The RTU is powered at low voltage (12VDC 160mA), preferably using a
power supply module with battery backup (RTU-Qxx), or using an ordinary
power supply having the same characteristics. The power cables must be
dimensioned as indicated in the table below. The maximum allowable voltage
drop on the power cable is 1V.
• Cable length(m) = 1V / (I[A] load x 2 x (res [Ohm/km] /1000))
The device is equipped with 2 non-removable cables of 2m length:
•
Two-pole, twisted, unpolarized cable dedicated to the LON line
connection
2
- LON a 0,325 mm
LON b 0,325 mm
-
white
2
orange
• Ten-pole cable, providing the following signals:
2
- +12VDC 0,34 mm
- GND 0,34 mm
- INPUT 1 + 0,22 mm
- INPUT 2 + 0,22 mm
- RELAY 2 contact C 0,22 mm
- RELAY 2 contact NC 0,22 mm
- RELAY 2 contact NO 0,22 mm
- RELAY 1 contact C 0,56 mm
- RELAY 1 contact NC 0,56 mm
- RELAY 1 contact NO 0,56 mm
red
2
black
2
green / white
2
gray / green
2
brown
2
white
2
blue
2
green
2
yellow
2
gray
The signals must be connected using a shunt box with IP protection level
in conformance with the type of environment in which it is to be used:
- IP55 for moist environments
- Recessed box or IP31 at least for inside installations
The shunt box must be positioned within the perimeter controlled by the
access control system.
Page 4 of 24
Page 5
If necessary, the repeater relays must be inserted inside the box for
r
r
electrical locking commands and the signal light.
2-pole LON
cable
4 mm diamete
2 metri
6,10 cm
15,60 cm
7,20 cm
8,00 cm
10 pole
cable
8.6mm
diamete
Figure 2: Position and dimensions of the non-removable cables
2 meters
4,20 cm
Shunt Box
RTUL19
Cable +12VDC
Cable LON
Cable IN 1
Cable IN 2
Cable OUT 1
Cable OUT 2
Figure 3: Shunt Box
Page 5 of 24
Page 6
N
L
W
11..33 L
OON
W
• The LONW
OORRKKS
S
ORKS
DDaattaa CCaabblleess
1
data cables must be double twisted-pair cables
• In a free topolo gy configuration, the overall length of the sections must not
exceed 500m
• In a bus configuration, the overall length of the sections must not exceed
2700m
• In the free topology configuration, the 50ohm terminator must be enabled
by inserting the appropriate jumper into the FTT10A plug-in on the CTUPLG06 board inside the TemaServer
• In a bus configuration, two terminators must be inserted at the two ends of
the bus (resistance of 100ohm 1% ½W)
• The L
ONWORKS
1
data cables must be dimensioned according to the
indications in Table 1
Cable Type Extension [m] based on cable capacitance
1. Placing the brac ket against the wall to indicate the proper positions of the
holes, make the holes for the two bolts that will go into the wall to hold the
bracket (the bolts are included in the installation kit)
2. M ake sure that the cable tray bathces with the hole for the passage of the
cables
3. Screw in the bolts.
Hole for Cables
Holes for wall
mounting
Hole for inserting bolt and
screw to press against the
anti-removal/anti-open
tamper
Figure 4: Wall Bracket: Front View and Side View
Page 7 of 24
Page 8
11..55 CCaabbllee CCoonnnneeccttiioonnss
1.5.1 LON Cable
LON A
LON B
Note: connection
not polarized
2 meters
6,10 cm
Figure 5: LON (1) Cable Connection
Page 8 of 24
Page 9
1.5.2 Power Supply Cable +12VDC
12VDC (red)
GND (black)
2 meters
6,10 cm
Figure 6: Power Supply Connection
Page 9 of 24
Page 10
1.5.3 Input Cable 1 – Door Contact
The balanced input 1 is dedicated to door status control; the balancing
resistances must be positioned near the clean sensor contact.
IN1 (green / white)
NC CONTACT
White
Yellow
magnetic door contact
GND (black)
Figure 7: Connection for Balanced Input 1 – Door Contact
Page 10 of 24
Page 11
1.5.4 Input Cable 2 - Button
Balanced input 2 is dedicated to status control of the Open button; the
balancing resistances must be positioned near the clean contact of the
button.
IN2 (green / gray)
NO CONTACT
White
Yellow
button contact
GND
Figure 8: Connection for Balanced Input 2 - Button
Page 11 of 24
Page 12
1.5.5 Output Cable Relay 1- Door Open
The Relay 1 output is used for door control. It makes both NO and NC
contacts available.
The external load can be powered directly by AC or DC, in accordance
with the following limits:
- Minimum Load: 12VDC / 10mA
Voltage Working Current Peak Current
Inductive load with direct current:
In this case it is mandatory
to use the 1N4004 diode, which is provided,
(or an equivalent) in parallel to the coil of the electrical locking device, to
increase the life of the relay inside the RTU – see Figure 9.
• Inductive load with alternating current:
In this case it is mandatory
to use the MOV (75VAC), which is provided,
(or an equivalante) in parallel to the coil of the electrical locking device,
to increase the life of the relay inside the RTU − see Figure 10.
•
Life: assuming the relay is activated 200 times a day and that the
voltage/current limits of the preceding table are respected, the life is
guaranteed for at least 6 years; if the relay is activated less frequently,
the life of the relay increases proportionally.
In case of excessive use (> 200 operations / day) it is suggested to use
an external relay.
Page 12 of 24
Page 13
1N4004
Diode Transient
Suppresso
r
VEXT _+VDC
VEXT_GND
Relay 1
Green = C
Yellow = NC
Gray = NO
coil for electrical locking device/repeater
Figure 9: Connection for Output Relay 1 (NO) – Door Open – DC Voltage
VEXT_Vac1
Mov75Vac
Soppressore
di transienti
VEXT _Vac2
Green = C
Yellow = NC
Gray = NO
Figure 10: Connection for Output Relay 1 (NO) – Door Open – AC Voltage
Rele 1
Bobina elettroserratura / relè di ripetizione
Page 13 of 24
Page 14
1.5.5.1 Using an External Relay
In case of excessive use or use under elevated current or voltage, you must
insert a relay capable of supporting the load for a higher number of
operations.
The coil for the repeater relay must always be equipped with transient
suppressors, as can be seen in Figures 9 and 10.
It is also suggested to use a transient suppressor on the load in order to
prolong the life of the external relay.
Output Relay 2 is used for signaling the status of the door (gateway
occupied / free ) and provides both NO and NC contacts.
The external load can be powered directly from AC or DC power, in
accordance with the following limits:
Voltage Working Current Peak Current (max
Suppressor
0.5 Sec)
30VDC 0.5 A 2 A 1N4004 Diode
30VAC 0.5 A 2 A MOV 75Vrms
•
Inductive load with direct current:
In this case, it is mandatory to use a repeater relay and a 1N4004 diode
in parallel to the coil for the electrical locking device in order to increase
the life of the relay inside the RTU − see Figure 12.
•
Inductive load with alternating current:
In this case, it is mandatory to use a repeater relay and the MOV
(75VAC) in parallel to the coil for the electrical locking device in order to
increase the life of the relay inside the RTU see Figure 13.
• Life: assuming the relay is activated 200 times a day and that the
voltage/current limits of the preceding table are respected, the life is
guaranteed for at least 6 years; if the relay is activated less frequently,
the life of the relay increases proportionally.
• In case of excessive use (> 200 operations / day) it is suggested to use
an external relay.
Page 15 of 24
Page 16
VEXT
Signaling Device (LED)
VEXT
Relay 2
Brown = C
White = NC
Blue = NO
Figure 12: Connection for Output Relay 2 (NO) – Resistive Load – AC/DC
Voltage
To identify the node, you can call the service pin using the relay-reed found
inside the device (see Figure 15). Use the following steps for this procedure:
1. Place a small magnet as indicated in Figure 15 to call the service pin. The
signal is linked to the yellow service LED (at the center), which will blink
throughout the operation.
2. The TemaServer will send a wink command in response to the service pin,
which lights the yellow LED and the buzzer three times. This allows you to
verify that communications are operational to and from the TemaServer.
3. Check to see that the service LED is off at the end of the operation.
The label with the neuron ID that comes with the kit must be applied by the
installer on the appropriate identification sheet. You also must indicate the
location of the terminal in the appropriate box (see example in Table 3).
Description of Location
Entrance to Offices, First Floor, Stairway E
Description of TemaServer
Panel2, Entrance, First Floor, Stairway E
RTUL19
Table 3: Example of Compiled Identification Sheet
Page 19 of 24
Page 20
2 TECHNICAL DATA
22..11 TTeemmaaKKeeyy TTKKLL1199
((RRTTUU--LL1199 ccooddee
11550000115544xxx
)
x
)
Parameter Value
Power Supply 12VDC±15% 100mA nominal (1.4W),
160mA max (2W)
Weight 0.3 kg
Dimensions 156 Lu x 40 La x 27 sp mm
Degree of Protection IP55
Operational
-20 to 60 °C
Temperature
Storage Temperature -20 to 70 °C
Relative Humidity of
0 to 95 % without condensation
Storage
LED 1 LED tricolor Red / Green / Yellow
Buzzer 1
Inputs
2 balanced inputs with 4 statuses:
normal, alarm, cut, short
Output Relay 1
Output Relay 2
Electrical Locking Device Command
• Contacts: C / NC / NO (see page 12)
Lamp Command
• Contacts: C / NC / NO (see page 15)
Antenna proxy 125KHz for HID cards
LONWORKS®2
Connection
Conformance to Norms
2
LONWORKS® is a trademark of the Echelon Corporation
reading distance 0 to 40 mm
(MD-15W internal controller)
"Free Topology" type connected with
unshielded double twisted pair cable
In application of directive 2002/96/EC regarding electrical and electronic waste devices, in vigor from 13 August 2005,
Honeywell engages, when requested by the customer, to the collection, treatment, recovery, and proper disposal of all
devices produced.
All users within the European Union are hereby informed of the requirement for the proper elimination of the product as
regulated by laws, rules, and local procedures.
Page 22 of 24
Page 23
Notes:
Page 23 of 24
Page 24
Figure 16: Temakey TKL19
Page 24 of 24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.