Honeywell TKL19, RTUL19 Installation Manual

Page 1
TKL19
(RTUL19)
Tema1.0_L19_IM_1.0_EN Pagina 1 di 24
Installation Manual
Page 2
CONTENTS
1.1 Wall Set Up for the Cable Trays.........................................................3
1.2 Electrical Connections........................................................................4
1.3 LONWORKS Data Cables................................................................6
1.4 Mounting the Wall Bracket..................................................................7
1.5 Cable Connections ............................................................................. 8
1.5.1
1.5.2
LON Cable.............................................................................. 8
Power Supply Cable +12VDC................................................9
1.5.3 Input Cable 1 – Door Contact............................................... 10
1.5.4
1.5.5
Input Cable 2 - Button ..........................................................11
Output Cable Relay 1- Door Open ....................................... 12
1.5.6 Output Cable Relay 2 – Signal Light .................................... 15
1.6 Mounting the Device on the Wall Bracket.........................................17
1.7 Identification Using the Service Pin..................................................18
1.8 Identification Using the Neuron ID....................................................19
2.1 TemaKey TKL19 (RTU-L19 code 1500154xx) ...................................20
2.1.1
2.1.2
Supplied Parts......................................................................21
Optional Parts....................................................................... 21
2.2 Recycling..........................................................................................22
Page 2 of 24
Page 3
PPRREEPPAARRAATTIIOONNSS
11..11 WWaallll SSeett UUpp ffoorr tthhee CCaabbllee TTrraayyss
The cables must:
1) Protrude from the wall.
2) Come out at 120cm
cable tray
from ground (see Figure 1) (advised).
cables
m c
0 2 1
Figure 1: Wall Set Up for the Cable Trays
Version: 1.0 E N
Floor
Page 3 of 24
Page 4
11..22 EElleeccttrriiccaall CCoonnnneeccttiioonnss
The RTU is powered at low voltage (12VDC 160mA), preferably using a power supply module with battery backup (RTU-Qxx), or using an ordinary power supply having the same characteristics. The power cables must be dimensioned as indicated in the table below. The maximum allowable voltage drop on the power cable is 1V.
Cable length(m) = 1V / (I[A] load x 2 x (res [Ohm/km] /1000))
Cabl e Type
AWG mm2 ohm/ Km 160 [ mA] 320 [ mA]
12 3. 3 5. 7 548 274 14 2 8. 8 355 178 16 1. 3 14 223 112 18 0. 9 21 149 74 20 0. 6 34 92 46 22 0. 35 52 60 30 24 0. 2 85 37 18
Ext ensi on [ m] based on l oad
The device is equipped with 2 non-removable cables of 2m length:
Two-pole, twisted, unpolarized cable dedicated to the LON line connection
2
- LON a 0,325 mm LON b 0,325 mm
-
white
2
orange
Ten-pole cable, providing the following signals:
2
- +12VDC 0,34 mm
- GND 0,34 mm
- INPUT 1 + 0,22 mm
- INPUT 2 + 0,22 mm
- RELAY 2 contact C 0,22 mm
- RELAY 2 contact NC 0,22 mm
- RELAY 2 contact NO 0,22 mm
- RELAY 1 contact C 0,56 mm
- RELAY 1 contact NC 0,56 mm
- RELAY 1 contact NO 0,56 mm
red
2
black
2
green / white
2
gray / green
2
brown
2
white
2
blue
2
green
2
yellow
2
gray
The signals must be connected using a shunt box with IP protection level in conformance with the type of environment in which it is to be used:
- IP55 for moist environments
- Recessed box or IP31 at least for inside installations
The shunt box must be positioned within the perimeter controlled by the access control system.
Page 4 of 24
Page 5
If necessary, the repeater relays must be inserted inside the box for
r
r
electrical locking commands and the signal light.
2-pole LON
cable
4 mm diamete
2 metri
6,10 cm
15,60 cm
7,20 cm
8,00 cm
10 pole
cable
8.6mm
diamete
Figure 2: Position and dimensions of the non-removable cables
2 meters
4,20 cm
Shunt Box
RTUL19
Cable +12VDC
Cable LON
Cable IN 1
Cable IN 2
Cable OUT 1
Cable OUT 2
Figure 3: Shunt Box
Page 5 of 24
Page 6
N
L
W
11..33 L
OON
W
• The LONW
OORRKKS
S
ORKS
DDaattaa CCaabblleess
1
data cables must be double twisted-pair cables
• In a free topolo gy configuration, the overall length of the sections must not exceed 500m
• In a bus configuration, the overall length of the sections must not exceed 2700m
• In the free topology configuration, the 50ohm terminator must be enabled by inserting the appropriate jumper into the FTT10A plug-in on the CTU­PLG06 board inside the TemaServer
• In a bus configuration, two terminators must be inserted at the two ends of the bus (resistance of 100ohm 1% ½W)
• The L
ONWORKS
1
data cables must be dimensioned according to the
indications in Table 1
Cable Type Extension [m] based on cable capacitance
AWG mm2 Ohm/Km 50nF/Km 100nF/Km 200nF/Km 500nF/Km 1uF/Km
12 3.3 5.7 2676 1892 1338 846 598 14 2 8.8 2153 1523 1077 681 482 16 1.3 14 1707 1207 854 540 382 18 0.9 21 1394 986 697 441 312 20 0.6 34 1096 775 548 346 245 22 0.35 52 886 626 443 280 198 24 0.2 85 693 490 346 219 155
Table 1: Length/Capacitance of LONW
• The FTT10A Echelon
ORKS
v1.2 User’s Guide suggests using the cables as
1
Cables
indicated in Table 2.
Make and Model AW
G
Belden 85102 16 2700 500 500 Belden 8471 16 2700 400 500 Level IV (twisted pair, solid, unshielded) JY (St) 2x2x0,8 (4 solid wires, spiral­twisted, shielded) TIA Cat5 / 900 250 450
22 1400 400 500
20 900 320 500
Bus Connection Max Length total [m]
Free Topology
Connection Node­to-Node Max Length [m]
Free Topology -
Connection Max Length total [m]
Table 2: Suggested LONWORKS Cables
1
LONWORKS® is a trademark of the Echelon Corporation
Page 6 of 24
Page 7
11..44 MMoouunnttiinngg tthhee WWaallll BBrraacckkeett
Mount the bracket onto the wall as follows:
1. Placing the brac ket against the wall to indicate the proper positions of the holes, make the holes for the two bolts that will go into the wall to hold the bracket (the bolts are included in the installation kit)
2. M ake sure that the cable tray bathces with the hole for the passage of the cables
3. Screw in the bolts.
Hole for Cables
Holes for wall mounting
Hole for inserting bolt and screw to press against the anti-removal/anti-open tamper
Figure 4: Wall Bracket: Front View and Side View
Page 7 of 24
Page 8
11..55 CCaabbllee CCoonnnneeccttiioonnss
1.5.1 LON Cable
LON A LON B
Note: connection not polarized
2 meters
6,10 cm
Figure 5: LON (1) Cable Connection
Page 8 of 24
Page 9
1.5.2 Power Supply Cable +12VDC
12VDC (red) GND (black)
2 meters
6,10 cm
Figure 6: Power Supply Connection
Page 9 of 24
Page 10
1.5.3 Input Cable 1 – Door Contact
The balanced input 1 is dedicated to door status control; the balancing resistances must be positioned near the clean sensor contact.
IN1 (green / white)
NC CONTACT
White
Yellow
magnetic door contact
GND (black)
Figure 7: Connection for Balanced Input 1 – Door Contact
Page 10 of 24
Page 11
1.5.4 Input Cable 2 - Button
Balanced input 2 is dedicated to status control of the Open button; the balancing resistances must be positioned near the clean contact of the button.
IN2 (green / gray)
NO CONTACT
White
Yellow
button contact
GND
Figure 8: Connection for Balanced Input 2 - Button
Page 11 of 24
Page 12
1.5.5 Output Cable Relay 1- Door Open
The Relay 1 output is used for door control. It makes both NO and NC contacts available.
The external load can be powered directly by AC or DC, in accordance with the following limits:
- Minimum Load: 12VDC / 10mA Voltage Working Current Peak Current
Suppressor max 0.5 Sec (inductive load)
12VDC 3A 10A 1N4004 Diode 30VDC 2A 10A 1N4004 Diode 42VDC 0.5A 7A 1N4004 Diode 42VAC 0.5A 7A MOV 75Vrms
Inductive load with direct current: In this case it is mandatory
to use the 1N4004 diode, which is provided, (or an equivalent) in parallel to the coil of the electrical locking device, to increase the life of the relay inside the RTU – see Figure 9.
Inductive load with alternating current: In this case it is mandatory
to use the MOV (75VAC), which is provided, (or an equivalante) in parallel to the coil of the electrical locking device, to increase the life of the relay inside the RTU − see Figure 10.
Life: assuming the relay is activated 200 times a day and that the voltage/current limits of the preceding table are respected, the life is guaranteed for at least 6 years; if the relay is activated less frequently, the life of the relay increases proportionally.
In case of excessive use (> 200 operations / day) it is suggested to use an external relay.
Page 12 of 24
Page 13
1N4004 Diode Transient Suppresso
r
VEXT _+VDC
VEXT_GND
Relay 1
Green = C Yellow = NC Gray = NO
coil for electrical locking device/repeater
Figure 9: Connection for Output Relay 1 (NO) – Door Open – DC Voltage
VEXT_Vac1
Mov75Vac Soppressore di transienti
VEXT _Vac2
Green = C Yellow = NC Gray = NO
Figure 10: Connection for Output Relay 1 (NO) – Door Open – AC Voltage
Rele 1
Bobina elettroserratura / relè di ripetizione
Page 13 of 24
Page 14
1.5.5.1 Using an External Relay
In case of excessive use or use under elevated current or voltage, you must insert a relay capable of supporting the load for a higher number of operations.
The coil for the repeater relay must always be equipped with transient suppressors, as can be seen in Figures 9 and 10.
It is also suggested to use a transient suppressor on the load in order to prolong the life of the external relay.
Mov75Vac Transient Suppressor
Transient Suppressor
Vac
C
NC NO
Vac
VEXT _relay
coil for electrical locking device/repeater
Vext AC = Mov75Vac Vext DC = diodo 1N4004
VEXT_relay
coil for repeater relay
:
Relay 1
Figure 11: Connection for Output Relay 1 (NO) – External Relay
Page 14 of 24
Page 15
1.5.6 Output Cable Relay 2 – Signal Light
Output Relay 2 is used for signaling the status of the door (gateway occupied / free ) and provides both NO and NC contacts.
The external load can be powered directly from AC or DC power, in accordance with the following limits:
Voltage Working Current Peak Current (max
Suppressor
0.5 Sec) 30VDC 0.5 A 2 A 1N4004 Diode 30VAC 0.5 A 2 A MOV 75Vrms
Inductive load with direct current: In this case, it is mandatory to use a repeater relay and a 1N4004 diode
in parallel to the coil for the electrical locking device in order to increase the life of the relay inside the RTU − see Figure 12.
Inductive load with alternating current: In this case, it is mandatory to use a repeater relay and the MOV
(75VAC) in parallel to the coil for the electrical locking device in order to increase the life of the relay inside the RTU see Figure 13.
Life: assuming the relay is activated 200 times a day and that the voltage/current limits of the preceding table are respected, the life is guaranteed for at least 6 years; if the relay is activated less frequently, the life of the relay increases proportionally.
In case of excessive use (> 200 operations / day) it is suggested to use an external relay.
Page 15 of 24
Page 16
VEXT
Signaling Device (LED)
VEXT
Relay 2
Brown = C White = NC Blue = NO
Figure 12: Connection for Output Relay 2 (NO) – Resistive Load – AC/DC Voltage
Mov x Vac Transient Suppressor
Transient Suppressor
Vac_lamp
C
NC NO
Vac_lamp
VEXT _relay
Vext AC = Mov75Vac Vext DC = diodo 1N4004
VEXT_relay
coil for repeater relay
:
Relay 2
Brown = C White = NC Blue = NO
Figure 13: Connection for Output Relay 2 (NO) – Inductive Load – Repeater Relay
Page 16 of 24
Page 17
11..66 MMoouunnttiinngg tthhee DDeevviiccee oonn tthhee WWaallll BBrraacckkeett
Figure 14: Mounting
1) The RTUL19 is positioned atop the wall bracket protrusion
2) The back part is aligned with the wall by rotating
3) The RTUL19 is mounted onto the bracket using screws
Page 17 of 24
Page 18
ACTIVATION
11..77 IIddeennttiiffiiccaattiioonn UUssiinngg tthhee SSeerrvviiccee PPiinn
To identify the node, you can call the service pin using the relay-reed found inside the device (see Figure 15). Use the following steps for this procedure:
1. Place a small magnet as indicated in Figure 15 to call the service pin. The signal is linked to the yellow service LED (at the center), which will blink throughout the operation.
2. The TemaServer will send a wink command in response to the service pin, which lights the yellow LED and the buzzer three times. This allows you to verify that communications are operational to and from the TemaServer.
3. Check to see that the service LED is off at the end of the operation.
Position of magnet
The LED goes yellow
Figure 15: Calling the Service Pin Using a Magnet
Page 18 of 24
Page 19
11..88 IIddeennttiiffiiccaattiioonn UUssiinngg tthhee NNeeuurroonn IIDD
The label with the neuron ID that comes with the kit must be applied by the installer on the appropriate identification sheet. You also must indicate the location of the terminal in the appropriate box (see example in Table 3).
Description of Location
Entrance to Offices, First Floor, Stairway E
Description of TemaServer
Panel2, Entrance, First Floor, Stairway E
RTUL19
Table 3: Example of Compiled Identification Sheet
Page 19 of 24
Page 20
2 TECHNICAL DATA
22..11 TTeemmaaKKeeyy TTKKLL1199
((RRTTUU--LL1199 ccooddee
11550000115544xxx
)
x
)
Parameter Value
Power Supply 12VDC±15% 100mA nominal (1.4W),
160mA max (2W)
Weight 0.3 kg Dimensions 156 Lu x 40 La x 27 sp mm Degree of Protection IP55 Operational
-20 to 60 °C
Temperature Storage Temperature -20 to 70 °C Relative Humidity of
0 to 95 % without condensation
Storage LED 1 LED tricolor Red / Green / Yellow Buzzer 1 Inputs
2 balanced inputs with 4 statuses: normal, alarm, cut, short
Output Relay 1
Output Relay 2
Electrical Locking Device Command
Contacts: C / NC / NO (see page 12)
Lamp Command
Contacts: C / NC / NO (see page 15)
Antenna proxy 125KHz for HID cards
LONWORKS®2 Connection
Conformance to Norms
2
LONWORKS® is a trademark of the Echelon Corporation
reading distance 0 to 40 mm (MD-15W internal controller)
"Free Topology" type connected with unshielded double twisted pair cable
FT3120 Smart Transceiver, 78Kbps
Directive EMC 89/336/EEC, 92 /31/EEC, Low Voltage Directive 72/23/EEC, 93/68/EEC: EN60950 /
Page 20 of 24
EN55022-B / ETSI EN300-330 / EN55024
Page 21
2.1.1 Supplied Parts
KIT of resistances for input balancing
Fisher bolts for wall
2 White resistances 2 Yellow resistances
2 (S4 type) + screws
mounting Fisher bolt for tamper 1 (S4 type) + screws 1N4004 Diode 2 MOV 75Vrms 2
2.1.2 Optional Parts
TORX TX10 Screwdriver Code 1500108AA
Page 21 of 24
Page 22
22..22 RReeccyycclliinngg
In application of directive 2002/96/EC regarding electrical and electronic waste devices, in vigor from 13 August 2005, Honeywell engages, when requested by the customer, to the collection, treatment, recovery, and proper disposal of all devices produced.
All users within the European Union are hereby informed of the requirement for the proper elimination of the product as regulated by laws, rules, and local procedures.
Page 22 of 24
Page 23
Notes:
Page 23 of 24
Page 24
Figure 16: Temakey TKL19
Page 24 of 24
Loading...