Controllable anti-pollution check valve EA type
RV284...A
RV284...B
Construction
The check valve comprises:
•Housing
• DVGW-approval check valve cartridge
• Test plug with seal ring
Materials
• Dezincification resistant brass housing
• High grade synthetic material check valve cartridge
• High quality synthetic material test plug
• NBR seal ring
RV284
Product specification sheet
Application
Check valves of this type are for use as an independent means
of preventing reverse water flow.
They can also be used for industrial, commercial and similar systems where back pressure, back flow and back syphonage
must be prevented.
The classicfications of appliances to meet these requirements
are specified in EN 1717.
Special Features
• DIN/DVGW-approved
• Universal application
• Easy installation
•Low pressure loss
• Quiet operation
• Create no shock pressure loadings
Range of Application
Medium Water
Technical Data
Operating temperature
Max. inlet pressure 25.0 bar
Opening pressure 0.05 bar
Connection size With internal thread
Up to 70 °C / 167 °F
(short term up to 90 °C / 194 °F)
1
/2" - 1"
With compression connections 15 mm,
∅22 mm and ∅28 mm
EN0H-1204GE23 R0206 y Subject to change without notice
www.honeywell.com 9

RV284 Controllable anti-pollution check valve EA type
RV284...A
Method of Operation
Spring loaded check valves have a moving seal disc which is lifted off the seat by a greater or lesser amount depending on the
flow rate through the valve. If the flow falls towards zero, then the
spring pushes the disc back onto the seat and seals the waterway.
To ensure continuing correct function it is recommended that
check valves be regularly checked and maintained (as specified
in EN 1717).
Options
RV284-... A = With internal thread
RV284-... B = With compression connections
RV284...B
Connection size
RV284...A RV284...B
Connection size R
1
/2"
3
/4"1"∅ 15 ∅ 22 ∅ 28
Weight approx. kg 0.125 0.168 0.220 0.170 0.260 0.390
Dimensions mm
L526369728489
H273339272932
D272929273646
Test and drain plug R
k
-value m3/h 4.1 8.8 16.5 4.1 8.8 16.5
vs
Nominal flow rate in m
3
/h
1
/4"
1.63.46.41.83.46.4
1
/4"
1
/4"
1
/4"
1
/4"
1
/4"
at ∆p = 0.15 bar
10 www.honeywell.com
EN0H-1204GE23 R0206 y Subject to change without notice

Installation Example
RV284 Controllable anti-pollution check valve EA type
4
6
8
2
bar
0
10
Installation Guidelines
• Install in horizontal pipework with test and drain plug downwards
o This position is best for draining
• Install shutoff valves
o Shutoff valves provide optimal serviceability
• Ensure good access
o Simplifies maintenance and inspection
• Install right after water meter if applicable
o Protects against backflow from water systems
Flow Diagram
Typical Applications
Check valves of this type are suitable for use as a safety device
on water installations as specified in EN 1717.
They can also be used within the scope of their specification.
The following are some typical applications:
• In central water supply systems
• After a water meter
• As a safety device up to liquid category 2 of EN 1717
EN0H-1204GE23 R0206 y Subject to change without notice
www.honeywell.com 11

RV284 Controllable anti-pollution check valve EA type
Spare Parts
Inlet check valve RV284, from 1997 onwards
No. Description Dimension Part No.
1
c Check valve cartridge
/2" 2166200
3
/4" 2110200
1" 2164400
d Blanking plug all S06K-1/4
with O-ring R
1
/4"
(5 pcs.)
3
e Seal ring
/4" 0901444
(10pcs.) 1" 0901445
Automation and Control Solutions
Honeywell GmbH
Hardhofweg
D-74821 Mosbach
Phone: (49) 6261 810
Fax: (49) 6261 81309
http://europe.hbc.honeywell.com
www.honeywell.com
Manufactured for and on behalf of the
Environmental and Combustion Controls Division
of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37, Switzerland by its Authorised Representative Honeywell GmbH
EN0H-1204GE23 R0206
Subject to change
© 2006 Honeywell GmbH