IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #52750
11/04/05 Revision:
A
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing
fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following
the recommendations of the current edition of the National
Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reaching
the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over
time. For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system,
crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local
manufacturer's representative. Maintenance should be
scheduled monthly or as required by National and/or local
fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of
all inspections should be kept.
PrecauLarge.PMD 01/10/2005
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F
RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the
useful life of the system's standby batteries and the electronic components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in
an environment with a nominal room temperature of 15-27°
C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of 93 ±2%
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is completely immune from lightning transients and interferences,
proper grounding will reduce susceptibility. Overhead or out-
side aerial wiring is not recommended, due to an increased
susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static-suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can ra-
diate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested
and found to comply with the limits for class A computing
device pursuant to Subpart B of Part 15 of FCC Rules,
which is designed to provide reasonable protection against
such interference when operated in a commercial environment. Operation of this equipment in a residential area is
likely to cause interference, in which case the user will be
required to correct the interference at their own
expense.
PrecauLarge.PMD 01/10/2005
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
1.1: Features and Options...................................................................................................................................12
1.2.1: Current Availability...........................................................................................................................15
1.3: Controls and Indicators ...............................................................................................................................16
2.7: UL Power-limited Wiring Requirements ....................................................................................................35
2.8: Digital Communicator.................................................................................................................................36
3.1: Programming Data Entry ............................................................................................................................42
3.2: User Programming ......................................................................................................................................43
3.5: Programming and Passwords ......................................................................................................................44
3.6.2: Point Program....................................................................................................................................48
3.6.2.2.3 Edit Module Screen for Monitor Module .............................................................................59
3.6.2.2.4 Edit Module Screen for Control Modules ............................................................................68
3.6.3: Zone Setup.........................................................................................................................................75
3.6.5: System Setup.....................................................................................................................................80
3.6.5.3.1 Time .....................................................................................................................................82
3.6.5.3.2 Date ......................................................................................................................................83
3.6.5.3.3 Clock Format ........................................................................................................................83
3.6.5.3.4 Daylight Savings Time .........................................................................................................83
3.6.5.5.2 Type ......................................................................................................................................88
3.6.5.5.4 Auto Silence .........................................................................................................................89
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) .........................................89
3.6.5.5.6 Zone ......................................................................................................................................91
3.6.11: Clear Program .................................................................................................................................117
3.6.12: Program Check................................................................................................................................118
3.7.1: Disable Point .....................................................................................................................................121
3.7.3: Program Check..................................................................................................................................123
3.7.6: Zone Setup ........................................................................................................................................126
4.1: Panel Control Buttons .................................................................................................................................128
4.2: LED Indicators ............................................................................................................................................129
4.3: Normal Operation........................................................................................................................................130
4.7: Process Monitor Operation..........................................................................................................................134
4.20: Special System Timers..............................................................................................................................138
4.22.1: System Point ...................................................................................................................................141
MS-9200UDLS P/N: 52750:A 11/04/05 7
Table of Contents
4.22.2: Zones ...............................................................................................................................................142
4.22.8: Program Check................................................................................................................................146
4.22.12: Central Station...............................................................................................................................148
4.22.13: Service Terminal............................................................................................................................149
7.2: Calculating the AC Branch Circuit..............................................................................................................163
7.3: Calculating the System Current Draw.........................................................................................................164
7.4.2: Selecting and Locating Batteries.......................................................................................................166
APPENDIX A: Software Zones ............................................................................................................................167
APPENDIX E: HVAC Control .............................................................................................................................179
E.1: Control Module Operation .........................................................................................................................179
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9200UDLS PN 52750:A 11/04/059
TB8
GND
DTR
RCV
T
X
TB8 (option to DB-25)
5 4 3 2 1
9 8 7 613 12 11 10
25 24 23 22 21 20 19 18 17 16 1 5 14
TB8
GND
DTR
RCV
T
X
White
Green
Black
Red
9 8 7 6
DB9F
5 4 3 2 1
OR
(Supervi sed, Power Limited)
NAC #1 & #2
Notification Appliance Circuits
Style Z (Class A)
+
NAC #2
+
using NA CKEY card.
NAC #1
2.5 am ps max. per circuit .
JP6 config ured for Class A
+
+
B
-
A
-
A
+
+
B
+
TB4
B
-
A
-
A
+
+
B
+
TB3
BA
SHIELDSLCSLC
shield
A
A
-
B
EIA-232
(nonsupervised)
to printer or
Notification Appliance Circuits
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
Upload/Download Utility.
For EDP- listed equipm ent or
personal computer
personal computer with FACP
50 foot maximu m within same room.
1 Fixed Trouble Relay
Nonsupervised relay co ntacts
Contact Ratings:
2.0 amp s @ 30 VDC (resi stive)
++
+
+
2
1
0.5 amp s @ 30 VAC (resis tive)
ELRs 4.7K, ½W
2 Programmable Relays &
++
NAC #4 NAC #2
++
for Class B using NACKEY card.
NAC #1 NAC # 3
(See Style Z ill ustrated near right edge of boar d).
(Special Appli cation) 2.5 amps max. pe r circuit. JP6 conf igured
SLC Loop
supervised)
(power-l imited,
ACS (EIA-485)
to ACS Annunc.
Contacts sh own below in normal
conditio n (AC power with no alar m,
trouble or supervisory acti vity).
++
+
+
4
3
OR
(supervised)
Manual for detailed
information on wiring
Refer to the SLC Wiring
TERM
(EIA-485)
to LCD-80F
NC NO C
A Fail Safe Trouble
relay switches to t he
NO position during
trouble con ditions and
2
1
-
SLCSLC
+
B+ A + B- A- A B
B
+
for Styl e 4, 6 and 7.
addressabl e devices
-
ACS
+
I
-
N
-
T
U
O
I
+
N
T
+
O
U
OUT+ IN+ OUT- IN-
Trouble
TB6TB8TB9TB10
Alarm*
NO NC C NO NC C
NO NC C NC NO CNO NC C
TB5
under loss of all power.
NO NC C
Supervisory*
(*)Factory default rela y programming
NAC
Number
B
-
B
-
B
+
2244
B
+
TB4TB7
1
B
-
-
B
33
B
+
B
+
1
-
TB3
-
+
TB2
- -
+ +
TB1
JP4
123
Cut this jumper to enable
Supervisory relay when
JP2
RELAY 2
RELAY 1
RELAY 3
NAC 2 CLASS A
NAC 2 & 4 CLASS B
B+ A+ A- B-B+ A+ A- B-
1B+ 3B+ 3B- 1B- 2B+ 4B+ 4B- 2B-
NAC 1 & 3 CLASS B
Config ure NACs for Cl ass A or
JP6
+ -
REMOTE PW R
SUPPLY SYN CNAC 1 CLAS S A
RST
+ 24V -
POWER
+ 24V -
POWER
NON-RST
4XTM F
J6
J5
4XTMF module is installed
JP7
REMOVE TO
DISABLE GND. FLT.
Class B wi ring using NACKEY
card. Factory defaul t is Class B.
J7
JP3
4XTMF
CUT TO
MONITOR
Flash Memo ry Load Enable Swit ch.
UP is no rmal posi tion for switch.
DOWN position allows loading of
factory software upg rades.
SW1
To disable ground fault detection,
remove jump er/shunt from J P7
KISSOFF
SEC. ACTIVE
J13J12
Cut this jumper to supervise
the 4XT MF module when
installed (see J5 & J6)
PRI. ACTIVE
SEC. P HONE LINE
PRI. PHONE LINE
(Nonpower-Limited)
PS2 Keyboard InterfaceDACT Phone Line Jacks
I/F
KEYPAD
J4
Remove this jumper
to disable the FACP
battery cha rger when
using external charger.
LCD DISPLAY
JP5
CAUTION!
HIGH VOLTAGE
J11
TRANSFORMER 2
J1
TB11
TRANSFORMER 1
MINI DIN
J3
KEYBOARDCONN.
- +
J9
BATTE RY
Battery
nonpower-l imited
24 VDC, supe rvised,
18 Amp Hour maximum
HOT NEUT EARTH
120 VAC, 60 HZ, 3.0 amps
220/240 VAC, 50 Hz, 1.5 amps
J10
only
Transformer 2 Connector
Removing Ground
Basic System Connections
Remote Synchronization Output
Special Applic ation Power
24 VDC filtered, supervised and power-limited.
0.040 amps maximum, follows NAC1 control circuit.
Requires 4.7kohm End-of-Line resistor.
Special Application DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay A77-716B
Nonresettable or Resettable Power
Jumper selectable by JP4, 24 VDC filtered,
power-li mited (0.500 amps maximum)
Supervision required. Nonresettable
Power suitable for powering annunciators,
Resett able Power sui table for po wering
Resettable Power - 24 VDC filtered, power-limited
(0.500 amps ma ximum) to smoke detec tors (IDC).
Supervision required.
smoke detectors..
UL/NFPA Sty le /C la ss
Important!
voids
Fault Disable Jumper JP7
identifications for circuits.
Remove jumper JP7
with the approval of the AHJ
(Authority Having Jurisdiction)
Transformer 1 Connector
CAUTIO N! HIGH VOLTAGE
10MS-9200UDLS PN 52750:A 11/04/05
Peripheral Devices and Their Documents:
ACS (EIA-485)
Annunciators
AFM-16ATF &
TERM (EIA-485)
Annunciators
SLC Loop
AFM-32AF
Doc. #15970
LCD-80F
Doc. #51338
Addressable Devices and SLC Wiring
AFM-16AF
Doc. #15210
Doc. #51309
ACS Series
51480
ACM-8RF
Doc. #50362
LDM-32F
Doc. #50055
92udperi.cdr
Battery Connector
CHG-120F Charger
Doc. #50888
CHG-75 Charger
Doc. # 51315
MS-9200UDLS PN 52750:A 11/04/0511
Product DescriptionFeatures and Options
SECTION 1Product Description
The Fire-LiteMS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and
DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This
compact, cost effective, intelligent addressable control panel has an extensive list of
powerful features. The combination of Fire-Lite’s newer series devices and legacy 300
Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection
technology. The power supply and all electronics are contained on a single circuit
board housed in a metal cabinet, providing a complete fire control system for most
applications. Optional modules, which plug into the main circuit board, are available
for special functions. Available accessories include LED, graphic and LCD
annunciators, reverse polarity/city box transmitter, local and remote upload/download
software and remote power expansion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central
Station via the public switched telephone network. It also allows remote and local
programming of the control panel using the PK-CD Upload/Download utility. In
addition, the control panel may be programmed or interrogated off-site via the public
switched telephone network. Any personal computer with Windows
and compatible modem with a speed of 14.4 kbps or faster and Fire•Lite Upload/
Download software kit PK-CD, may serve as a Service Terminal. This allows
download of the entire program or upload of the entire program, history file, walktest
data, current status and system voltages.
™
95 or greater,
MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS and the MS9200UDLSE FACPs (Fire Alarm Control Panels).
Inventory
When the MS-9200UDLS shipment is received, check to make certain that all parts
have been included in the shipment. The MS-9200UDLS shipment should consist of
one of each of the following:
main circuit board with display
backbox with door
plastic bag containing screws, cables, key, etc.
manual
1.1 Features and Options
•New LiteSpeed™ polling protocol for faster SLC response time
•SLC operates up to 10,000 ft. (3,000 m) with twisted, unshielded wire (refer to
"Wire Requirements" on page 178)
•Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
•198 addressable device capacity (99 detectors and 99 control/relay/monitor
modules)
•99 software zones
•Onboard NACs (Notification Appliance Circuits) which can be configured as
four Style Y (Class B) or two Style Z (Class A) circuits - special application
•3.0 amps total power for NACs and 24 VDC special application auxiliary power
outputs expandable to 6.0 amps
•3.6 amps total system power (includes battery charger) expandable to 6.6 amps
•Two programmable relay outputs and one fixed trouble relay
•Synchronization output for remote power supply applications (special
application)
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp
Maximum Battery Charger Capacity: 18 Amp Hour (MS-9200UDLS cabinet holds
maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120
Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F
Battery Box.
Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the
FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length or 3,000 ft.
(900 m) untwisted, unshielded pair length
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit requires ferrite bead per FCC requirement
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB3 & TB4
Each Terminal Block provides connections for two Style Y (Class B) or one Style Z
(Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs
Style is configured using NACKEY card plugged into JP6 on main board
Special Application full-wave rectified power
Power-limited circuitry
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC
Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.6 on page 32 for information on power-limited relay circuit wiring
Nonresettable Special Application Power (24 VDC Nominal) TB1, Terminals 1 (+) & 2 (-)
Jumper selectable (JP4) for conversion to resettable power output
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 0.5 amps (see Figure 1.1)
Power-limited circuit requires ferrite bead per FCC requirements
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC
nominal) - TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 0.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit requires ferrite bead per FCC requirements
Refer to the Device Compatibility Document for listed compatible devices
Remote Sync Output - TB2
Remote power supply synchronization output
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit requires ferrite bead per FCC requirements
The following figure illustrates the maximum current that is possible for each panel
circuit and the total current available from the FACP with optional second transformer.
Note: If NACs are
configured as two Style Z
(Class A) circuits, each
circuit can handle 2.5
amps maximum.
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability
6.0 amps with optional second
XRM-24(E) transformer.
3.0 amps max. with only
standard transformer installed.
owerdist9200ud.cdr
MS-9200UDLS PN 52750:A 11/04/0515
Product DescriptionControls and Indicators
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high
viewing angle LCD display. The
display includes a long life LED
backlight that remains illuminated. If
AC power is lost and the system is
not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•AC Power (green)
•Fire Alarm (red)
•Supervisory (yellow)
•Trouble (yellow)
•Maintenance/presignal (yellow)
•Alarm Silenced signals (yellow)
•Disabled (yellow)
•Battery fault (yellow)
•Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD
display and LED indicators as listed above. The key panel, which is visible with the
cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a
telephone keypad.
HONEYWELL LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 012102
Function keys:
•Acknowledge/Step
•Alarm Silence
•Drill
•Reset (lamp test)
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
2
1
4
GHI
78 9
PRS
*
QZ
ABC
5
JKL
TUVWXY
0
RECALL
3
DEF
6
MNO
#
-/.
1
CLR
ESC
MODE
st
EVENT
AC POWER
FIRE ALARM
SUPERVISORY
TROUBLE
ENTER
MAINTENANCE
ALARM
SILENCED
DISABLED
BATTERY
ACK/STEP
ALARM
SILENCE
DRILL
HOLD 2 SEC
RESET
GROUND
•1st Event key
•Clear key
Figure 1.2 Membrane/Display Panel
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and
supervisory conditions.
9600kypd.cdr
16MS-9200UDLS PN 52750:A 11/04/05
CircuitsProduct Description
1.4 Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. The SLC loop,
configurable for NFPA Style 4, 6 or 7, provides communication to addressable
detectors, monitor (initiating device) and control (output device) modules. Refer to the
Reference
Manual
SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
•Special Application Power
24 VDC Resettable (smoke detector power) output - 0.5 amps maximum
24 VDC Nonresettable or Resettable power output - 0.5 amps maximum
•24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY
card in JP6, are provided with various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The
fixed fail-safe relay monitors system trouble and the two programmable relays are
factory default programmed for system alarm and system supervisory. Contacts are
rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The
programmable relays can be programmed for the following operations:
•fire alarm
•trouble
•supervisory
•supervisory auto-resettable
•DACT communication failure
•process monitor
•process monitor auto-resettable
•hazard alert
•medical alert
•AC loss
1.5 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are
labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two
telephone line active red LEDs are provided as well as a green Kissoff LED. The
integral digital communicator provides the following functions:
•Line Seizure: takes control of the phone lines disconnecting any premises phones
•Off/On Hook: performs on and off-hook status to the phone lines
•Listen for dial tone: 440 Hz tone typical in most networks
•Dialing the Central Station(s) number: default is Touch-Tone
rotary
•For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s).
The frequency and time duration of the tone(s) varies with the transmission
format. The control panel will adjust accordingly.
•Communicate in the following formats:
12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
®
, programmable to
MS-9200UDLS PN 52750:A 11/04/0517
Product DescriptionComponents
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary
components and wiring interface connectors. The 4XTMF option module plugs in and
is mounted to the main circuit board.
See Page
Cabinet
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour).
Ample knockouts are provided for system wiring. Also available is an optional dress
panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for
Canadian installations). The dress panel must be installed to meet FM requirements.
Transformer Assembly
Optional
XRM-24(E)
One 100VA transformer is provided standard
with the panel (3.6 amps maximum). An
optional 100 VA transformer XRM-24
Standard
XRM-24(E)
(XRM-24E for the MS-9200UDLSE) is
available to provide maximum system and
accessory power (6.6 amp total).
9200xfor.cdr
Batteries
Battery Cable P/N 75287
The MS-9200UDLS cabinet provides space
for two batteries (up to 18 Amp Hour).
-
Batteries larger than 18 Amp Hour require an
external charger such as the CHG-75 or
+
+
-
CHG-120F and a UL listed battery box such
as the BB-55F. Batteries must be ordered
separately.
9200batt.cdr
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal)
of each detector. Each detector responds to an SLC address that is set in the detector
head using built-in rotary decimal switches. The maximum address cannot exceed
address 99. Note that a blinking LED on an intelligent detector indicates
communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface
Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible
with older 300 Series devices. If a mix of old and new series devices are installed on
the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the
SLC Wiring Manual for a list of compatible addressable detectors.
18MS-9200UDLS PN 52750:A 11/04/05
ComponentsProduct Description
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface
between the control panel and conventional notification and initiating devices. Each
module can be set to respond to an address with built-in rotary switches. The maximum
address cannot exceed address 99. Note that a blinking LED on an addressable module
indicates communication between the module and the control panel.
Reference
Manual
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface
Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible
with older 300 series devices. If a mix of old and new series devices are installed on the
same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC
Wiring Manual for a list of compatible addressable modules. Refer to the Device
Compatibility Document for a list of approved conventional notification and initiating
devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the
MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99.
Refer to the SLC Wiring Manual for a list of compatible addressable devices.
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module
documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada.
An ELR, which is supplied with each module and fire alarm control panel, is mounted
to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision
of a monitor and control module circuit.
MS-9200UDLS PN 52750:A 11/04/0519
Product DescriptionOptional Modules
1.7 Optional Modules
The MS-9200UDLS main circuit board includes option module connectors for the
following module:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter,
alarm and trouble reverse polarity. It includes a disable switch and disable trouble
LED. A jumper on the module is used to select an option which allows the reverse
polarity circuit to open with a system trouble condition if no alarm condition exists.
The module plugs into connectors J5 and J6 which are located near the right edge the
main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main
circuit board, must be cut to allow supervision of the module.
1.8 Accessories
1.8.1 PK-CD Programming Utility
The PK-CD Programming Utility can be used to program an MS-9200UDLS directly
from most IBM compatible computers, including laptops and portables, equipped with
a serial port. MS-9200UDLS program files can also be created and stored on the PC
and then downloaded to the control panel. The PK-CD Kit includes the MS9200UDLS Windows-based Programming Utility software on CD-ROM with on-line
help file. A serial cable (P/N: PRT/PK-CABLE), which must be purchased separately,
is required for connection of the PC to the RS-232 (PC/Printer) terminals at TB8 of the
MS-9200UDLS main circuit board. Refer to the illustration on page 10 and the section
titled "Printer/PC" on page 40, for the location and connections to this terminal.
1.8.2 Dress Panel
An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC
for Canadian installations). The dress panel restricts access to the system wiring while
allowing access to the key panel. A ground strap must be connected between the stud
on the inside of the dress panel and the ground stud in the backbox. The dress panel
must be installed to meet FM requirements.
dp9200udls.cdr
20MS-9200UDLS PN 52750:A 11/04/05
AccessoriesProduct Description
1.8.3 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the
CHG-75 Battery Charger. The battery box, which is red and is provided with
knockouts, was designed specifically to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 25 AH batteries, two 60 AH
batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two
25 AH or one 60 AH battery may also be housed in the battery box.
1.8.4 Battery Charger
1.8.4.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS9200UDLS FACP. The FACP battery charger must be disabled, by removing
jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be
housed in the BB-26 battery box. Larger batteries and the charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the CHG-75 Manual for additional information.
Reference
Manual
1.8.4.2 CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the
MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing
jumper JP5, when using the CHG-120F. The batteries and charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Note that when using the BB-55F for housing the charger and batteries
greater than 25AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual
for additional information.
MS-9200UDLS PN 52750:A 11/04/0521
Product DescriptionAccessories
1.8.5 Annunciators
ACS Series LED Zone Type Annunciators
The ACS Series Annunciators remotely display alarm and trouble status as well as
system status. In addition, they can provide remote Acknowledge, Silence, Reset and
Drill functions. For more detailed information, refer to the appropriate annunciator
manual. Following is a list of annunciators which can be used with the MS-
Reference
Manual
9200UDLS.
•ACM-16ATF
*
Annunciator Control Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder. It also has switches for
FACP Acknowledge, Silence, Reset and Drill. It has rotary address switches and
will accept up to three AEM-16ATF Expanders. In Canada, this module must be
used to annunciate the fire alarm input points/zones only.
•AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs
•AFM-16ATF
*
Annunciator Fixed Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble
LED, an On Line/Power LED and a local piezo sounder. It also has switches for
FACP Acknowledge, Silence, Reset and Drill. It is fixed at address ‘1.’ In
Canada, this module must be used to annunciate the fire alarm input points/zones
only.
•ACM-32AF
*
Annunciator Control Module annunciates 32 alarm zones with 32
red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED
and a local piezo sounder. It also has a switch for local piezo silence. It has
rotary address switches and will accept one AEM-32AF Expander. In Canada,
this module must be used to annunciate the fire alarm input points/zones only.
•AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32
red LEDs
•AFM-16AF
*
Annunciator Fixed Module annunciates 16 alarm zones with 16 red
alarm LEDs. In addition, it has a System Trouble LED, an On Line/Power LED
and a local piezo sounder. It also has a switch for local piezo silence. It is fixed
at address ‘1.’ In Canada, this module must be used to annunciate the fire alarm
input points/zones only.
•AFM-32AF
*
Annunciator Fixed Module annunciates 32 alarm zones with 32 red
LEDs. In Canada, this module must be used to annunciate the fire alarm input
points/zones only.
* In Canada, the color red must be used to indicate active alarm inputs. Yellow
indicates supervisory, burglary or trouble signals. Green indicates the presence of
power, or an activated output.
22MS-9200UDLS PN 52750:A 11/04/05
Getting StartedProduct Description
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is a compact 80-character backlit LCD remote fire
annunciator that is capable of displaying English language text. It mimics the display
on the control panel and will annunciate device type, point alarm, trouble or
supervisory condition, zone assignment plus any custom alpha labels programmed into
the FACP. The annunciator also provides system status LEDs to display AC Power,
Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the LCD80F is capable of remotely performing critical system functions such as Acknowledge,
Silence, Reset and Drill.
Communications between the control panel and the annunciator is accomplished over a
serial interface employing the EIA-485 communication standard. Up to 32 LCD-80F
annunciators may be connected to the EIA-485 circuit. The annunciators may be
powered from the host FACP or a remote UL listed filtered power supply such as the
Reference
Manual
Reference
Manual
FCPS Series. For more detailed information, refer to the LCD-80F manual.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and
LDM-E32F expander modules, are used to provide an interface to a custom graphic
LED annunciator. The master module provides power and control for a maximum of
three expander modules. The LDM-32F and LDM-E32F have output connectors which
are used to drive lamps or LEDs and input connectors which are used for remote switch
functions. Refer to the LDM Series Lamp Driver Modules manual for a complete
description.
1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS9200UDLS on-line:
•Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page
27)
•Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
•Enter Autoprogramming (refer to "Autoprogram" on page 47)
•Resolve Programming Conflicts
•Go to Point Program to Enter Specific Data (refer to "Point Program" on page
48). Use the right and left arrow keys to navigate between devices.
MS-9200UDLS PN 52750:A 11/04/0523
Product DescriptionTelephone Requirements and Warnings
1.10Telephone Requirements and Warnings
1.10.1Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the
telephone line. Excessive RENs on the telephone line may result in the devices not
ringing in response to an incoming call. In most, but not all areas, the sum of the RENs
should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to
determine the maximum REN for the calling area.
1.10.2Digital Communicator
Before connecting the control panel to the public switched telephone network, the
installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Note: This equipment complies with Part 68 of the FCC rules and the
requirements adopted by the ACTA. On the inside of the FACP door is a
label that contains, among other information, a product identifier in the
format US:AAAEQ##TXXXX. If requested, this number must be
provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an
emergency situation. It must be able to do this even if other equipment (telephone,
answering system, computer modem, etc.) already has the telephone line in use. To do
so, alarm dialing equipment must be connected to a properly installed RJ31X jack that
is electrically in series with and ahead of all other equipment attached to the same
telephone line. If there are any questions concerning these instructions, consult the
telephone company or a qualified installer about installing the RJ31X jack and alarm
dialing equipment. Refer to "Digital Communicator" on page 36 for an illustration of
the proper installation of this equipment.
Important! The DACT must not
per requirements of UL 864 9th Edition.
24MS-9200UDLS PN 52750:A 11/04/05
be used to dial a phone number that is call-forwarded
Telephone Requirements and WarningsProduct Description
1.10.3Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue
services and/or make changes in its facilities, services, equipment or procedures which
may affect the operation of this control panel. However, the telephone company is
required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company
reserves the right to temporarily discontinue service. Advance notification will be
provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any
problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR
PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the
same telephone line.
The control panel must be connected to the public switched telephone network
upstream (as first device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted
by ACTA. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular
jack that is also compliant.
MS-9200UDLS PN 52750:A 11/04/0525
Product DescriptionTelephone Requirements and Warnings
1.10.4For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective,
operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the
equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must
also be installed using an acceptable method of connection. The customer should be
aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company
cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of
the power utility, telephone lines and internal metallic water pipe system, if present, are
connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the
appropriate electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an
indication of the maximum number of terminals allowed to be connected to a telephone
interface. the termination of an interface may consist of any combination of devices
subject only to the requirement that the sum of the REN of all devices does not exceed
5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio
noise emissions from digital apparatus set out in the Radio Interference Regulations of
the Canadian Department of Communications.”
IC Certificate Number:
Ringer Equivalence Number (REN): 1.3B
Load Number: 2
26MS-9200UDLS PN 52750:A 11/04/05
Mounting BackboxInstallation
SECTION 2Installation
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using
two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The
key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a
clean, dry, vibration-free area where extreme temperatures are not encountered. The
area should be readily accessible with sufficient room to easily install and maintain the
panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with
the hinge mounting on the left. Determine the number of conductors required for the
devices to be installed. Sufficient knockouts are provided for wiring convenience.
Select the appropriate knockout(s) and pull the conductors into the box. All wiring
should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Mounting Backbox
The circuit board contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any boards so that static charges are removed from
!
the body. Use static suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis
with main circuit board and transformer can be easily removed. Loosen the tow 3/8”
nuts securing the top flanges of the chassis, then slide the chassis up to free it from the
lower tabs. Place the chassis assembly in a safe location until it can be reinstalled in the
backbox.
grounding stud
See Page
Mark and predrill hole in the wall for the center top keyhole mounting bolt
using the dimensions illustrated in Figure 2.3 on page 29
Install center top fastener in the wall with the screw head protruding
Place backbox over the top screw, level and secure
Mark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Install remaining fasteners and tighten
Main Circuit Board on chassis
mounting studs
mounting slots
92udchassisinbox.cdr
Backbox
Figure 2.1 MS-9200UDLS Chassis Removal
MS-9200UDLS PN 52750:A 11/04/0527
InstallationMounting Transformer
2.2 Mounting Transformer
One XRM-24(E) transformer is supplied standard with the control panel. An optional
second XRM-24(E) transformer can be ordered and installed to provide maximum
system power. Install the transformers in the locations indicated in the following
illustration.
1. When the location is dry and free of construction dust, install the chassis/
transformer/circuit board assembly.
2. Mount the chassis to the backbox by aligning the two mounting tabs with the
slots in the backbox, then position the two mounting hole tabs over the studs with
nuts located in the upper portion of the backbox.
3. Slide the tabs located on the bottom of the chassis into the mounting slots in the
backbox by pressing the chassis down.
4. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32)
at the top, and to ensure proper grounding, use a 3/8” nut driver or socket.
5. If the main circuit board is not already attached to the chassis, install it by
positioning the ten mounting holes over the studs on the chassis and secure with
the supplied screws.
6. Connect the Standard XRM-24 Transformer plug to Transformer 1 Connector
J10 on the FACP main circuit board
7. Connect the Optional XRM-24 Transformer plug to Transformer 2 Connector J11
on the FACP main circuit board.
8. Complete the installation as detailed in the following sections.
Optional XRM-24 Transformer
Standard XRM-24 Transformer
Mounting Studs
Mounting Slot
Figure 2.2 MS-9200UDLS Main Board/Chassis Installation
28MS-9200UDLS PN 52750:A 11/04/05
Mounting TransformerInstallation
Semi-Flush Mounting
Do not recess box more
than 3.875” into wall to
avoid covering venting
holes on top of box.
9050udencl.cdr
Figure 2.3 MS-9200UDLS Cabinet Mounting
MS-9200UDLS PN 52750:A 11/04/0529
InstallationMounting Transformer
9050udcab.cdr
Figure 2.4 MS-9200UDLS Cabinet Dimensions
30MS-9200UDLS PN 52750:A 11/04/05
Loading...
+ 158 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.