Honeywell R0512 User Manual

Excel 50/100/500/600/800
CONTROLLERS
SOFTWARE DESCRIPTION
® U.S. Registered Trademark EN2B-0092GE51 R0512 Copyright © 2012 Honeywell Inc. • All rights reserved
EXCEL 50/100/500/600/800
Trademark Information Echelon, LON, L
LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the L logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, and LonMaker are trademarks of Echelon Corporation.
ONMARK, LONWORKS, LonBuilder, NodeBuilder, LonManager,
ONMARK
EN2B-0092GE51 R0512
EXCEL 50/100/500/600
CONTENTS
REVISION OVERVIEW ....................................................................................................... 5
SYSTEM OVERVIEW ......................................................................................................... 6
DATAPOINTS ..................................................................................................................... 9
PHYSICAL DATAPOINTS ................................................................................................................................. 9
FLEXIBLE DATAPOINTS ................................................................................................................................ 10
PSEUDO DATAPOINTS .................................................................................................................................. 10
GLOBAL DATAPOINTS .................................................................................................................................. 11
MAPPED DATAPOINTS (V2.04.XX OR HIGHER) .......................................................................................... 12
ATTRIBUTES .................................................................................................................... 13
ACCESS LEVEL .............................................................................................................................................. 13
ACKNOWLEDGE ALARM (V2.04.XX OR HIGHER) ....................................................................................... 13
ACTIVE STATE (PRIOR TO V2.04.X) ............................................................................................................. 14
ACTIVE STATE (EXCEL 800) ......................................................................................................................... 14
ALARM DELAY................................................................................................................................................ 15
ALARM SUPPRESSION .................................................................................................................................. 15
ALARM STATUS (PRIOR TO V2.04.X) ........................................................................................................... 15
ALARM STATUS (V2.04.XX OR HIGHER) ...................................................................................................... 16
ALARM TYPE .................................................................................................................................................. 16
ALARM DEFINITION ....................................................................................................................................... 16
CYCLE COUNT ................................................................................................................................................ 18
DELAY TIME SWITCHING UP ........................................................................................................................ 18
DELAY TIME SWITCHING DOWN .................................................................................................................. 18
DESCRIPTORS ................................................................................................................................................ 19
ENGINEERING UNIT ....................................................................................................................................... 19
FEEDBACK DELAY ......................................................................................................................................... 19
HIGH/LOW ALARM/WARNING LIMITS .......................................................................................................... 19
HOURS RUN .................................................................................................................................................... 20
HOURS RUN LOG ........................................................................................................................................... 20
HOURS SINCE SERVICED ............................................................................................................................. 20
3 EN2B-0092GE51 R0512
EXCEL 50/100/500/600/800
HYSTERESIS................................................................................................................................................... 21
INPUT/OUTPUT STATUS TEXT (PRIOR TO V2.04.XX) ................................................................................. 24
INPUT/OUTPUT STATUS TEXT (V2.04.XX OR HIGHER) .............................................................................. 24
INTERVAL COUNT .......................................................................................................................................... 24
INTERVAL LIMIT ............................................................................................................................................. 25
I/O CHARACTERISTIC .................................................................................................................................... 25
PULL-UP RESISTOR HANDLING ................................................................................................................... 26
LAST CHANGE ............................................................................................................................................... 26
LED MODE (XF823X, XFL823X, AND XFX830X MODULES) ........................................................................ 27
MAINTENANCE ALARM ................................................................................................................................. 27
MANUAL VALUE ............................................................................................................................................. 27
NETWORK VARIABLE (V2.04.XX OR HIGHER) ............................................................................................ 28
Alarm Hysteresis ..................................................................................... 21
Trend Hysteresis ..................................................................................... 22
Broadcast Hysteresis .............................................................................. 23
Intrinsic Hysteresis for Analog Input Signals ........................................... 23
NORMALLY OPEN/NORMALLY CLOSED (V2.04.XX OR HIGHER) ............................................................. 28
MOTOR RUN TIME .......................................................................................................................................... 29
OFF PHASE ..................................................................................................................................................... 29
OPERATING MODE ........................................................................................................................................ 29
OUTPUT TYPE ................................................................................................................................................ 31
POINT ALARMS .............................................................................................................................................. 31
PULSE DURATION ......................................................................................................................................... 32
SAFETY POSITION (XFX822X, XFX824X, AND XFX830X MODULES) ........................................................ 32
SCALING FACTOR ......................................................................................................................................... 32
SENSOR OFFSET ........................................................................................................................................... 33
SUPPRESS POINT .......................................................................................................................................... 33
SWITCHING DOWN ........................................................................................................................................ 33
SWITCH-ON COUNTER .................................................................................................................................. 34
Subtype ................................................................................................... 31
TECHNICAL ADDRESS .................................................................................................................................. 34
TREND LOGGING ........................................................................................................................................... 34
USER ADDRESS ............................................................................................................................................. 36
EN2B-0092GE51 R0512 4
Value Hysteresis ..................................................................................... 35
Trend Cycle (V2.03.x) ............................................................................. 35
EXCEL 50/100/500/600/800
VALUE ............................................................................................................................................................. 36
WRITE PROTECTION ..................................................................................................................................... 37
LIST OF DATAPOINT ATTRIBUTES .............................................................................................................. 38
TIME PROGRAMS ............................................................................................................ 41
STRUCTURE ................................................................................................................................................... 41
INDIVIDUAL TIME PROGRAMS ..................................................................................................................... 41
GENERATING A TIME PROGRAM ................................................................................................................. 43
Daily Program .......................................................................................... 41
Weekly Program ...................................................................................... 42
Annual Program....................................................................................... 42
Special Day List ....................................................................................... 43
The "TODAY" Function ............................................................................ 43
ALARM HANDLING .......................................................................................................... 45
POINT ALARMS .............................................................................................................................................. 45
SYSTEM ALARMS .......................................................................................................................................... 46
USER PROGRAM ALARMS ............................................................................................................................ 51
DATA STORAGE ............................................................................................................................................. 51
System Alarms Suppression (V. 2.04.xx or higher) ................................. 50
Alarms Sent across the System Bus ....................................................... 51
TEST MODE (V2.03.X) ..................................................................................................... 53
COMMUNICATION ........................................................................................................... 53
SYSTEM BUS .................................................................................................................................................. 53
Access ..................................................................................................... 54
Bus Initialization ...................................................................................... 54
Bus Communication ................................................................................ 54
I/O Runtime Synchronization ................................................................... 54
Initialization of Distributed I/O Modules ................................................... 55
New Bus Devices .................................................................................... 55
Network-Wide Controller Time Synchronization ...................................... 55
Point Refreshing ...................................................................................... 56
PC COMMUNICATION .................................................................................................................................... 56
EXCEL IRC ...................................................................................................................................................... 56
REMOTE COMMUNICATION .......................................................................................................................... 56
REMOTE TRENDING (DIAL-UP) ..................................................................................................................... 58
MODEMFAQ .................................................................................................................................................... 59
General .................................................................................................... 58
Controller Firmware 2.03.xx and Higher .................................................. 58
Controller Firmware 2.04.xx and Higher .................................................. 58
Excel 800 ................................................................................................. 59
MISCELLEANOUS ........................................................................................................... 60
CUSTOMIZE WINDOWS DEFAULT REGIONAL AND LANGUAGE SETTINGS ........................................... 60
INDEX .............................................................................................................................. 83
5 EN2B-0092GE51 R0512
EXCEL 50/100/500/600/800
EN2B-0092GE51 R0512 6
EXCEL 50/100/500/600/800
page
change

REVISION OVERVIEW

The following pages have been changed from the previous issue of this document:
33 Section “SENSOR OFFSET” added
5 EN2B-0092GE51 R0512
EXCEL 50/100/500/600/800

SYSTEM OVERVIEW

General Excel 50/500/800 controllers support both LONWORKS communi c ation and the
Software The Excel 50/100/500/600/800 system includes a comprehensive software package
Firmware version number All information appearing in this Software Description is valid for firmware versions
Honeywell proprietary C-Bus communication. All L described in the L
Excel 50/100/500/600/800 is a control and monitoring system specially designed for use in buildings. These Excel controllers use the latest Direct Digital Control (DDC) technology. Excel 50/500/800 controllers are also capable of communicating on an open Echelon® L particularly well-suited to controlling buildings such as schools, hotels, offices, and hospitals. Excel 50/100 controllers differ from Excel 500/600/800 controllers in having a fixed input/output configuration. Excel 50 controllers have a smaller fixed input/output configuration, and are designed for smaller buildings such as restaurants, shops, banks, and offices.
Excel 50/100/500/600/800 functions are:
Heating control
Air conditioning control
Energy management
Energy optimization
Other building management functionality
specially designed to meet the requirements of application engineers. It comprises the following:
Datapoint description
Time program
Alarm handling
Password protection
The software package comes with all the files listed. The menu-driven format allows quick and easy operation.
V1.3.xx and earlier. All information, functions, and attributes valid for newer firmware versions (V1.5.xx or higher) are marked by the corresponding version number for which they are valid. Fig. 1 shows various controllers and the firmware version numbers that they support.
ONWORKS Mechanism document (EN0B-0270GE51).
ONWORKS® network. Excel 50/100/500/600/800 controllers are
ONWORKS-related information is
6 EN2B-0092GE51 R0512
EXCEL 50/100/500/600/800 OVERVIEW
7
firmware 2.06.07
firmware 2.06.08
firmware ≤ 2.06.07
firmware 2.06.08
Fig. 1. Controllers and their supported firmware versions
Excel 50 firmware compatibility Please always make sure that your firmware and the bootstrap loader match; if in
doubt, consult Software Release Bulletin(s). Special care must be taken in particular in the case of the combinations of firmware and bootstrap loader with XD50B-xxx modules as set forth in Error! Reference source not found..
Table 1. Firmware / bootstrap loader compatibility with XD50B-xxx modules
bootstrap loader ≤ 1.01.07 NO* OK bootstrap loader ≥ 1.01.08 OK OK *Problems may occur when LONWORKS bus is in use.
Table 2. Firmware / bootstrap loader compatibility with XD50-xxx modules
bootstrap loader ≤ 1.01.07 OK OK bootstrap loader ≥ 1.01.08 OK OK *Problems may occur when LONWORKS bus is in use.
Datapoint description Datapoints are the basis of the Excel 50/100/500/600/800 system. Datapoints
contain system-specific information such as values, status, limit values, and default settings. The user has easy access to datapoints and the information they contain. The user can recall and modify information in the datapoints.
Time programs Whenever you want, you can use time programs to enter the setpoint or status for
any datapoint. The following time programs are available:
Daily programs
Weekly programs
EN2B-0092GE51 R0512
OVERVIEW EXCEL 50/100/500/600/800
Annual programs
The "TODAY" function
Special day list
Daily programs are used to create a weekly program. The annual program is created automatically by multiplying the weekly program and then incorporating additional daily programs. The "TODAY" function enables you to have a direct influence on the switching program. This function enables you to allocate a setpoint or status to the selected datapoints for a defined time period. This action does not depend on the current daily program.
Alarm handling The alarm handling facility offers system security. Alarm signal s can, for example,
Application program You can use the Honeywell CARE engineering tool to create application programs
Passwords Your control system is also protected by passwords. This ensures that only
alert the operator to maintenance work that is due. All alarms that occur are stored in data files and reported immediately. If your system configuration allows, you can also list alarms on a printer or transmit alarms to higher-level front-ends. There are two kinds of alarm: Critical and Non-critical. Critical alarms have priority over non­critical alarms. System alarms, caused by a fault in a controller, are always critical alarms.
To distinguish between alarm types, you can generate your own alarm messages or select appropriate messages already in the system.
The following events all generate alarm messages:
Exceeding limit values
Overdue maintenance work
Totalizer readings
Digital datapoint changes of state
for your system. A particular advantage offered by Honeywell CARE is the ability to create a fully functional control program without having to be familiar with the programming language. CARE stands for Computer Aided Regulation Engineering.
authorized persons have access to the system data. There are four operator levels, each protected by its own password.
Operator level 1: Read only; the operator can display information about setpoints, switching points, and operating hours.
Operator level 2: Read and make limited changes; the operator can display system information and modify certain preset values.
Operator level 3: Read and make changes; system information can be displayed and modified.
Operator level 4: Programming.
Password protection prevents unauthorized access system information and ensures permanent, secure system operation.
EN2B-0092GE51 R0512 8
EXCEL 50/100/500/600/800

DATAPOINTS

An Excel 50/100/500/600/800 system can have the following number of datapoints:
Excel 50: 22 physical (onboard I/Os) plus up to 46 physical LON I/Os
Excel 100: 36 physical (onboard I/Os)
Excel 500: 128 physical I/Os, extendable via L
Excel 600: 128 physical I/Os
Furthermore, Excel 50/100/500/600 support an additional 256 pseudo datapoints. Excel 800: 381 datapoints (random mix of physical and pseudo datapoints) A datapoint has different attributes according to its type. Attributes are displayed
and modified on the XI581 (not with XCL5010, Excel 100C), XI582, and the PC­based XL-Online operator interfaces or on the Excel 50 MMI. Attributes contain information about the given datapoint. This information could be:
Input limits values
Operating status
Current temperature
Elapsed run time
The following sections provide more-detailed information about the different kinds of datapoints and datapoint attributes and explain which attributes are assigned to which datapoints.
ONWORKS I/Os

Physical Datapoints

Physical datapoints are inputs and outputs attached to hardware devices like sensors and actuators.
Fig. 2. Physical datapoint symbols
The following are examples of physical datapoints
Analog inputs NTC, PT 1000, PT 3000, BALCO Sensors (PT 3000/BALCO not with Excel 100C),
Analog outputs Outputs with a continuous 0...10 V output signal for controlling continuous actuators
Digital inputs Inputs for processing voltage-free signals (switches, contacts). Digital outputs (not Excel 100C) Outputs for driving three-position actuators, for example, a damper motor; two
Totalizer inputs Digital inputs for processing pulsed signals up to 20 Hz (depending on Distributed
standard 0 (2)...10 V and 0 (4)...20 mA input, to connect e.g. outside air temperature sensors.
(Excel 100C supplies up to 20 mA on the analog outputs).
position devices, for example
I/O module specifications), for example
, a circulation pump; 0...10 V and pulsed outputs
, metered energy consumption.
EN2B-0092GE51 R1111 9
DATAPOINTS EXCEL 50/100/500/600/800
Pulse 2 “on”
Pulse 2 “off”
Relay 1
Relay 2

Flexible Datapoints

Flexible datapoints allow the control of more than one physical output with one datapoint. There are three subordinate types of flexible datapoints:
Pulse 2
Multi-stage
Pulse 2 flexible datapoint A pulse 2 datapoint allows to pulse two digital outputs (e.g. relays). When activated
Feedback.
(e.g. set to “on”), Pulse 2 triggers one of the digital outputs, and when deactivated, Pulse 2 triggers the other digital output.
Fig. 3. Pulse 2 flexible datapoint switching
Multistage flexible datapoint Multistage flexible datapoints allow to switch up to six physical digital outputs via
one datapoint. A typical example stage fan. A multistage flexible datapoint provides up to six editable stage texts, e.g., stage 1, stage 2, stage 3, etc, to be edited in CARE.
Feedback flexible datapoint Feedback flexible datapoints, also called “DO feedback DI” combine up to three
pairs of digital outputs/digital inputs to form up to three-stage switching with feedback. The digital inputs of each pair act as the feedback point. If the digital input does not feedback the actual equipment status within a predefined time “Off Phase”, then the software will switch down this point type until a "non-alarm" state is reached. In extreme cases, the point may be switched to the off position. See also “Off Phase”.
Increased support (V2.04.xx or higher) Excel 500 controllers now support up to 60 flexible datapoints. In case of Feedback
flexible points, the maximum number is 128. Previous firmware versions supported only up to 20 flexible datapoints.
would be a multi-stage electric heater or a multi-

Pseudo Datapoints

Excel 50/100/500/600 support 256 pseudo datapoints, while Excel 800 supports 381 datapoints (consisting of a random mix of physical and pseudo datapoints) Pseudo datapoints are values (intermediate results and parameters) computed while the application program is running. In contrast to physical datapoints, pseudo datapoints are not directly connected to hardware devices.
Access via the user address During system operation, you may need to access these values. To simplify this
process, you can include pseudo datapoints in the datapoint list, where you can access them directly via their user addresses. Like physical datapoints, pseudo datapoints, too, can have different attributes; for example manual value, set minimum and maximum values, or log trends.
The following are types of pseudo datapoints:
, they can specify a
EN2B-0092GE51 R0512 10
EXCEL 50/100/500/600/800 DATA POINTS
11
C
SYSTEM BUS
LON
Pseudo analog points
Pseudo digital points
Pseudo totalizer inputs
Pseudo point multistage
Pseudo analog points Pseudo analog points are software points containing an analog value in the user
Pseudo digital points Pseudo digital points are software points containing a digital value in the user
Pseudo totalizer inputs Pseudo totalizer inputs are digital software points from the user program, where a .
Pseudo point multistage Pseudo point multistage datapoints are identical to flexible datapoint of the type
program. A pseudo analog point could, for example
, contain a flow temperature setpoint calculated from the room setpoint and the outside air temperature via the heating curve.
program. For example, logical AND operation.
The AND operation provides a logical 1 output when all input conditions are also logical 1. Otherwise the output is a logical 0. If the user program contains such an AND operation on different input conditions, then the output could be available as a pseudo digital datapoint.
totalizer counter input is recorded
"multistage" except that they allow for 16 stages (including the “off stage“) and the attribute "Status Text" allows for 16 status texts to be attached. The attribute "Tech­nical Address" is not required.

Global Datapoints

If your control and monitoring system contains more than one controller, the con­trollers communicate with one another via the system bus. Any given controller can thus both receive (read) datapoints from other controllers and transmit datapoints to other controllers. Such datapoints are referred to as global datapoints.
NOTE: The term “global” as used here encompasses more than just those points
explicitly labeled as “global” in the CARE engineering tool.
Global datapoints which a controller receives (reads) from other controllers are referred to as local global datapoints, and global datapoints which a controller transmits to other controllers are referred to as remote global datapoints. During CARE engineering, the program engineer must take care that he does not exceed the maximum allowed 256 global datapoints (remote and local) per controller.
Fig. 4. Global datapoints are available to all controllers on the system bus
EN2B-0092GE51 R0512
DATAPOINTS EXCEL 50/100/500/600/800

Mapped Datapoints (V2.04.xx or higher)

With firmware version V2.04.xx or higher, those Excel 50/500 controllers which feature free programmability on L
ONWORKS (those that contain the 3120E5 Neuron
chip, i.e. date code 0044 or higher) may have I/O devices connected via the
ONWORKS network. LONWORKS network variables (or individual fields of structured
L network variables) can be mapped to the attribute "Value" of physical datapoints (AI/DI/AO/DO). Pseudo analog, pseudo digital, and pseudo multistage points are also supported for NV mapping.
See Excel 50/500 L for more information on L
ONWORKS Mechanisms Interface Description, EN0B-0270GE51,
ONWORKS network variables and datapoint mapping.
EN2B-0092GE51 R0512 12
EXCEL 50/100/500/600/800

ATTRIBUTES

Each datapoint type has associated with it various parameters which allow the user to set, e.g., the user address, the level of access protection, alarm behavior, and other options. These parameters are called attributes. Each attribute performs a specific function related to the datapoint. A complete list of datapoint types and their attributes appears in Table 17 through Table 19. Not all attributes are available for every datapoint type.
Point refreshing (V1.5.x) Four attributes ("Value", "Manual Value", "Operating Mode", and "Alarm Status") will
be simultaneously refreshed to an XL-Online operator interface. NOTE: A complete list of attributes associated with the various datapoint types
can be found in the section "List of Datapoint Attributes" on page 38.

Access Level

Four levels of protection The attribute "Access Level" protects datapoints against unauthorized changes on
the basis of the password level needed to modify a datapoint. "Access Level" attributes between "1" and "4" are assigned to a point. These attributes correspond to the four password levels found in the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces and the Excel 50 MMI:
Operator level 1: Read only.
Operator level 2: Read and make limited changes.
Operator level 3: Read and make changes.
Operator level 4: Programming.
For example, setting the "Access Level" attribute for the datapoint with the user address "room temp floor 1" to "2" means that all attributes for this datapoint can now only be edited or modified at password level 2 or higher.

Acknowledge Alarm (V 2.04.xx or higher)

The attribute "Acknowledge Alarm" allows a controller to acknowledge an alarm for a flexible datapoint of the type "feedback" without changing the operating mode. The controller takes the point out of alarm as soon as a rising edge is detected on the input of the WIA statement writing to the attribute "Acknowledge Alarm".
Fig. 5. The "Acknowledge Alarm" attribute for WIA statement
This attribute is a virtual attribute and can be accessed only by a WIA statement in CARE. It is not part of the datapoint description and therefore cannot be displayed on an MMI or building supervisor.
EN2B-0092GE51 R1111 13
ATTRIBUTES EXCEL 50/100/500/600/800
(NC/NO system diagram)
digital input
contact status
(NC/NO system diagram)

Active State (prior to V 2.04.x)

The attribute "Active State" defines when a digital input/output is active.
NOTE: The "Active State" attribute does not reflect the current condition of a
NOTE: This is not applicable to digital inputs in applications designed for con-
The following values are possible:
0 = digital input/output is active when a "logical 0 signal" is present
1 = digital input/output is active when a "logical 1 signal" is present
Table 3 indicates the active state for various conditions of the XF523 and XFL523 modules.
Table 3. Active state for the digital input of XF523 and XFL523 modules
digital input
contact status open closed CARE definition
NC NO NC NO
digital datapoint.
trollers using V2.04.xx firmware or higher. In such applications, this attribute is fixed at 1, and the new attribute "Normally Open/Normally Closed" (NO/NC) is active (see section "Normally Open/Normally Closed (V2.04.xx or higher)" on page 28 for more details).
definition - in XL-Online DP­Editor attribute "Active State" (change Active/Passive State text)
CARE interpretation (control table)
display at operator interface (status text)
1 0 1 0 1 0 1 0
1 1 0 0 0 0 1 1
OFF/
trouble:
alarm
ON/
operating
RTN*
* RTN = Return To Normal NOTE: XFL523 Module is applicable only for V2.0.xx software.
OFF/
trouble:
alarm
ON/
operating
RTN*
ON/
operating
RTN*
OFF/
trouble:
alarm
operating
ON/
RTN*

Active State (Excel 800)

The attribute "Active State" defines when a digital input/output is active. 1 means, that a digital input/output is active when a "logical 1 signal" is present
NOTE: "Active State" = 0 is not allowed/possible. NOTE: The "Active State" attribute does not reflect the current condition of a
digital datapoint.
Table 4. Active State for the digital input of XF823 and XFL823 modules
OFF/
trouble:
alarm
CARE definition
definition - in XL-Online DP­Editor attribute "Active State" (change Active/Passive State text)
EN2B-0092GE51 R0512 14
open closed
NC NO NC NO
1 1 1 1
EXCEL 50/100/500/600/800 ATTRIBUTES
15
digital input
Alarm
Alarm
CARE interpretation (control table)
display at operator interface (status text)
1 0 0 1
OFF/
trouble:
alarm
* RTN = Return To Normal
OFF/
trouble:
alarm
ON/
operating
RTN*
ON/
operating
RTN*

Alarm Delay

Delaying alarm outputs The alarm delay time (in seconds) is entered in the attribute "Alarm Delay". The
alarm delay time determines how long an alarm condition must exist before an alarm is generated. Entering an alarm delay time of 10 seconds means that the limit value must be exceeded for at least 10 seconds before this datapoint generates an alarm. If the limit value lasts for only 7 second, then no alarm occurs.

Alarm Suppression

The attribute “Suppress Alarm” establishes whether or not alarm messages from the following alarm attributes should be suppressed:
Operational status
Min/Max. limit
Maintenance alarm
Interval counter
Alarm Status
The following entries are possible:
Off Alarms not s uppress ed
On Alarms suppress ed
Digital input example In addition to a variety of other attributes, a digital input also has the "Operating
Suppression of system The controller will not issue a system alarm when the alarm’s system alarm text alarms (V2.04.xx or higher) starts with an @ character.
Mode", "Alarm Status", and "Maintenance Alarm" attributes. If alarm suppression is activated for this datapoint, then no message is displayed during an operating mode change-over, or when changing into the alarm condition, or when reaching the maintenance alarm.

Alarm Status (prior to V2.04.x)

Alarm monitoring In the case of a digital input or a pseudo digital point, the attribute "Alarm Status"
EN2B-0092GE51 R0512
specifies whether or not alarm monitoring is required. The following entries are possible:
Yes: Alarm monitoring is required
No: Alarm monitoring is not required
When alarm monitoring is required, the alarm message occurs when the digital point changes from the active state to the passive state (alarm reached). An additional message is generated (alarm going) when the digital point returns to the active state (see Fig. 6. Alarm status messaging)
reached
ending
ATTRIBUTES EXCEL 50/100/500/600/800
Operating Mode
Min. Limit
Interval Counter
Alarm Status
DI in
DI in
“Active State”
“Passive State”
Fig. 6. Alarm status messaging
NOTE: The active state and passive state are defined in the "Active State"
datapoint attribute.

Alarm Status (V2.04.xx o r higher)

Alarm monitoring In the case of a digital input or a pseudo digital point, the attribute "Alarm Status"
specifies whether or not alarm monitoring is required. The following entries are possible:
Yes: Alarm monitoring is required
No: Alarm monitoring is not required
When alarm monitoring is required, the alarm message occurs depending on the physical contact status and on the logical status as defined in the online attribute “Normally Open/Normally Closed”.

Alarm Type

The attributes listed in Table 5 are capable not only of generating alarms, but also of writing them to the internal alarm memory and sending them to the PC front-end or to the modem module (when connected).
attribute always critical optional critical or non-critical
Max. Limit X
Maintenance
Alarm
Changing over the attribute "Operating Mode" always results in a critical alarm, but the attribute "Alarm Type" offers a choice for the alarm attributes "Min. Limit", "Max. Limit", "Maintenance Alarm", "Totalizer", and "Alarm Status" whether an alarm is classified as critical or non-critical. Distinguishing between critical and non-critical alarms is significant for the subsequent reporting of the alarms to the PC front-end or to the modem module. Compared to non-critical alarms, critical alarms are given priority on the bus when several alarms are in the alarm queue. When the type of alarm for a datapoint has been decided, e.g. "critical" alarm type, it refers to all alarm attributes for this datapoint.
Table 5. Alarm attributes
X
X
X
X X

Alarm Definition

EN2B-0092GE51 R0512 16
EXCEL 50/100/500/600/800 ATTRIBUTES
17
In the datapoint description, the alarms can be influenced using the functions described below (see also Table 6 on page 17).
Alarm type For each datapoint in the datapoint description, the user can determine whether the
Alarm delay An alarm signal can be delayed by entering an alarm delay time. An alarm signal
Suppress alarm If an alarm signal is not desired from a particular datapoint, this can be fixed in the
signals generated are to be treated as critical or non-critical alarm.
will be generated only if an alarm continues uninterrupted during the alarm delay time.
datapoint description. Thus, all the alarm signals relevant to the particular datapoint and the "Operating Mode" alarm types are suppressed.
Fig. 7. Alarm condition depending on point value and Suppress Alarm status
Fig. 7
shows an example of a changing point value that rises above and falls below the limit Max 2. If Suppress Alarm is not active, then the alarm c ondition s witches between normal to alarm, according to the limit Max 2. If Suppress Alarm is active, then the alarm condition remains normal unless Suppress Alarm is switched off before the point value falls below the limit Max 2. Regardless of the setting of the Alarm suppression flag, an alarm is entered into the controller's history buffer and is also available in the EBI alarm report.
Point alarm It is possible to view all datapoints at the operator interfaces for which the limit
value (analog point) or the alarm status (digital point) is currently exceeded. Driven by a menu, the user address and the accompanying alarm text are displayed on the XI581 (not with XCL5010, Excel 100C) or XI582 operator interfaces or Excel 50 MMI. On the XL-Online operator interface, a datapoint within the framework of the datapoint description can be seen in all four password levels. If a current alarm is present for the point in question, the attribute “Point in Alarm” produces the display “Yes”, otherwise “No”. Within the framework of the datapoint description, it is possible, under the attribute “Alarm text”, to enter an alarm text of up to 18 characters in addition to the prepro­grammed text. There are 256 alarm texts in total. Table 6 presents a summary of various alarm types and attributes.
Table 6. Alarm summary
alarm type/attributes alarm status
enter alarm delay time
alarm suppression
point in alarm
no. of prepro­grammed texts
supplementary text
Limit Values selection in DPD* possible possible X 8 possible Alarm Status selection in DPD* possible possible X 2 possible Maintenance Alarm selection in DPD* - possible - 1 ­Totalizer selection in DPD* - possible - 1 ­Operating Mode always critical - possible - 2 ­System Alarms always critical - - - approx. 110 -
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
delay time
suppression
alarm
grammed texts
text
alarm type/attributes alarm status
user program reports always non-critical - - - - ­*DPD = datapoint description
enter alarm
NOTE: A point is still seen as “in alarm” even when alarm suppression is
enabled.
The attribute "Cycle Count" contains the value indicating the number of transitions to the active state (see "Active State (prior to V2.04.x)" on page 14).
alarm
point in
no. of prepro-

Delay Time Switching Up

This attribute is used in conjunction with flexible points of the type "feedback". It defines the delay time between switching upwards from one stage to another. The delay time affects every stage. The delay time also takes effect when switching, e.g. from manual value 0 to 2. In this case, it is switched from stage 0 to stage 1, then to stage 2 with the delay time between the switching processes.
Range: 0 to 255s Default value: 10s Resolution: 1s
supplementary

Cycle Count

Fig. 8. Delay time switching up

Delay Time Switching Down

This attribute is used in conjunction with flexible points of the type "feedback". It defines the delay time between switching downwards from one stage to another. The delay time affects every stage.
Range: 0 to 255s Default value: 10s Resolution: 1s
The feedback delay time starts to count after termination of delay time switching up/delay time switching down.
EN2B-0092GE51 R0512 18
EXCEL 50/100/500/600/800 ATTRIBUTES
19
Fig. 9. Delay time switching down

Descriptors

Informative descriptors A controller contains up to 128 physical datapoints and up to 256 pseudo
datapoints. The Excel 100C provides 36 physical datapoints. An individual user address can be assigned to each of these 384 datapoints. 255 plain-language descriptors can be created with a maximum of 32 characters each. These descriptors are then assigned to datapoints in the datapoint description via the attribute "Descriptor". Descriptors complete the information concealed behind the user address. They can contain, for instance, a reference to a section of a building. The following list is an example of the relationship between user addresses and descriptors:
User Address Descriptor
Room temp floor 1 Heating circuit, West wing Room temp floor 3 Heating circuit, West wing Room temp floor 10 Heating circuit, East Room temp corridor Heating circuit, East Flow temp floor 1 Heating circuit, West wing Lights floor 1 Building section V Lights corridor Building section V

Engineering Unit

The attribute "Engineering Unit" contains a list for selecting different engineering units for both analog datapoints (physical and pseudo), totalizer inputs (physical and pseudo), and digital datapoints. If, for instance, the external temperature is measured by an analog datapoint, the engineering unit of this datapoint must be set to "°C" or "°F". If the electrical load is detected by a totalizer input, the engineering unit must be set to "kWh" for kilowatt­hours.

Feedback Delay

The attribute "Feedback Delay" determines the time delay between, e.g. when a pump switched on (and detected) and when this status is made available to a program.

High/Low Alarm/Warning Limits

Specifying limit values In the case of analog inputs (e.g. inputs for sensing room temperature) and pseudo
analog points (for instance, internally computed datapoints for the heating flow setpoint), two minimum and two maximum monitored limit values may be entered.
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
The following four limit value attributes exist:
Low Warning Limit
Low Alarm Limit
High Warning Limit
High Alarm Limit
Example: Monitoring supply air temperature limits (see Fig. 10).
Exceeding the limi t values generates an alarm.
Fig. 10. Monitoring supply air temperature limits

Hours Run

Display of elapsed hours The attribute "Hours Run" returns the total number of hours during which any of the
stages is in the ON position. However, if more than one stage is in the ON position, the "Hours Run" count is not added up, but rather counted only once. Display of the elapsed hours run with activated hours run logging (see also "Hours Run Log" on page 20).
NOTE: If the attribute "Active State" of the point is 0, then the OFF position is
also counted.

Hours Run Log

Hours run log An hours run log can be carried out for digital datapoints (physical and pseudo) and
for flexible datapoints, e.g. logging the hours run by a heating circuit pump. This requires the decision: hours run log = Yes/No to be made in the attribute "Hours Run Log". The accumulated hours run are displayed in the attribute “Hours Run”. Hours run are logged with a sample rate of 1 minute.

Hours Since Serviced

Display hour s run since last maintenance The elapsed hours run since the last maintenance work are totaled in the attribute
"Last Maintained". If, for example has already been running for 120 hours, then the entry in the attribute “Last
EN2B-0092GE51 R0512 20
, the maintenance alarm is 500 hours, and a pump
EXCEL 50/100/500/600/800 ATTRIBUTES
21
maintained” will be 120 hours. By comparing the attributes "Maintenance Alarm" and "Last Maintained", the user can see that the next maintenance period will be after an additional 380 hours have elapsed. If the maintenance alarm is reached, and the maintenance work has been performed, the counter can be reset manually. The counter can also be reset manually before reaching the maintenance alarm if, for instance, the maintenance has been performed earlier. If the counter is not reset, on expiration of the maintenance alarm, e.g. after 500 hours, the elapsed hours run continues to be incremented, and an additional alarm will be generated when 1000 hours running has been reached.

Hysteresis

The following hysteresis attributes allow the user to control the triggering conditions based on a changing parameter under which actions are taken, such as alarm signaling, writing values to buffers, etc. A hysteresis can be used, e.g., to prevent an alarm from being generated unless the value being monitored changes by more than a given value. This eliminates unnecessary alarm generation and reduces bus communication traffic.

Alarm Hysteresis

Alarm hysteresis (V1.5.x) In the case of analog inputs and pseudo analog points, the attribute "Alarm
Hysteresis" is available. It provides variable hysteresis that can be implemented, e.g., in order to reduce the cost of communicating with a remote front-end. The hysteresis value is set from an MMI and can have a value anywhere in the range defined by [10 the attribute "Engineering Unit". The minimum value for the hysteresis is 10 Alarms are generated under the following conditions:
Max 1 Alarm (generated if MAX 1 is exceeded)
Max 2 Alarm (generated if MAX 2 is exceeded)
Max 2 Normal (generated if the value falls below MAX 2-Hysteresis)
Max 1 Normal (generated if the value falls below MAX 1-Hysteresis)
Min 1 Alarm (generated if the value falls below MIN 1)
Min 2 Alarm (generated if the value falls below MIN 2)
Min 2 Normal (generated if the value MIN 2+Hysteresis is exceeded)
Min 1 Normal (generated if the value MIN 1+Hysteresis is exceeded)
The CARE default value (i.e. 1% of actual value and no less than 0.2) for this attribute is 0. Access to "Alarm Hysteresis" is also possible via RIA/WIA.
NOTE: The number of decimal places can be changed only using CARE. NOTE: Attempting to enter a hysteresis value that is less than the allowed
Example: In this example, the number of decimal places in the attribute "Engineering Unit"
has been chosen to have a value of 2. Fig. 11 as a function of time that increases and decreases over the range from Max 1 to Min 1.
-a
to (Max1 - Min1)] where “a” is the number of decimal places set in
minimum will result in the attribute being assigned the minimum value as defined above.
shows an example datapoint value
-a
.
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
Fig. 11. Example of alarm hysteresis
The “normal” and “alarm” states as defined by the attribute "Alarm Hysteresis" are the determined using the appropriate values in the formula given above:
Range = [10
-2
to (Max1 -Min1)] = [0.01 to 2]
Table 7 lists the resulting alarm conditions for the chosen hysteresis value of 0.05:
Table 7. Alarm conditions for alarm hysteresis
limit normal to alarm condition alarm to normal condition
Max 1 4.00 4.00 - 0.05 = 3.95 Max 2 5.00 5.00 - 0.05 = 4.95 Min 1 2.00 2.00 + 0.05 = 2.05 Min 2 0.5 0.5 + 0.05 = 0.55

Trend Hysteresis

Trend hysteresis (V1.5.x) The attribute "Trend Hysteresis" is available for the trend functions “Local Trend
Data” and “Trend Setup Data”. The attribute "Trend Hysteresis" prevents new values from being written to the trend buffer unless the datapoint value changes (positively or negatively) at more than the specified trend hysteresis. The minimum hysteresis value is 10
-a
(a = number of decimal places set in the attribute "Engineering Unit"). The CARE default value (i.e. 1% of actual value and no less than 0.2) for this attribute is 0. Access to "Trend Hysteresis" is also possible via RIA/WIA.
This value can be edited from an operator interface (XI581 (not with XCL5010,
Excel 100C), XI582, XL-Online, or Excel 50 MMI) via the B port (XC5010C/XC6010) or the serial port, the system bus (XBS 1.3.3 and higher and XFI 1.6.1 and higher) and CARE RIA/WIA statements. The password level for this attribute is determined by the attribute "Access" (default initialization value in CARE is 0).
Fig. 12. Example of the attribute "Trend Hysteresis"
EN2B-0092GE51 R0512 22
EXCEL 50/100/500/600/800 ATTRIBUTES
23
MIN LIMIT
MAX LIMIT

Broadcast Hysteresis

Broadcast hysteresis (V1.5.x) The attribute "Broadcast Hysteresis" is available for the datapoint type "Global
Analog". The attribute "Broadcast Hysteresis" prevents new values from being broadcast to other controllers unless the datapoint value changes (positively or negatively) at least by the amount specified in the attribute "Broadcast Hysteresis". The minimum hysteresis value is 10 attribute "Engineering Unit"), but not smaller than 0.2 (see also the example section " value and no less than 0.2) for this attribute is 0. Access to the attribute "Alarm Hysteresis" is also possible via RIA/WIA. This value can be edited from an operator interface (XI581 [not with XCL5010, Excel 100C], XI582, XL-Online, and Excel 50 MMI) via the B port (XC5010C / XC6010) or the serial port (Excel 100C, Excel 500), the system bus (XBS 1.3.3 and higher and XFI 1.6.1 and higher), and CARE RIA/WIA statements. The password level for this attribute is determined by the "Access" attribute (default initialization value in CARE is 0). If several global points (remote points) are assigned to the same physical point, the lowest global point "Broadcast Hysteresis" value of all assigned global points is used.
Value Hysteresis" on page 35). The CARE default value (i.e. 1% of actual
-a
(a = number of decimal places set in the
in

Intrinsic Hysteresis for Analog Input Signals

A minimum default hysteresis of 37 mV (24 - 1 bit) for 0 to 10 V input signals is implemented. Due to the nonlinearity of NTC sensors, the hysteresis varies over the temperature range, whereas it is approximately constant for PT 100/1000/3000 and Balco 500 sensors. Approximations of hysteresis depending on the sensor and temperature range are summarized below.
NOTE The Intrinsic Hysteresis for analog input signals is not a user-
NTC 20k Hysteresis varies nonlinearly over the entire temperature range and depending on
whether the upper boundary (MAX LIMIT) or the lower boundary (MIN LIMIT) is exceeded. The approximations shown in (intermediate values can be interpolated):
temperature range
programmable attribute, but rather an intrinsic hysteresis of the Excel 50/100/500/600/800.
Table 8 can be used in practice
Table 8. Intrinsic hysteresis values for various temperature ranges
average hysteresis
average hysteresis
-40 °C (-40 °F) 2.2 K (4.0 °F) 2.5 K (4.5 °F)
-30 °C (-22 °F) 1.3 K (2.3 °F) 1.3 K (2.3 °F) 0 °C (32 °F) 0.4 K (0.7 °F) 0.4 K (0.7 °F) 40 °C(104 °F) 0.5 K (0.9 °F) 0.4 K (0.7 °F) 80 °C (40 °F) 1.5 K (2.7 °F) 1.5 K (2.7 °F) 100 °C (212 °F) 3.0 K (5.4 °F) 2.7 K (4.9 °F) 130 °C (266 °F) 8.5 K (15.3 °F) 7.2 K (13.0 °F)
PT 100 (not with Excel 100C) Hysteresis increases approx. linearly with temperature.
PT 1000/1 Hysteresis increases approx. linearly with temperature.
EN2B-0092GE51 R0512
Average hysteresis: 0.75 K (1.35 °F) Hyst. At -45 °C (-49 °F): 0.7 K (1.3 °F) Hyst. At 145 °C (293 °F): 0.8 K (1.4 °F)
Average hysteresis: 0.8 K (1.4 °F) Hyst. At -45 °C (-49 °F): 0.7 K (1.3 °F) Hyst. At 145 °C (293 °F): 0.9 K (1.6 °F)
ATTRIBUTES EXCEL 50/100/500/600/800
Input/Output Status
Active State (prior to V.2.04.x)
Status Text
PT 1000/2 Hysteresis increases approx. linearly with temperature.
PT 3000 (not with Excel 100C) Hysteresis increases approx. linearly with temperature.
Balco 500 (not with Excel 100C) Hysteresis decreases approx. linearly with temperature.
Average hysteresis: 1.6 K (2.9 °F) Hyst. At 0 °C (32 °F): 1.3 K (2.3 °F) Hyst. At 400 °C (752 °F): 2.0 K (3.6 °F)
Average hysteresis: 0.8 K (1.4 °F) Hyst. At -45 °C (-49 °F): 0.7 K (1.3 °F) Hyst. At 145 °C (293 °F): 1.0 K (1.8 °F)
Average hysteresis: 0.9 K (1.6 °F) Hyst. At -50 °C (-49 °F): 1.0 K (1.8 °F) Hyst. At 150 °C (293 °F): 0.7 K (1.3 °F)

Input/Output Status Text (prior to V2.04.xx)

2 status texts per digital data output Two status texts can be assigned to each digital datapoint status. Status texts give
an overview of the condition of the sensor or switching device c onnected to the datapoint.
The associated status text appears in the attribute "Value" depending on the actual point status.
For instance, the status texts could be as follows for a point connected to a digital output:
Digital point status 0: Status Text: "Passive” Digital point status 1: Status Text: "Active”
Table 9. Relationships between I/O Status, Active State, and Status Text
0 0 active 0 1 passive 1 0 passive 1 1 active
Status Text with flexible datapoints The attribute "Status Text" allows you to describe the value sent to the controller by
the digital output Pulse 1 and by flexible datapoints. In the case of flexible datapoints of the type "feedback", the status text refers to the value of the feedback flexible datapoint and not to the required value.

Input/Output Status Text (V2.04.xx or higher)

With firmware 2.04.xx or higher, the relationship between physical output status and logical output status as defined by the attribute "Normally Open/Normally Closed" determines the display of the equivalent status text. See section "Normally Open/Normally Closed (V2.04.xx or higher)" on page 28 for details.

Interval Count

Interval count The attribute "Interval Count" shows the totalizer value (pulse x scaling factor)
Displaying the interval count The attribute "Interval Count" can be viewed on the XI581, XI582, and Excel 50 MMI
accumulated since the last reset.
operating units as well as via the XL-Online Operating Software and building Supervisor front-ends like XBS, EBI and XFI. Based on mathematical rounding, it is
EN2B-0092GE51 R0512 24
EXCEL 50/100/500/600/800 ATTRIBUTES
25
possible that not every value is displayed when high frequency values with high scaling factors are received.
Resetting the interval count Resetting takes place either manually via an operating unit, by reaching the
Totalizer overflow When the “Interval Limit” or the “totalized” constant is reached, a “Totalizer
“Interval Limit” value, or by reaching the “totalized” constant, which is 2 to the power of 31.
Overflow” system alarm is created.

Interval Limit

The attribute “Interval Limit” is that value of the "Interval Count" attribute which, when reached, will generate a “Totalizer Overflow” alarm. The highest possible value for the attribute "Interval Count" is 99,999,999.
Electrical energy example A message should be generated after the “consumption” of 5 MWh of electrical
power. The input in the attribute “Interval Limit” must therefore be 5 MWh. Once the interval count reaches its reporting level of 5 MWh, then a report is generated, the interval count is reset to “Zero”, and a new totalizing period is started.

I/O Characteristic

The attribute "I/O Characteristic" enables the user to display special input and out­put characteristics (see Fig. 13) for analog inputs/outputs. Special characteristics permit, for instance, the adaptation of Excel 50/100/500/600/800 to many different sensor types. Ten individual input/output characteristics are available per Excel 50/100/500/600/800 controller. Each special characteristic is assigned a name that can be recalled from the attribute "I/O Characteristic". Thus, the desired characteristic can be assigned to the selected datapoint.
Fig. 13. Example of a special output characteristic
Creation of characteristics is carried out at programming level. Up to a maximum of four reference points can be specified per characteristic. Up to ten different characteristics can be defined for each controller. For XFL and XFC I/O modules, user-defined characteristics are supported from CARE 5.0 and controller firmware 2.06.05 onwards.
CAUTION
Regarding I/O characteristic, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS
2.06.05 and higher engineered using CARE 7 and higher. See also section “Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500
7.01.02” in Excel CARE – User Guide (EN2B-0182GE51).
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
pull-up
load-free voltage
(1
controller firmware 2.03;
When using the XF821A/XFL821A for current inputs, be sure to assign "@" as the first digit of the input characteristic name.
A
D
18.2 k (pull-up)
Ω
100 k
Ω
100 k
Ω
5 V
A
D
24.9 k (pull-up)
Ω
150 k
Ω
49.9 k
Ω
10 V
A
D
24.9 k (pull-up)
Ω
150 k
Ω
49.9 k
Ω
10 V
Case 1
Case 2 Case 3

Pull-Up Resistor Handling

Table 10. Pull-up resistor handling
device
voltage hardware
de-
activated
by @ (8)
configured
by DIP switch
configured
by plug-in
activated
for DI on AI
XF830A XFU830A XF821A
optional
switch-off
YES
XFL821A YES XF521,
XF521A
10 V
fixed NO NO case 2 8.89 V
NO
YES
XF526 XFL521,
XFL521A/B Smart I/O
XFC
5 V YES XL20 XL50 XL100,
10 V
XL100A XL100B XL100C YES(1 NO YES(5
optional
switch-off
fixed NO
optional
switch-off
fixed
optional
switch-off
(3
YES
(4
YES(7 case 3 5 V
NO
config.(6 case 1
YES
YES case 2
YES(2 YES(5 case 1 0 V
NO
NO
YES case 2 8.89 V
YES configurable
input
circuit diagram (Fig. 14)
with NTC
or low-
impedance
input
for voltage
input or
high-
impedance
input
case 1
8.89 V
8.89 V
8.89 V
case 1 0 V
0 V
0 V
(2
controller firmware 2.02;
(3
controller firmware 2.03 (local/shared mode), CARE 5.00.01 (open mode);
(4
CARE 5.00.01;
(5
controller firmware < 2.04;
(6
controller firmware < 2.04 (local/shared mode), CARE 5.01.xx (open mode);
(7
CARE ≥ 5.01.xx;
(8
Assigning "@" as first digit of input characteristic name (e.g.: "@0-10V") in the CARE text editor disables the pull-up resistor.
Fig. 14. Input circuit diagram

Last Change

In the attribute "Last Change", the last change of state of a digital input/output is stored with the time and date.
EN2B-0092GE51 R0512 26
EXCEL 50/100/500/600/800 ATTRIBUTES
27
In this way it is possible to determine the last switch-on point of a fan, pump, etc. connected via a digital output.
In the case of analog inputs and pseudo analog points, the last time an alarm limit occurred is stored.

LED Mode (XF823x, XFL823x, and XFx830x modules)

The XF823x Panel Bus Binary Input Module, the XFL823x Lonworks Bus Binary Input Module, and the XF830x / XFU830x modules support the “LED Mode” attribute, which can be set in the CARE datapoint editor. The following attribute options are provided:
“Alarm” LEDs will be red/green (red = alarm state, not XF830x / XFU830x modules)
“Status” LEDs will be yellow/off (yellow = active state)
NOTE: XF830x / XFU830x modules do not support the Alarm option. Hence, do
NOTE: When the XFL823x L
not assign this attribute to datapoints allocated to one of these modules.
non-Excel 800 controllers, the LED mode can only be set in the
ONWORKS NV settings in CARE, and not in the CARE datapoint editor.
L
ONWORKS Bus Binary Input Module is used with

Maintenance Alarm

Specifying a maintenance alarm In the case of those datapoints for which an hours run log has been activated, a
time entry can occur within the attribute "Maintenance Alarm" to indicate after how many operational hours an alarm message should be generated. Entering “Zero” results in no alarm message.
Example: Maintenance should be carried out every 500 hours on the heating circuit pump
controlled via a digital output. To achieve this, a time interval duration of 500 hours is entered in the attribute "Maintenance Alarm" for this datapoint. At the same time, activation of the hours run log must also take place in the attribute “Hours Run log” for this datapoint. An alarm message now occurs after 500 hours, to bring to the operator’s attention the necessary pump maintenance.

Manual Value

When the attribute "Operating Mode" is set to "Manual", the operator can enter a manual value or state, and the application program will work with this manual value or state until the operating mode is set back to “Automatic”.
Fig. 15. Example of a sensor input
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
output signal
NO/NC attribute
logical status
text displayed
In Fig. 15, the attribute "Operating Mode" is set to "Manual", i.e. the value entered manually is processed in the application program.
NOTE:
“Value” and “Manual Value” are online attributes, relevant only during controller operation via MMI or XL-Online. Furthermore, “Manual Value” is an internal online attribute only, not visible to the operator! The operator will see only the online attribute “value”, which can be edited only if the attribute "Operating Mode" is set to "Manual". See also section "Operating Mode" on page 29.

Network Variable (V2. 04.xx or higher)

Datapoints which are mapped to network variables on the LONWORKS network have an attribute named "Network Variable" containing the network variable index (0-
4095) and the network variable name which allows this information to be displayed on an MMI.

Normally Open/Normally Closed (V2.04.xx or higher)

The attribute "Normally Open/Normally Closed" defines the relationship between the input/output signal of a digital datapoint and its logical status. This attribute is also applicable when the digital point is the basic point of a flexible datapoint.
NOTE: The attribute "Active State" is fixed at 1 and is no longer relevant for
Table 11 and Table 12 show the relationship between the I/O signals, the attributes, and the logical status for digital inputs and digital outputs, respectively.
Table 11. The attribute " Normally Open/Normally Closed " – Digital Inputs
Table 12. The attribute " Normally Open/Normally Closed " – Digital Outputs
applications designed for this controller firmware version. Applications designed for an older controller version will still work with this firmware though, and in that case the attribute "Active State" is still active.
input signal NO/NC attribute logical status text displayed
Low (<2.5 V) N.O. 0 passive
High (>5 V) N.O. 1 active
Low (<2.5 V) N.C. 1 active
High (>5 V) N.C. 0 passive
Low (<2.5 V) N.O. 0 passive
High (>5 V) N.O. 1 active
Low (<2.5 V) N.C. 1 active
High (>5 V) N.C. 0 passive
In the open LON mode, the "Normally Open/Normally Closed" functionality is supported from CARE 5.0 and controller firmware 2.06.05 onwards.
CAUTION
Regarding “Normally Open/Normally Closed,” the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS 2.06.05 and higher engineered using CARE 7 and higher. See also section “Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500 7.01.02” in Excel CARE – User Guide (EN2B-
EN2B-0092GE51 R0512 28
0182GE51).
EXCEL 50/100/500/600/800 ATTRIBUTES
29

Motor Run Time

Time to open / time to close For actuators controlled via a three-position output, two values (time to open / time
to close) can be entered in the attribute “Motor Run Time”. This attribute defines the time required by the actuator to change from the “Open” to the “Closed” state, and vice versa. If no value is entered for the “Time to Closed” motor run time, then the “Time to Open” motor run time is assumed automatically. In the case of the motor run-on time, when reversing directions, 1% of the “Time to Open” motor run time is added to the calculated time. The three-position output relay energizes when the calculated run time reaches 500 ms. The stated run time always amounts to 500 ms or a multiple thereof. A calculated run time of, for instance, 1215 ms results in an actual run time of 1000 ms.
CAUTION
Regarding motor run time, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS
2.06.05 and higher engineered using CARE 7 and higher. See also section “Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500
7.01.02” in Excel CARE – User Guide (EN2B-0182GE51).

Off Phase

Fig. 16. Off phase
The attribute "Off Phase" is used in conjunction with flexible datapoints of the type "feedback". It defines the duration of the OFF phase on switching down. It is of relevance only if the attribute “Switching Down” is set to 0, i.e. if OFF phases are selected on switching down.
Range: 0 to 255s
Default value: 10s
Resolution: 1s
The OFF phase has to be defined for devices with large inertia, such as fans.

Operating Mode

The attribute "Operating Mode" enables the user to switch between manual and automatic operation.
Automatic Under automatic operation, the controller processes the values at the inputs, for
EN2B-0092GE51 R0512
instance from temperature sensors. For outputs, under automatic operation, the status shown by the user/time switch program is adopted, e.g., "Heating circuit pump off".
ATTRIBUTES EXCEL 50/100/500/600/800
mode
mode
operating mode
automatic value*
resulting value
output signal
Manual During manual operation, the controller uses the manual values, for example, "flow
temperature setpoint = 60°C". Outputs adopt the preselected condition, for example
, "Heating circuit pump on".
Automatic/Manual Alarm For automatic operation, the attribute "Operating Mode" contains the inputs "Auto"
and "Manual". Each switch from automatic to manual operation and back again generates a critical alarm.
Remote (V2.0.x) (not Excel 100C) If manual override controls are present on either the Analog Output (XFL522) or
Digital Output (XFL524) modules connected via a L
ONWORKS network, then the
status of these controls (automatic/manual override) is stored in the attribute "Operating Mode". If the manual override controls are set to automatic, the attribute "Operating Mode" can be set to either automatic or manual. If the manual override controls are set to manual override, then the attribute "Operating Mode" can be in the remote mode, only. Fig. 17 and Fig. 18 demonstrate the relationship between the attribute "Operating Mode", and both the attributes "Value" and "Manual Value" for input and output functions.
Fig. 17. Control flow for input functions
Fig. 18. Control flow for output functions
NOTE: The attribute "Remote" is available only if Manual Override modules are
installed on the Distributed I/O output modules. This attribute is therefore not applicable to Excel 50/100/600.
Analog Points Table 13 indicates the analog point signals depending on the attribute "Operating
Mode":
Table 13. Analog point signals
auto operating
manual operating
remote**
20% don’t care don't care
manual value don't care 10% don't care remote value don't care don't care 50%
20% 10% 50%
2 V 1 V 5 V
* Automatic value is either the physical point value (inputs) or the value from the program (outputs)
EN2B-0092GE51 R0512 30
EXCEL 50/100/500/600/800 ATTRIBUTES
31
manual Value
remote value
*Automatic value is either the physical point value (inputs) of the value from the **Output only (V2.0.x)
** Output only (V2.0.x)
Digital points Table 14 indicates the digital point signals depending on the attribute "Operating
Mode":
automatic value* ON don’t care don’t care
resulting Value ON OFF ON output signal HIGH LOW HIGH
program (outputs)
Table 14. Digital point signals
auto operating
mode
don’t care OFF don’t care
n/a n/a ON
manual operating
mode
remote**
operating mode
Alarming The change from the 'automatic' to the 'manual' mode will create a point alarm if
Firmware prior to V.2.04.x With controller firmware prior to V.2.04.xx, the alarm will report the status of the
Firmware V.2.04.x Beginning with controller firmware V.2.04.x, the alarm will report the status of the
other alarm conditions are set accordingly.
operating mode as it was before the change.
operating mode as it is after the change.

Output Type

Three-position outputs are digital outputs. From an operational viewpoint, they are assigned the same datapoint description as analog outputs, i.e. a three-position output possesses attributes similar to those of an analog output.
Analog or 3-position output The attribute "Output Type" determines whether the analog output datapoint
description should be assigned to an analog output or to a three-position output. The following inputs are possible:
Continuous The analog output datapoint description is assigned to an analog output.
Three-position The analog output datapoint description is assigned to a three-position output.
Remote three-position Output to the Excel 100 MCE 3 and MCD 3 output modules.

Subtype

The attribute "Subtype" is used in conjunction with digital outputs and flexible datapoints. It determines whether the digital output is of the non-pulsed type.
The attribute "Point in Alarm" refers to alarm messages from the alarm attributes "Min. Limit", "Max. Limit", and "Alarm Status". The attribute "Point in Alarm" indicates whether or not those datapoints using these attributes are currently in alarm. The following entries are possible:
Yes = the chosen datapoint is in alarm
No = the chosen datapoint is not in alarm
EN2B-0092GE51 R0512

Point Alarms

ATTRIBUTES EXCEL 50/100/500/600/800
As soon as an alarm occurs (e.g. through exceeding a limit value), the attribute "Point in Alarm" is set to "Yes". The attribute is immediately set back to "No" when the limit value returns to normal.

Pulse Duration

The attribute "Pulse Duration" is used for the pulsed subtypes of the digital output (i.e. "Pulse 1") and flexible datapoints of the type "Pulse 2". It defines the duration between coming and going edge of a pulsed signal. The values for this attribute can vary from 1 to 255 seconds; the resolution is 1 second. The default value is 1 second.
NOTE: After a power failure or disconnection of the controller, the “Pulse 1” and
“Pulse 2” outputs will resume their last output pulse behavior before the outage.

Safety Position (XFx822x, XFx824x, and XFx830x modules)

The analog output modules XF822x/XFL822x/XFLR822x, the relay output modules XFL824x/XFL824x/XFLR824x and the mixed I/O modules XF830x/XFU830x support the “Safety Position” attribute, which can be set in the CARE datapoint editor. The modules will put the outputs into the safety position as soon as communication with the Excel 800 CPU is lost. The XF822x/XF824x modules detect this lost communication once no more polls are received from the Excel 800 CPU for more than one second. The XFL822x/XFL824x and XF830x/XFU830x modules detect this lost communication once no more polls are received from the Excel 800 CPU within the heartbeat time of the module.
XF822x/XFL822x –”The following attribute options are provided:
“0%” equals 0 Vdc or 2 Vdc (0…11 Vdc or 2…11 Vdc characteristic)
“50%” equals 5 Vdc or 6 Vdc (0…11 Vdc or 2…11 Vdc characteristic)
“100%” equals 10 Vdc
“Remain in last position” (this is the default setting).
XF824x/XFL824x and XF830x/XFU830x –”The following attribute options are provided:
“Off (logical)”
“On (logical)”
“Remain in last position” (this is the default setting).
NOTE: When the XFL822x/XFLR822x and XFL824x/XFLR824x modules are
used with non-Excel 800 controllers, the Safety Position can only be set
ONWORKS NV settings in CARE, and not in the CARE datapoint
in the L editor.

Scaling Factor

Input pulses from utility meters (gas, water, heat, etc.) can be connected to the totalizer inputs using the attribute "Scaling Factor". The pulses supplied by the meters are multiplied by the scaling factor and are then ready to be read as pure consumption values. The "Scaling Factor" thus always indicates the value of each pulse received. The adjustable range is 0.0 through 100,000,000.0,
Example: A heat meter supplies 10 pulses per kW h "consumed". Accordingly, the scaling
EN2B-0092GE51 R0512 32
The number of decimal places depends on the selected engineering unit.
factor (= value of a pulse) is 0.1 kWh/pulse.
EXCEL 50/100/500/600/800 ATTRIBUTES
33
Pseudo totalizers: In the event that you have selected the datapoint type "pseudo totalizer inputs," you
must set the attribute "Scaling Factor" to "1"; otherwise, the number of pseudo totalizer inputs will not be counted.

Sensor Offset

The attribute “Sensor Offset” is designed for the compensation of the resistance of the sensor wiring for low-resistance sensors, like Pt 100, Pt 1000, Balco 500. The voltage offset due to the wire resistance is approximately constant, the attribute “Sensor Offset” functionality has therefore been designed to compensate constant voltage offsets at the analog input.
Function principle The principle is that the attribute “Sensor Offset” can be defined at a selected tem-
perature, e.g., 1 °C at 20 °C. The Excel controller processes this temperature offset into a voltage offset, e.g., -0.11 V, and applies this very voltage offset for correcting (offsetting) all voltages measured.
In order to display a temperature, the controller processes the resulting voltage back into a temperature. This principle and the processing (including mathematical rounding) from “°C” into “volt” and back into “°C” leads to slightly inconstant offsets across the temperature range.
Example for a selected “Sensor Offset” of 1°C: Measured Temperature Corrected Temperature
20°C 19°C
-10°C -8,4°C For XFL and XFC I/O modules, "Sensor Offset" functionality is supported from
CARE 5.0 and controller firmware 2.06.05 onwards.
CAUTION
Regarding sensor offset, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS
2.06.05 and higher engineered using CARE 7 and higher. For example, for XL50 internal AI and XL500 internal AI (XF521/527
modules), the sensor offset is subtracted from the datapoint value. For XL50 and XL800 controllers using XF821 modules, the sensor offset is
added to the datapoint value. See also section “Sensor Offset Handling” in Excel CARE – User Guide
(EN2B-0182GE51).

Suppress Point

The attribute "Suppress Point" means that datapoints are no longer processed and checked. As a result, no alarms are generated for suppressed points. Where you have flexible datapoints, this attribute acts upon all basic types of physical datapoints.
IMPORTANT
Never suppress a datapoint used via your application program. This causes system failure.

Switching Down

The attribute "Switching Down" is used in conjunction with flexible datapoints of the type "feedback". On switching down from one stage to another, it determines
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
020401
Input/output number Controller number (set via MMI)
Module number (set via address swi tch on each I/O module)
whether the off-phase is selected between the single stages, e.g., for ventilators, or whether the next lower stage is selected directly, e.g., for electrical air heaters.
Switching down Switching down behavior
0 3, OFF, 2, OFF, 1, OFF 1 3, 2 , 1

Switch-On Counter

Record switching frequency The attribute "Switch-On Counter" gives information about the switching frequency
of digital datapoints. The change of state from 0 to 1 is counted in each case.

Technical Address

Technical address An Excel 500/600 controller consists of 16 Distributed input/output modules with a
Mapped points (V2.04.xx or higher) Datapoints that are mapped only to L
total of 128 physical inputs and outputs. The Excel 100C provides 36 physic al I/Os (see Excel 100C Installation Instructions, form no. EN1R-0144GE51, for technical addresses). Where a system requires additional inputs and outputs, several con­trollers can be connected together. Controllers then communicate with one another via the system bus. Each physical datapoint within the system must have an address that identifies the point uniquely. The technical address contains information about the controller number, the I/O module number, and also the input/output number in this module (see Fig. 19).
Fig. 19. Example of a technical address
Thus, the address 02.04.01 uniquely identifies the first input/output in the fourth module of the second controller in your system.
NOTE: The Excel 50 controller does not have I/O modules, but its technical
addresses follow the same pattern, with module numbers referring to internal I/O boards. For details, see the Excel 50 Installation Instructions.
ONWORKS network variables are not assigned
to any I/O board. In this case, the board number (module number) of the technical address is zero.
EN2B-0092GE51 R0512 34

Trend Logging

Up to 20 datapoints (all datapoint types, except for global datapoints) in each controller can be trend logged simultaneously. This means changes in the input or output value can be stored with the user address, value (or status), date, and time for 20 different datapoints. This is achieved by selecting the attribute "Trend Logging" to YES in the datapoint description. For analog values (see Fig. 20), the value, e.g., 20 °C / 68 °F, is displayed in addition to the user address, date, and time. For digital values (see Fig. 21), the status text, e.g., "On", is displayed in addition to the user address, date, and time.
EXCEL 50/100/500/600/800 ATTRIBUTES
35
Fig. 20. Trend log display (analog input)
Fig. 21. Trend log display (digital input)
200 values can be written to the local trend log memory. If the memory is full, the earliest data is overwritten with new data. The 200 most up-to-date values are always available in the memory.
If several datapoints are selected for the trend log, those datapoints whose value or status changes more frequently will create a larger number of values to be logged. Each change in status is logged for digital points. For analog points, there are two different types of trending: value hysteresis and time-based. The datapoint attributes for each of these types of trending are described below.

Value Hysteresis

When value hysteresis trending is selected (i.e. when the attribute "Trend Cycle" is set to 0), a new value is written to the memory when the point changes more than the given hysteresis compared to the previous value. The default hysteresis value is 1% of the actual value, but not less than 0.2 (see also section "Trend Hysteresis" on page 22).
Example 1: The current measured value is 20°C
1 % of 20°C = 0.2°C A new trend log value is stored at either 20.2°C or 19.8°C
Example 2: The current measured value is 9°C
A new trend log value is stored at either 9.2°C or 8.8°C The trend can be displayed as text and as a graphic. The graphic display offers the following features:
Simultaneous display of an analog and a digital datapoint
Auto-scaling of the time and the value axis
Scrolling the time axis
Manual re-scaling of the time axis (ZOOM/UNZOOM function) with possible
resolutions:
- minute display
- hourly display
- daily display
- weekly display
Quick change between graphic and text display

Trend Cycle (V2.03.x)

With V2.03.xx firmware, it is possible to perform time-based trending for physical and pseudo analog points for both local and remote trending. A trend value is stored in the trend buffer at the end of a fixed interval given by the datapoint attribute "Trend Cycle", as shown in Fig. 22:
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800

VALUE

flexible datapoint
number of technical addresses
TREND VALUE
TREND VALUE
TREND VALUE
TREND CYCLE
TREND CYCLE
Fig. 22. The attribute "Trend Cycle"
The value of the attribute "Trend Cycle" is given in minutes, and the valid range is 0 to 1440 min (=24 hours). A trend cycle value of 0 will disable time-based trending (this is the default) and value-hysteresis trending is used if the trend log attribute is set. The value for the attribute "Trend Cycle" can be changed via the MMI, C-Bus, or modem connection to EBI/SymmetrE, and also via CARE RIA/WIA statements.
NOTE If the attribute "Trend Cycle" is set to anything other than 0, trending will
be time-based and the attribute "Trend Hysteresis" will be ignored.

User Address

The attribute "User Address" is a sequence of up to 18 letters and numbers assigned to each datapoint (physical and pseudo).
Example The temperature of a room is recorded at a sensor input; the associated user
address could be as follows: Room Temp.1.10 (Room temperature, 1st floor, room 10) The datapoint can be accessed directly by selecting this user address on the XI581
(not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces or the XL50-MMI.
In the case of basic types of physical data, a user address always corresponds exactly to one technical address (see Table 15).
The user address of flexible datapoints may refer to up to six technical addresses .
Table 15. Number of technical addresses for flexible datapoints
EN2B-0092GE51 R0512 36
Pulse 2 2 Multi-stage up to 6 Feedback up to 6 (in pairs of 2)
Value
When the controller is working in automatic (the attribute "Operating Mode" is set to "Auto"), the value currently being processed by the program, or the current status, can be found in the attribute "Value". The attribute "Value" for an analog input could contain, for example, the current room temperature of 21 °C / 70 °F.
A pump switched by a digital output could contain the current status of the pump, for example ON, in its attribute "Value".
EXCEL 50/100/500/600/800 ATTRIBUTES
37
operator level XBS
access for write protection values

Write Protection

The attribute "Write Protection" (XBS, only) prevents data from being overwritten. The default setting of the attribute is 0 (="No"). If the datapoint should be protected, then "No" must be overwritten with a value between 0 and 100.
0 = No write protection 100 = Highest priority required
To change this attribute, the operator must log in at an operator level that corresponds to the current write protection attribute (see Table 16).
1 no access 2 no access 3 0 to 60 4 0 to 80 5 0 to 100
The operator's authority level is compared to the write protection status of the datapoint to establish whether or not any modification can be made. As soon as the operator receives permission, he can alter the attribute of secured datapoints. The operator can also set the write protection to a higher value or cancel write protection completely.
Example: A datapoint with a write protection value of 61 can be altered only at operator level
4 or 5. The write protection can be reduced to 0 from level 4 as well as level 5. The datapoints can be altered through level 3. A detailed high priority can then be given through the write protection.
NOTE: When online, the XI581 (not with XCL5010, Excel 100C), XI582, and XL-
Online operator interfaces and the XL50-MMI do not recognize the attribute "Write Protection". You can still change any datapoint via the user interface, even if the datapoint is write-protected.
Table 16. Access values for operator levels
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
analog input
analog output
digital input
digital output
digital output (pulse 1)
1

List of Datapoint Attributes

Different attributes are assigned to each datapoint type. Table 17, Table 18, and Table 19 list the attributes assigned to the various datapoint types:
User Address User Address User Address User Address User Address Descriptor Descriptor Descriptor Descriptor Descriptor Technical Address Technical Address Technical Address Technical Address Technical Address Suppress Point Suppress Point Suppress Point Suppress Point Suppress Point Access Level Access Level Access Level Access Level Access Level Write Protection Write Protection Write Protection Write Protection Write Protection Operating Mode Operating Mode Operating Mode Operating Mode Operating Mode Value Value Value Value Value Manual Value Manual Value Manual Value Manual Value Manual Value Engineering Unit Engineering Unit Alarm Delay Alarm Type Alarm Type I/O Characteristic I/O Characteristic Alarm Type Alarm Reporting Alarm Reporting Sensor Offset Alarm Reporting Alarm Status Trend Logging Trend Logging Low Warning Limit Trend Logging Point in Alarm Hours Run Log Hours Run Log Low Alarm Limit Subtype Alarm Reporting Hours Run Hours Run High Warning Limit Time to Open Trend Logging Service Interval Pulse Duration High Alarm Limit Time to Close Hours Run Log Hours Since Serviced Service Interval Alarm Delay Trend Hysteresis Hours Run Active State Hours Since Serviced Alarm Type Trend Cycle Service Interval Active State Text Active State Point in Alarm Suppress Alarm Hours Since Serviced Passive State Text Active State Text Alarm Reporting NV Name and Index Active State Cycle Count Passive State Text Trend Logging Safety Position1 Active State Text Last Changed Cycle Count Alarm Status
changed Alarm Hysteresis Last Changed Suppress Alarm Subtype Trend Hysteresis Cycle Count Suppress Alarm Trend Cycle Suppress Alarm NV Name and Index * Normally Open /
Suppress Alarm NV Name and Index * NV Name and Index * NV Name and Index * LED Mode1 Safety Position1 * Read-only attribute. Changing the NV name and index requires changing the datapoint to NV mapping in CARE.
Excel 800, only.
Passive State Text Subtype Last Changed
Table 17. Datapoint attributes
Normally Closed
Normally Open / Normally Closed
EN2B-0092GE51 R0512 38
EXCEL 50/100/500/600/800 ATTRIBUTES
39
input
Table 18. Datapoint attributes
totalizer input
pseudo totalizer
pseudo analog point pseudo digital point pseudo point multistage
User Address User Address User Address User Address User Address Descriptor Descriptor Descriptor Descriptor Descriptor Technical Address Suppress Point Access Level Access Level Point Enable Suppress Point Access Level Write Protection Write Protection Access Access Level Write Protection Operating Mode Operating Mode Write protection Write Protection Operating Mode Value Value Operating Mode Operating Mode Value Manual Value Manual Value Value Value Manual Value Engineering Unit Alarm Type Value Manual Manual Value Engineering Unit Low Warning Limit Alarm Delay Status Text Engineering Unit Alarm Type Low Alarm Limit Alarm Status Alarm Type Alarm Type Trend Logging High Warning Limit Point in Alarm Trend Logging Trend Logging Scaling Factor High Alarm Limit Alarm Reporting Hours Run log Scaling Factor Interval Limit Alarm Type Trend Logging Hours Run Interval Limit Interval Value Alarm Delay Hours Run Log Maintenance Alarm Interval Value Suppress Alarm Point in Alarm Hours Run Last Serviced Suppress Alarm Trend Logging Service Interval Last Change Alarm Status changed Active State Switch on Counter Alarm Hysteresis Hours Since Serviced Number of Stages Trend Hysteresis Active State Text Suppress Alarm Trend Cycle Passive State Text NV Name and Index * Suppress Alarm Cycle Count NV Name and Index * Last Changed Suppress Alarm NV Name and Index * * Read-only attribute. Changing the NV name and index requires changing the datapoint to NV mapping in CARE.
EN2B-0092GE51 R0512
ATTRIBUTES EXCEL 50/100/500/600/800
(analog)
(digital)
(type: Pulse 2)
(type: feedback)
multi-stage)
global datapoint
User Address User Address User Address User Address User Address Descriptor Descriptor Descriptor Descriptor Descriptor Technical Address Technical Address Technical Address 1/2 Technical Address
Access Level Access Level Suppress Point Status Suppress Point Write Protection Write Protection Access Level Switching down Access Level Operating Mode Operating Mode Write Protection Off phase Write Protection Value Value Operating Mode Delay switch up Operating Mode Manual Value Manual Value Status Delay switch down Value Engineering Unit Alarm Type Manual Status Feedback Delay Manual Value Low Warning Limit Alarm Delay Status Text Operating Mode Status Text Low Alarm Limit Alarm Status Ala rm Type Manual status Active State High Warning Limit Point in Alarm Trend Logging Status Text Alarm Type High Alarm Limit Alarm Reporting Hours Run Log Suppress Point Alarm Reporting Alarm Type Trend Logging Hours Run Access Level Trend Logging Alarm Delay Hours Run Log Pulse Duration Write Protection Hours Run Log Point in Alarm Hours Run Service Interval Trend Logging Hours Run Trend Logging Service Interval Hours Since Serviced Hours Run Log Service Interval Alarm Status changed Active State Last Changed Hours Run Hours Since Serviced Alarm Hysteresis Hours Since Serviced Cycle Count Service Interval Last Changed Trend Hysteresis Active State Text Suppress Alarm Subtype Cycle Count Trend Cycle Passive State Text Hours Since Serviced Suppress Alarm Suppress Alarm Cycle Count Alarm Type Broadcast Hysteresis Last Changed Point in Alarm Suppress Alarm Alarm Reporting Last Changed Cycle Count Suppress Alarm
global datapoint
Table 19. Datapoint attributes
flexible datapoint
flexible datapoint
1/2/3/4/5/6
flexible datapoint (type:
Technical Address 1/2/3/4/5/6
EN2B-0092GE51 R0512 40
EXCEL 50/100/500/600/800
41

TIME PROGRAMS

Time programs allow you to set values and control states for specific datapoints at specific times. You can adapt time programs to suit the structure of your system.
Network-wide time synchronization Time synchronization of all devices connected to the system bus is carried out by
the controller designated as the synchronization master. Synchronization is based on date, hours, minutes, and seconds to an accuracy of ± 120 seconds (see also "Network-Wide Controller Time Synchronization" on page 55).

Structure

Flexible time programs An Excel 50/100/500/600/800 time program can consist of several individual time
programs. You define these individual time programs according to their function and assign a name to each one. This means you can generate a time program for each section of your system or building.
Time programs are created on the basis of the following modules:
daily programs
weekly programs
annual programs
Further, these modules can be modified as needed using the following two functions:
the special day list
the “TODAY” function
Daily programs are combined to form a weekly program. The weekly program is then automatically copied repeatedly to form the annual program. If you need to execute a different daily program on certain days of the year, you can enter the customized daily program directly in the annual program. The special day list and the "TODAY" function are available as additional features. The special day list allows you to mark specific days as being legal holidays. You can also use the special day list for floating legal holidays, for example Good Friday and Easter Monday. The "TODAY" function allows you to overwrite time program assignments "ad hoc" for a defined time period without permanently changing the entire time program.

Individual Time Programs

Daily Program

Daily programs are the basic building blocks of any time program. Using daily programs, you enter the switching times with the desired setpoints and switching conditions for the datapoints. When preparing a daily program and assigning the name, there is initially no specific relationship to a particular day in the week. The modular structure of the time program makes it possible for the user to establish various different daily programs, keep them in a library, and to include them in the weekly program as desired. The user is free to extend the list of daily programs to meet his special requirements. The repeated use of the same daily program is also possible (for example, the same daily program can apply from Monday to Friday in the weekly program). Changes in a daily program are immediately effective in the weekly and annual programs as well as in the special day list. A daily program can also have the name "Sundays and holidays", for example. The names of the daily program provide a reference to the switching points. In the "Workday 22 hr" daily program, the setpoint is reduced from 22.0°C to 12.0°C at
22.00 hr.
EN2B-0092GE51 R1111
TIME PROGRAMS EXCEL 50/100/500/600/800
The daily programs of the heating loops are independent from each other. In spite of their having the same name, such as "Sunday and holidays", the daily programs for all heating circuits are distinguished through the user addresses defined. The same also applies to the service water loop daily programs. The switch points and values can therefore be changed as desired in any daily program without influencing another daily program. The exact procedure for creating a daily program is described in the Operating Instructions.
Switching points A daily program can be regarded as a module that contains information about
New daily program Daily programs can be generated at operator level 2 (read and limited changes) of
V1.05.x The daily program is automatically assigned the name "DPn" (English language) or
Application Daily programs are used in the following sections of time programs:
Deleting a daily program If a daily program is to be deleted, the system will check whether this program is
switching times related to the duration of one day. It contains all user addresses addressed in this time interval.
The number of switching points per user address is not restricted. These switching points are defined by means of a switching time, referenced user address, and a setpoint value or control state. The switching times are set to the minute. Several switching points can be allocated to one switching instant. Switching points can be re-entered, changed, or deleted to modify the daily program. The permissible range (minimum or maximum value) for a user address or its control state is defined in the datapoint description. No values may be entered outside this range.
the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces and the XL50-MMI. It is possible to assign a name to a daily program generated on the XL-Online.
"TPn" (German language) (n = sequence power of the daily program) if no name is assigned by the user or, if the program is generated on the XI581 (not with XCL5010, Excel 100C), XI582, or the Excel 50 MMI. Once selected, program names can be changed via the XL-Online.
To generate weekly programs
For direct entries in annual programs
For holidays in the special day list
still required in the time program. This daily program cannot be deleted if it is still contained in the time program.

Weekly Program

A separate weekly program is generated for each time program. The weekly program defines which daily program is to be used for which weekday. A daily program is assigned to each day of the week (Monday to Sunday). It is also possible to assign the same daily program to several weekdays. The weekly program, if defined, is automatically copied for each week in the annual program. If a change is made to a weekday in a weekly program, this change will affect the weekday in every week of the year. If a daily program is entered directly in the annual program, this daily program will have priority over the daily program from the weekly program. The definition of a weekly program forms the basis of the annual program.

Annual Program

The annual program is structured like a calendar and consists of successive weekly programs. It provides an overview of which daily programs are valid on which calendar days. If the daily program in a weekly program does not apply on a particular calendar date, another daily program can be entered for it directly in the annual program. The annual program starts on the current day. Each day, the time frame shifts one day. Days added at the end are automatically assigned the daily program from the weekly program. This ensures that every day is assigned a daily program.
EN2B-0092GE51 R0512 42
EXCEL 50/100/500/600/800 TIME PROGRAMS
43
Entries in the annual program must therefore be made only if a daily program differing from the one selected is to be used. An undefined daily program to be inserted in the annual program can be defined in the daily program.

Special Day List

One special day list exists per time program. It makes a number of holidays and special days available to which a daily program can be assigned. This daily pro­gram will then apply to this holiday or special day every year. The date of floating holidays is calculated automatically by the Excel 500. If no daily program is entered on certain holidays, the special day list is not taken into account on this day. The following holidays and special days are contained in the list:
New Year's Day (1
Epiphany (6
st
th
of January)
of January)
Monday before Ash Wednesday
Shrove Tuesday
Ash Wednesday
Good Friday
Easter Sunday
Easter Monday
Labor Day (1
st
of May)
Ascension Day
Whit Sunday
Whit Monday
Corpus Christi
Assumption Day (15
Day of German Unity (3
Reformation Day (31
All Saint's Day (1
th
of August)
rd
of October)
st
of October)
st
of November)
Day of Prayer and Repentance
1st to 4th Sundays in Advent
Christmas Eve (24
Christmas Day (25
Boxing Day (26
New Year's Eve (31
th
of December)
th
of December)
th
of December)
st
of December)
First Saturday in the month (Germany) If a daily program that has not yet been defined should be entered in the special
day list, it must first be defined in the "Daily program" section of the time program. NOTE: To activate the special day list, you must set the special day status to
ON.

The "TODAY" Function

Using the "TODAY" function, it is possible to perform on/off changes to setpoint values or control states without having to access the annual program or to define a new daily program. New setpoint values or control states and the period of validity (i.e. start and end) for a specific user address are defined. These changes are carried out at operator level 2 of the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces or the Excel 50 MMI. The start time must be within 24 hours from the entry time. The end time must be within 24 hours from the start time. The duration of the change can thus amount to a maximum of 24 hours. The entry is deleted automatically after the end time point is exceeded.

Generating a Time P rogram

A new time program is defined at operator level 4 (programming level) of XL-Online or on the Excel CARE engineering system. The new time program is given a name
EN2B-0092GE51 R0512
TIME PROGRAMS EXCEL 50/100/500/600/800
and assigned a user address. This process thus defines which user addresses are to be referenced by the time program.
Up to 20 time programs can be defined for each Excel 500. The time programs are extremely flexible. The switching points for a section of the system or building are usually combined in one time program. It is also possible to combine all datapoints in one time program. The following steps can also be carried out at operator level 2 (read and limited changes) of the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces and the XL50-MMI.
1) Daily programs are generated and given a name.
2) User addresses with a switching time and setpoint value or control state are entered in the daily program.
3) A daily program is assigned to each weekday in the weekly program section after the daily programs have been generated.
4) This weekly program is automatically copied for each week in the annual program.
The generation of an executable time program is now complete. If, on a certain day in the annual program, a daily program differing from the one specified in the weekly program is to be used, this new daily program can be entered directly in the annual program. The defined weekly program is not modified and continues to be used on those days which have not been modified, in any way, in the annual program. Any changes to be made to switching times, setpoint values, or control states must be carried out in the daily programs. The special day list is available. It contains a number of holidays; a different daily program can be assigned to each holiday. Once assigned to a holiday, the daily program will apply on this holiday every year. That is valid for holidays with fixed date (for example (Ascension Day, Good Friday). The dates of floating holidays will be calculated automatically by Excel 500. If there are no entries, then the existing daily program of the annual program remains valid on that holiday.
New Year’s Day or Christmas Eve) as well as for floating holidays
EN2B-0092GE51 R0512 44
EXCEL 50/100/500/600/800
45

ALARM HANDLING

The Excel 50/100/500/600/800 alarm handling facility offers a high degree of security by both storing and immediately displaying all alarms that occur at the operator interfaces. The user chooses whether an alarm is critical or non-critical. The user can also create personalized alarm texts, if required.
If your Excel 50/100/500/600/800 is connected to a front-end or a modem, critical alarms are transmitted as high priority.

Point Alarms

The type of alarm generated by a datapoint depends on the type of datapoint involved. Furthermore, there are alarm types which are valid for all datapoints or which refer to system alarms in the control unit.
Limit monitoring In the case of an analog input or pseudo analog point, two maximum limits (limit
Alarm status In the case of a digital input or pseudo digital point, a decision can be made
Maintenance Alarm In the case of a digital input, a digital output, or a pseudo digital point, the hours run
Totalizer A pulse input signal interval can be fixed for a totalizer input that, if exceeded,
Max. 1, limit Max. 2) and two minimum limits (limit Min 1, limit Min 2) can be set for a particular value. The limit values are entered in the datapoint description. Each time this limit value is reached, irrespective of the direction, an alarm is triggered. If, for example, a measured value takes on a value that exceeds a maximum limit or drops below a minimum limit, an alarm is generated (alarm reached). If the value returns from the alarm range to the normal range and, in doing so, reaches a limit value in the opposite direction, an alarm signal is given in the same way (alarm reached). Since this sequence is identical for all four limit values, a total of eight different alarm signals are possible for one analog datapoint. These eight alarm signal texts are programmed permanently, and require no input from the user.
whether or not an alarm check is desired. The entry is made in the datapoint description.
Prior to V.2.04.x
Alarm Check Enter "Yes" No Alarm Check Enter "No"
If an alarm check is desired, an alarm signal is produced if the digital point changes from Active State to Passive State (alarm reached). When the digital point returns to Active State, an additional signal is generated (alarm going). The two alarm signal texts are permanently programmed and require no input from the user. The fixing of active and passive states must be carried out in the datapoint description under the attribute "Active State".
0 = Active state with "0" signal 1 = Active state with "1" signal
V.2.04.x
The attribute "Active State" is fixed to “1”. This means that the alarm status is no longer dependant upon the attribute "Active State", but rather only upon the physical contact status and upon the logical status as defined in the online attribute "Normally Open/Normally Closed".
time entry can be activated and a maintenance interval can be fixed. If the latter is exceeded, an alarm signal is generated. The text of this signal is permanently programmed and requires no input from the user. If a check is to be skipped, a "0" is entered in the datapoint descriptor under the attribute "Maintenance Interval".
triggers an alarm signal. The alarm signal text is permanently programmed and requires no input from the user. If a check is not desired, a "0" is entered in the datapoint description under the attribute "Interval Count".
EN2B-0092GE51 R1111
ALARM HANDLING EXCEL 50/100/500/600/800
Operational status All datapoints can be switched from the 'automatic' to the 'manual' operational
Remote (V2.0.x) (not with Excel 100C) If a manual override control is changed on a Distributed I/O module, an alarm
Alarm suppression in manual mode Under controller firmware 2.06.02 and higher, the following datapoint alarms can be
mode. Each time the operating mode is changed, irrespective of the direction involved, a critical alarm signal is generated. Both alarm signal texts are preprogrammed and require no input from the user.
“overr.switch_manu” or “overr.switch_auto” is generated and the “manu” value is transmitted.
suppressed for as long as the corresponding datapoints are in the 'manual override' mode:
min. and max. limit alarms (of analog datapoints, only);
status alarms (of digital datapoints, only).
This alarm suppression is activated during CARE engineering by inserting the "at" sign ("@") at the beginning of the descriptor text of the pseudo datapoint "Startup".
Benefits:
As long as this alarm suppression is in effect, the repair or replacement of defective and/or malfunctioning (flickering) inputs (resulting e.g. from sensor breakage, sensor short-circuiting, defective alarm switches, etc.) can be performed while the corresponding datapoint is in the "manual override" mode.
NOTE: Only when using XFI 2.1.0 SIM1 will the event behavior and visualization
behavior be identical to that of Honeywell Deltanet controllers.

System Alarms

Operating errors that occur in a control unit or during communication with other
Alarm no.
1 AI Module Defect 25 Maximum conversion time was exceeded while testing ADC (defect on an AI card). 2 AI 0 Volt Error 24
3 AI 5 Volt Failure 23 4 MAX 2 alarm 2 Alarm limit for AI-, PA points
5 MAX 2 normal 76 Alarm limit for AI-, PA points 6 MAX 1 alarm 1 Alarm limit for AI-, PA points 7 MIN 2 alarm 4 Alarm limit for AI-, PA points 8 MIN 2 normal 78 Alarm limit for AI-, PA points 9 MIN 1 alarm 3 Alarm limit for AI-, PA points 10 MAX 1 normal 75 Alarm limit for AI-, PA points 11 MIN 1 normal 77 Alarm limit for AI-, PA points
12 Alarm memory full 22
13 Alarm 6 Alarm condition control for DI , PD points.
alarm text English)
cond. code #
Excel 50/100/500/600/800 units are recognized and displayed by the computer module. These alarm signals can relate, for example need to change the buffer battery (data protection), or the presence of one digital output module too many (maximum 10). These alarm signal texts are preprogrammed. They are always critical alarms.
Table 20. System alarms
cause/reason
While measuring GND voltage on an AI card, one value greater than 0.5 V was measured (AI card defect).
While measuring the 5-V reference voltage on an AI card, one value greater than 5 V or smaller than 4.5 V was measured (AI card defect or incorrect power supply of AI card).
1) After starting the Field I/O Task with the parameter "INIT", the default datapoint description couldn't be installed because USX didn't provide enough storage space for sending CNAP telegrams.
2) Alarm send buffer full.
, to a defective module, the
EN2B-0092GE51 R0512 46
EXCEL 50/100/500/600/800 ALARM HANDLING
47
Alarm no.
alarm text English)
cond. code #
cause/reason
14 Return to normal 79 Alarm condition control for DI, PD points. 15 Hware clock failed 61 Error while initializing the system clock. 16 Battery low 17 Battery voltage too low or battery not existent.
17 Battery sta tu s OK 87
18 Wrong Module ID 71
19
Too Many DO Module
60 Too many modules of the same type (XF521, XF522, ...).
Battery voltage back to normal again (alarm occurs only after alarm message "Battery low").
An invalid module ID is read (error on internal I/O or defect module or the module has an as-yet unspecified module ID).
20 Contr. w/o Flash 81 Error occurred when burning the Flash EPROM. 21 FLASH Mem Full 82 Not enough Flash memory space to save application. 22 Link Point Alarm - Xlink alarm. 23 Link Comm Down - Xlink alarm. 24 No characteristic 57 The application part "Characteristics" is defect.
25
RCL Submod missing
- RACL sub-module missing. 26 Download SSI Now - Xlink alarm. 27
28 RACL inconsistent 29
29
30
31
32
Download CPU Now
Nested submodules!
alarm message 158
RACL undef. OpCode
RACL program fault
- Xlink alarm.
Incompatible version numbers of RACL program and RACL parameter files and/or datapoint description.
30 RACL program contains errors (MCAL from submodule).
- Alarm not used.
32 RACL program contains errors (undefined Operation code).
33 RACL program contains errors (Checksum changed).
1) During RACL run, datapoint contains errors or point is locked.
33 Unknown datapoint 34
2) An unrecognized (missing) characteristic in the datapoint editor has been used. Check if the default file set of the controller is different from the set used in CARE.
34 SSI Points Active Xlink alarm. 35 Invalid operation 36
Non-valid arithmetical operation during RACL performance (e.g. division by zero or RACL statements LN with input value 1.0 ).
36 RACL overflow 37 Arithmetic overflow at RACL performance "+infinite". 37
38
RACL neg. overflow
RACL inval. OpCode
38 Arithmetic underflow at RACL performance "-infinite".
39 RACL program contains errors (invalid Operation Code).
39 Z-Reg. index error 40 Access to non-existing Z register (e.g.: RACL statements ISTO and IRCL). 40 Invalid Y-Register 41 Too many statements (exits) in one column. 41 Invalid P-Register 42 Attempt to use non-existent P register. 42 Invalid T-Register 43 Attempt to use non-existent T register. 43 Invalid Z-Register 44 Attempt to use non-existent Z register. 44 SSI Interface Up - Xlink alarm. 45 No parameter file - RACL parameter file missing. 46 No Z file - RACL Z register file missing. 47 No T file - RACL time register file missing.
EN2B-0092GE51 R0512
ALARM HANDLING EXCEL 50/100/500/600/800
Alarm no.
48 Part applic. mi s s
alarm text English)
cond. code #
46 47 48 49 52
cause/reason
1) No RACL program.
2) No parameter file.
3) No Z register file.
4) No T register file.
5) No datapoint description. 26 1) Submodule does not exist. 27 2) Parameter file missing. 28 3) No M0 module.
49 RACL environ fault
31 4) Invalid SKIP destination. 34 5) Info points STARTUP, SHUTDOWN, or EXECUTING_STOPPED are missing or
6) During RACL start datapoint contains errors. 1
7) freely programmable application loaded into Excel 50 controller (system alarm
parameters set to 0,0,0). 50 INIT div. by zero 14 Reason of new start: Division by zero. 51 INIT under OpCode 15 Reason of new start: the system software contains an undefined Operation Code. 52 Power failure 16 Reason of new start: power failure, data in RAM ok. 53 Link Config Bad - Xlink alarm.
54 I/O board missing 19
55 Unused I/O board 18
The required configuration contains at least one module which is not included in the
hardware configuration.
The hardware configuration contains at least one module that is not needed (can be taken
out).
1) Hardware Configuration file (.kfx file) not complete loaded.
2) Different modules are plugged under the same address (set using the rotary HEX
56 HW Config. failure 20
switch) in the required configuration and in the hardware configuration.
3) An application containing NV-mapping is rejected by the target controller because the
hardware does not have the 3120E5 Neuron® chip. 57 Wrong version no. 21 The version number of the application files and the configuration file are not the same. 58 Totalizer overflow 5 Overflow operation hours counter, point value of counters and interval impulse counter.
59 Maintenance alarm 7
Course of a service interval for digital points or course or the message/calling interval for
counters. Call intervals for counters. 60 Undef. RACL input 62 Undefined RACL errors.
The loaded application contains too many remote points. An application with more than 46 61 Too many Globals 63
62 C-Bus error 64
63
No Globals memory
9 No remote storage; the remote controller has no storage left for requested remote points.
NVs has been rejected for download into an Excel 50 freely programmable controller
located on a L
ONWORKS network.
Communication defect/disturbance between Excel 500 and C-Bus submodule. Logical
modem device in controller has gotten a C-Bus # already in use for a C-Bus controller.
64 Global pnt mis sing 10 The user address of the remote point was not found in the remote controller. 65 Glob Pnt Occupied 11 A remote output to a remote controller is already assigned to another controller. 66 CPU stopped 12 The remote controller is in stopped condition. 67 CPU not available 13 The remote controller is switched off or does not respond to C-Bus communication. 68 Init. actuators 65 Floating outputs (3-position outputs) are synchronized. 69 WARM START 66 Reason of new start: watchdog. 70 COLD START 67 Reason of new start: power failure, data in RAM destroyed. 71 Point in manual 68 When falling back to pass word level 3 there are still points in manual override. 72 Report too large 69 Not enough space in the report file for initialization.
73 XI 581 required 70
After a download, an entry is demanded in the initializing phase of the ASPECD
application. This can happen only with XI581 emulation. 74 New appli. loaded 74 Download of a new application part or entire application.
EN2B-0092GE51 R0512 48
EXCEL 50/100/500/600/800 ALARM HANDLING
49
Alarm no.
alarm text English)
cond. code #
cause/reason
75 Auto operation 80 Point is in automatic mode. 76 Manual operation 8 Point is in manual override mode. 77 Too many trend pnt 73 Too many points in trend. 78 No C-BUS refresh 110 No memory to execute refresh / trend functionality. 79 Template too long 85 Template for wildcard search too long.
80 206
Used only for MCR200 controllers. MCR200 rejects the setting of summer time if it is done with corresponding function of XBS or XL-Online.
Used only for MCR200 controllers. A weekday is allocated to the daily programs of
81 207
another weekday by copying the corresponding data. While copying, the name of the daily programs (weekday) remains whereas it would be exchanged by allocation.
82 83
83 B-Port Download 100
84 C-Bus Download 101
85 B-Port change 102
86 C-Bus change 103
Only used for MCR200 controllers. Texts from XIP100 or MCR200 Fax were not able to be loaded into the MCR200.
Download was done via B-Port. In addition to this alarm, one of the following alarms is displayed: 88 to 98.
Download was done via C-Bus. In addition to this alarm, one of the following alarms is displayed: 88 to 98.
Online changes were done via B Port. In addition to this alarm, one of the following alarms is displayed: 88 to 93.
Online changes were done via C-Bus. In addition to this alarm, one of the following alarms
is displayed: 88 to 93. 87 Device logged 84 Operator has logged himself in with MMI via C-Bus (Remote Login). Not sent on C-bus. 88 DDC Parameter - This alarm is shown in addition to one of the following alarms: 83 to 86. 89 DDC Z-Register - This alarm is shown in addition to one of the following alarms: 83 to 85. 90 DDC T-Register - This alarm is shown in addition to one of the following alarms: 83 to 84. 91 Datapoints - This alarm is shown in addition to one of the following alarms: 83 to 86. 92 Time Program - This alarm is shown in addition to one of the following alarms: 83 to 86 and 101. 93 ASPECD Program - This alarm is shown in addition to one of the following alarms: 83 to 85. 94 Alarm Texts - This alarm is shown in addition to one of the following alarms: 83 and 84. 95 Characteristics - This alarm is shown in addition to one of the following alarms: 83 and 84. 96 Descriptors - This alarm is shown in addition to one of the following alarms: 83 and 84. 97 Engineering Units - This alarm is shown in addition to one of the following alarms: 83 and 84. 98 State Texts - This alarm is shown in addition to one of the following alarms: 83 and 84. 99 Field I/O - This alarm is shown in addition to one of the following alarms: 101. 100 Glob.Pnt.Transfer - This alarm is shown in addition to one of the following alarms: 101.
104
101 Applic. stopped
105 106
Application task was stopped. This alarm, together with one of the following alarms, is
shown: 92, 99, 100, 102.
107
102 DDC Program - This alarm is shown in addition to one of the following alarms: 83 to 86 and 101. 103 I/O board present 108
A module which is part of the required configuration but was missing in the hardware
configuration has been added to the hardware configuration again. 104 Time dev. > 2 min 98 A time deviation greater than 2 minutes has been detected on a device on the C-Bus. 105 Manual time sync. 99 Somebody has changed the system time of the C-Bus devices via a local MMI. 106 Dig.Out.Conflict 109 Application error: An XL50 DO is using a triac already in use by a 3-position output. 107 Overr. switch auto 111 Manual override switches on Distributed I/O output modules are reset to automatic mode.
108 Overr. switch manu 112
Manual override switches on Distributed I/O output modules are set into override mode
(values coming from the XL controller will be overwritten by the switches).
EN2B-0092GE51 R0512
ALARM HANDLING EXCEL 50/100/500/600/800
network or a sensor break or a
Alarm no.
109 Hardware Failure 88
110 Hardware OK 89
111 M-Bus (XL50, only) - Used only in Excel 50 fixed applications. Shown together with M-Bus-related alarms. 112 OVFL crit. alarms 113 Critical alarm buffer full. 113 OVFL non-crit. al. 114 Non-critical alarm buffer full. 114 OVFL trend 115 Remote trend buffer full.
115 NV Bindings lost 116
116 pls upload trends! 117
117 config data def. 118 118 unauthorized acc. 119 Unauthorized telephone number and/or unauthorized password tried to dial in.
119 out of memory 120 No more memory available for alarm handling.
120 Please disconnect! 121
121 front-end not avail. 122 Front-end could not be reached. Line occupied or disconnected. 122 config complete 123 Configuration for the remote communication received, accepted and complete. 123 modem device OK 124 Response message to the XBS life check.
124 C bus error 125 125 LON- I/O init start 126 Initialization start of the Distributed I/O modules.
126 LON- I/O init done 127 Initialization of the Distributed I/O modules finished. 127 IP-DIO conflict 128 Standard I/O module XF5xx plugged with address of already-used DIO module XFL5xx. 128 Invalid user ID 212 CARE license key tag in the application is incorrect.
129 MTO Binding failed 155
130 board missing 19
131 board present 108
alarm text English)
cond. code #
cause/reason
A Distributed I/O module was removed from the LONWORKS sensor short-circuit or missing NV update from a bound NV was detected on a Distributed I/O module.
A missing Distributed I/O module was reconnected to the L sensor was reconnected on a Distributed I/O module or a sensor break / short-circuit was repaired or a missing NV update from a bound NV was supplied.
If the network interface has been changed in CARE and the changed application has been downloaded, all bindings will be lost.
The remote trend buffer has reached its notification level and should be uploaded in order to avoid trend buffer overflow.
Configuration data for the remote communication lost or corrupt due to power failure, EEPROM fault or uncharged gold cap.
Front-end X is online while remote trend buffer for front-end Y exceeds the notification level. Terminate dial-up connection with the controller in order to allow it to transmit its remote trend buffer to front-end Y.
No C-Bus communication between remote communication device number and application device number. Probably the application device number is missing.
The user has tried to make more “many-to-one-bindings” during controller runtime than were specified during CARE engineering. The “many” relation of a “many-to-one-binding” (MTO) is specified during CARE engineering. (The entered “many” relation will be used to calculate the memory space taken from the controller's application memory for the “many­to-one-binding”.)
In the event of a module defect or power failure (initialization), this alarm is related to the datapoints on this board. The required configuration contains at least one module not included in the hardware configuration.
In the event of a module defect or power failure (initialization), this alarm is related to the datapoints on this board. A module which is part of the required configuration but was missing in the hardware configuration has been added to the hardware configuration again.
ONWORKS network or a missing

System Alarms Suppression (V. 2.04.xx or higher)

System alarms can be suppressed during CARE engineering by inserting the "at" sign ("@") at the beginning of the corresponding alarm text in the alarm text file. In order to avoid alarm showers at power failure and power return, separate system alarms are provided for module power failure and for input failures on the modules (see Table 21).
EN2B-0092GE51 R0512 50
EXCEL 50/100/500/600/800 ALARM HANDLING
51
Reason for fault Module alarm Poi n t alarm
Care 3.x applications for controller firmware V. 2.04.xx
Care 4.x applications for controller firmware V. 2.04.xx
Care 4.x applications for controller firmware V. 2.06.xx
Procedure Engineer CARE 4.x applications for controller firmware version 2.04.xx, and then
defective module or power failure sensor break / short-circuit or
missing NV update from bound NV defective module or power failure sensor break / short-circuit or
missing NV update from bound NV defective module or power failure sensor break / short-circuit or
missing NV update from bound NV
Table 21. Avoiding alarm datapoint showers
"I/O board missing" (54) "I/O board present" (103)
"I/O board missing" (54) "I/O board present" (103)
Due to open LON, module alarms are no longer possible!
suppress the datapoint system alarms 109 and 110 by placing the @ character at the first position of the corresponding alarm text.
"hardware failure" (109) "hardware OK" (110)
"hardware failure" (109) "hardware OK" (110)
"board missing" (130) "board present" (131)
"hardware failure" (109) "hardware OK" (110)
"board missing" (130) "board present" (131)
"hardware failure" (109) "hardware OK" (110)

User Program Alarms

It is possible to generate alarm signals at any point in the user program by using a special program command. The alarm text can be individually created and may contain up to 18 characters.

Data Storage

Each alarm is stored in the alarm memory that can hold up to 99 alarms. Alarm sig­nals in the alarm memory contain neither an indication of the nature of the alarm signals in the alarm (critical/non-critical) nor an acknowledgment of the alarm on the operator interface. The alarm memory entry contains user address, alarm text, date, and time. If the memory capacity is exceeded, new alarm signals are accepted, such that the last 99 alarms always remain in the alarm memory. The alarm memory can be viewed on the XI581 (not with XCL5010, Excel 100C), XI582 and XL-Online operator interfaces and the Excel 50 MMI.

Alarms Sent across the System Bus

Alarm recovery Once the capacity of the temporary alarm buffer for system alarms is reached (max.
Refresh list deletion (V1.5.x) If an XBS or XL-Online is disconnected from the bus/controller, then the refresh list
99 alarms for firmware 2.03.xx or lower, and max. 50 alarms for firmware 2.04.x), then any additional alarms cause the datapoint to be labeled "in alarm" and given a description of the type of alarm that has occurred. Labeling is carried out only for the last occurring alarm for that datapoint. When a C-bus connection to a front-end has been established, then all alarm messages of the temporary system alarm buffer are sent to the front-end. After­wards, alarms for datapoints that are labeled “in alarm” are sent directly to the C­bus (except those that are in alarm suppression). If the controller’s alarm history buffer still contains information related to such an alarm, then this information is sent to the front-end. Otherwise, only the alarm type (without data or time) is sent. In this case, the datapoints appear at the front-end with an asterisk indicating that the data and time shown do not correspond to the generation of the alarm.
is deleted after a period of 2 minutes. This allows point values to be updated that
EN2B-0092GE51 R0512
ALARM HANDLING EXCEL 50/100/500/600/800
are set in refresh after a short-time interruption (maximum: 2 minutes) due to a communication error.
EN2B-0092GE51 R0512 52
EXCEL 50/100/500/600/800
53

TEST MODE (V2.03.X)

General Excel 50/100/500/800 controllers feature a special test mode intended specifically
Distributed I/O testing (V2.04.xx or higher)
for troubleshooting or system checkout and which allows manually setting outputs and verifying inputs. When entering the test mode, a set of default datapoints is generated corresponding to the physical I/O of the controller. The default user addresses are coded to correspond with the physical I/O in the following way:
AI0101: Analog input, module 1, input 1 AO0201: Analog output, module 2, output 1 DI0301: Digital input, module 3, input 1 DO0401: Digital output, module 4, output 1 3P0101: Motor output, module 1, output 1
NOTE: Excel 50/100 controllers do not have I/O modules, but their technical
addresses follow the same pattern, with module numbers referring to internal I/O boards. For details, see the Excel 50 and Excel 100 Installation Instructions. Excel 800 supports the test mode for the Panel Bus I/O Modules, only (XF8xxxx).
Values are displayed (0/1 for digital points) for each of the default datapoints, and the values are refreshed in this screen as they change. Outputs can be set manual­ly via MMI. The alarm buffer records all system alarms and all changes of state of inputs.
Beginning with controller firmware V2.04.x, Distributed I/O modules can be checked out in the same way as described above. For details, see the Software Release Bulletin for XL500, controller firmware version 2.04.00.

COMMUNICATION

General Control systems often need to carry out complex monitoring and control functions
L (V2.04.xx or higher)
ONWORKS communication
as part of their building management task. This is difficult if individual subsystems cannot exchange data with one another. Control applications using such equipment soon reach the performance limits of their controllers. This is because there is only a limited number of inputs and outputs available and it is difficult for the controller to monitor several processes simultaneously. In addition, it may not be economical to connect different parts of a plant because they are too far away from one another. Equipment that has been specially designed to implement only a particular application has the disadvantages of being more expensive in the first place and inflexible to future needs. The Excel 50/100/500/600/800 have a modular structure, so they can be tailored to match the plant they are controlling. The individual Excel controllers are able to communicate with one another, so that the configuration of one section of your system does not limit the overall size of your building management system.
Excel 50 and Excel 500 controllers equipped with 3120E5 Neuron chips (date code 0044 or higher) are capable of communicating with devices on an Echelon®
ONWORKS® network. For more information, see Excel 50/500 LONWORKS
L Mechanisms Description, EN0B-0270GE51.

System Bus

Up to 30 Excel controllers can be connected to one another via a System Bus (C­bus). Other C-bus compatible components can be substituted for any of the 30 Excel controllers. Example controllers, the Excel EMC, and Excel Building Supervisors. The C-bus allows con-
s of C-bus compatible components are Excel IRC Multi-
EN2B-0092GE51 R1111
COMMUNICATION EXCEL 50/100/500/600/800
trollers and devices to exchange data such as measured values, alarms log, and trends. This means that values from one controller or device can be sent to the entire system. Besides allowing communication between controllers and devices, the C-bus also enables the entire system to be connected to PC front-ends. When a controller does not have a modem directly connected, the C-bus also allows controllers to communicate with other controllers that do have a modem connected, so that data can be transmitted via the public telephone network.

Access

The C-bus supports multi-master communication using the token passing pro­cedure. A bus master is a controller governing communication between bus devices. The master asks for data and then distributes the data on the bus. Con­trollers transmit data only when asked for it by the master or when they assume the function of the master. Multi-master communication means that all controllers in the system can function as the master, so the right to request and transmit data is not permanently assigned to a specific controller. This has the advantage that a part of the system can still continue working even if one of the controllers is defective. The flow of data between devices can be structured hierarchically as part of the software in the user program. Structuring data exchange means defining what infor­mation can be exchanged between which bus devices. Communication is still carried out on the multi-master principle, but bus access time is reduced by con­centrating specific data in specific controllers.

Bus Initialization

When your system first starts up, the software runs a check to see what devices are connected to the C-bus. This process is called initialization. The software stores the information as the Device Type List in the controllers. During initialization, the bus master requests information about global datapoints from each controller. At the same time, the controllers store the address of the device making the request so that the controllers can subsequently transmit the appropriate data to the appropriate device. After initialization, each controller knows the address of the next controller with the right to transmit data. If a controller now stops communication, the bus master recognizes that this controller is no longer online and interrupts token passing. As a result, the C-bus reinitializes automatically and also updates the Device Type List, excluding controllers that are no longer online. This ensures continuous bus communication even when individual controllers go off line.

Bus Communication

The Excel 50/100/500/600/800 controller does not transmit any plant-specific data before the C-bus has been initialized. Controller communication depends on the user program stored in each controller. Bus-wide communication occurs when global datapoints have been defined in the user program. See "Global Datapoints" on page 11 for details on defining global datapoints. During normal operation, the bus master transmits active values. The bus master transmits only values which have changed or which have been requested by another device on initialization or when a device has been offline. This method of exchanging data reduces the load on the bus and means controllers store only the data they need for their own communication.

I/O Runtime Synchronization

XF525 After application download and after a power failure a runtime synchronization takes
EN2B-0092GE51 R0512 54
place which takes the complete runtime as defined in the datapoint description plus an additional 10%.
EXCEL 50/100/500/600/800 COMMUNICATION
55
Calculated Runtime Actual Runtime
>100% permanently open >96% 96% plus 100% of defined runtime (Excel 500) 96% plus 200% of defined runtime (Excel 50) <2% 2% minus 100% of defined runtime (Excel 500) 2% minus 200% of defined runtime (Excel 50) <0% permanently closed
XF825 Synchronization will take place in the following situations:
Internal hysteresis is 2 to 3.125% and 95 to 96% of defined runtime.
Calculated position < Lower sync threshold
The floating actuators will be synchronized when the ass oc i ated input signal drops below the lower synchronization threshold, which is 2% by default. In order to avoid any logical interlock problems, this type of synchronization will immediately be finished when the input signal exceeds the lower synchronization threshold + sensitivity hysteresis. The actuator will drive to –“Synchronization Time” in this case. An additional synchronization with -20 % is done after half an hour and one hour in order to compensate temperature drifts of the valve.
Example: A cooling valve is closed. The valve is cold at the time it is closed. The valve will get warm and expand. This may result in leakage.
Calculated position > Upper sync threshold
The floating actuators will be synchronized when the ass oc i ated input signal exceeds the upper synchronization threshold, which is 98% by default. In order to avoid any logical interlock problems, this type of synchronization will immediately be finished when the input signal drops below upper synchronization threshold – sensitivity hysteresis.
Synchronization after power-up / 24 hours
The floating actuators will be synchronized in the following situations:
Always after power-up or reset of the Excel 800 controller
Optionally, once every 24 hours the actuator will be driven towards the “closed”
position.

Initialization of Distributed I/O Modules

XFL52x V1.02 with Excel 500 V2.01.03 During and after initialization of the Distributed I/O modules, the output of the
Remote Override Modules XFR522/XFR522A and XFR524/XFR524A will remain unchanged. This means that the output status will always remain unchanged as long as the 24 Vac power supply is applied and as long as there is no manual change at the XFRxxxx modules.

New Bus Devices

The system automatically detects new devices. When it has detected a new device, the system reinitializes so the new device is included in the Device Type List.

Network-Wide Controller Time Synchronization

Network-wide time synchronization is carried out automatically once each hour by the designated synchronization master. Each controller with firmware V2.0.xx or higher can act as a synchronization master. If the time is manually changed on any of the connected system bus controllers, then this time is adopted for synchroni­zation. If the controller on which the time was changed is eligible as a synchroni­zation master, then it will become the synchronization master on the bus. Synchronization is based on date, hours, minutes, and seconds to an accuracy of ± 120 seconds across the system bus (detected after no more than 1 hour). If this time is exceeded, an alarm is generated. Daylight saving time is included in the
EN2B-0092GE51 R0512
COMMUNICATION EXCEL 50/100/500/600/800
synchronization process. Any new device added to the system bus will adopt the bus system time.
NOTE: If you enter the time on the local MMI of an older device (prior to
V2.0.xx), synchronization will not be carried out. Even the locally entered time might be overwritten by a synchronization coming from a newer device (V2.0.xx or higher).

Point Refreshing

Excel controllers provides a refresh mechanism (that is adapted to the Token timing) for sending the values of the attributes "Value", "Manual Value", "Operating Mode", and "Alarm Status" to either an MMI interface or to a front-end. (A maximum of two point refresh messages can be sent while the controller is holding the Token.)

PC Communication

An Excel 50/100/500/600/800 system can also accommodate a PC connected to the C-bus. Multi-master communication is still supported and token passing continues between the individual bus devices. The C-bus treats controllers as being equal in rank to a PC.

Excel IRC

Excel controllers support communication with the Excel IRC control system. This system monitors and controls individual rooms within a building. The Excel IRC system communicates on the C-bus via its Multicontroller (MC). The Application control functions for Excel IRC, called ACFs, are all processed by the MC. See EXCEL 5000 IRC Integration System Overview and Application Guide, EN3R-1182GE51, for additional information.

Remote Communication

Excel 50/100/500/600/800 controllers are all able to communicate to remote building supervisors via an analog or ISDN modem connected to them. This allows two-way communication between the building supervisors and the controllers. The Excel 100/500 controllers can store the numbers and passwords for up to three supervisors and can call them in response to critical alarms or other programmed triggers, or the supervisor can call at any time for status, trend, or alarm information.
Disable dial-out (V2.04.xx or higher) Automatic upload of the remote trend buffer can be disabled by a remote front-end
Direct modem connection
(Excel 50/500, V2.01.xx or higher and Excel 800, V3.00.xx or higher)
(XBS 1.6.0 or higher). In this case, remote trend values are stored in the buffer, with newest values overwriting oldest when the buffer is full, but the controller does not dial out to send remote trend buffer level alarms or to flush the buffer. The controller will still dial out for critical and uncritical alarms. Excel 100 and 600 controllers and Excel 500 controllers with V1.5.xx firmware or earlier can, when operating as stand-alone controllers, make use of the XDM506 modem submodule mounted on the CPU board. The XDM506 can perform all of the functions of the XM100A in providing remote communication capability with up to three building supervisors.
Excel 50/500 controllers with firmware version V2.01.xx or higher, Excel 100C controllers, as well as Excel 800 controllers with firmware version V3.00.xx or higher have the advantage of allowing direct connection of a modem or ISDN terminal
EN2B-0092GE51 R0512 56
EXCEL 50/100/500/600/800 COMMUNICATION
57
adapter to the controller for either C-Bus systems or stand-alone controller applications. No additional hardware is necessary. Excel 50/100/500/800 controllers can store 100 trend values (by default) for the connected EBI/SymmetrE, in addition to handling normal building control functions. Data transmission rates up to 38.4 Kbaud are supported with modem/ISDN terminal adapter attached. If no special modem behavior is needed, it is not necessary to set up or initialize the modem/ISDN terminal adapter. The Excel 50/100/500/800 controller will detect the modem attached to the serial port and set the communication speed to the default value of 9.6 Kbaud. The Excel 50/100/500/800 controller will also detect whether the modem/ISDN terminal adapter is initialized in auto-answer or manu-answer mode, and it will initialize the modem for manu-answer mode (S0=0).
NOTE: Remote communication to XBSi building supervisors is not supported by
NOTE: IRC alarming can be accomplished only indirectly with firmware version
direct modem connection.
V2.01.xx by using a separate Excel 500 controller with special operating system firmware (XL IRC V1.03.x) which allows mapping between it and an IRC Multicontroller. In that case, the IRC alarms are treated like normal C-Bus data.
Fig. 23. Remote Modem Connection
EN2B-0092GE51 R0512
COMMUNICATION EXCEL 50/100/500/600/800

Remote Trending (dial-up)

General

Per front-end (XBS, EBI), trend values for a total of 20 data points can be stored (via dial-up) in the remote trend buffer of the controller to which the modem has been connected. These 20 data points can come from the controller to which the modem has been connected, or they can come from various other controllers on the same C-Bus or L
Per front-end (XBS, EBI), trend values for a total of 100 data points can be stored (via dial-up) in the remote trend buffer of the controller to which the modem has been connected. These 100 data points can come from the controller to which the modem has been connected, or they can come from various other controllers on the same C-Bus or L additional remote trend buffer.
In combination with the large RAM controllers XD52-FC, XD52-FCS, XC5210C, a total of 384 KB of additional trend buffer is available. This increase in the trend buffer size reduces the number of times the controller must dial-up the front-end and lowers the risk of trend values being overwritten due to a full buffer. By exploiting this feature, it is possible, when no application is downloaded, to use the EXCEL controller as a pure trending device. The amount of additional memory available for the remote trend buffer is deter­mined by the value for “Application Memory Size” entered with the MMI during the start-up sequence of the controller. This number is subtracted from the total application memory, and the resulting number, in Kbytes, is the additional remote trend buffer size. Fig. 24 illustrates the adjustable remote trend buffer.
TOTAL APPLICA TION MEMORY
UNUSED APPLICATION MEMORY
ONWORKS bus.

Controller Firmware 2.03.xx and Higher

ONWORKS bus. Unused application memory can be used as

Controller Firmware 2.04.xx and Higher

REMOTE TREND BUFFER
e.g. 58 KB
58 KB = 1263 ADDITIONAL TREND SAMPLES
128 KB
APPLICATION
e.g. 70 KBYTES
+ 100 TREND SAMPLES (DEFAULT)
= 1363 T0TAL TREND SAMPLES
Fig. 24. Adjustable remote trend buffer example
The maximum number of trend values will be displayed on the MMI once a value for application memory size is entered. The adjustment range for the application memory size is the following:
Table 22. Adjustment range for application memory size
application memory size trend values in remote trend buffer
maximum (default): 128 Kbyte 42 per front-end example: 120 Kbyte 100 per front-end minimum: 38 Kbyte 100 per front-end; PLUS “N” for front-end A
EN2B-0092GE51 R0512 58
EXCEL 50/100/500/600/800 COMMUNICATION
59
160
Remote trend buffer size formula For XD52-FC, XD52-FCS, and XC5210C controller (512 Kbytes of RAM):
N = (128 Kbytes - appl. size (in Kbytes) + 384 Kbytes) * 1024 bytes / 47 bytes
For all other controllers equipped with Flash EPROMS:
N = (128 Kbytes - appl. size (in Kbytes)) * 1024 bytes / 47 bytes Hence, the maximum value of N is 10,327 trend values for large RAM controllers and 1,960 trend values for all others containing Flash memory. This means that for all Flash memory-equipped modules with a minimum application size of 38 Kbytes, there will be 2,064 (1,960 + 104) trend values for front-end A and 104 trend values each for front-end B and front-end C. If an application being downloaded exceeds the application memory size, a warning message will be displayed on the MMI, and the download will not be executed.

Excel 800

Excel 800 controllers provide a reserved Remote Trend Memory of 60Kbytes, which allows a total of 2591 trend entries to be stored – see also diagram below: 2391 trend entries for front-end A Plus 100 trend entries for front-end B Plus 100 trend entries for front-end C
-------------------------------------------------­TOTAL = 2591 trend entries
TOT AL APPLICATION MEMORY
REMOTE TREND MEMORY:
60 KBYTES = 2501 TREND ENTRIES
REMOTE TREND BUFFER
60 KBYTES = 2591 TREND ENTRIES
APPLICATION (excluding RACL)
KBYTES
= max. 100 KBYTES
= 2391 PER FRONT-END A + 100 PER FRONT-END B + 100 PER FRONT-END C
Fig. 25. Adjustable remote trend buffer example (Excel 800)
Unused application memory can be used for storing additional remote trend entries. In order to do so, the adjustment range for the application memory size is the following.
Table 23. Adjustment range of application memory size
application memory size trend values in remote trend buffer
maximum (default): 100 Kbyte 2501 example: 80 Kbyte 2936 minimum: 38 Kbyte 3851

MODEMFAQ

Detailed information and guidance can be obtained from the MODEMFAQ document, which can be found on the following servers:
http://web.ge51.honeywell.de/dep/mc/HVAC_Products/Automation_and_Control/Ce ntralPlantControls/Modem-Interface/MODMFAQ4.DOC
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800

MISCELLEANOUS

Customize Windows Default Regional and Language Settings

In order to setup an Excel 5000 system that uses any language other than the respective Windows default language, you must customize the Regional and Language Options Settings in Windows as a prerequisite before working with CARE / COACH and Excel Online / COACH Online. In addition, for a successful application engineering, the controller must be equipped with the appropriate firmware and XI582 with the appropriate EPROM.
For all settings to be done, please refer to the country and language settings table that lists the settings for:
Windows
CARE / COACH
Excel Online / COACH Online
XI852 EPROM
Controller firmware
For information on coding special characters in Western, Eastern and Turkish languages, please refer to the character settings tables following the country and language settings table.
To customize Windows, refer to the procedure following the character settings tables.
Country
XL 40 XL 50 XL 50 XL100/500/800
Several
Australia
Albania
Austria
Belgium
Bulgaria
Brazil
Canada
China
Windows Version /
Regional and Language
Options Settings
Arabic
English (Australia)
Albanian
German (Austria)
Dutch (Belgium), French (Belgium)
Bulgarian
Portuguese (Brazil)
English (Canada)
Chinese (Simplified)
Table 24. HBS Country and Language Settings
CARE Country
Code / Location
Selection
Arabic (not supported)
Australia
not supported not supported not supported
Austria
Belgium
Russia
Brazil
Canada
PR China
Controllers with Internal Text MMI
XL40A2MMI
XI40AI (required firmware)
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or or higher
not supported not supported
not supported not supported
XL50L207.02C or higher
not supported not supported
XL50- MMI-xxxx
XL50D
XL50A-MMI-xxxx
XL50A-UMMI-xxxx
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
Internal
Graphic MMI
XL50CH XL50CY
XL50TW XL50ACH XL50ACY
XL50ATW
(required
firmware)
not supported not supported not supported
EU50L207.02C or higher
not supported not supported Western
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
External
XI581/2
XI581/2
XI581B/2B
(required
hardware)
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Cyrillic
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU XI581B/2B-CH
XL Online
CHINESE_ BIG5
EN2B-0092GE51 R0512 60
EXCEL 50/100/500/600/800 MISCELLEANOUS
61
Country
XL 40 XL 50 XL 50 XL100/500/800
Croatia
Czech Republic
Denmark Danish
Finland
France
Germany German
Several
Hungary
Iceland
Ireland
Italy
Japan Japanese Japan not supported not supported not supported XI581B/2B-JP Japanese Korea Korean Korea not supported not supported not supported not supported Western Several
Lithuania Lithuanian
Macedonia Macedonian
Mexico
Morocco
Nether­lands
New Zealand
Norway
Poland
Portugal
Windows Version /
Regional and Language
Options Settings
Croatian
Czech
Finnish
French
Hebrew
Hungarian
Icelandic
English (Ireland)
Italian
Several
Spanish (Mexico)
French
Dutch
English (New Zealand)
Norwegian
Polish
Portuguese
CARE Country
Code / Location
Selection
Slovakia
Slovakia
Denmark
Finland
France
Germany
Hebrew
Hungary
Iceland
Ireland
Italy
Latin America XL50L207.02C
not supported not supported not supported
Russia
Mexico
France
Netherlands
New Zealand
Norway
Slovakia
Portugal
Controllers with Internal Text MMI
XL40A2MMI
XI40AI (required firmware)
not supported not supported
not supported not supported
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
or higher
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
not supported not supported
not supported not supported
not supported not supported
XL50- MMI-xxxx
XL50D
XL50A-MMI-xxxx
XL50A-UMMI-xxxx
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
Internal
Graphic MMI
XL50CH
XL50CY
XL50TW XL50ACH XL50ACY
XL50ATW
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
not supported not supported
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
External
XI581/2
XI581/2
XI581B/2B
(required
hardware)
XI581B/2B-EU Central
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Cyrillic
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Central
XI581B/2B-EU Western
XL Online
European
European
European
Cyrillic
European
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Country
XL 40 XL 50 XL 50 XL100/500/800
Romania Romanian
Russia
Serbia
Slovakia
Slovenia
Spain
Sweden
Switzerland
Taiwan
Tunisia
Turkey
U.A.E.
Ukraine
United Kingdom
United States
Windows Version /
Regional and Language
Options Settings
Russian
Serbian (Latin, Bosnia and Herzegovina)
Slovak
Slovenian
Spanish
Swedish
German (Switzerland), French (Switzerland), Italian (Switzerland)
Chinese (Taiwan)
French
Turkish
Arabic (U.A.E.)
Ukrainian
English (United Kingdom) United Kingdom XL50L207.02C
English
CARE Country
Code / Location
Selection
Slovakia
Russia
not supported not supported not supported
Slovakia
Slovakia
Spain
Sweden
Switzerland
Taiwan
France
Turkey
Arabic (not supported)
Russia
United States
Controllers with Internal Text MMI
XL40A2MMI
XI40AI (required firmware)
not supported not supported
not supported not supported
not supported not supported
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
not supported not supported
XL50L207.02C or higher
not supported not supported
not supported not supported
not supported not supported
or higher XL50L207.02C
or higher
XL50- MMI-xxxx
XL50D
XL50A-MMI-xxxx
XL50A-UMMI-xxxx
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher TW50L207.02C or higher XL50L207.02C or higher
Controllers with
Internal
Graphic MMI
XL50CH XL50CY
XL50TW XL50ACH XL50ACY
XL50ATW
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
not supported not supported Cyrillic
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
TW50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
not supported not supported not supported
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher TW50L207.02C or higher XL50L207.02C or higher
Controllers with
External
XI581/2
XI581/2
XI581B/2B
(required
hardware)
XI581B/2B-EU Central
XI581B/2B-EU Cyrillic
XI581B/2B-EU Central
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU
XI581B/2B-TW Thai
XI581B/2B-EU Western
XI581B/2B-EU Turkish
XI581B/2B-EU Cyrillic
XI581B/2B-EU Western
XI581B/2B-EU XI581B/2B-TW XI581B/2B-CH XI581B/2B-JP XI581B/2B-CY
XL Online
European
European
European
Western
Western
EN2B-0092GE51 R0512 62
EXCEL 50/100/500/600/800 MISCELLEANOUS
63
Table 25. CentraLine Country and Language Settings
Country
Tiger Panther Panther Lion
Several
Australia
Albania
Austria
Belgium
Bulgaria
Brazil Portuguese (Brazil) not supported not supported not supported not supported not supported not supported Canada English (Canada) not supported not supported not supported not supported not supported not supported China Chinese (Simplified) not supported not supported not supported not supported not supported not supported Croatia
Czech Republic
Denmark Danish
Finland
France
Germany German
Several
Hungary
Iceland
Ireland
Italy
Japan Japanese not supported not supported not supported not supported not supported not supported Korea Korean not supported not supported not supported not supported not supported not supported Lithuania Lithuanian
Windows Version /
Regional and Language
Options Settings
Arabic
English (Australia)
Albanian
German (Austria)
Dutch (Belgium), French (Belgium)
Bulgarian
Croatian
Czech
Finnish
French
Hebrew
Hungarian
Icelandic
English (Ireland)
Italian
COACH Country
Selection
not supported not supported not supported
Australia
Albanian
Austria
Belgium
Bulgaria
Croatia
Czech Republic not supported not supported
Denmark
Finland
France
Germany
as desired
Hungary
Iceland
United Kingdom XL50L207.02C
Italy
Lithuania
Controllers with Internal Text MMI
CLTG38L11
CLTG00MMI
(required firmware)
XL50L207.02C or higher
not supported not supported
XL50L207.02C or higher
XL50L207.02C or or higher
not supported not supported
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
or higher XL50L207.02C
or higher
not supported not supported
CLPA13LC1x CLPA13LM1x CLPA21CM1x CLPA21LC1x CLPA21LM1x
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
Internal
Graphic MMI
CLPA13LC2x CLPA13LM2x CLPA21LC2x CLPA21LM2x
(required
firmware)
not supported not supported
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
External
CLMMI00N2x
CLMMI00N2x
(required
hardware)
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Cyrillic
XI581B/2B-EU Central
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Cyrillic
COACH
Online
not supported
European
European
European
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Country
Tiger Panther Panther Lion
Macedonia Macedonian
Mexico Spanish (Mexico) not supported not supported not supported not supported not supported not supported Morocco
Nether­lands
New Zealand
Norway
Poland
Portugal
Romania Romanian
Russia
Serbia
Slovakia
Slovenia
Spain
Sweden
Switzerland
Taiwan Chinese (Taiwan) not supported not supported not supported not supported not supported not supported Tunisia
Turkey
U.A.E.
Ukraine
United Kingdom
Windows Version /
Regional and Language
Options Settings
French
Dutch
English (New Zealand)
Norwegian
Polish
Portuguese
Russian
Serbian (Latin, Bosnia and Herzegovina)
Slovak
Slovenian
Spanish
Swedish
German (Switzerland), French (Switzerland), Italian (Switzerland)
French
Turkish
Arabic (U.A.E.)
Ukrainian
English (United Kingdom) United Kingdom XL50L207.02C
COACH Country
Selection
Macedonia
Morocco
Netherlands
not supported not supported not supported
Norway
Poland
Portugal
Romania
Russia
Serbia
Slovakia
Slovenia
Spain
Sweden
Switzerland France not supported
Tunisia
Turkey
U.A.E. (not supported)
Ukraine
Controllers with Internal Text MMI
CLTG38L11 CLTG00MMI
(required firmware)
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
not supported not supported
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
XL50L207.02C or higher
not supported not supported
not supported not supported
not supported not supported
or higher
CLPA13LC1x
CLPA13LM1x
CLPA21CM1x
CLPA21LC1x CLPA21LM1x
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
Internal
Graphic MMI
CLPA13LC2x
CLPA13LM2x
CLPA21LC2x
CLPA21LM2x
(required
firmware)
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
not supported not supported not supported
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
EU50L207.02C or higher
not supported not supported not supported
EU50L207.02C or higher
EU50L207.02C or higher
Controllers with
External
CLMMI00N2x
CLMMI00N2x
(required
hardware)
XI581B/2B-EU Cyrillic
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Central
XI581B/2B-EU Cyrillic
XI581B/2B-EU Cyrillic
XI581B/2B-EU Central
XI581B/2B-EU Central
XI581B/2B-EU Western
XI581B/2B-EU Western
XI581B/2B-EU
XI581B/2B-EU Western
XI581B/2B-EU Turkish
XI581B/2B-EU Cyrillic
XI581B/2B-EU Western
COACH
Online
European
European
European
European
Western
EN2B-0092GE51 R0512 64
EXCEL 50/100/500/600/800 MISCELLEANOUS
65
Country
Tiger Panther Panther Lion
United States
Windows Version /
Regional and Language
Options Settings
English
COACH Country
Selection
United Kingdom
Controllers with Internal Text MMI
CLTG38L11
CLTG00MMI
(required firmware)
XL50L207.02C or higher
CLPA13LC1x CLPA13LM1x CLPA21CM1x CLPA21LC1x CLPA21LM1x
(required
firmware)
EU50L207.02C or higher TW50L207.02C or higher XL50L207.02C or higher
Controllers with
Internal
Graphic MMI
CLPA13LC2x CLPA13LM2x CLPA21LC2x CLPA21LM2x
(required
firmware)
EU50L207.02C or higher TW50L207.02C or higher XL50L207.02C
Controllers with
External
CLMMI00N2x
CLMMI00N2x
(required
hardware)
EU50L207.02C or higher TW50L207.02C or higher XL50L207.02C
Table 26. Character Settings (Western Europe)
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
20 32 32 SPACE 23 35 # 35 NUMBER SIGN
COACH
Online
Western
24 36 $ 36 DOLLAR SIGN 25 37 % 37 PERCENT SIGN 26 38 & 38 AMPERSAND 27 39 ' 39 APOSTROPHE 28 40 ( 40 LEFT PARENTHESIS 29 41 ) 41 RIGHT PARENTHESIS 2E 46 . 46 FULL STOP 30 48 0 48 DIGIT ZERO 31 49 1 49 DIGIT ONE 32 50 2 50 DIGIT TWO 33 51 3 51 DIGIT THREE 34 52 4 52 DIGIT FOUR 35 53 5 53 DIGIT FIVE 36 54 6 54 DIGIT SIX 37 55 7 55 DIGIT SEVEN 38 56 8 56 DIGIT EIGHT 39 57 9 57 DIGIT NINE 3A 58 : 58 COLON 40 64 @ 64 COMMERCIAL AT 41 65 A 65 LATIN CAPITAL LETTER A 42 66 B 66 LATIN CAPITAL LETTER B
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Hex
43 67 C 67 LATIN CAPITAL LETTER C 44 68 D 68 LATIN CAPITAL LETTER D 45 69 E 69 LATIN CAPITAL LETTER E 46 70 F 70 LATIN CAPITAL LETTER F 47 71 G 71 LATIN CAPITAL LETTER G 48 72 H 72 LATIN CAPITAL LETTER H 49 73 I 73 LATIN CAPITAL LETTER I 4A 74 J 74 LATIN CAPITAL LETTER J 4B 75 K 75 LATIN CAPITAL LETTER K 4C 76 L 76 LATIN CAPITAL LETTER L 4D 77 M 77 LATIN CAPITAL LETTER M 4E 78 N 78 LATIN CAPITAL LETTER N 4F 79 O 79 LATIN CAPITAL LETTER O 50 80 P 80 LATIN CAPITAL LETTER P 51 81 Q 81 LATIN CAPITAL LETTER Q
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
52 82 R 82 LATIN CAPITAL LETTER R 53 83 S 83 LATIN CAPITAL LETTER S 54 84 T 84 LATIN CAPITAL LETTER T 55 85 U 85 LATIN CAPITAL LETTER U 56 86 V 86 LATIN CAPITAL LETTER V 57 87 W 87 LATIN CAPITAL LETTER W 58 88 X 88 LATIN CAPITAL LETTER X 59 89 Y 89 LATIN CAPITAL LETTER Y 5A 90 Z 90 LATIN CAPITAL LETTER Z 5F 95 _ 95 LOW LINE 61 97 a 97 LATIN SMALL LETTER A 62 98 b 98 LATIN SMALL LETTER B 63 99 c 99 LATIN SMALL LETTER C 64 100 d 100 LATIN SMALL LETTER D 65 101 e 101 LATIN SMALL LETTER E 66 102 f 102 LATIN SMALL LETTER F 67 103 g 103 LATIN SMALL LETTER G 68 104 h 104 LATIN SMALL LETTER H 69 105 i 105 LATIN SMALL LETTER I 6A 106 j 106 LATIN SMALL LETTER J 6B 107 k 107 LATIN SMALL LETTER K
EN2B-0092GE51 R0512 66
EXCEL 50/100/500/600/800 MISCELLEANOUS
67
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
6C 108 l 108 LATIN SMALL LETTER L 6D 109 m 109 LATIN SMALL LETTER M 6E 110 n 110 LATIN SMALL LETTER N 6F 111 o 111 LATIN SMALL LETTER O 70 112 p 112 LATIN SMALL LETTER P 71 113 q 113 LATIN SMALL LETTER Q 72 114 r 114 LATIN SMALL LETTER R 73 115 s 115 LATIN SMALL LETTER S 74 116 t 116 LATIN SMALL LETTER T 75 117 u 117 LATIN SMALL LETTER U 76 118 v 118 LATIN SMALL LETTER V 77 119 w 119 LATIN SMALL LETTER W 78 120 x 120 LATIN SMALL LETTER X 79 121 y 121 LATIN SMALL LETTER Y 7A 122 z 122 LATIN SMALL LETTER Z 7E 126 ~ 126 TILDE 80 128 Ç 199 LATIN CAPITAL LETTER C WITH CEDILLA 81 129 ü 252 LATIN SMALL LETTER U WITH DIAERESIS 82 130 é 233 LATIN SMALL LETTER E WI TH ACUTE 83 131 â 226 LATIN SMALL LETTER A WI TH CIRCUMFLEX 84 132 ä 228 LATIN SMALL LETTER A WI TH DIAERESIS 85 133 à 224 LATIN SMALL LETTER A WI TH GRAVE 86 134 å 229 LATIN SMALL LETTER A WI TH RING ABOVE 87 135 ç 231 LATIN SMALL LETTER C WITH CEDILLA 88 136 ê 234 LATIN SMALL LETTER E WITH CIRCUMFLEX 89 137 ë 235 LATIN SMALL LETTER E WI TH DIAERESIS 8A 138 è 232 LATIN SMALL LETTER E WITH GRAVE 8B 139 ï 239 LATIN SMALL LETTER I WITH DIAERESIS 8C 140 î 238 LATIN SMALL LETTER I WITH CIRCUMFLEX 8D 141 ì 236 LATIN SMALL LETTER I WITH GRAVE 8E 142 Ä 196 LATIN CAPITAL LETTER A WITH DIAERESIS 8F 143 Å 197 LATIN CAPITAL LETTER A WITH RING ABOVE 90 144 É 201 LATIN CAPITAL LETTER E WITH ACUTE 91 145 æ 230 LATIN SMALL LETTER AE 92 146 Æ 198 LATIN CAPITAL LETTER AE 93 147 ô 244 LATIN SMALL LETTER O WITH CIRCUMFLEX
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Hex
94 148 ö 246 LATIN SMALL LETTER O WITH DIAERESIS 95 149 ò 242 LATIN SMALL LETTER O WITH GRAVE 96 150 û 251 LATIN SMALL LETTER U WITH CIRCUMFLEX 97 151 ù 249 LATIN SMALL LETTER U WITH GRAVE 98 152 ÿ 255 LATIN SMALL LETTER Y WITH DIAERESIS 99 153 Ö 214 LATIN CAPITAL LETTER O WI TH DIAERESIS 9A 154 Ü 220 LATIN CAPITAL LETTER U WITH DIAERESIS 9B 155 ø 248 LATIN SMALL LETTER O WITH STROKE 9D 157 Ø 216 LATIN CAPITAL LETTER O WITH STROKE 9F 159 ƒ 402 LATIN SMALL LETTER F WITH HOOK A0 160 á 225 LATIN SMALL LETTER A WITH ACUTE A1 161 í 237 LATIN SMALL LETTER I WITH ACUTE A2 162 ó 243 LATIN SMALL LETTER O WITH ACUTE A3 163 ú 250 LATIN SMALL LETTER U WITH ACUTE A4 164 ñ 241 LATIN SMALL LETTER N WITH TILDE
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
A5 165 Ñ 209 LATIN CAPITAL LETTER N WITH TILDE A8 168 ¿ 191 INVERTED QUESTION MARK B5 181 Á 193 LATIN CAPITAL LETTER A WITH ACUTE B6 182 Â 194 LATIN CAPITAL LE TTER A WITH CIRCUMFLEX B7 183 À 192 LATIN CAPITAL LETTER A WITH GRAVE C6 198 ã 227 LATIN SMALL LETTER A WITH TILDE C7 199 Ã 195 LATIN CAPITAL LETTER A WITH TILDE D0 208 ð 240 LATIN SMALL LETTER ETH D1 209 Ð 208 LATIN CAPITAL LETTER ETH D2 210 Ê 202 LATIN CAPITAL LETTER E WITH CIRCUMFLEX D3 211 Ë 203 LATIN CAPITAL LETTER E WITH DIAERESIS D4 212 È 200 LATIN CAPITAL LETTER E WITH GRAVE D5 213 ı 305 LATIN SMALL LETTER DOTLESS I D6 214 Í 205 LATIN CAPITAL LETTER I WITH ACUTE D7 215 Î 206 LATIN CAPITAL LETTER I WITH CIRCUMFLEX D8 216 Ï 207 LATIN CAPITAL LETTER I WITH DIAERESIS DE 222 Ì 204 LATIN CAPITAL LETTER I WITH GRAVE E0 224 Ó 211 LATIN CAPITAL LETTER O WITH ACUTE E1 225 ß 223 LATIN SMALL LETTER SHARP S E2 226 Ô 212 LATIN CAPITAL LETTER O WITH CIRCUMFLEX E3 227 Ò 210 LATIN CAPITAL LETTER O WITH GRAVE
EN2B-0092GE51 R0512 68
EXCEL 50/100/500/600/800 MISCELLEANOUS
69
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
E4 228 õ 245 LATIN SMALL LETTER O WITH TILDE E5 229 Õ 213 LATIN CAPITAL LETTER O WITH TILDE E6 230 µ 181 MICRO SIGN E7 231 þ 254 LATIN SMALL LETTER THORN E8 232 Þ 222 LATIN CAPITAL LETTER THORN E9 233 Ú 218 LATIN CAPITAL LETTER U WITH ACUTE EA 234 Û 219 LATIN CAPITAL LETTER U WITH CIRCUMFLEX EB 235 Ù 217 LATIN CAPITAL LETTER U WITH GRAVE EC 236 ý 253 LATIN SMALL LETTER Y WITH ACUTE ED 237 Ý 221 LATIN CAPITAL LETTER Y WITH ACUTE EF 239 ´ 180 ACUTE ACCENT F8 248 ° 176 DEGREE SIGN
Table 27. Character Settings (Eastern Europe)
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
20 32 32 SPACE 23 35 # 35 NUMBER SIGN 24 36 $ 36 DOLLAR SIGN 25 37 % 37 PERCENT SIGN 26 38 & 38 AMPERSAND 27 39 ' 39 APOSTROPHE 28 40 ( 40 LEFT PARENTHESIS 29 41 ) 41 RIGHT PARENTHESIS 2E 46 . 46 FULL STOP 30 48 0 48 DIGIT ZERO 31 49 1 49 DIGIT ONE 32 50 2 50 DIGIT TWO 33 51 3 51 DIGIT THREE 34 52 4 52 DIGIT FOUR 35 53 5 53 DIGIT FIVE 36 54 6 54 DIGIT SIX 37 55 7 55 DIGIT SEVEN 38 56 8 56 DIGIT EIGHT 39 57 9 57 DIGIT NINE 3A 58 : 58 COLON
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Hex
40 64 @ 64 COMMERCIAL AT 41 65 A 65 LATIN CAPITAL LETTER A 42 66 B 66 LATIN CAPITAL LETTER B 43 67 C 67 LATIN CAPITAL LETTER C 44 68 D 68 LATIN CAPITAL LETTER D 45 69 E 69 LATIN CAPITAL LETTER E 46 70 F 70 LATIN CAPITAL LETTER F 47 71 G 71 LATIN CAPITAL LETTER G 48 72 H 72 LATIN CAPITAL LETTER H 49 73 I 73 LATIN CAPITAL LETTER I 4A 74 J 74 LATIN CAPITAL LETTER J 4B 75 K 75 LATIN CAPITAL LETTER K 4C 76 L 76 LATIN CAPITAL LETTER L 4D 77 M 77 LATIN CAPITAL LETTER M 4E 78 N 78 LATIN CAPITAL LETTER N
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
4F 79 O 79 LATIN CAPITAL LETTER O 50 80 P 80 LATIN CAPITAL LETTER P 51 81 Q 81 LATIN CAPITAL LETTER Q 52 82 R 82 LATIN CAPITAL LETTER R 53 83 S 83 LATIN CAPITAL LETTER S 54 84 T 84 LATIN CAPITAL LETTER T 55 85 U 85 LATIN CAPITAL LETTER U 56 86 V 86 LATIN CAPITAL LETTER V 57 87 W 87 LATIN CAPITAL LETTER W 58 88 X 88 LATIN CAPITAL LETTER X 59 89 Y 89 LATIN CAPITAL LETTER Y 5A 90 Z 90 LATIN CAPITAL LETTER Z 5F 95 _ 95 LOW LINE 61 97 a 97 LATIN SMALL LETTER A 62 98 b 98 LATIN SMALL LETTER B 63 99 c 99 LATIN SMALL LETTER C 64 100 d 100 LATIN SMALL LETTER D 65 101 e 101 LATIN SMALL LETTER E 66 102 f 102 LATIN SMALL LETTER F 67 103 g 103 LATIN SMALL LETTER G 68 104 h 104 LATIN SMALL LETTER H
EN2B-0092GE51 R0512 70
EXCEL 50/100/500/600/800 MISCELLEANOUS
71
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
69 105 i 105 LATIN SMALL LETTER I 6A 106 j 106 LATIN SMALL LETTER J 6B 107 k 107 LATIN SMALL LETTER K 6C 108 l 108 LATIN SMALL LETTER L 6D 109 m 109 LATIN SMALL LETTER M 6E 110 n 110 LATIN SMALL LETTER N 6F 111 o 111 LATIN SMALL LETTER O 70 112 p 112 LATIN SMALL LETTER P 71 113 q 113 LATIN SMALL LETTER Q 72 114 r 114 LATIN SMALL LETTER R 73 115 s 115 LATIN SMALL LETTER S 74 116 t 116 LATIN SMALL LETTER T 75 117 u 117 LATIN SMALL LETTER U 76 118 v 118 LATIN SMALL LETTER V 77 119 w 119 LATIN SMALL LETTER W 78 120 x 120 LATIN SMALL LETTER X 79 121 y 121 LATIN SMALL LETTER Y 7A 122 z 122 LATIN SMALL LETTER Z 7E 126 ~ 126 TILDE 80 128 Ç 199 LATIN CAPITAL LETTER C WITH CEDILLA 81 129 ü 252 LATIN SMALL LETTER U WITH DIAERESIS 82 130 é 233 LATIN SMALL LETTER E WITH ACUTE 83 131 â 226 LATIN SMALL LETTER A WITH CIRCUMFLEX 84 132 ä 228 LATIN SMALL LETTER A WITH DIAERESIS 85 133 ů 367 LATIN SMALL LETTER U WITH RING ABOVE 86 134 ć 263 LATIN SMALL LETTER C WITH ACUTE 87 135 ç 231 LATIN SMALL LETTER C WITH CEDILLA 88 136 ł 322 LATIN SMALL LETTER L WITH STROKE 89 137 ë 235 LATIN SMALL LETTER E WITH DIAERESIS
8A 138 Ő 336
LATIN CAPITAL LETTER O WITH DOUBLE ACUTE
8B 139 ő 337 LATIN SMALL LETTER O WITH DOUBLE ACUTE 8C 140 î 238 L A TIN SMALL LE TTER I WITH CIRCUMFLEX 8D 141 Ź 377 LATIN CAPITAL LETTER Z WITH ACUTE 8E 142 Ä 196 LATIN CAPITAL LETTER A WITH DIAERESIS 8F 143 Ć 262 LATIN CAPITAL LETTER C WITH ACUTE
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Hex
90 144 É 201 LATIN CAPITAL LETTER E WITH ACUTE 91 145 Ĺ 313 LATIN CAPITAL LETTER L WITH ACUTE 92 146 ĺ 314 LATIN SMALL LETTER L WITH ACUTE 93 147 ô 244 LATIN SMALL LETTER O WITH CIRCUMFLEX 94 148 ö 246 LATIN SMALL LETTER O WITH DIAERESIS 95 149 Ľ 317 LATIN CAPITAL LETTER L WITH CARON 96 150 ľ 318 LATIN SMALL LETTER L WI TH CARON 97 151 Ś 346 LATIN CAPITAL LETTER S WITH ACUTE 98 152 ś 347 LATIN SMALL LETTER S WITH ACUTE 99 153 Ö 214 LATIN CAPITAL LETTER O WITH DIAERESIS 9A 154 Ü 220 LATIN CAPITAL LETTER U WITH DIAERESIS 9B 155 Ť 356 LATIN CAPITAL LETTER T WITH CARON 9C 156 ť 357 LATIN SMALL LETTER T WITH CARON 9D 157 Ł 321 LATIN CAPITAL LETTER L WITH STROKE 9F 159 č 269 LATIN SMALL LETTER C WITH CARON
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
A0 160 á 225 LATIN SMALL LETTER A WITH ACUTE A1 161 í 237 LATIN SMALL LETTER I WITH ACUTE A2 162 ó 243 LATIN SMALL LETTER O WITH ACUTE A3 163 ú 250 LATIN SMALL LETTER U WITH ACUTE A4 164 Ą 260 LATIN CAPITAL LETTER A WITH OGONEK A5 165 ą 261 LATIN SMALL LETTER A WITH OGONEK A6 166 Ž 381 LATIN CAPITAL LETTER Z WITH CARON A7 167 ž 382 LATIN SMALL LETTER Z WITH CARON A8 168 Ę 280 LATIN CAPITAL LETTER E WITH OGONEK A9 169 ę 281 LATIN SMALL LETTER E WITH OGONEK AB 171 ź 378 LATIN SMALL LETTER Z WITH ACUTE AC 172 Č 268 LATIN CAPITAL LETTER C WITH CARON AD 173 ş 351 L ATIN SMALL LETTER S WITH CEDILLA B5 181 Á 193 LATIN CAPITAL LETTER A WITH ACUTE B6 182 Â 194 LATIN CAPITAL LETTER A WITH CIRCUMFLEX B7 183 Ě 282 LATIN CAPITAL LETTER E WITH CARON B8 184 Ş 350 LATIN CAPITAL LETTER S W I TH CEDILLA BD 189 Ż 379 LATIN CAPITAL LETTER Z WITH DOT ABOVE BE 190 ż 380 LATIN SMALL LETTER Z WITH DOT ABOVE C6 198 Ă 258 LATIN CAPITAL LETTER A WITH BREVE C7 199 ă 259 LATIN SMALL LETTER A WITH BREVE
EN2B-0092GE51 R0512 72
EXCEL 50/100/500/600/800 MISCELLEANOUS
73
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
D0 208 đ 273 LATIN SMALL LETTER D WITH STROKE D1 209 Đ 272 LATIN CAPITAL LETTER D WITH STROKE D2 210 Ď 270 LATIN CAPITAL LETTER D WITH CARON D3 211 Ë 203 LATIN CAPITAL LETTER E WITH DIAERESIS D4 212 ď 271 LATIN SMALL LETTER D WITH CARON D5 213 Ň 327 LATIN CAPITAL LETTER N WITH CARON D6 214 Í 205 LATIN CAPITAL LETTER I WITH ACUTE D7 215 Î 206 LATIN CAPITAL LETTER I WITH CIRCUMFLEX D8 216 ě 283 LATIN SMALL LETTER E WITH CARON DD 221 Ţ 354 LATIN CAPITAL LETTER T WITH CEDILLA DE 222 Ů 366 LATIN CAPITAL LETTER U WITH RING ABOVE E0 224 Ó 211 LATIN CAPITAL LETTER O WITH ACUTE E1 225 ß 223 LATIN SMALL LETTER SHARP S E2 226 Ô 212 LATIN CAPITAL LETTER O WITH CIRCUMFLEX E3 227 Ń 323 LATIN CAPITAL LETTER N WITH ACUTE E4 228 ń 324 LATIN SMALL LETTER N WITH ACUTE E5 229 ň 328 LATIN SMALL LETTER N WITH CARON E6 230 Š 352 LATIN CAPITAL LETTER S WITH CARON E7 231 š 353 LATIN SMALL LETTER S WITH CARON E8 232 Ŕ 340 LATIN CAPITAL LETTER R WITH ACUTE E9 233 Ú 218 LATIN CAPITAL LETTER U WITH ACUTE EA 234 ŕ 341 LATIN SMALL LETTER R WITH ACUTE
EB 235 Ű 368
LATIN CAPITAL LETTER U WITH DOUBLE ACUTE
EC 236 ý 253 L ATIN SMALL LETTER Y WI TH ACUTE ED 237 Ý 221 LATIN CAPITAL LETTER Y WITH ACUTE EE 238 ţ 355 LATIN SMALL LETTER T WITH CEDILLA F8 248 ° 176 DEGREE SIGN FB 251 ű 369 LATIN SMALL LETTER U WITH DOUBLE ACUTE FC 252 Ř 344 LATIN CAPITAL LETTER R WITH CARON FD 253 ř 345 LA TIN SMALL LE TTER R WITH CARON
Table 28. Character Settings (Turkey)
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
20 32 32 SPACE 23 35 # 35 NUMBER SIGN
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Hex
24 36 $ 36 DOLLAR SIGN 25 37 % 37 PERCENT SIGN 26 38 & 38 AMPERSAND 27 39 ' 39 APOSTROPHE 28 40 ( 40 LEFT PARENTHESIS 29 41 ) 41 RIGHT PARENTHESIS 2E 46 . 46 FULL STOP 30 48 0 48 DIGIT ZERO 31 49 1 49 DIGIT ONE 32 50 2 50 DIGIT TWO 33 51 3 51 DIGIT THREE 34 52 4 52 DIGIT FOUR 35 53 5 53 DIGIT FIVE 36 54 6 54 DIGIT SIX 37 55 7 55 DIGIT SEVEN
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
38 56 8 56 DIGIT EIGHT 39 57 9 57 DIGIT NINE 3A 58 : 58 COLON 40 64 @ 64 COMMERCIAL AT 41 65 A 65 LATIN CAPITAL LETTER A 42 66 B 66 LATIN CAPITAL LETTER B 43 67 C 67 LATIN CAPITAL LETTER C 44 68 D 68 LATIN CAPITAL LETTER D 45 69 E 69 LATIN CAPITAL LETTER E 46 70 F 70 LATIN CAPITAL LETTER F 47 71 G 71 LATIN CAPITAL LETTER G 48 72 H 72 LATIN CAPITAL LETTER H 49 73 I 73 LATIN CAPITAL LETTER I 4A 74 J 74 LATIN CAPITAL LETTER J 4B 75 K 75 LATIN CAPITAL LETTER K 4C 76 L 76 LATIN CAPITAL LETTER L 4D 77 M 77 LATIN CAPITAL LETTER M 4E 78 N 78 LATIN CAPITAL LETTER N 4F 79 O 79 L ATIN CAPITAL LETTER O 50 80 P 80 LATIN CAPITAL LETTER P 51 81 Q 81 LATIN CAPITAL LETTER Q
EN2B-0092GE51 R0512 74
EXCEL 50/100/500/600/800 MISCELLEANOUS
75
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
52 82 R 82 LATIN CAPITAL LETTER R 53 83 S 83 LATIN CAPITAL LETTER S 54 84 T 84 LATIN CAPITAL LETTER T 55 85 U 85 LATIN CAPITAL LETTER U 56 86 V 86 LATIN CAPITAL LETTER V 57 87 W 87 LATIN CAPITAL LETTER W 58 88 X 88 LATIN CAPITAL LETTER X 59 89 Y 89 LATIN CAPITAL LETTER Y 5A 90 Z 90 LATIN CAPITAL LETTER Z 5F 95 _ 95 LOW LINE 61 97 a 97 LATIN SMALL LETTER A 62 98 b 98 LATIN SMALL LETTER B 63 99 c 99 LATIN SMALL LETTER C 64 100 d 100 LATIN SMALL LETTER D 65 101 e 101 LATIN SMALL LETTER E 66 102 f 102 LATIN SMALL LETTER F 67 103 g 103 LATIN SMALL LETTER G 68 104 h 104 LATIN SMALL LETTER H 69 105 i 105 LATIN SMALL LETTER I 6A 106 j 106 LATIN SMALL LETTER J 6B 107 k 107 LATIN SMALL LETTER K 6C 108 l 108 LATIN SMALL LETTER L 6D 109 m 109 LATIN SMALL LETTER M 6E 110 n 110 LATIN SMALL LETTER N 6F 111 o 111 LATIN SMALL LETTER O 70 112 p 112 LATIN SMALL LETTER P 71 113 q 113 LATIN SMALL LETTER Q 72 114 r 114 LATIN SMALL LETTER R 73 115 s 115 LATIN SMALL LETTER S 74 116 t 116 LATIN SMALL LETTER T 75 117 u 117 LATIN SMALL LETTER U 76 118 v 118 LATIN SMALL LETTER V 77 119 w 119 L ATIN SMALL LETTER W 78 120 x 120 LATIN SMALL LETTER X 79 121 y 121 LATIN SMALL LETTER Y 7A 122 z 122 LATIN SMALL LETTER Z
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Hex
7E 126 ~ 126 TILDE 80 128 Ç 199 LATIN CAPITAL LETTER C WITH CEDILLA 81 129 ü 252 LATIN SMALL LETTER U WITH DIAERESIS 82 130 é 233 LATIN SMALL LETTER E WITH ACUTE 83 131 âyyy 226 LATIN SMALL LETTER A WITH CIRCUMFLEX 84 132 ä 228 LATIN SMALL LETTER A WITH DIAERESIS 85 133 à 224 LATIN SMALL LETTER A WITH GRAVE 86 134 å 229 LATIN SMALL LETTER A WITH RING ABOVE 87 135 ç 231 LATIN SMALL LETTER C WITH CEDILLA 88 136 ê 234 LATIN SMALL LETTER E WITH CIRCUMFLEX 89 137 ë 235 LATIN SMALL LETTER E WITH DIAERESIS 8A 138 è 232 LATIN SMALL LETTER E WITH GRAVE 8B 139 ï 239 LATIN SMALL LETTER I WITH DIAERESIS 8C 140 î 238 LATIN SMALL LETTER I WITH CIRCUMFLEX 8D 141 ı 305 LATIN SMALL LETTER DOTLESS I
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
8E 142 Ä 196 LATIN CAPITAL LETTER A WITH DIAERESIS 8F 143 Å 197 LATIN CAPITAL LETTER A WITH RING ABOVE 90 144 É 201 LATIN CAPITAL LETTER E WITH ACUTE 91 145 æ 230 LATIN SMALL LETTER AE 92 146 Æ 198 LATIN CAPITAL LETTER AE 93 147 ô 244 LATIN SMALL LETTER O WITH CIRCUMFLEX 94 148 ö 246 LATIN SMALL LETTER O WITH DIAERESIS 95 149 ò 242 LATIN SMALL LETTER O WITH GRAVE 96 150 û 251 LATIN SMALL LETTER U WITH CIRCUMFLEX 97 151 ù 249 LATIN SMALL LETTER U WITH GRAVE 98 152 İ 304 LATIN CAPITAL LETTER I WITH DOT ABOVE 99 153 Ö 214 LATIN CAPITAL LETTER O WITH DIAERESIS 9A 154 Ü 220 LATIN CAPITAL LETTER U WITH DIAERESIS 9B 155 ø 248 LATIN SMALL LETTER O WITH STROKE 9D 157 Ø 216 LATIN CAPITAL LETTER O WITH STROKE 9E 158 Ş 350 LATIN CAPITAL LETTER S WITH CEDILLA 9F 159 ş 351 LATIN SMALL LETTER S WITH CEDILLA A0 160 á 225 LATIN SMALL LETTER A WITH ACUTE A1 161 í 237 LATIN SMALL LETTER I WITH ACUTE A2 162 ó 243 LATIN SMALL LETTER O WITH ACUTE A3 163 ú 250 LATIN SMALL LETTER U WITH ACUTE
EN2B-0092GE51 R0512 76
EXCEL 50/100/500/600/800 MISCELLEANOUS
77
Hex
Dec Char Unicode ISO/IEC 10646-1:2000 Character Name
A4 164 ñ 241 LA TIN SMALL LETTER N WITH TILD E A5 165 Ñ 209 LATIN CAPITAL LETTER N WITH TI LDE A6 166 Ğ 286 LATIN CAPITAL LETTER G WITH BREVE A7 167 ğ 287 LATIN SMALL LETTER G WITH BREVE A8 168 ¿ 191 INVERTED QUESTION MARK B5 181 Á 193 LATIN CAPITAL LETTER A WITH ACUTE B6 182 Â 194 LATIN CAPITAL LETTER A WITH CIRCUMFLEX B7 183 À 192 LATIN CAPITAL LETTER A WITH GRAVE C6 198 ã 227 LATIN SMALL LETTER A WITH TILDE C7 199 Ã 195 LATIN CAPITAL LETTER A WITH TILDE D2 210 Ê 202 LATIN CAPITAL LETTER E WITH CIRCUMFLEX D3 211 Ë 203 LATIN CAPITAL LETTER E WITH DIAERESIS D4 212 È 200 LATIN CAPITAL LETTER E WITH GRAVE D6 214 Í 205 LATIN CAPITAL LETTER I WITH ACUTE D7 215 Î 206 LATIN CAPITAL LETTER I WITH CIRCUMFLEX D8 216 Ï 207 LATIN CAPITAL LETTER I W I TH DIAERESIS DE 222 Ì 204 LATIN CAPITAL LETTER I WITH GRAVE E0 224 Ó 211 LATIN CAPITAL LETTER O WITH ACUTE E1 225 ß 223 LATIN SMALL LETTER SHARP S E2 226 Ô 212 LATIN CAPITAL LETTER O WITH CIRCUMFLEX E3 227 Ò 210 LATIN CAPITAL LETTER O WITH GRAVE E4 228 õ 245 LA TIN SMALL LETTER O WITH TILDE E5 229 Õ 213 LATIN CAPITAL LETTER O WI TH TILDE E6 230 µ 181 MICRO SIGN E9 233 Ú 218 LATIN CAPITAL LETTER U WITH ACUTE EA 234 Û 219 LATIN CAPITAL LETTER U WITH CIRCUMFLEX EB 235 Ù 217 LATIN CAPITAL LETTER U WITH GRAVE EC 236 ì 236 LATIN SMALL LETTER I WITH GRAVE ED 237 ÿ 255 LATIN SMALL LETTER Y WITH DIAERESIS F8 248 ° 176 DEGREE SIGN
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
Procedure 1. In Windows, click Start>Settings>Control panel.
2. Double-click Regional and Language Options. The Regional and Language Options dialog box displays.
3. On the Regional Options tab under Standards and formats, select the language for displaying standards and formats such as format numbers, currencies, dates, and time.
4. Under Location, select the matching country for supporting you with local services such as news and weather.
5. Select the Languages tab.
6. If you want to support Arabic, Armenian, Georgian, Thai, Hebrew, Indic, Thai and Vietnamese languages, check Install files for complex script and right- to-left languages (including Thai).
7. If you want to support Japanese, Chinese and Korean languages, chec k Install files for East Asian languages under Supplemental language support.
8. Make sure that you have the necess ary harddisk space indicated in the message boxes displayed. Close the message boxes by clicking OK.
After confirming by clicking OK or Apply, the additional files will be installed on
the PC.
EN2B-0092GE51 R0512 78
EXCEL 50/100/500/600/800 MISCELLEANOUS
79
9. After successful installation, repeat steps 1 through 5, and then proceed with step 10.
10. Click Details button. The Text Services and Input Languages dialog box displays. The actual input language is selected in Default input language and the corresponding installed services are highlighted in bold under Installed services.
11. To add a new input language, click the Add button. The Add Input Language dialog box displays.
12. In Input Language, select the language, in this case Italian. Check/select optional settings for Keyboard layout/IME, Handwriting recognition and Speech if available and if desired.
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
13. Click OK. The new language and its services are added to the Installed Services list and can be selected as default input language.
14. In Default input language, select the language, in this case Italian.
15. In the Text Services and Input Languages dialog box, click the Language bar button. The Language Bar Settings dialog box displays. Check Show the
Language bar on the desktop and Show additional Language bar icons in the task bar. These enabled options allow toggling between several
language(s) on the desktop and in the taskbar after the customization is finished.
EN2B-0092GE51 R0512 80
EXCEL 50/100/500/600/800 MISCELLEANOUS
81
16. Click OK.
17. In the Text Services and Input Languages dialog box, click OK, and then select the Advanced tab in the Regional and Language Options dialog box.
18. In Language for non-Unicode programs, select the language, in this case Italian.
19. Click OK to save all settings. The Advanced message box may display.
20. Follow the instructions described in the message box, and close the message box. The Change Regional Options message box displays.
EN2B-0092GE51 R0512
MISCELLEANOUS EXCEL 50/100/500/600/800
21. Restart the PC by clicking Yes. After restart, the new language, in this case Italian is added to the Language bar.
22. Check the language in the Language bar.
23. For selecting the language in CARE, COACH, XL-Online respectively in COACH Online, please refer to the corresponding Online Help and/or PDF documentation.
EN2B-0092GE51 R0512 82
EXCEL 50/100/500/600/800 INDEX
83

INDEX

alarms
alarm definition, 17 alarm delay, 17 alarm handling, 45 alarm hysteresis, 21 alarm status, 45 alarm suppression, 17, 18, 33, 46, 50 alarm type, 16, 17 alarms sent across the system bus, 51 automatic/manual alarms, 30, 31, 45 data storage, 51 point alarms, 17, 31, 45 specifying a maintenance alarm, 27, 45 specifying alarm limit values, 19 system alarm Totalizer Overflow, 25 system alarms, 46 user program alarms, 51
attributes
Access, 22 Access Level, 13 Acknowledge Alarm, 13 Active State, 14, 16, 20, 28, 45 Alarm Delay, 15 Alarm Hysteresis, 21, 23 Alarm Status, 13, 15, 16, 31, 56 Broadcast Hysteresis, 23 Cycle Count, 18 Delay Time Switching Down, 18 Delay Time Switching Up, 18 Descriptor, 19 Engineering Unit, 19 Feedback Delay, 19 High Alarm Limit, 20 High Warning Limit, 20 Hours Run, 20 Hours Run Log, 20 I/O Characteristic, 25 Interval Count, 24, 45 Interval Limit, 25 Last Change, 26 Last Maintained, 20 Low Alarm Limit, 20 Low Warning Limit, 20 Maintenance Alarm, 15, 16, 21, 27 Maintenance Interval, 45 Manual Value, 13, 56 Max. Limit, 16, 31 Min. Limit, 16, 31 Motor Run Time, 29 Network Variable, 28 Normally Open/Normally Closed, 16, 24, 28, 45 Off Phase, 29 Operating Mode, 13, 15, 16, 27, 29, 30, 56 Output Type, 31 Point in Alarm, 17 Pulse Duration, 32 Remote, 30 Scaling Factor, 31, 32 Sensor Offset, 33
Status Text, 11, 24 Subtype, 31 Suppress Alarm, 15 Suppress Point, 33 Switch Down, 29 Switching Down, 33 Switch-On Counter, 34 Technical Address, 11, 34 Totalizer, 16 Trend Cycle, 35 Trend Hysteresis, 22, 36 Trend Logging, 34 User Address, 36 Value, 12, 13, 36, 56 Write Protection, 37
communication, 53
Excel IRC, 56 PC communication, 56 remote communication, 56 system bus, 53
data-points, 9
flexible data-points, 10, 13, 18, 20, 24, 28, 29, 31, 32,
33, 36 global data-points, 11 mapped data-points, 12, 28, 34 physical data-points, 9 pseudo data-points, 10
Distributed I/O modules, 30
initialization, 55 XFL522, 30 XFL524, 30 XFR522, 55 XFR522A, 55 XFR524, 55 XFR524A, 55
MODEMFAQ, 59 pseudo data-points, 10
pseudo analog points, 11, 19, 21, 27, 35, 45 pseudo digital points, 11, 15, 16, 45 pseudo point multistage data-points, 11 pseudo totalizer inputs, 11
remote communication
direct modem connection, 56 disabling dial-out, 56
test mode, 53 time programs, 41
annual program, 42 daily program, 41 generating a time program, 43 special day list, 43 structure of, 41 TODAY function, 43 weekly program, 42
user addresses, 36
access via, 10 assignable to each of 384 data-points, 19 default user addresses, 53 number of switching points per, 42 relationship between user addresses and descriptors, 19
EN2B-0092GE51 R0512
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Straße 17 D-71101 Schönaich Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany EN2B-0092GE51 R0512
Loading...