RV280
Controllable anti-pollution check valve EA type with internal thread
Product specification sheet
Application
Check valves of this type are for use as an independent means
of preventing reverse water flow.
They can also be used for industrial, commercial and similar systems where back pressure, back flow and back syphonage
must be prevented.
The classicfications of appliances to meet these requirements
are specified in EN 1717.
Special Features
• Universal application
• Suitable for installation in any position
• Create no shock pressure loadings
• Meets KTW recommendations for potable water
•Low pressure loss
Range of Application
Medium Water, compressed air, petroleum, medi-
um and light fuel oils, kerosene, gasoline
with less than 15 % aromatic content.
Not suitable for gaseous mediums below
0.5 bar, steam, heavy oils and benzole.
Construction
The check valve comprises:
1
• Housing with test and drain plugs (
test plugs only)
• Check valve insert
• Union connector with internal thread
• Test and drain plugs
•Disc guide
•Spring
• Disc with lip seal ring
Materials
• Brass housing
• Brass union nuts
• High grade synthetic material disc guide and disc
• NBR lip sealing ring
• Stainless steel spring
• High grade synthetic material blanking plugs
/2" device with
Max. operating pressure
Technical Data
Operating temperature
Opening pressure approx. 0.05 bar
Connection size
16 bar
Water up to 75 °C (short term up to 90 °C)
Compressed air and other mediumsup to
70 °C
1
/2“ - 2“
EN0H-1201GE23 R0206 y Subject to change without notice
www.honeywell.com 13

RV280 Controllable anti-pollution check valve EA type with internal thread
Method of Operation
Spring loaded check valves have a moving seal disc which is lifted off the seat by a greater or lesser amount depending on the
flow rate through the valve. If the flow falls towards zero, then the
spring pushes the disc back onto the seat and seals the waterway.
To ensure continuing correct function it is recommended that
check valves be regularly checked and maintained (as specified
in EN 1717).
Options
RV280-... A = Standard version
Connection size
Special Versions available on request
Connection size Rp
1
/2"*
3
/4"1"1
1
/4"1
1
/2"2"
Weight approx. kg 0.2 0.3 0.5 0.8 1.0 1.9
Dimensions mm
L 65 75 93 110 120 150
H293235434755
sw 27 32 41 50 55 70
Test and drain plug R
-value m3/h 4.5 9.1 17.0 28.0 38.0 60.0
k
vs
Nominal flow rate in m
3
/h
1
/4"*
1
/4"
1
/4"
1
/4"
1
/4"
1
at ∆p = 0.15 bar 1.7 3.5 6.6 10.8 14.7 23.2
* Test plug only
/4"
14 www.honeywell.com
EN0H-1201GE23 R0206 y Subject to change without notice