Find out more
Contact Honeywell Analytics:
www.honeywellanalytics.com
Europe, Middle East, Africa
Life Safety Distribution AG
Wilstrasse 11-U31
CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
gasdetection@honeywell.com
Americas
Honeywell Analytics Distribution, Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8208
detectgas@honeywell.com
www.honeywell.com
Technical Services
ha.emea.service@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (1)
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050,
Korea
Tel: +82 (0)2 2025 0307
Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com
INSTALLATION INSTALLATION INSTALLATION
INSTALLATION
6. The earth bonding arrangement must ensure that the maximum
peak voltage between the unit case earth and any eld cable
conductor is less than 350V. Voltages in excess of this can cause
permanent damage to the unit’s RFI protection lters.
7. The use of a single, screened cable for each gas detector ensures
maximum screening and minimum crosstalk. Cabling arrangements
which use a single cable for connecting a number of eld devices
compromise screening, increase the potential for crosstalk and
prevent implementation of true star earthing.
8. Any electrical interference induced onto the 4-20mA loop
conductors by the installation must be kept below the levels
necessary to comply with the general requirements of EN50054.
In practice, this means that peak noise currents induced on the
current loop should be no greater than ± 0.25mA.
9. The 0V rail of the control card
/ control system is often directly
connected to one side of the 4-20mA current sensing resistor.
Electrical noise on such a rail is therefore directly connected to
the 4-20mA input. In order to avoid additional noise being induced
on the 0V rail, it should not be commoned with the safety earth/
ground, which frequently carries a high level of electrical noise.
10. All electrical equipment connected to the system should comply
with EN50081 & EN50082.
11. The 24V supply should be free from large transients and
uctuations.
12. The eld cabling conductors should have sufcient cross sectional
area to ensure that the minimum supply voltage applied to the
system is 18V at a current of 420mA.
This corresponds to a maximum round loop impedance of 14 ohms
for a nominal 24V system supply.
13. Receivers should not be installed in close proximity to the antennae of
high powered radios, radar and satellite communication equipment.
4.3.2 Electrical Installation
1. Isolate all associated power supplies and ensure that they remain OFF
during this procedure.
2. If the units are to be installed with junction boxes other than DVC100/
DX100 junction boxes, ensure that the boxes:
• have M20 cable gland entries for BASEEFA units, or 3/4 NPT for
UL and CSA.
• have terminals for 5 wires and an earth.
3. Remove the M20 blanking plugs (if tted) and attach the Excel
transmitter and receiver cables to their junction box. Fit the locking
rings (if supplied) before terminating the cables in the junction box.
4. Fit approved cable glands to the junction box cable entries, using
sealing washers where necessary to maintain the ingress protection
rating.
5. Fit approved blanking plugs to all unused cable entries.
6. Make appropriate electrical connections as shown in the following
diagrams.
4.3.3 Receiver Connections via DVC100
4.3.4 Receiver Connections via DX100
4.3.5 Transmitter Connections
4.3.6 Remote Installation Receiver Connections
4.3.7 Transmitter Connections - Turbo Heating Disabled
11 12 13 14
Installation Guide
Searchline Excel
Open Path Infrared Gas Detector
CONTENTS
1. Introduction 2
2. Safety 3
3. Mechanical assembly 4
3.1 General 4
3.2 Transmitter 4
3.3 Receiver 4
3.4 Adjustable Mountings 5
4. Installation 6
4.1 General 6
4.2 Mechanical Installation 6
4.3 Electrical Installation 10
4.3.1 Electrical Connections 10
4.3.2 Electrical Installation 12
4.3.3 Receiver Connections via DVC100 12
4.3.4 Receiver Connections via DX100 13
4.3.5 Transmitter Connections 13
4.3.6 Remote Installation Receiver Connections 14
4.3.7 Transmitter Connections - Turbo Heating Disabled 14
1 2
1. INTRODUCTION
This guide provides the installation personnel with the basic information
necessary to mechanically install the Searchline Excel system units and
make the necessary electrical connections.
This guide is not intended to replace the associated Searchline Excel
Technical Handbook (2104M0505) which contains the full safety,
installation, commissioning, maintenance and fault nding instructions.
These procedures assume that consideration of the location and
mounting of the system units has already been taken into account in
accordance with the guidelines in the Technical Handbook.
The following diagram shows a typical system conguration and
identies the main parts.
DVC100 / DX100
(or other junction box)
Mounting Plate
Mounting Bracket
PL612
(or other junction box)
Path
5 - 200m
Receiver
Transmitter
Flexible Conduit
Pivot Block
Issue 02 12/2005
H_MAN0558_ 2104M0510
09-07
© 2007 Honeywell Analytics
11063
2. SAFETY 3. MECHANICAL ASSEMBLY
MECHANICAL ASSEMBLY
4. INSTALLATION
Ensure that you read and understand these instructions BEFORE
handling or operating the equipment.
Please pay particular attention to the Safety Warnings.
WARNINGS
The Searchline Excel System is certied for and intended
for use in potentially hazardous areas. Install and use the
Searchline Excel System in accordance with the latest
regulations.
For installations in the UK, the Code of Practice
SELECTION, INSTALLATION AND MAINTENANCE OF
ELECTRICAL APPARATUS FOR USE IN POTENTIALLY
EXPLOSIVE ATMOSPHERES should be strictly observed.
General recommendations are given in BS5345:Part 1:1989.
Specic requirements for ameproof (Type ‘d’), intrinsically
safe (Type ‘I’) and increased safety (type ‘e’) protection are
given in BS 5345: Part 3: 1979, BS 5345:Part 4:1977 and
BS 5345: Part 6:1978 respectively.
For installations in North America, the national Electrical
Code (NFPA 70 - 1990) or later issues should be strictly
observed.
Elsewhere, the appropriate local or national regulations
should be used.
The Code of Practice regarding SELECTION,
INSTALLATION, USE AND MAINTENANCE OF APPARATUS
FOR THE DETECTION OF COMBUSTIBLE GASES (OTHER
THAN FOR MINING APPLICATIONS OR EXPLOSIVE
PROCESSING AND MANUFACTURE) must be complied
with. Refer to BS6959:1988 in the UK or the appropriate
local or national regulations.
3.1 GENERAL
This section details the mechanical assembly information and important
dimensions necessary for installing the system units. Adjustable parts
which form part of the mounting assemblies are also shown.
3.2 TRANSMITTER
3.3 RECEIVER
160mm (SR)
211mm (MR/LR)
291 (SR) 353 (MR/LR)
Approximately 300mm
417mm
417 (SR)
433 (MR/LR)
160mm
291mm
3.4 ADJUSTABLE MOUNTINGS
Clamp Nut
Mounting Bracket
adjusting screws (2 off)
Adjustment Clamp
lock screw (2 off)
Pivot Block
adjusting screw (2 off)
Adjustment Clamp
lock screw (2 off)
Clamp Nut
4.1 GENERAL
Searchline Excel is designed to allow installation to be performed by a
single operator.
The installation procedure is split into mechanical installation and
electrical installation. Each unit needs to mounted to a supporting
structure before making the electrical connections. The diagrams show
different ways of orientation for the mountings.
4.2 MECHANICAL INSTALLATION
This mechanical installation procedure applies to both the receiver and
the transmitter.
1. Ensure that the equipment to be
installed is correct for the type
Mounting
Plate
of installation required (i.e. short/
medium/long range).
2. Fit the mounting bracket to the
mounting plate for the unit, as
shown.
Mounting
Bracket
Isolation Kit
3. Fit the mounting plate to the
supporting structure in one of the
following ways:
• by through bolts directly to a at surface.
• by U-bolts (2 off) to a single 150mm diameter pipe/pole.
• by U-bolts (4 off) to two 55mm diameter pipes/poles,
166mm apart.
Honeywell Analytics Limited reserve the right to change or revise the
information supplied in this document without notice and without
obligation to notify any person or organisation of such revision or
change. If further details are required that do not appear in this
document, contact Honeywell Analytics Limited or one of their agents.
3
INSTALLATION
Identify the mounting holes using the following diagram and the
accompanying table. The subsequent diagrams show the different types
of mountings.
Notes: 1. Mounting plate fixing holes are clear. Searchline Excel system
component mounting holes are threaded.
2. The mounting plate fixings are not supplied.
7
Approximately 300mm
4
INSTALLATION
Identity Quantity Size Used For
A 8
∅ 7.5mm
B 8
C 4
D 3
E 4
F 2
G 4
H 3
J 3
∅ 9.5mm
M6 tapped.
M6 tapped.
M10 tapped
M6 tapped
M6 tapped
M8 tapped
M10 tapped
4. Fit an adjustment clamp to the unit’s pivot
block mounting stud so that it sits on the
stud’s shoulder with the correct orientation
as shown in the diagram.
5. Tighten the adjustment clamp’s
grubscrews until they just grip the
unthreaded part of the mounting stud.
6. Fit the pivot block to the mounting bracket
using a self-locking clamp nut and washer
(M12 or M20) with the correct orientation
as shown in the diagram.
Do not fully tighten the nut.
Duel 2 ‘’ pipe or pole mounting, at
surface mounting.
Single 6’’ pole, at surface mounting,
dual 2.5’’ ID pipe.
PL612/Bartec mounting.
DVC100 mounting.
DX100 mounting.
Killark/Akron mounting.
Sun/heat shade mounting.
Short range transmitter, all receiver
brackets.
Me d ium/ L ong ran g e tr ansm i tter
mounting bracket.
8 9 10
Mounting Stud
Adjustment
Clamp
Pivot
Block
Mounting
Bracket
Self-locking
Clamp Nut and
Washer
Mounting
Bracket
Grubscrew
5
INSTALLATION INSTALLATION
Ensure that the adjustment clamp’s stub lever is positioned
approximately centrally between the mounting bracket’s grubscrews.
Adjust the screws if required.
7. Fit an adjustment clamp to the unit’s
pivot block mounting stud so that it
sits on the stud’s shoulder with the
correct orientation as shown in the
diagram.
8. Tighten the adjustment clamp’s
grubscrews until they just grip
the unthreaded part of the unit’s
mounting stud.
9. Fit the unit to the pivot block using
a self-locking clamp nut and washer
(M12 or M20).
Do not fully tighten the nut.
Ensure that the adjustment clamp’s
stub lever is approximately centrally
positioned between the pivot block’s
grub screws. Adjust the screws if
required.
10. Fit a suitable junction box, e.g.
DVC100/DX100 or other suitable type
of junction box, to the mounting plate
Note: For information about alternative
types of junction box see Section
4.2 Electrical Installation.
11. Measure the distance (in metres)
between the transmitter and receiver
units.
This distance is required by the
system commissioning personnel.
Mounting
Stud
Stub Lever
Adjustment
Clamp
Surface Mounting
Single Pipe / Pole
Dual Pipes / Poles
6
4.3 ELECTRICAL INSTALLATION
4.3.1 Electrical Connections
All ranges of Searchline Excel comply with the EMC requirements
EN50081 & EN50082. In order to maintain compliance with these
standards it is essential that the electrical installation of Excel is
engineered correctly.
Electrical installation standards vary for different countries, companies
and applications and it is the responsibility of the installation design
authority to determine the applicable standards and ensure compliance
with them. When designing electrical installations for Excel,
Honeywell Analytics Limited recommend that the installation design
authority considers the following:
1. Where possible the unit cases should not be electrically connected
to electrically noisy (dirty) metalwork or conductors. An electrical
isolation kit is available (see Technical Handbook) to provide the
required electrical insolation between the units mountings and
its mounting plate. The case is internally connected to the green/
yellow GND wire which should preferably be connected to a low
noise (clean) earth line. See also 5 of this section.
2. The entire length of the eld cabling connected to each unit should
be fully shielded with the shield connected to a low noise (clean)
earth line.
3. The low noise (
clean) earth line should only be connected to safety
earth (usually dirty) at a single point. This connection should be
made in such a manner that it does not introduce noise onto the
low noise earth. Star earthing arrangements minimise earth current
crosstalk.
4. The shields of the eld cabling should not be connected such that
earth loops are produced, or in a manner that will result in the
shields carrying large currents from heavy plant or equipment.
5. Ideally, the eld cable shield should be connected to the unit’s
green/yellow GND wire, providing a single, continuous earth shield.
This connection mus t not be allowed to complete an earth loop.