is advised that sample gases and vapours are sucked
(negative pressure) rather than blown (positive pressure)
through this housing and that sample ow rates do not
exceed 2 litres per minute.
It is recommended that a ow failure indicator is tted
within the sampling system and the minimum ow rates are
suitable for the application and not less than 0.7 litres per
minute.
Note: response time will increase with a decreasing ow
rate.
The commissioning and calibration of an Optima equipped
with a ow housing is described in Sections 5 and 6.
It is useful for units installed in ducts or in areas
where obtaining access is difcult. The RGC window
can be removed for cleaning.
Note:
During production, Optima Plus units are calibrated
with gas in the main measurement chamber, not in the
RGC. The RGC is not recommended for calibration
or high accuracy calibration testing purposes.
(The only exception to this is where units are being
used to measure high %V/V gases using the RGC as
a flow cell. In this instance, the units are production
calibrated with gas in the RGC.)
In order to avoid pressurisation effects, the ow rate should
be kept below 0.3 litres / minute.
The RGC option is factory tted.
26
Page 27
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
3.4.10 Junction Box Adaptor Plate (04200-A-1040)
The Junction Box Adaptor Plate provides a means of
increasing the spacing between the junction box's gland
entries and the mounting surface. This enables low gland
clearance junction boxes to be used without the Optima
Plus fouling on the wall / mounting surface. Junction boxes
which can be accommodated include the Hawke PL612 and
PJB1.
27
Page 28
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
3.4.11 European Duct Mounting Kit (04200-A-1015)
This kit enables Optima Plus to be conveniently mounted
inside a duct. Electrical connections are made to the
detector via a junction box which is mounted outside of the
duct. Using this kit, test gas can be non-invasively applied to
the detector via the gassing points provided.
250
Note 1: Dimensions
shown in mm.
250
125
63
63
125
188
250
Note 2: The cutout
250
in the duct should be
188
230mm x 230mm.
28
Page 29
MAN0551 Issue 07 - 09/08
Gassing
Points
Searchpoint
Optima
Duct
Mounting
Junction
Box
Bracket
Junction
Box
2108M0501
3. INSTALLATION
Notes: 1. In order to make use of the gassing points provided,
the Optima unit must be fitted with the Remote Gassing
Cell (2108B0240).
2. In offshore HVAC ducts or ducts without inlet
filtering, the use of the Storm Baffle (2108D0280) is
recommended.
3. CSA approval only applies for flow rates less than 5
m/s and does not cover the use of the Storm Baffle.
The duct mounting kit is assembled and installed onto a duct
as below:-
(1) Cut a square 230mm * 230mm hole in the duct wall. Drill
the holes required to attach the mounting plate to the duct
wall.
(2) Place the Optima unit on the side of the mounting plate
where the threaded bushes protrude and feed the wires
through the central hole.
29
Page 30
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
(3) Locate the unit's boss in the central hole and feed the
unit's wires through the chosen cable entry on the junction
box.
(4) Screw the unit into the junction box until the assembly is
secure with the mounting plate trapped between the box and
the Optima.
(5) Cut off the seals on the ends of the gassing cell inlet
tubes.
(6) Attach the gassing tubing to the ends of the gassing cell
inlet tubes.
(7) Fasten the mounting plate to the wall of the duct,
ensuring that the seal is compressed.
(8) Wire up the unit in accordance with the electrical
connection details in Section 4.
(9) Ensure that all cable entries are either used or plugged in
strict accordance with the relevant certication requirements
and local codes of practice.
30
Page 31
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
3.4.12 US Duct Mounting Kit
This kit enables Optima Plus to be conveniently mounted
inside a duct. Electrical connections are made to the
detector via a junction box which is mounted outside of the
duct. Using this kit, test gas can be non-invasively applied to
the detector via the gassing points provided.
Note 1: Dimensions shown in inches.
31
Page 32
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
The duct mounting kit is assembled and installed onto a duct
as below:-
(1) Cut a square 6" x 6" hole in the duct wall. Drill the holes
required to attach the mounting plate to the duct wall.
(2) Remove the cover from the junction box.
32
Page 33
MAN0551 Issue 07 - 09/08
2108M0501
3. INSTALLATION
(3) Feed the wires from the Searchpoint Optima Plus through
the weldment into the junction box. DO NOT SECURE THE
WIRES TO THE TERMINALS AT THIS TIME.
(4) Secure the sensor to the weldment.
(5) Attach the both tubing assemblies.
(6) Secure the mounting plate to the duct.
33
Page 34
MAN0551 Issue 07 - 09/08
2108M0501
34
Page 35
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
CAUTION
The reliability and performance of instrumentation
installed at industrial and petrochemical facilities can
be strongly inuenced by the design and quality of the
electrical installation. It is strongly recommended that
before designing an electrical installation for Searchpoint
Optima Plus the electrical installation design authority
reads Section 4.1.
4.1 GENERAL
Searchpoint Optima Plus complies with the European EMC
requirements set out in standard EN50270:1999. In order
to maintain compliance with these standards it is essential
that the electrical installation of Searchpoint Optima Plus is
engineered appropriately.
Electrical installation standards and practices vary for
different countries, companies and hazardous area
approvals. It is the responsibility of the electrical installation
design authority to determine the applicable standards
/ practices and ensure compliance with them. When
designing electrical installations for Searchpoint Optima
Plus it is recommended that the design authority considers
the following:-
a. Ideally, the cases of units should not be connected
to electrically noisy (dirty) metalwork or conductors.
Preferably, the case (internally connected to the unit’s
green / yellow GND wire) should be connected to a
low noise instrument (clean) earth.
b. Preferably, the eld cable screen should be connected
to the unit’s green / yellow GND wire, providing a
single, continuous earth screen connected to a low
noise instrument (clean) earth. This connection must
35
Page 36
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
not be allowed to complete an earth loop or connect
instrument earth to safety earth.
c. If armoured cable is being used it is necessary to
prevent safety (dirty) earth from becoming connected
to instrument (clean) earth via the continuity plate in
the eld junction box. This is most easily achieved by
the use of insulating cable glands for the eld cable
entry.
d. For UL / CSA certied installations it is not practical to
isolate the unit’s case from safety (dirty) earth. The unit
and its junction box should be earthed in a manner
that complies with the certication requirements.
e. Any earth / ground bonding arrangement employed
should ensure that the maximum peak voltage
between the unit’s case earth and any eld cable
conductor is less than 350V. This includes conditions
where transient surge voltages are generated
by lightning or the switching of heavy electrical
plant. Surge voltages in excess of 350V can cause
permanent damage to the unit’s RFI lters and such
damage is not covered by warranty.
f. Earthing / grounding arrangements that employ
multiple protective earths or earth grids signicantly
increase the likelihood of large transient surge voltages
being generated between a unit’s case earth and the
eld cable conductors.
g. If it is suspected that the earth / ground bonding
arrangement employed will not prevent voltages
between the unit’s case earth and any eld cable
conductor from exceeding 350V it is strongly
recommended that surge suppression devices be
installed close to the unit. Suitable, certied surge
suppression devices include MTL’s TP-48-I-NDI and
36
Page 37
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
Pepperl & Fuchs’ FN-LB-1. Two of these devices are
sufcient to provide protection of the +24V, 0V,
4-20mA and RS485 (A) connections to a unit.
h. In general, correctly engineered star earthing
arrangements minimise earth current crosstalk and
noise, improving the reliability and performance of
instrumentation.
i. Low noise instrument (clean) earth should only be
connected to safety earth (usually dirty) at a single
point on a site / installation. This connection should
be made in such a manner that it does not introduce
noise onto the instrument earth.
j. The entire length of the eld cabling connected to
a unit should be screened / shielded. This screen /
shield should be connected to a low noise instrument
(clean) earth at a single end. (The screen / shield can
be connected to the unit’s earth in the junction box,
provided that this is isolated from all other earths /
grounds.)
k. For installations where the eld cable conductors run
through conduit or armour connected to safety (dirty)
earth, the conduit or armour should not be considered
as a sufcient screen / shield. A separate cable screen
/ shield, connected to a low noise instrument earth
should be employed.
l. The screens / shields of eld cabling should not be
connected in a manner that creates earth loops or
that will result in the screens / shields carrying large
currents from heavy plant or equipment.
m. The use of a single, screened / shielded cable for
each eld device ensures good screening / shielding
and reduces crosstalk. Cabling arrangements that use
a single cable to connect a number of eld devices
37
Page 38
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
compromise screening and increase the potential
for crosstalk. Such arrangements should only be
employed if the electrical installation design authority
is condent that this will not adversely affect the
reliability or performance of the system.
n. Any electrical interference induced onto the
conductors of a 4-20mA loop by the installation must
be kept below the levels necessary to comply with the
general requirements of EN61779 or other applicable
gas detector performance requirements / standards.
In practice, this means that peak noise currents
induced on the current loop should be no greater than
+/- 0.25mA. If peak noise currents larger than this are
induced on the current loop it is possible that spurious
gas readings, alarms and faults will be reported by the
control system monitoring the current loop.
o. The 0V rail of a control card / control system is often
connected directly to one side of the 4-20mA input’s
current sensing resistor. In such instances, any
electrical noise on the 0V rail can be considered to
be directly connected to the 4-20mA input. In order
to reduce the likelihood of such noise adversely
affecting the performance of a gas detection system it
is desirable to keep noise on the 0V rail to a minimum.
Safety earth / ground frequently carries a high level
of electrical noise and it is therefore advisable not to
connect the 0V rail to safety earth / ground. If the 0V
rail cannot be isolated from earth it is advisable to
either connect it to a low noise instrument (clean) earth
or through a path that presents a high impedance to
noise on the earth.
p. For installations in Europe, all electrical equipment
connected to the system should comply with
EN50270. For non-European installations, electrical
equipment connected to the system should comply
with applicable national or international EMC
standards.
38
Page 39
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
q. Searchpoint Optima Plus is designed to operatecorrectly with supply voltages down to 18V. When
supplied with 18V, the maximum current drawn
by a single Searchpoint Optima Plus unit will be
250mA. The eld cabling conductors should have
sufcient cross sectional area to ensure that when
a unit is drawing 250mA the voltage reaching it does
not fall below 18V. For a control room voltage of 24V,
the maximum round loop cable resistance must
therefore be 24 Ohms. Round loop cable resistances
greater than those necessary to ensure that units
always receive at least 18V may result in unreliable
operation.
r. Ideally, the 24V supply reaching units should be free
from large transients, uctuations or high frequency
noise. Transients or uctuations which take the
supply voltage outside of the 18-32V range may
result in units switching off and re-booting.
s. In order to reduce the likelihood of radio frequency
interference affecting the operation of units it is
recommended that neither units nor their cabling are
installed in close proximity to the antennae of high
powered radio, radar or satellite communication
equipment.
39
Page 40
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
4.2 ANALOGUE CONNECTION
The unit’s analogue 4-20mA output is non-isolated and
shares the 0V return (black wire) connection with the DC
supply to the unit. The 4-20mA output is factory congured
for current source or current sink. The conguration is
identied by a label on the white 4-20mA output wire. The
connections to the unit are shown in the following gures.
Note: If using Searchpoint Optima Plus to replace an existing
catalytic sensor, a Current to Bridge converter must be
used.
4.3 DIGITAL CONNECTION
Searchpoint Optima Plus has a built-in RS485 digital
communications link. When using Termination Units, this link
can be connected to using the IS socket. For other junction
boxes, this link can be connected to using the SHC
Protection Device between the junction box terminals and
the SHC-1 Handheld Interrogator.
40
Page 41
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
The RS485 communications link is connected to the unit’s
orange (RS485(A)) and blue (RS485(B)) wires. If not used,
these wires must be separately terminated in a suitable
terminal or junction facility.
4.4 +24V POWER CONNECTION
The +24V DC power supply feed should be connected to the
unit via the red (+24V) and black (0V return) wires.
4.5 EARTH CONNECTION
An earth connection can be made to the unit in a number of
ways. When deciding how to earth the unit, consideration
should be given to the recommendations in section 4.1.
Physically, the earth connection can be made either via
the unit’s green/yellow earth wire, a metal nut between the
unit and the junction box’s earth continuity plate or a wire
connected to the unit’s external earthing point.
41
Page 42
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
42
Minimum Configuration for Retrofit Application (Optional Current to Bridge Converter)
Page 43
MAN0551 Issue 07 - 09/08
Optional Modbus Output
(M version only)
IS
Socket
SHC-1
Termination Unit
(refer to indicidual Terminal Unit manuals
for specific electrical connections
2108M0501
4. ELECTRICAL CONNECTIONS
Configuration for Termination Unit with IS Socket and Hand-Held Interrogator
43
Page 44
MAN0551 Issue 07 - 09/08
2108M0501
4. ELECTRICAL CONNECTIONS
44
Standard Configuration for Retrofit Application (With SHC Protection Device and Hand-Held Interrogator Option.)
Page 45
MAN0551 Issue 07 - 09/08
2108M0501
45
Page 46
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
5.1 GENERAL
WARNINGS
1. Alarm level signals may be intentionally generated
during the commissioning procedure. Ensure
that appropriate steps are taken to prevent the
unintended sounding of alarms or executive
actions. It is recommended that the control card
corresponding to the detector is isolated or inhibited
during the majority of the commissioning procedure.
2. In order to commission units installed with basic
junction boxes (i.e. not DVC100 or DX100), it will be
necessary to open the junction boxes under power.
This will require the appropriate safe operating
procedures to be employed.
3. The Optima Plus commissioning procedure
is best performed using an SHC-1 Handheld
Interrogator and a digital multimeter. Use of the
SHC-1 interrogator in combination with a multimeter
enables more comprehensive checks and testing
(Section 5.2). If however, an SHC-1 interrogator
is not available, basic commissioning can be
performed using just a multimeter (Section 5.3).
IMPORTANT
Searchpoint Optima Plus is supplied calibrated and
ready for use. It does not require calibration during
commissioning. Reference is made in this section to
a Gas Response Test. This is not a full calibration of
the sensor where zero and span values are set, but a
response test using a known concentration of gas to
validate the calibration of the sensor.
46
Page 47
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
5.2 COMMISSIONING PROCEDURE USING
SHC-1 AND MULTIMETER
5.2.1 Electrical Commissioning and Tests
(SHC-1 & Multimeter)
The procedure for verifying the electrical installation of the
unit is described below:-
(1) Before applying power to the unit, ensure that the eld
wiring is correct and all electrical connections are in
accordance with Section 4.
(2) Check that the unit’s 4-20mA output conguration is
correct for the type of control card that it is connected
to. (Source output for sink input, sink output for source
input. Unit’s output conguration is on label attached
to white wire.)
(3) Apply power to the control card connected to the unit
being commissioned. Wait for 1 minute to allow the
unit to initialise and stabilise. Using a multimeter set
on dc volts, measure the voltage across the red (+24V)
and black (0V return) connections. Nominally, this
voltage should be +24V. Voltages in the range +18V to
+32V are acceptable.
(4) Using either the IS socket on the Termination Unit,
or the SHC Protection Device, connect the SHC-1
Handheld Interrogator to the unit’s RS485 comms
link.(See Section 4.2 for SHC Protection Device
connections.)
(5) Select the DIAGNOSTICS option on the interrogator
menu and instruct the unit to display any ACTIVE
WARNINGS or ACTIVE FAULTS. (Diagnosis of FAULT /
WARNING codes is described in Section 8.)
47
Page 48
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
a. If there are any ACTIVE FAULTS, the cause(s) of
these must be identied and remedied before the
unit will become fully operational.
b. If there are any ACTIVE WARNINGS, the unit can
operate correctly despite the warning(s). However,
for reliable long term operation it is strongly
recommended that problems causing warnings are
xed before a unit is fully commissioned.
5.2.2 Gas Response Testing (SHC-1 & Multimeter)
The procedure for testing gas response as part of the
commissioning process is described below:-
(1) Select the DISPLAY mode on the SHC-1 Handheld
Interrogator. Check that the displayed gas reading
is 0.0% LEL. If the displayed gas reading is not
0.0% LEL, check that their is no background gas
concentration present, the optics are clean and free
from condensation and that the unit has been given
sufcient time to stabilise in it’s intended operating
environment. (For best results, it is recommended
that a unit is left powered up for one hour before
performing zero or span calibration / test activities.)
(2) Using the SHC-1 interrogator, put the detector into
INHIBIT (this will prevent gas readings from being
signalled on the 4-20mA output).
(3) Making use of either the gassing cover, or the remote
gassing cell (where tted), perform a functional gas
test. The procedure for performing functional gas
tests is detailed in Section 5.5. For a nominal 50%
LEL test gas concentration, the displayed reading
should be between 45% LEL and 55% LEL. (If
necessary, test gas concentrations between 20%LEL
and 95%LEL can be used with the same +/- 5% LEL
test tolerance.)
48
Page 49
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
Provided the displayed gas reading falls within the +/-5%
LEL test tolerance range, the functional gas test has been
completed satisfactorily.
CAUTION
If the displayed gas reading is not as expected, do not
proceed to re-calibrate the unit immediately. Instead,
double check the unit’s zero, the test gas and the gassing
technique. (IR gas detectors do not exhibit signicant
span drift and in most instances, any problem will be with
the zero or the test gas / technique.) Only consider
re-calibrating a unit when certain that the zero, test gas
and technique are correct and that the unit’s gas response
is signicantly out. The calibration technique is detailed in
Section 6.3.
5.2.3 System Level Testing (SHC-1 & Multimeter)
Conrmation of correct operation of the complete gas
detection system can be done using either test gas at the
required concentrations (Option B) or by FORCEing the
unit’s 4-20mA output under control of the SHC-1 interrogator
(Option A):-
CAUTION
When performing system level tests, ensure that any
resulting alarms or executive actions will not give rise to
unintended emergency drills or loss of production /
shut-down.
Note: It is assumed that the control system has been set up
for currents of 4mA and 20mA to read 0.0% LEL and
100% LEL respectively. If necessary, the FORCE 4-20mA
option can be used for setting up the control card. Be
aware that a 10 minute timeout applies to FORCE’d
4-20mA outputs.
49
Page 50
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
Option A) System Test Using FORCE’d 4-20mA
(1) The easiest way of performing system level functional
tests is to use the SHC-1 interrogator to FORCE the
4-20mA output to currents that are just above the
relevant alarm thresholds.
(2) The FORCE 4-20mA option is available from the
CALIBRATE menu. Using this option, FORCE the
4-20mA output to a current just above the A1 alarm
threshold. For example, with an A1 of 20% LEL, a
current of 7.5mA should sufce. Verify that the system
reports and responds as intended to this A1 signal.
(3) FORCE the 4-20mA output to a current just above the
A2 alarm threshold. With an A2 of 60% LEL, a current
of 14mA should sufce. Verify that the system reports
and responds correctly to this A2 signal.
(4) RELEASE the 4-20mA output. Conrm that the
system returns to normal, with no active alarms or
faults.
Option B) System Test Using Gas
If system level functional tests must be performed using gas,
test gas concentrations at least 5% LEL (ideally 10% LEL)
above each alarm threshold are required in order to allow for
system tolerances.
(1) Using either the gassing cover or the remote
gassing cell, apply test gas to the detector at the
concentration required to reliably exceed the A1
alarm threshold. For example, with an A1 alarm
threshold of 20% LEL, the minimum nominal test gas
concentration should be 25% LEL (ideally 30% LEL).
Verify that the system responds as intended to an A1
signal generated in this manner.
50
Page 51
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
(2) Apply test gas at the concentration required to reliably
exceed the A2 alarm threshold. With an A2 alarm
threshold of 60% LEL, the minimum nominal test gas
concentration should be 65% LEL (ideally 70%LEL).
Verify that the system responds correctly to an A2
signal generated in this manner.
5.2.4 Final Commissioning (SHC-1 & Multimeter)
The commissioning process is nished off as described
below:-
(1) Remove or disconnect any gas testing equipment
from the unit.
(2) Ensure that any test gas used is fully vented from the
measurement chamber or gassing cell. Verify that the
displayed gas reading returns to zero. (If the remote
gassing cell has been used, ensure that once vented,
it’s inlet tubes are sealed with the protective caps
provided (or a suitable alternative).)
(3) If required, remove the detector from INHIBIT.
(4) Select DIAGNOSTIC mode and verify that the unit has
no ACTIVE FAULTs or ACTIVE WARNINGs.
(5) Disconnect the SHC-1 interrogator. Replace the
junction box lid (where removed).
(6) When all of the relevant steps above are completed
satisfactorily, the unit has been commissioned and is
ready for operational use.
51
Page 52
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
5.3 COMMISSIONING PROCEDURE WITH
MULTIMETER ONLY
5.3.1 Electrical Commissioning and Tests
(Multimeter) Only
The procedure for verifying the electrical installation of the
unit is described below:-
(1) Before applying power to the unit, ensure that the
eld wiring is correct and in accordance with
Section 4.
(2) Check that the unit’s 4-20mA output conguration
is correct for the type of control card that the unit
is connected to. (Source output for sink input,
sink output for source input. The unit’s output
conguration is on a label attached to the white wire.)
(3) Apply power to the control card connected to the unit
being commissioned. Wait for 1 minute to allow the
unit to initialise and stabilise. Using the multimeter
set on dc volts, measure the voltage across the red
(+24V) and black (0V return) connections. Nominally,
this voltage should be +24V. Voltages in the range
+18V to +32V are acceptable.
(4) Remove power from the unit.
(5) Insert the multimeter set to read current (mA) in series
with the 4-20mA loop as follows:-
a. Current Sink Output
Remove the unit’s white 4-20mA output wire from
the terminal for the 4-20mA loop connection.
Connect the multimeter’s negative probe to the
white 4-20mA wire. Connect the multimeter’s
positive probe to either the +24V terminal or the
4-20mA loop terminal.
52
Page 53
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
b. Current Source Output
Remove the unit’s white 4-20mA output wire from
the terminal for the 4-20mA loop connection.
Connect the multimeter’s positive probe to the
white 4-20mA wire. Connect the multimeter’s
negative probe to either the 0V terminal or the
4-20mA loop terminal.
(6) Apply power to the unit and monitor it’s 4-20mA
output to conrm that it executes the correct powerup sequence as below:-
a. Output current of 0.0mA (0.0 to 0.5mA) for a period
of approximately seven seconds.
b. Output current of 2mA (INHIBIT current, 1.8 to
2.2mA) for a period of up to one minute whilst the
unit initialises and stabilises.
c. Output current of 4mA (ACTIVE zero gas current,
3.8mA to 4.2mA), which indicates that the unit is
operational and reading 0.0% LEL gas.
Note: If the unit is powered up in a non-zero
gas concentration, it will output a signal
corresponding to the gas concentration.
53
Page 54
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
5.3.2 Gas Response Testing (Multimeter) Only
CAUTION
Without the SHC-1 interrogator it is not possible to
INHIBIT the gas detector. To avoid unintended executive
actions or alarms, it is recommended to either isolate
the detector itself or inhibit / isolate the corresponding
control card.
Functional gas testing can be performed using the
multimeter to monitor the 4-20mA output:-
(1) Isolate the detector by disconnecting the 4-20mA
output from the loop terminal and connecting the
multimeter to measure the 4-20mA current to either
the +24V (for current sink) or 0V (for current source).
Alternatively, if the control card has been isolated /
inhibited, connect the multimeter in series with the
4-20mA loop.
(2) Making use of either the gassing cover, or the remote
gassing cell (where tted), perform a functional gas
test as detailed in Section 5.5.
CAUTION
If the 4-20mA current is not as expected, double check
the unit’s zero, the test gas and the gassing technique.
(IR gas detectors do not exhibit signicant span drift and
in most instances the problem is with the zero or the
test gas / technique.) Only consider re-calibrating a unit
when certain that the zero, test gas and technique are
correct and that the unit’s gas response is signicantly
out. The calibration procedure is detailed in Section 6.3.
54
Page 55
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
For a nominal 50% LEL test gas concentration, the
4-20mA output current should be between 11mA and 13mA.
If the measured current falls within the correct range, the
functional gas test has been completed satisfactorily.
Note: Zeroing and calibration activities require use of the
SHC-1 interrogator.
5.3.3 System Level Testing (Multimeter)
If it is necessary to conrm the correct operation of the
complete gas detection system during commissioning
(without an SHC-1 interrogator), this can only be done using
test gases at concentrations which are at least 5% LEL
(ideally 10% LEL) above the relevant alarm thresholds.
(1) Remove power from the unit. Reconnect the unit’s
4-20mA output to the appropriate loop terminal (the
multimeter should still be in series to measure current).
(2) Making use of either the gassing cover, or the
remote gassing cell (where tted), introduce gas at
the required A1 test concentration into the unit. For
example, with an A1 alarm threshold of 20% LEL, the
minimum test gas concentration required is 25% LEL.
The corresponding 4-20mA output current should be
between 7.2mA and 8.8mA. Conrm that the correct
current and system responses are observed when the
A1 test gas is introduced into the unit.
(3) Introduce gas at the required A2 test concentration
into the unit. With an A2 alarm threshold of 60% LEL,
the minimum test gas concentration required is 65%
LEL. The corresponding 4-20mA output current should
be between 13mA & 15mA. Conrm that the correct
current and system responses are observed when the
A2 test gas is introduced into the unit.
55
Page 56
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
5.3.4 Final Commissioning (Multimeter)
The commissioning process is nished off as described
below:-
(1) Remove or disconnect any gas testing equipment
from the unit.
(2) Ensure that any test gas used is fully vented from the
measurement chamber or gassing cell. (If the remote
gassing cell has been used, ensure that once vented,
it’s inlet tubes are sealed with the protective caps
provided (or a suitable alternative)).
(3) Verify that after the initialisation and stabilisation
period (approximately 1 minute), the 4-20mA output
returns to 4mA nominal (between 3.8mA and 4.2mA).
(4) Remove power from the unit and disconnect the
multimeter from the 4-20mA loop. Connect the white
4-20mA wire back directly to the loop terminal.
Re-apply power to the unit.
(5) Verify that the unit returns to ACTIVE status and that
the gas reading displayed on the control card is
0.0% LEL.
(6) Replace the junction box lid.
(7) When all of the relevant steps above are completed
satisfactorily, the unit has been commissioned and is
ready for operational use.
56
Page 57
MAN0551 Issue 07 - 09/08
2108M0501
5. COMMISSIONING
5.4 CONTROL SYSTEM SETUP
If the controller is in need of setting up, ie. for a 4 to 20mA
signal to show an equivalent reading eg. 0 - 100% fsd, this
may be done in two ways:
i) By using the Hand-Held Interrogator to FORCE the
required signal to the controller (see Section 6.4 of
this manual)
or
ii) With calibration gas applied to the sensor.
In each of these cases, a known signal is sent to the
controller, and the controller is set to show the equivalent
signal.
5.5 FUNCTIONAL RESPONSE CHECKING AND
CALIBRATION
Searchpoint Optima Plus is supplied factory calibrated and
when commissioning a unit, all that should be required to
verify correct operation is a functional response check.
The procedure for functional response checking is described
in Section 7 Routine Checks.
Where local regulations or working practices require gas
detectors to be calibrated when they are commissioned,
this should be performed in accordance with the procedure
described in Section 6 Calibration.
57
Page 58
MAN0551 Issue 07 - 09/08
2108M0501
58
Page 59
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.1 GENERAL
Searchpoint Optima Plus is supplied factory calibrated for
a particular hydrocarbon gas (approximately 100 different
gas calibrations are currently available). Properly installed
and maintained, Optima Plus does not require routine
calibration. This operational benet is made possible
by the inherent stability of the IR absorption process
and the fully compensated optical conguration used.
In order to maintain condence in the continued correct
operation of elded Optima Plus units it is recommended
that a functional gas test is incorporated into the planned
maintenance procedure for the unit. In most applications
and installations, a planned maintenance / service interval
of 1 year is appropriate, although this will depend upon
site conditions and requirements. EN50073 and national
regulations should be observed.
Where site operating procedures or regulations require
routine calibration of gas detectors, this is possible using
the SHC-1 Handheld Interrogator and the gassing cover.
Care needs to be taken in order to ensure that routine
eld calibrations do not reduce the calibration accuracy
compared to the original factory calibration. (Factory
calibration is performed in more controlled conditions than
are readily achievable in the eld.)
Functional gas testing and calibration are made considerably
easier by use of the SHC-1 Handheld Interrogator. If an
SHC-1 is not available, basic functional gas testing can be
performed using just a multimeter to monitor the 4-20mA of
the unit being tested.
CAUTION
Searchpoint Optima Plus is a robust, ammable gas
detector, it is not an analyser. Where the performance or
features of an analyser are required, an analyser should
be used.
59
Page 60
MAN0551 Issue 07 - 09/08
LCD Display
Push Buttons
Hand-Held
Interrogator
Type SHC-1
2108M0501
6. CALIBRATION
6.2 SHC-1 HANDHELD INTERROGATOR
The SHC-1 Handheld Interrogator is a portable, Intrinsically
Safe (IS) device which can be used to calibrate, test and
commission all of Honeywell Analytics Searchpoint and
Searchline optical gas detection products. The SHC-1
interrogator communicates with detectors via a digital RS485
link. Electrically, this link can be made either by using the IS
socket on the DVC100 / DX100 or by connecting the ying
leads on the SHC Protection Device (04230-A-1025) to the
appropriate junction box terminals.
WARNING
The IS certication of the SHC-1 Handheld Interrogator
only remains valid if it is used in conjunction with the
Termination Unit or the SHC Protection Device. Do not
attempt to connect the SHC-1 interrogator directly to
units, always use either the Termination Unit or the SHC
Protection Device.
Press ↵ and hold for three
seconds to switch on.
Press ↵ and esc together
and hold to switch off.
Unit powers down
auto-matically after
10 minutes to prolong
battery life.
60
Page 61
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.2.1 Connecting the SHC-1 Hand-Held Interrogator
6.2.1.1 Termination Units
When using a Termination Unit, the SHC-1 Handheld
Interrogator can be directly connected to the IS socket on
the bottom of the Termination Unit.
Termination Unit
Optima
IS Socket
SHC1
6.2.1.2 Other Junction Boxes
(Use of SHC Protection Device)
WARNING
The SHC Protection Device can only be used in a safe
area. ie. When a local safe area is achieved using a hot
work permit or other appropriate gas free permit.
Interrogator connections to units mounted on junction boxes
other than the DVC100 / DX100 can be made using the
SHC Protection Device. The procedure for using the SHC
Protection Device is as follows:-
(1) Remove the cover to the respective junction box.
61
Page 62
MAN0551 Issue 07 - 09/08
To Optima
Communications
Link Connections
in Junction Box
brown
blue
SHC Protection Device
To Hand-Held
Interrogator
SHC-1
2108M0501
6. CALIBRATION
(2) Connect the brown lead of the SHC Protection Device
to the orange lead of the Optima communications link.
(3) Connect the blue lead of the SHC Protection Device to
the blue lead of the Optima communications link.
(4) Connect the Hand-Held Interrogator SHC-1 to the
SHC Protection Device connector.
Note: When transporting the SHC Protection Device in a
hazardous area, the SHC Protection Device must be
disconnected from the Hand-Held Interrogator.
6.2.2 Hand-Held Interrogator Operating Modes
The Hand-Held Interrogator version 4v0 is compatible
with Searchpoint Optima, Searchpoint Optima Plus and
Searchline Excel. To work with a specic product the correct
operating mode has to be selected as follows:
(1) Press ↵ to switch on the power.
(2) The display will rst show a title screen:
Z - SHC 1 Optima
Interrogator 4v0
The current operating mode is shown in the top right
of the display.
(3) Press esc and the display will show:
Z - SHC 1 Optima +
Interrogator 4v0
62
Page 63
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(4) Press esc again and the display will show:
Z - SHC 1 Excel
Interrogator 4v0
If esc is pressed again the operating mode will
change to Optima and the different modes can be
stepped through again.
(5) When the display shows Optima + as the operating
mode wait three seconds for the main menu to be
displayed:
Main
Note: 1. The current operating mode is remembered when
the Hand-Held is switched off.
2. The operating mode can also be changed by
selecting the change mode option on the main menu.
Display
(6) Press
Main
(7) Press and the display will show:
Main
(8) Press and the display will show:
Main
and the display will show:
Calibrate
Diagnose
Gas Tables
63
Page 64
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(9) Press and the display will show:
Main
(10) Press and the display will show:
Main
(11) Press and the display will show:
Main
Congure
Change Mode
Power Off
64
Page 65
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
Power Off
Main
Gas Tables
Main
Diagnose
Main
Calibrate
Main
Main
Show Gas
Gas Tables
Active Faults
Diagnose
Display
Calibrate
Congure
Main
Show Library
Gas Tables
Active Warns
Diagnose
Cal Sensor
Calibrate
Change Mode
Select Gas
Gas Tables
Self Test
Diagnose
Calibrate
Diagnose
Force 4-20
Calibrate
Soft Reset
This diagram shows all the Hand-held Interrogator
Software features. Use of the and keys to display
Normal 4-20
the individual menu options. The options are selected
by pressing ↵ and exited by press esc.
SHC-1 Hand-held Calibrator Menu Structure
Interrogator 4v0
Z- SHC1 Optima +
Display
Main
65
Page 66
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.2.3 Other Hand-Held Features
6.2.3.1 Display
Selecting this option from the main menu displays:
Optima + Methane
xx.x % LEL
The display shows the gas type, the gas reading and in the
bottom right a status indicator:
Rotating bar indicates a healthy active unit.
F indicates an active fault condition.
W indicates an active warning.
A indicates a gas concentration in excess of
the units internal alarm threshold
O indicates an active overrange.
I indicates inhibit condition.
Pressing
or ↵ changes the display to show:
Optima + S/W
4v0
The version of software currently installed within the
Searchpoint Optima Plus unit.
Pressing
, or ↵ will return the display to showing the
current gas reading.
Pressing esc exits the display option to the main menu.
66
Page 67
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.2.3.2 Calibrate
Display
The Display option on the Calibrate menu provides the same
information as the Display option on the Main menu except
the analogue output will be inhibited. This function is useful
if a response check is to be carried out and you do not wish
the gas reading to be reported on the analogue output.
Note: The rotating bar will not be shown on the gas reading
display when the analogue output is inhibited.
Normal 4-20
This action releases the analogue output. It should be
used if a communication error occurs while performing an
operation with the Hand-Held which Inhibited the analogue
output.
Note: The unit will release its analogue output automatically 10
minutes after it was Inhibited if no digital communication
occurs.
6.2.3.3 Diagnostics
Active Faults/Active Warning
Selecting one of these actions displays any fault or warning
conditions which are present in the unit. If more than one
condition is simultaneously present, these may be scrolled
through by pressing the
or keys.
FAULT conditions prevent the unit from working as a gas
detector and are always signalled on the analogue output as
0mA.
67
Page 68
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
WARNING conditions indicate that the unit is operating
close to the limits of its specied operating envelope. The
unit may go into fault in the near future. If a fault condition
is present in the unit while the active warnings are being
displayed, the top line of the display will show Fault Present.
Correct the Fault condition rst.
A list of fault and warning conditions and the actions
which should be taken to correct the problem are given
in section 8.
Self Test
This action instructs the unit to complete a self test cycle. If
a fault or warning condition was found in the unit, the HandHeld display will show:
Error 13
Error in Unit
Details of the fault or warning can be viewed by selecting
the Active Fault/Active Warning menu option.
Soft Reset
Selecting this option forces the unit to reboot. It is
equivalent to switching the power to the unit off and
then on.
6.2.3.4 Gas Table
The Show Gas menu option displays the current gas type.
The Show Library action displays the part number and issue
of the data base within the unit which contains the details of
the diferent gasses which can be detected.
The Select Gas menu option allows the gas type of the unit
to be changed. The gas types available on the standard
unit are listed in Section 11.1.
The unit is inhibited while this action is performed. The unit
should be calibrated after the gas type is changed.
68
Page 69
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.2.3.5Cong
The Show Cong option on the Cong menu shows the
values of a number of key paramaters in the Searchpoint
Optima Plus. These may be scrolled through by pressing the
or keys.
OptimaPlusCongurationParameters
Conguration
Parameters
Auto Zero
Alarm
Threshold
Inhibit
Current
Warning
Current
Overrange
Current
Protocol
Address
Parameter
Title
Zero
Tracking
Alarm
Threshold
Inhibit mA
Warning mA
Overrange mA
Digital
Address
Purpose
Enables automatic zero tracking
function within the unit. Used only
in specialist applications, function
is normally disabled.
Sets a gas concentration thresh-
old (adjustable over the range
10% to 50% full scale, default
25%) beyond which the unit
considers a dangerous level of
gas is present. A fault will be
signaled if the output current can
not be driven to a value in excess
of this threshold.
Denes the output current for
Inhibit condition.
Denes the output current when a
warning is present.
Denes the output current when
the gas concentration exceeds
full scale.
Denes the protocol address of
the unit when connected into a
multi-drop digital network.
Used only in specialist
applications.
6.2.3.6 Power Off
Entering this menu and pressing ↵ turns off the Hand-held
Interrogator to preserve battery life.
69
Page 70
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.3 CALIBRATING THE CONTROLLER
This procedure allows the user to calibrate the controller by
FORCE’ing a known current out of the unit’s 4-20mA output.
Use of this technique enables calibration of the controller’s
0-100% fsd scale without the need for gas. The output can
be forced in the range 1.0 to 21mA (0.1mA resolution).
It is recommended that calibration of the controller is
performed at two points, ideally 4mA (0.0% fsd) and 12mA
(50% fsd). Provided that no background gas concentration
is present, the unit’s 4mA (0.0% fsd) output can be used to
calibrate the control cards zero point. The span calibration
of the controller can then be calibrated by FORCE’ing the
required current as follows:-
(1) Connect the Hand-Held Interrogator to the unit.
(2) Press ↵ to switch the power on, ensure the Hand-held
is in Optima + mode and wait ve seconds.
The display will show:
Main
(3) Press and the display will show:
Main
(4) Press ↵ and the display will show:
Calibrate
Display
Calibrate
Display
70
Page 71
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(5) Press and the display will show:
Calibrate
(6) Press and the display will show:
Calibrate
This selects the FORCE'd 4-20mA routine which can
be used to calibrate the controller.
(7) Press ↵ and the display will show:
O/P 4-20 current
Cal Sensor
Force 4-20
4.0 mA
(8) Press
or to change the displayed mA value in
0.1mA steps:
O/P 4-20 current
12.0 mA
Choose the desired value.
(9) Press ↵ and the display will show:
Fixed: nn.nn mA
Press enter
where nn.nn is the current measured by the Optima
Plus diagnostic function. The analogue output is now
set to the selected value set in step (8). Specied
accuracy is ±1% FS (±0.2mA).
71
Page 72
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(10) Calibrate the controller to display the correct reading
for the current being FORCE'd on the 4-20mA output.
(11) Press ↵ and the display will show:
Press Enter To
Release 4 - 20
Note: The unit will return to normal operation after 10 minutes
if no key is pressed.
(12) Press ↵ and the display will show for 3 seconds:
4 - 20 Released
The analogue output has now returned to normal
operation.
(13) Wait and the display will show:
Calibrate
Force 4-20
Returns to the Calibrate Menu.
(14) Press esc twice to return to the Main Menu:
Main
Display
(15) The Hand-Held Interrogator may be switched off by
pressing esc and ↵ together.
72
Page 73
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
6.4 CALIBRATING THE SENSOR
CAUTIONS
1. Searchpoint Optima Plus is supplied factory
calibrated for a particular hydrocarbon gas and
should not require routine gas calibration. In general,
this factory calibration will be more accurate than
what can be achieved in the eld. Only perform gas
calibration if this is required by local regulations or
if there is clear evidence of a signicant calibration
error. In most instances, the zeroing and functional
testing procedure described in Section 7 should be
sufcient to maintain a unit’s performance without
the need for gas re-calibration.
2. Ensure that the correct calibration gas and
concentration are used. The concentration of
calibration gas should be known to be accurate to
within +/-2.5% of the value declared on the cylinder
/ bottle.
3. It is important to present the calibration gas correctly
to the detector. Only use Searchpoint Optima Plus
gassing accessories as directed.
4. Searchpoint Optima, in common with other IR gas
detectors, measures the total number of target
gas molecules in it’s beam and hence readings
are directly related to the gas pressure in the
measurement path. Avoid pressurising calibration
gas inside the unit’s measurement path by keeping
gas ow rates below the maximum recommended
levels and ensuring that gas can freely vent to
atmospheric pressure. The maximum recommended
ow rates are 0.3 l / min for the remote gassing cell,
2 l / min for the gassing cover and 2 l / min for the
ow housing.
73
Page 74
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
5. Do not attempt to perform calibration during
periods of exceptionally low or high atmospheric
pressure. (Normally associated with unusual or
extreme weather conditions. Calibration is not
recommended during storms, very strong winds or
highly changeable weather conditions.)
6. Ordinarily, during production Optima Plus units
are calibrated with gas in the main measurement
chamber, which is where they will detect gas in
operational service. The response in the RGC
is not production calibrated. The RGC is not
recommended for calibration or for high accuracy
calibration testing. (The only exception to this is
where units are being used to measure high %V/V
gases using the RGC as a ow cell. In this instance,
the units are production calibrated with gas in the
RGC.)
7. Always allow unit’s to stabilise in the operating
environment for at least 30 minutes (ideally 1 hour)
before performing gas calibration.
Equipment Required:
Gassing Cover
Instrument Air (if a zero in ambient air cannot be guaranteed)
Calibration Span Gas (i.e. 2.2% V/V methane for 50% LEL
output if working in accordance with EN61779)
SHC-1 Handheld Interrogator
74
Page 75
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
To calibrate the sensor, proceed as follows:
(1) Connect the Hand-Held SHC-1, press ↵ to switch on
the power, check the Hand-held is in Optima + mode,
wait ve seconds and the display will show:
Main
(2) Press and the display will show:
Main
(3) Press ↵ and the display will show:
Calibrate
(4) Press and the display will show:
Display
Calibrate
Display
Calibrate
Cal Sensor
(5) Press ↵ and the display will show:
Inhibiting 4 - 20
Please Wait
This sets the analogue output to the inhibit level
(default 2mA) for the duration of the calibration
sequence.
(6) Remove weather protection and dust barrier. Check
that the optics are clean and dry. Clean / dry optics
if necessary. Ret the dust barrier and weather
protection.
75
Page 76
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(7) Wait and the display will show:
Ensure Zero Gas
Press Enter
Note: If at this stage the zero reading in ambient air cannot
be guaranteed, fit the gassing cover over the weather
protection and apply instrument air at one litre/minute
for 30 seconds.
(8) Press ↵ and the display will show:
Processing Data
Please wait
After 10s the display will show:
Zero Calibrated
The new baseline (zero) is now set.
(9) Wait and the display will show:
Cal Span, Enter
Exit Cal, ESC
(10) Either:
a. press esc to end the calibration sequence without
carrying out a span calibration, or
b. press ↵ and the display will show:
Press Enter To
Select Gas Conc.
76
Page 77
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
This means set the gas concentration (ie. 50% LEL:
for 2.2% methane if working in accordance with
EN61779).
(11) Press ↵ and the display will show:
Span Gas
(12) Press or to change the displayed gas value
between 30 and 125%LEL (1% steps) to the value
being applied.
(13) Press ↵ and the display will show:
(14) Fit the gassing cover over the weather protection of
the Searchpoint Optima.
50.0 % LEL
Press Enter when
Stable: xx.x
(15) Apply span calibration gas at a rate of one litre/
minute and wait for reading to stabilise. This will take
approximately 30 seconds to 1 minute, depending
upon ow rate.
Press Enter when
Stable: xx.x
(16) Press ↵ and the display will show:
Processing Data
Please wait . . . .
After 10s the display will show:
Span Calibrated
77
Page 78
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(17) Wait and the display will show:
Remove gas, Press
Enter: xx.x
(18) Remove the gassing cover from the weather
protection. Ensure the reading has returned to 00.0%
LEL.
(19) Press ↵ and the display will show:
Press Enter To
Release 4 - 20
Releases the analog output from 2mA (inhibit signal)
to normal operation (4mA).
(20) Press ↵ and the display will show for 3 seconds:
4 - 20 released
The analogue output has now returned to normal
operation.
(21) Wait and the display will show:
Calibrate
Cal Sensor
Returns to the Calibrate Menu.
(22) Press esc twice to return to the Main Menu:
Main
Display
78
Page 79
MAN0551 Issue 07 - 09/08
2108M0501
6. CALIBRATION
(23) The Hand-Held Interrogator may be switched off by
pressing esc and ↵ together.
Gassing Cover Fitted Over Weather Protection
79
Page 80
MAN0551 Issue 07 - 09/08
2108M0501
80
Page 81
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
7.1 GENERAL
Searchpoint Optima Plus is designed to require minimal
routine maintenance and testing during use. Installed and
operated correctly, the only maintenance actions required
should be occasional cleaning and re-zeroing.
Continuous self-diagnostics ensure that if a unit develops a
problem, this is reported as a FAULT or WARNING. Warnings
are reported by a default signal of 3 mA (congurable).
Provided that a unit is reporting 4mA (or a congured
WARNING signal) it is an active gas detector.
Inspection and maintenance intervals vary depending upon
local regulations and requirements. EN50073 and national
regulations should be observed. If no specic requirements
exist, it is recommended that units are inspected and
functionally tested at twelve monthly intervals. Details of
the recommended routine inspection and functional test
procedure are presented in Section 7.2
7.2 INSPECTION AND FUNCTIONAL
RESPONSE CHECK PROCEDURE
The recommended procedure for inspecting and functionally
testing Searchpoint Optima Plus units is detailed below:-
Equipment Required:-
Gassing Cover (or Calibration Cap)
Test Gas (normally equivalent to 50% fsd)
SHC-1 Handheld Interrogator
Cleaning materials (soft cloth or cotton buds, mild detergent
or window cleaner)
(1) Inspect the Searchpoint Optima Plus unit, it’s junction
box and cabling for any signs of physical damage.
81
Page 82
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(2) Connect the SHC-1 interrogator to the unit.
(3) INHIBIT the unit by selecting the DISPLAY option in
the CALIBRATE menu.
(4) Unscrew the two retaining nuts and remove the
Standard Weather Protection. Inspect the Standard
Weather Protection for damage or build up of debris
/ contaminants. If required, clean or replace weather
protection.
(5) Inspect the Dust Barrier and clean or replace if
required.
(6) Remove the Dust Barrier and inspect the optics.
(7) Clean any dust or contaminants from the optics using
mild detergent or window cleaner and a soft cloth or
cotton bud.
Note: If a remote gassing cell is fitted, the cell window can be
unscrewed and removed for cleaning purposes where
necessary. When replacing, ensure that the cell window
is fully screwed home (the effective thickness of the
gassing cell is reliant upon this).
CAUTIONS
1. Do not attempt to clean the optics using abrasive or
corrosive materials.
2. Do not attempt to clean the unit using a sand-blaster
or similar equipment.
3. Do not use concentrated organic solvents to clean
the unit. These substances contain hydrocarbons
which may give rise to gas readings when they
evaporate.
82
Page 83
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(8) Ret or replace the Dust Barrier and Standard Weather
Protection.
(9) Verify that there are no ACTIVE FAULTs or WARNINGs
by checking that the ‘/’ line is present on the right
side of the CALIBRATE / DISPLAY screen. If there are
FAULTs or WARNINGs, the ‘/’ will be replaced with
either an F or a W.
(10) If ACTIVE FAULTs or WARNINGs are present,
investigate these by using the DIAGNOSTIC menu
options. Wherever possible, correct any ACTIVE
FAULTs or WARNINGs before proceeding to the next
stage.
Having completed the above steps, you are now ready to
perform a functional response check. Functional response
checks can either be performed using the Gassing Cover and
%LEL concentration gas or using the Remote Gassing Cell
and high %V/V gas. The procedures for performing functional
response checks are described in the following sections.
7.2.1 Response Check Using Gassing Cover and
%LEL Concentration Gas
Note: For best results when performing functional response
checks it is important to re-ZERO a unit before the
response check.
(1) For best results, allow the sensor to remain under
power for one hour prior to performing response check.
This allows the unit's temperature to stabilise in the
operating environment.
(2) Fit the Gassing Cover over the weather housing,
ensuring the gas entry slot at the base of the standard
weather protection is covered.
83
Page 84
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(3) Ensure that there is a suitable zero gas inside the
unit’s main measurement chamber and the remote
gassing cell (if tted). Suitable zero gases include
fume/vapour-free atmospheric air, instrument air
and nitrogen. (In most outdoor or well ventilated
installations, atmospheric air will sufce for zeroing.
Instrument air or nitrogen should only be necessary
for poorly ventilated installations or where a signicant
hydrocarbon background is present or expected.)
(4) Select the CALIBRATE / CAL SENSOR menu option
and re-zero the unit. (Do not re-calibrate the unit’s
span gas response.)
(5) Select the CALIBRATE / DISPLAY menu option.
(6) Using the Gassing Cover, apply test gas to the unit.
Allow approximately 30 seconds to 1 minute for the
gas concentration in the measurement chamber to
stabilise.
(7) Monitor the DISPLAY’ed gas reading and conrm that
it is within +/-5% LEL of the anticipated reading. If the
reading is within +/- 5% LEL of what is anticipated, the
unit is denitely operating correctly. Do not consider
re-calibrating units with apparent “calibration errors”
less than +/- 5% LEL. Be aware that eld calibration
84
Page 85
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
and response checking techniques are not sufciently
accurate to determine whether such small “errors” are
genuine, or to correct them.
(8) If the DISPLAY’ed gas reading is within +/-10% fsd of
the anticipated reading, it is possible that there might
be a calibration error but it is still more likely that the
error will be due to the prevailing conditions or test
gas / technique. Before considering re-calibration,
double-check the following:-
a. The optics are clean and un-contaminated.
b. The unit has been correctly zeroed in a genuine
zero gas background.
c. The correct test gas and concentration are being
used for the range being tested.
d. The tolerance on the test gas concentration is
signicantly less than the apparent reading error.
e. There is adequate test gas in the cylinder.
(Cylinders that are nearly empty tend to read on
the low side.)
f. The test gas in the measurement chamber /
remote gassing cell is not being pressurised due to
high ow rates or blockages / restrictions.
g. The atmospheric pressure is not unusually high
or low.
h. The unit has had sufcient time to stabilise in it’s
operating environment. (At least 30 minutes, ideally
1 hour after any signicant change or power-up.)
i. An approved, Honeywell Analytics supplied
gas testing accessory is being used. (Either the
gassing cover, calibration cap or the remote
gassing cell.)
85
Page 86
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
If after checking the above, the error remains,
consider re-calibrating the unit in accordance with the
procedure detailed in Section 6.4.
(9) Errors in the DISPLAY’ed gas reading larger than +/-
10% fsd are rare. Where encountered, they are more
likely to be associated with the considerations listed
in (8) for double-checking than errors in the actual
unit's calibration. Ensure that all of the considerations
are fully checked before re-calibrating. If the apparent
calibration error is larger than +/-15% fsd, contact
Honeywell Analytics or their representatives for advice
before attempting re-calibration.
(10) Before releasing the detector from INHIBIT, ensure that
any test gas inside the unit’s measurement chamber
has been fully removed. This can be achieved either
by blowing instrument air / nitrogen through the
Gassing Cover, or by removing the Gassing Cover and
allowing the test gas to escape (this takes around 30
seconds).
(11) Release the detector from INHIBIT by selecting the
MAIN DISPLAY menu option.
(12) Provided that on the MAIN DISPLAY, the unit is
reading 0.0% LEL and the ‘/’ line is rotating, the unit
is operating normally and all tests and maintenance
activities have been completed.
If the ‘/’ line has been replaced by a W, there is an
ACTIVE WARNING in the unit, which should be
investigated and where possible cleared before leaving
the unit for operational use.
If the ‘/’ line is not rotating or has been replaced by an
F, there is an ACTIVE FAULT. The unit will not operate
with an ACTIVE FAULT. Use the DIAGNOSTICS menu
option to identify the cause of the FAULT and remedy
where possible.
86
Page 87
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(13) Disconnect the SHC-1 interrogator from the unit.
(14) The functional response check has been completed
7.2.2 Response Check Using Remote Gassing Cell &
High %VV Gas
Note: 1. This only applies if the optional Remote Gassing Cell
has been selected and fitted.
2. The Remote Gassing Cell is designed to facilitate
functional response checking of units installed in
positions where obtaining access is difficult. The
RGC is not recommended for calibration or for high
accuracy calibration testing. During production,
Optima Plus units are calibrated with gas in the
main measurement chamber, which is where they
will detect gas in operational service. The response
in the RGC is not production calibrated. (The only
exception to this is where units are being used to
measure high %V/V gases using the RGC as a
flow cell. In this instance, the units are production
calibrated with gas in the RGC.)
3. The functional response check limits recommended
for this procedure include reasonable allowances
for the effects of atmospheric pressure, test gas
tolerances and test repeatability. These functional
response check limits are representative of what
the user should expect to achieve under typical field
conditions.
4. This procedure assumes the Searchpoint Optima
Plus has been calibrated for 0 - 100% LEL methane.
87
Page 88
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
CAUTIONS
1. In order to avoid pressurisation, gas should ow
through the remote gassing cell at no more than
0.3 litre/min.
2. Ensure that the exhaust pipe is not blocked since
this may pressurise the ow through the cell and
may cause permanent damage to the unit.
3. Never blow air from the lungs directly into the
remote gassing cell since the presence of any
foreign substances within the cell will adversely
affect the operation of the unit.
4. Always use a Flow Filter on the inlet of the remote
gassing cell when a remote gassing pipe is
permanently installed.
5. For other gases, contact Honeywell Analytics
Limited.
88
Page 89
MAN0551 Issue 07 - 09/08
Flow Through Gas Cell
High Concentration
(V/V cell) Nozzles
Dust Caps
2108M0501
7. ROUTINE CHECKS
Equipment Required:
Flow Through Cell Gassing Kit, consisting of:
Lengths of plastic tube with In Line Particle Filter.
Cylinder of 50% v/v Methane.
Cylinder of nitrogen (zero gas).
Exhaust Pipe (at least one metre of plastic tube).
Multimeter.
(1) Remove the dust caps from the two pipes / tubes
leading to the Remote Gassing Cell Nozzles. (Whilst
the RGC is not being used for response checking, the
pipes / tubes leading to the RGC should be sealed
to prevent dirt / moisture ingress into the RGC. It is
assumed that the dust caps supplied tted to the
gassing cell nozzles will be used for this purpose.)
(2) Connect the outlet from the zero gas cylinder to the
pipe / tube leading to the RGC.
(3) Ensure that the exhaust pipe / tube coming from
the RGC is clear and that it vents well away from
the Searchpoint Optima. (If concentrated %V/V gas
leaving the exhaust pipe / tube gets into the main
measurement chamber it will signicantly affect the
readings obtained when using the RGC.)
89
Page 90
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(4) Flush the RGC with zero gas for at least 30 seconds.
(5) Select the CALIBRATE / CAL SENSOR menu option
and re-ZERO the unit. (Do not re-calibrate the unit’s
span gas response.)
(6) Disconnect the zero gas and connect the high
concentration %V/V span test gas to the pipe / tube
leading to the RGC.
(7) Apply 50%V/V methane to the RGC at a ow rate of
0.3 litres / minute.
(8) Allow approximately 30 seconds to 1 minute for the
gas concentration in the RGC to stabilise.
(9) Monitor the DISPLAY’ed gas reading and conrm
that it is within +/-10% LEL of the anticipated reading
(57.5%LEL +/- 10%LEL for 50%V/V methane in the
RGC.). If the reading is within +/- 10% LEL of what
is anticipated, the unit is operating correctly. Do not
consider re-calibrating units with apparent errors less
than +/- 10% LEL. Be aware that eld calibration and
response checking techniques using the RGC are not
sufciently accurate to determine whether such errors
are genuine, or to correct them.
(10) If the DISPLAY’ed gas reading differs from the
anticipated reading by more than +/- 10% LEL, it is
possible that there might be a calibration error but
it is still more likely that any errors will be due to the
prevailing conditions, test gas or gassing technique.
Before considering re-calibration, double-check the
following:-
a. The optics are clean and un-contaminated.
b. The unit has been correctly zeroed in a genuine
zero gas background.
90
Page 91
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
c. The correct test gas and concentration are being
used for the range being tested.
d. The tolerance on the test gas concentration is
signicantly less than the apparent reading error.
e. There is adequate test gas in the cylinder.
(Cylinders that are nearly empty tend to read on
the low side.)
f. The test gas in the measurement chamber / remote
gassing cell is not being pressurised due to high
ow rates or blockages / restrictions.
g. The atmospheric pressure is not unusually high
or low.
h. The unit has had sufcient time to stabilise in it’s
operating environment. (At least 30 minutes, ideally
1 hour after any signicant change or power-up.)
i. An approved, Honeywell Analytics supplied gas
testing accessory is being used. (Either the gassing
cover, calibration cap or the remote gassing cell.)
If after checking the above, the error remains,
consider re-calibrating the unit in accordance with the
procedure detailed in Section 6.4.
(11) Before releasing the detector from INHIBIT, ensure
that any test gas inside the unit’s RGC has been fully
removed. This can be achieved by blowing instrument
air / nitrogen through the RGC for approximately
1 minute.
(12) Re-seal the pipes / tubes leading to the RGC using
the dust caps provided (or a suitable alternative).
(13) Release the detector from INHIBIT by selecting the
MAIN DISPLAY menu option.
91
Page 92
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(14) Provided that on the MAIN DISPLAY, the unit is
reading 0.0% LEL and the ‘/’ line is rotating, the unit
is operating normally and all tests and maintenance
activities have been completed.
If the ‘/’ line has been replaced by a W, there is an
ACTIVE WARNING in the unit, which should be
investigated and where possible cleared before leaving
the unit for operational use.
If the ‘/’ line is not rotating or has been replaced by an
F, there is an ACTIVE FAULT. The unit will not operate
with an ACTIVE FAULT. Use the DIAGNOSTICS menu
option to identify the cause of the FAULT and remedy
where possible.
(15) Disconnect the SHC-1 interrogator from the unit.
(16) The functional response check has been completed.
7.3 INSPECTION AND TESTING OF UNITS
INSTALLED IN DUCTS
Obtaining access to units mounted in ducts can be more
difcult than for units in open installations. Ideally, one would
wish to perform all inspection and testing activities without
removing units or their mounting plates from the duct wall.
92
Page 93
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
The duct mounting kit makes it possible to interrogate
and functionally gas test units in-situ, which covers most
recommended maintenance and testing activities. However,
it is not possible to inspect or clean a unit whilst it is inside
the duct. The requirement to inspect and clean a unit varies
depending upon the conditions inside the duct:-
a. Clean / Dry Ducts: Where the conditions inside a duct
are clean and dry, the likelihood of contaminant or
condensation build-up on the dust barrier or optics
is relatively low. Provided that a unit is not reporting
any FAULTs or WARNINGs, it should not be necessary
to physically inspect it. Typical clean / dry duct
installations include ltered, onshore HVAC inlets and
outlets from clean plant / building areas.
b. Dirty / Damp Ducts: Where the conditions inside a
duct are dirty or damp, the likelihood of contaminant
or condensation build-up on the dust barrier or optics
is signicantly increased. It is therefore strongly
recommended that units are temporarily de-mounted
from the duct in order to perform inspection and
cleaning. Typical dirty / damp duct installations
include offshore HVAC inlets and un-ltered plant /
building inlets.
The procedure for testing and inspection of units installed
in ducts is essentially the same as that described in
Section 7.2.
93
Page 94
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
7.4 REMOVAL AND REFITTING OF FLOW
HOUSING
7.4 1 Removal of Flow Housing
Before the inspection check can be carried out on a
Searchpoint Optima Unit tted with a Flow Housing, the Flow
Housing must be removed as follows:
(1) Disconnect any pipework attached to the owhousing.
(2) Using a ½ inch A/F open ended spanner, remove the
two black nuts which retain the ow housing. Keep
the O-ring seals which are below the retaining nuts.
(3) Slide the ow housing off the Optima. NB: This may
require some force due to the friction of the O ring.
(4) The window and mirror can now be inspected and
cleaned if necessary.
7.4.2RettingofFlowHousing
To ret the ow housing, proceed as follows:
(1) Check the window and mirror are free from
contamination.
(2) Ensure that the large sealing O ring, in the body of
the ow housing, and the two small O rings, which
go below the retaining nuts, are clean and in good
condition. Replace if in doubt.
(3) Slide the ow housing over the end of the
Searchpoint Optima and push until the ow housing
is rmly seated.
94
Page 95
MAN0551 Issue 07 - 09/08
2108M0501
7. ROUTINE CHECKS
(4) Place the small O-rings on the threaded pipes which
are used to secure the ow housing. Fit the retaining
nuts to the threaded pipes and tighten them down.
(5) Ensure that the main seal and the seals below the
retaining nuts are fully compressed and providing a
good seal.
(6) Reconnect any pipework that was attached to the
ow housing.
95
Page 96
MAN0551 Issue 07 - 09/08
2108M0501
96
Page 97
MAN0551 Issue 07 - 09/08
2108M0501
8. FAULT FINDING
8.1 TROUBLESHOOTING
The table below describes some possible faults and problems that can
be encountered and their most likely causes and remedies. The user
should be aware that there are often signicant differences between what
appears to be the problem and the actual problem when fully diagnosed.
Experience has shown that a methodical, whole-system orientated
approach is the most effective for solving problems with gas detection
systems and installations.
Fault / Problem
Output is 0mA
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
Cause / Remedy
Unit is in FAULT condition
Connect SHC-1 interrogator to unit
and use DIAGNOSTIC menu options to
ascertain reason for FAULT report.
Electrical installation problem.
(1) Check +24V power supply to unit.
(2) Check cables and connections,
especially 4-20mA loop connections.
(3) Check that unit has correct 4-20mA
output conguration for use with the
controller.
Optical surfaces are obscured by dirt /
contaminants.
Clean optical surfaces.
Unit’s zero position has negative offset.
Check that optics are clean and dry.
Re-zero unit.
97
Page 98
MAN0551 Issue 07 - 09/08
2108M0501
8. FAULT FINDING
Fault / Problem
Output is 0mA
Unit fails to
respond to
SHC-1 Handheld
Interrogator
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
Cause:
Cause / Remedy
Unit has developed an electrical fault.
Most electrical faults result from damage
caused by site / installation problems.
Check for correct wiring, voltage spikes
/ transients, power surges and earthing
problems.
Incorrect connection of interrogator’s
communication link.
Check that the SHC-1 is correctly plugged
into IS socket or that SHC Protection
Device leads are connected to the right
junction box terminals.
Incorrect software version in Handheld
Interrogator.
Optima Plus only works with version 3V0
interrogator software and above. Check
interrogator software version.
No power applied to Optima Plus unit.
Remedy:
Cause:
Remedy:
Cause:
Remedy:
Check +24V power supply to unit.
Incorrect mode selected on interrogator.
Select Optima + mode on interrogator.
Battery failed in Handheld Interrogator.
Check / replace interrogator battery.
98
Page 99
MAN0551 Issue 07 - 09/08
2108M0501
8. FAULT FINDING
Fault / Problem
Unit does not
respond to test
gas.
Unit does
not produce
the predicted
response to test
gas.
Cause:
Remedy:
Cause:
Remedy:
Cause / Remedy
If unit is sending 4mA (active), this is more
likely to be a problem with the test gas or
gassing technique than with the unit.
(1) Check that the functional gas test
procedure is being performed
correctly. (See Section 7.2)
(2) Check that correct test gas and
concentration are being used.
(3) Check that the gas cylinder is not
empty.
(4) Check that any gas tubing or
inlet pipes used are not broken or
blocked.
(5) Check that the unit is not in FAULT
(0mA) or FORCE’d to a particular
4-20mA output current.
Problem with test gas or gassing
technique.
(1) Check that the functional gas test
procedure is being performed
correctly. See Section 7.2, paying
particular attention to items 15)
to 17). (Also see Section 6.4
CAUTIONS.)
Cause:
Remedy:
(2) Check that the correct test gas and
concentration are being used.
Calibration error or span drift.
If certain that the gas and gassing
technique are correct and that any
discrepancy is due to the unit’s calibration,
re-calibrate the unit in accordance with
Section 6.4.
99
Page 100
MAN0551 Issue 07 - 09/08
2108M0501
8. FAULT FINDING
Fault / ProblemCause / Remedy
Unit’s output
appears to be
drifting.
Cause:
Remedy:
Cause:
Remedy:
Correct response to genuine, low level
uctuations in gas concentration where
the unit is installed.
A commonly misinterpreted problem
which is resolved when the source of the
uctuating gas leak is nally identied.
If a unit is transmitting a gas reading,
double-check the gas concentration at
the exact point where the detector is
installed using a sensitive portable gas
detector that has been carefully zeroed.
(Do not use a standard catalytic detector
on a 0-100% LEL range, they are not
sensitive enough to reliably detect low %
LEL concentrations.)
Build-up of contaminants on optics,
especially oil-mist, exhaust fumes, grease
and solvents.
Check that dust barrier is tted correctly,
clean and intact. Closely inspect the
optics to be sure that nothing is building
up on them. Clean and re-zero unit if
necessary.
Cause:
Remedy:
Exposure of unit to extreme
temperatures.
Check unit’s FAULT / WARNING log
to see if it has records of Temp Lim
Exceded. If temperature problems are
conrmed, either relocate or shield the
detector or consider use of a sampling
system.
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.