Honeywell MS-9200UDLS, MS-9200UDLSE User Manual

Page 1
PN: 52750:A ECN 05-680
Fire Alarm Control Panel
MS-9200UDLS
MS-9200UDLSE
IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
A
Page 2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control panel with remote notifi­cation capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat de­tectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, com­munications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medi­cation. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main­tenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized profes­sional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 01/10/2005
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for indoor dry opera­tion at 0-49° C/32-120° F RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the elec­tronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recom­mended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications sec­tion for maximum allowable I.R. drop from the specified de­vice voltage.
and at a relative humidity of 93 ±2%
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is com­pletely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or out-
side aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are antici­pated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can ra-
diate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause in­terference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ­ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
PrecauLarge.PMD 01/10/2005
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Page 4
Notes
4 MS-9200UDLS PN 52750:A 11/04/05
Page 5
Table of Contents
SECTION 1: Product Description ........................................................................................................................12
1.1: Features and Options...................................................................................................................................12
1.2: Specifications ..............................................................................................................................................13
1.2.1: Current Availability...........................................................................................................................15
1.3: Controls and Indicators ...............................................................................................................................16
1.4: Circuits ........................................................................................................................................................17
1.5: Digital Alarm Communicator/Transmitter..................................................................................................17
1.6: Components.................................................................................................................................................18
1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................18
1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................19
1.6.3: 300 Series Intelligent Addressable Devices......................................................................................19
1.6.4: Addressable Device Accessories.......................................................................................................19
1.7: Optional Modules........................................................................................................................................20
1.8: Accessories..................................................................................................................................................20
1.8.1: PK-CD Programming Utility ............................................................................................................20
1.8.2: Dress Panel........................................................................................................................................20
1.8.3: Battery Box .......................................................................................................................................21
1.8.4: Battery Charger.................................................................................................................................21
1.8.4.1 CHG-75 Battery Charger ........................................................................................................21
1.8.4.2 CHG-120F Battery Charger ....................................................................................................21
1.8.5: Annunciators .....................................................................................................................................22
1.9: Getting Started.............................................................................................................................................23
1.10: Telephone Requirements and Warnings....................................................................................................24
1.10.1: Telephone Circuitry.........................................................................................................................24
1.10.2: Digital Communicator.....................................................................................................................24
1.10.3: Telephone Company Rights and Warnings.....................................................................................25
1.10.4: For Canadian Applications..............................................................................................................26
SECTION 2: Installation .......................................................................................................
2.1: Mounting Backbox......................................................................................................................................27
2.2: Mounting Transformer ................................................................................................................................28
2.3: Power...........................................................................................................................................................31
2.3.1: AC Power and Earth Ground Connection.........................................................................................31
2.3.2: Battery Power....................................................................................................................................31
2.3.3: Special Application DC Power Output Connection..........................................................................31
2.4: Relays..........................................................................................................................................................32
2.5: Notification Appliance Circuits ..................................................................................................................32
2.5.1: Configuring NACs ............................................................................................................................33
2.5.2: Style Y (Class B) NAC Wiring.........................................................................................................33
2.5.3: Style Z (Class A) NAC Wiring ........................................................................................................34
2.6: Remote Synchronization Output .................................................................................................................34
2.7: UL Power-limited Wiring Requirements ....................................................................................................35
2.8: Digital Communicator.................................................................................................................................36
2.9: Optional Module Installation ......................................................................................................................37
2.9.1: 4XTMF Transmitter Module Installation..........................................................................................38
2.9.2: Printer/PC..........................................................................................................................................40
2.9.3: Digital Communicator and Annunciators .........................................................................................41
2.9.3.1 ACM-8RF Relay Control Module ..........................................................................................41
2.9.3.2 ACS and AFM Series Annunciators .......................................................................................41
SECTION 3: Programming ..................................................................................................................................42
3.1: Programming Data Entry ............................................................................................................................42
3.2: User Programming ......................................................................................................................................43
3.3: Initial Power-up...........................................................................................................................................44
................................27
MS-9200UDLS P/N: 52750:A 11/04/05 5
Page 6
Table of Contents
3.4: Programming Screens Description..............................................................................................................44
3.5: Programming and Passwords ......................................................................................................................44
3.6: Master Programming Level.........................................................................................................................46
3.6.1: Autoprogram .....................................................................................................................................47
3.6.2: Point Program....................................................................................................................................48
3.6.2.1 Detector Programming ............................................................................................................48
3.6.2.1.1 Add Detector ........................................................................................................................48
3.6.2.1.2 Delete Detector .....................................................................................................................49
3.6.2.1.3 Edit Detector ........................................................................................................................49
3.6.2.2 Module Programming .............................................................................................................58
3.6.2.2.1 Add Module .........................................................................................................................58
3.6.2.2.2 Delete Module ......................................................................................................................59
3.6.2.2.3 Edit Module Screen for Monitor Module .............................................................................59
3.6.2.2.4 Edit Module Screen for Control Modules ............................................................................68
3.6.3: Zone Setup.........................................................................................................................................75
3.6.3.1 Enable ......................................................................................................................................75
3.6.3.2 Disable .....................................................................................................................................76
3.6.3.3 Zone 97, 98 and 99 ..................................................................................................................76
3.6.3.4 Zones Installed ........................................................................................................................77
3.6.3.5 Zones Enabled .........................................................................................................................77
3.6.3.6 Zones Disabled ........................................................................................................................77
3.6.3.7 Zone Type ...............................................................................................................................78
3.6.3.8 Zones Available ......................................................................................................................79
3.6.4: Loop Setup ........................................................................................................................................79
3.6.4.1 Style .........................................................................................................................................79
3.6.4.2 Loop Protocol ..........................................................................................................................79
3.6.5: System Setup.....................................................................................................................................80
3.6.5.1 Trouble Reminder ...................................................................................................................81
3.6.5.2 Banner .....................................................................................................................................81
3.6.5.3 Time-Date ...............................................................................................................................82
3.6.5.3.1 Time .....................................................................................................................................82
3.6.5.3.2 Date ......................................................................................................................................83
3.6.5.3.3 Clock Format ........................................................................................................................83
3.6.5.3.4 Daylight Savings Time .........................................................................................................83
3.6.5.4 Timers .....................................................................................................................................84
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay ................................................................................84
3.6.5.4.2 Pre-signal Delay ...................................................................................................................85
3.6.5.4.3 Waterflow Delay ..................................................................................................................85
3.6.5.4.4 AC Loss Delay .....................................................................................................................86
3.6.5.5 NAC (Notification Appliance Circuit) ....................................................................................86
3.6.5.5.1 Enabled .............................................................................................................
....................87
3.6.5.5.2 Type ......................................................................................................................................88
3.6.5.5.3 Silenceable ...........................................................................................................................88
3.6.5.5.4 Auto Silence .........................................................................................................................89
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) .........................................89
3.6.5.5.6 Zone ......................................................................................................................................91
3.6.5.5.7 Silence Inhibited ...................................................................................................................91
3.6.5.5.8 Sync Type .............................................................................................................................91
3.6.5.6 Relays ......................................................................................................................................92
3.6.5.7 Canadian Option ......................................................................................................................93
3.6.5.8 Waterflow Silenceable ............................................................................................................93
3.6.6: Verify Loop .......................................................................................................................................93
3.6.7: History...............................................................................................................................................94
3.6.7.1 View Events ............................................................................................................................94
3.6.7.2 Erase History ...........................................................................................................................94
3.6.8: Walktest.............................................................................................................................................95
6
MS-9200UDLS P/N: 52750:A 11/04/05
Page 7
Table of Contents
3.6.9: Option Modules................................................................................................................................96
3.6.9.1 Annunciators/UDACT ............................................................................................................96
3.6.9.2 Onboard DACT .......................................................................................................................97
3.6.9.2.1 Onboard DACT Enable ........................................................................................................97
3.6.9.2.2 Primary Phone ......................................................................................................................98
3.6.9.2.3 Secondary Phone ..................................................................................................................98
3.6.9.2.4 Service Terminal ..................................................................................................................99
3.6.9.2.5 Central Station ......................................................................................................................101
3.6.9.2.6 Trouble Call Limit (Dialer Runaway Prevention) ...............................................................102
3.6.9.2.7 Manual Dial Mode ...............................................................................................................114
3.6.9.3 Printer/PC ................................................................................................................................115
3.6.10: Password Change ............................................................................................................................116
3.6.11: Clear Program .................................................................................................................................117
3.6.12: Program Check................................................................................................................................118
3.7: Maintenance Programming Level ...............................................................................................................120
3.7.1: Disable Point .....................................................................................................................................121
3.7.2: History...............................................................................................................................................122
3.7.3: Program Check..................................................................................................................................123
3.7.4: Walktest.............................................................................................................................................124
3.7.5: System...............................................................................................................................................124
3.7.6: Zone Setup ........................................................................................................................................126
SECTION 4: Operating Instructions ....................................................................................................................128
4.1: Panel Control Buttons .................................................................................................................................128
4.1.1: Acknowledge/Step ............................................................................................................................128
4.1.2: Alarm Silence....................................................................................................................................128
4.1.3: Drill/Hold 2 Sec ................................................................................................................................128
4.1.4: Reset..................................................................................................................................................128
4.2: LED Indicators ............................................................................................................................................129
4.3: Normal Operation........................................................................................................................................130
4.4: Trouble Operation .......................................................................................................................................130
4.5: Alarm Operation..........................................................................................................................................132
4.6: Supervisory Operation.................................................................................................................................133
4.7: Process Monitor Operation..........................................................................................................................134
4.8: Hazard/Tornado Condition Operation.........................................................................................................134
4.9: Medical Alert Condition Operation.............................................................................................................134
4.10: NAC Operation .........................................................................................................................................134
4.11: Programmed Zone Operation....................................................................................................................135
4.12: Disable/Enable Operation .........................................................................................................................135
4.13: Waterflow Circuits Operation ...................................................................................................................135
4.14: Detector Functions .......................................................................................................
.............................135
4.15: Time Functions: Real-Time Clock ............................................................................................................135
4.16: Synchronized NAC Operation ..................................................................................................................136
4.17: Coded Operation .......................................................................................................................................136
4.18: Presignal....................................................................................................................................................136
4.19: Positive Alarm Sequence ..........................................................................................................................137
4.20: Special System Timers..............................................................................................................................138
4.20.1: Silence Inhibit Timer.......................................................................................................................138
4.20.2: Autosilence Timer...........................................................................................................................138
4.20.3: Trouble Reminder ...........................................................................................................................138
4.20.4: Waterflow Retard Timer..................................................................................................................138
4.20.5: Alarm Verification (None or One Minute)......................................................................................139
4.21: Walktest.....................................................................................................................................................139
4.22: Read Status................................................................................................................................................140
4.22.1: System Point ...................................................................................................................................141
MS-9200UDLS P/N: 52750:A 11/04/05 7
Page 8
Table of Contents
4.22.2: Zones ...............................................................................................................................................142
4.22.3: Power...............................................................................................................................................143
4.22.4: Trouble Reminder............................................................................................................................144
4.22.5: Timers..............................................................................................................................................144
4.22.6: NAC ................................................................................................................................................145
4.22.7: Relays..............................................................................................................................................145
4.22.8: Program Check................................................................................................................................146
4.22.9: History.............................................................................................................................................146
4.22.10: Annunciators .................................................................................................................................147
4.22.11: Phone Line.....................................................................................................................................147
4.22.12: Central Station...............................................................................................................................148
4.22.13: Service Terminal............................................................................................................................149
4.22.14: Printer/PC......................................................................................................................................149
4.22.15: Print ...............................................................................................................................................150
4.22.16: Time-Date......................................................................................................................................152
SECTION 5: Central Station Communications ...................................................................................................153
5.1: Transmittal Priorities...................................................................................................................................156
SECTION 6: Remote Site Upload/Download .......................................................................................................158
6.1: Downloading Program.................................................................................................................................158
6.1.1: Security Features...............................................................................................................................159
6.2: Downloading Initiated at a Service Terminal..............................................................................................161
6.3: Uploading Initiated at a Service Terminal...................................................................................................162
SECTION 7: Power Supply Calculations .............................................................................................................163
7.1: Overview .....................................................................................................................................................163
7.2: Calculating the AC Branch Circuit..............................................................................................................163
7.3: Calculating the System Current Draw.........................................................................................................164
7.3.1: Overview ...........................................................................................................................................164
7.3.2: How to Use Table 7.3 on page 165 to Calculate System Current Draw ...........................................164
7.4: Calculating the Battery Size ........................................................................................................................166
7.4.1: NFPA Battery Requirements .............................................................................................................166
7.4.2: Selecting and Locating Batteries.......................................................................................................166
APPENDIX A: Software Zones ............................................................................................................................167
A.1: Correlations ...............................................................................................................................................167
APPENDIX B: Default Programming .................................................................................................................173
APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................174
APPENDIX D: Wire Requirements .....................................................................................................................178
APPENDIX E: HVAC Control .............................................................................................................................179
E.1: Control Module Operation .........................................................................................................................179
E.1.1: HVAC SHUTDN .............................................................................................................................179
E.2: Monitor Module Operation ........................................................................................................................179
E.2.1: HVAC RESTART ...........................................................................................................................179
E.2.2: HVAC OVRRIDE ...........................................................................................................................180
8
MS-9200UDLS P/N: 52750:A 11/04/05
Page 9
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-LiteDevice Compatibility Document #15384 SLC Wiring Manual Document #51309 AFM-16ATF & AFM-32AF Document #15970 AFM-16AF Annunciator Document #15210 ACS Series Annunciators Document #51480 CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 LDM Series Lamp Driver Modules Document #50055 LCD-80F Remote Fire Annunciator Document #51338 ACM-8RF Relay Control Module Document #50362
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9200UDLS PN 52750:A 11/04/05 9
Page 10
TB8
GND DTR RCV
T
X
TB8 (option to DB-25)
5 4 3 2 1
9 8 7 613 12 11 10
25 24 23 22 21 20 19 18 17 16 1 5 14
TB8
GND DTR RCV T
X
White
Green
Black
Red
9 8 7 6
DB9F
5 4 3 2 1
OR
(Supervi sed, Power Limited)
NAC #1 & #2
Notification Appliance Circuits
Style Z (Class A)
+
NAC #2
+
using NA CKEY card.
NAC #1
2.5 am ps max. per circuit .
JP6 config ured for Class A
+
+
B
-
A
-
A
+
+
B
+
TB4
B
-
A
-
A
+
+
B
+
TB3
BA
SHIELDSLCSLC
shield
A A
-
B
EIA-232
(nonsupervised)
to printer or
Notification Appliance Circuits
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
Upload/Download Utility.
For EDP- listed equipm ent or
personal computer
personal computer with FACP
50 foot maximu m within same room.
1 Fixed Trouble Relay
Nonsupervised relay co ntacts
Contact Ratings:
2.0 amp s @ 30 VDC (resi stive)
++
+
+
2
1
0.5 amp s @ 30 VAC (resis tive)
ELRs 4.7K, ½W
2 Programmable Relays &
++
NAC #4 NAC #2
++
for Class B using NACKEY card.
NAC #1 NAC # 3
(See Style Z ill ustrated near right edge of boar d).
(Special Appli cation) 2.5 amps max. pe r circuit. JP6 conf igured
SLC Loop
supervised)
(power-l imited,
ACS (EIA-485)
to ACS Annunc.
Contacts sh own below in normal
conditio n (AC power with no alar m,
trouble or supervisory acti vity).
++
+
+
4
3
OR
(supervised)
Manual for detailed
information on wiring
Refer to the SLC Wiring
TERM
(EIA-485)
to LCD-80F
NC NO C
A Fail Safe Trouble
relay switches to t he
NO position during
trouble con ditions and
2
1
-
SLCSLC
+
B+ A + B- A- A B
B
+
for Styl e 4, 6 and 7.
addressabl e devices
-
ACS
+
I
-
N
-
T
U
O
I
+
N T
+
O
U
OUT+ IN+ OUT- IN-
Trouble
TB6 TB8 TB9 TB10
Alarm*
NO NC C NO NC C
NO NC C NC NO CNO NC C
TB5
under loss of all power.
NO NC C
Supervisory*
(* )Factory default rela y programming
NAC
Number
B
-
B
-
B
+
2244
B
+
TB4 TB7
1
B
-
-
B
33
B
+
B
+
1
-
TB3
-
+
TB2
- -
+ +
TB1
JP4
123
Cut this jumper to enable
Supervisory relay when
JP2
RELAY 2
RELAY 1
RELAY 3
NAC 2 CLASS A
NAC 2 & 4 CLASS B
B+ A+ A- B- B+ A+ A- B-
1B+ 3B+ 3B- 1B- 2B+ 4B+ 4B- 2B-
NAC 1 & 3 CLASS B
Config ure NACs for Cl ass A or
JP6
+ -
REMOTE PW R
SUPPLY SYN C NAC 1 CLAS S A
RST
+ 24V -
POWER
+ 24V -
POWER
NON-RST
4XTM F
J6
J5
4XTMF module is installed
JP7
REMOVE TO
DISABLE GND. FLT.
Class B wi ring using NACKEY
card. Factory defaul t is Class B.
J7
JP3
4XTMF
CUT TO
MONITOR
Flash Memo ry Load Enable Swit ch.
UP is no rmal posi tion for switch.
DOWN position allows loading of
factory software upg rades.
SW1
To disable ground fault detection,
remove jump er/shunt from J P7
KISSOFF
SEC. ACTIVE
J13 J12
Cut this jumper to supervise
the 4XT MF module when
installed (see J5 & J6)
PRI. ACTIVE
SEC. P HONE LINE
PRI. PHONE LINE
(Nonpower-Limited)
PS2 Keyboard Interface DACT Phone Line Jacks
I/F
KEYPAD
J4
Remove this jumper
to disable the FACP
battery cha rger when
using external charger.
LCD DISPLAY
JP5
CAUTION!
HIGH VOLTAGE
J11
TRANSFORMER 2
J1
TB11
TRANSFORMER 1
MINI DIN
J3
KEYBOARD CONN.
- +
J9
BATTE RY
Battery
nonpower-l imited
24 VDC, supe rvised,
18 Amp Hour maximum
HOT NEUT EARTH
120 VAC, 60 HZ, 3.0 amps
220/240 VAC, 50 Hz, 1.5 amps
J10
only
Transformer 2 Connector
Removing Ground
Basic System Connections
Remote Synchronization Output
Special Applic ation Power
24 VDC filtered, supervised and power-limited.
0.040 amps maximum, follows NAC1 control circuit.
Requires 4.7kohm End-of-Line resistor.
Special Application DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay A77-716B
Nonresettable or Resettable Power
Jumper selectable by JP4, 24 VDC filtered,
power-li mited (0.500 amps maximum)
Supervision required. Nonresettable
Power suitable for powering annunciators,
Resett able Power sui table for po wering
Resettable Power - 24 VDC filtered, power-limited
(0.500 amps ma ximum) to smoke detec tors (IDC).
Supervision required.
smoke detectors..
UL/NFPA Sty le /C la ss
Important!
voids
Fault Disable Jumper JP7
identifications for circuits.
Remove jumper JP7
with the approval of the AHJ
(Authority Having Jurisdiction)
Transformer 1 Connector
CAUTIO N! HIGH VOLTAGE
10 MS-9200UDLS PN 52750:A 11/04/05
Page 11
Peripheral Devices and Their Documents:
ACS (EIA-485)
Annunciators
AFM-16ATF &
TERM (EIA-485)
Annunciators
SLC Loop
AFM-32AF
Doc. #15970
LCD-80F
Doc. #51338
Addressable Devices and SLC Wiring
AFM-16AF
Doc. #15210
Doc. #51309
ACS Series
51480
ACM-8RF
Doc. #50362
LDM-32F
Doc. #50055
92udperi.cdr
Battery Connector
CHG-120F Charger
Doc. #50888
CHG-75 Charger
Doc. # 51315
MS-9200UDLS PN 52750:A 11/04/05 11
Page 12
Product Description Features and Options
SECTION 1 Product Description
The Fire-LiteMS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features. The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software and remote power expansion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote and local programming of the control panel using the PK-CD Upload/Download utility. In addition, the control panel may be programmed or interrogated off-site via the public switched telephone network. Any personal computer with Windows and compatible modem with a speed of 14.4 kbps or faster and Fire•Lite Upload/ Download software kit PK-CD, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages.
95 or greater,
MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS and the MS­9200UDLSE FACPs (Fire Alarm Control Panels).
Inventory
When the MS-9200UDLS shipment is received, check to make certain that all parts have been included in the shipment. The MS-9200UDLS shipment should consist of one of each of the following:
main circuit board with displaybackbox with doorplastic bag containing screws, cables, key, etc.manual
1.1 Features and Options
New LiteSpeed™ polling protocol for faster SLC response time
SLC operates up to 10,000 ft. (3,000 m) with twisted, unshielded wire (refer to "Wire Requirements" on page 178)
Built-in DACT (Digital Alarm Communicator/Transmitter)
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
198 addressable device capacity (99 detectors and 99 control/relay/monitor modules)
99 software zones
Onboard NACs (Notification Appliance Circuits) which can be configured as four Style Y (Class B) or two Style Z (Class A) circuits - special application
3.0 amps total power for NACs and 24 VDC special application auxiliary power outputs expandable to 6.0 amps
3.6 amps total system power (includes battery charger) expandable to 6.6 amps
Two programmable relay outputs and one fixed trouble relay
Synchronization output for remote power supply applications (special application)
Built-in Programmer
12 MS-9200UDLS PN 52750:A 11/04/05
Page 13
Specifications Product Description
Telephone Line Active LEDs
Communication Confirmation (Kissoff) LED
Touchtone/Rotary dialing
Programmable Make/Break Ratio
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensationMaintenance alertDetector sensitivity test capability (NFPA 72 compliant)Automatic device type-code verificationPoint trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, AFM annunciators or LCD-80F Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
Upload/Download (local or remote) of program and data via integral DACT
Compatible with Fire-Lite’s newer series devices (refer to SLC Wiring Manual for a list of compatible addressable devices)
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible addressable devices)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Annunciators:
ACS Series-LED Zone AnnunciatorsLDM Graphic Annunciator SeriesLCD-80F Liquid Crystal Display point annunciatorACM-8RF Relay Module
1.2 Specifications
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB11
MS-9200UDLS: 120 VAC, 60 Hz, 3.0 amps MS-9200UDLSE: 240 VAC, 50 Hz, 1.5 amps Wire size: minimum 14 AWG (2.00 mm
MS-9200UDLS PN 52750:A 11/04/05 13
2
) with 600 V insulation
Page 14
Product Description Specifications
Battery (Lead Acid Only) - J9
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp Maximum Battery Charger Capacity: 18 Amp Hour (MS-9200UDLS cabinet holds maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box. Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length or 3,000 ft. (900 m) untwisted, unshielded pair length Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit requires ferrite bead per FCC requirement Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB3 & TB4
Each Terminal Block provides connections for two Style Y (Class B) or one Style Z (Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs Style is configured using NACKEY card plugged into JP6 on main board Special Application full-wave rectified power Power-limited circuitry Maximum voltage drop in wiring: 2.0 VDC Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 15) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.6 on page 32 for information on power-limited relay circuit wiring
Nonresettable Special Application Power (24 VDC Nominal) ­TB1, Terminals 1 (+) & 2 (-)
Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 0.5 amps (see Figure 1.1) Power-limited circuit requires ferrite bead per FCC requirements
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) - TB3, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 0.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1) Power-limited circuit requires ferrite bead per FCC requirements Refer to the Device Compatibility Document for listed compatible devices
Remote Sync Output - TB2
Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7KΩ Output linked to NAC 1 control Supervised and power-limited circuit requires ferrite bead per FCC requirements
14 MS-9200UDLS PN 52750:A 11/04/05
Page 15
Specifications Product Description
EIA-485 (TERM) or EIA-232 (ACS) - TB8
EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +), 3 (Out -), 4 (In -) EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (Ground)
EIA-485 (ACS) - TB9
ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead
1.2.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer.
Note: If NACs are configured as two Style Z (Class A) circuits, each circuit can handle 2.5 amps maximum.
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability
6.0 amps with optional second XRM-24(E) transformer.
3.0 amps max. with only standard transformer installed.
owerdist9200ud.cdr
MS-9200UDLS PN 52750:A 11/04/05 15
Page 16
Product Description Controls and Indicators
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance/presignal (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 012102
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
2
1
4
GHI
78 9
PRS
*
QZ
ABC
5
JKL
TUV WXY
0
RECALL
3
DEF
6
MNO
#
-/.
1
CLR
ESC
MODE
st
EVENT
AC POWER FIRE ALARM
SUPERVISORY
TROUBLE
ENTER
MAINTENANCE
ALARM SILENCED
DISABLED BATTERY
ACK/STEP
ALARM SILENCE
DRILL
HOLD 2 SEC
RESET
GROUND
•1st Event key
Clear key
Figure 1.2 Membrane/Display Panel
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
9600kypd.cdr
16 MS-9200UDLS PN 52750:A 11/04/05
Page 17
Circuits Product Description
1.4 Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the
Reference
Manual
SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
Special Application Power
24 VDC Resettable (smoke detector power) output - 0.5 amps maximum24 VDC Nonresettable or Resettable power output - 0.5 amps maximum
24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY card in JP6, are provided with various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations:
fire alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
•AC loss
1.5 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone rotary
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats: 12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types
4+1 Ademco Express 4+2 Ademco Express Ademco Contact ID
®
, programmable to
MS-9200UDLS PN 52750:A 11/04/05 17
Page 18
Product Description Components
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board.
See Page
Cabinet
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations). The dress panel must be installed to meet FM requirements.
Transformer Assembly
Optional XRM-24(E)
One 100VA transformer is provided standard with the panel (3.6 amps maximum). An optional 100 VA transformer XRM-24
Standard XRM-24(E)
(XRM-24E for the MS-9200UDLSE) is available to provide maximum system and accessory power (6.6 amp total).
9200xfor.cdr
Batteries
Battery Cable P/N 75287
The MS-9200UDLS cabinet provides space for two batteries (up to 18 Amp Hour).
-
Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or
+
+
-
CHG-120F and a UL listed battery box such as the BB-55F. Batteries must be ordered separately.
9200batt.cdr
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The maximum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable detectors.
18 MS-9200UDLS PN 52750:A 11/04/05
Page 19
Components Product Description
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99. Note that a blinking LED on an addressable module indicates communication between the module and the control panel.
Reference
Manual
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable modules. Refer to the Device
Compatibility Document for a list of approved conventional notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices.
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4­wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control module circuit.
MS-9200UDLS PN 52750:A 11/04/05 19
Page 20
Product Description Optional Modules
1.7 Optional Modules
The MS-9200UDLS main circuit board includes option module connectors for the following module:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circuit board, must be cut to allow supervision of the module.
1.8 Accessories
1.8.1 PK-CD Programming Utility
The PK-CD Programming Utility can be used to program an MS-9200UDLS directly from most IBM compatible computers, including laptops and portables, equipped with a serial port. MS-9200UDLS program files can also be created and stored on the PC and then downloaded to the control panel. The PK-CD Kit includes the MS­9200UDLS Windows-based Programming Utility software on CD-ROM with on-line help file. A serial cable (P/N: PRT/PK-CABLE), which must be purchased separately, is required for connection of the PC to the RS-232 (PC/Printer) terminals at TB8 of the MS-9200UDLS main circuit board. Refer to the illustration on page 10 and the section titled "Printer/PC" on page 40, for the location and connections to this terminal.
1.8.2 Dress Panel
An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox. The dress panel must be installed to meet FM requirements.
dp9200udls.cdr
20 MS-9200UDLS PN 52750:A 11/04/05
Page 21
Accessories Product Description
1.8.3 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger. The battery box, which is red and is provided with knockouts, was designed specifically to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 25 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two 25 AH or one 60 AH battery may also be housed in the battery box.
1.8.4 Battery Charger
1.8.4.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS­9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
Reference
Manual
1.8.4.2 CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than 25AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
MS-9200UDLS PN 52750:A 11/04/05 21
Page 22
Product Description Accessories
1.8.5 Annunciators
ACS Series LED Zone Type Annunciators
The ACS Series Annunciators remotely display alarm and trouble status as well as system status. In addition, they can provide remote Acknowledge, Silence, Reset and Drill functions. For more detailed information, refer to the appropriate annunciator manual. Following is a list of annunciators which can be used with the MS-
Reference
Manual
9200UDLS.
ACM-16ATF
*
Annunciator Control Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has switches for FACP Acknowledge, Silence, Reset and Drill. It has rotary address switches and will accept up to three AEM-16ATF Expanders. In Canada, this module must be used to annunciate the fire alarm input points/zones only.
AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red
alarm LEDs and 16 yellow trouble LEDs
AFM-16ATF
*
Annunciator Fixed Module annunciates 16 zones with 16 red alarm LEDs and 16 yellow trouble LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has switches for FACP Acknowledge, Silence, Reset and Drill. It is fixed at address ‘1.’ In Canada, this module must be used to annunciate the fire alarm input points/zones only.
ACM-32AF
*
Annunciator Control Module annunciates 32 alarm zones with 32 red LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. It has rotary address switches and will accept one AEM-32AF Expander. In Canada, this module must be used to annunciate the fire alarm input points/zones only.
AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32
red LEDs
AFM-16AF
*
Annunciator Fixed Module annunciates 16 alarm zones with 16 red alarm LEDs. In addition, it has a System Trouble LED, an On Line/Power LED and a local piezo sounder. It also has a switch for local piezo silence. It is fixed at address ‘1.’ In Canada, this module must be used to annunciate the fire alarm input points/zones only.
AFM-32AF
*
Annunciator Fixed Module annunciates 32 alarm zones with 32 red LEDs. In Canada, this module must be used to annunciate the fire alarm input points/zones only.
* In Canada, the color red must be used to indicate active alarm inputs. Yellow
indicates supervisory, burglary or trouble signals. Green indicates the presence of power, or an activated output.
22 MS-9200UDLS PN 52750:A 11/04/05
Page 23
Getting Started Product Description
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is a compact 80-character backlit LCD remote fire annunciator that is capable of displaying English language text. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the LCD­80F is capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill.
Communications between the control panel and the annunciator is accomplished over a serial interface employing the EIA-485 communication standard. Up to 32 LCD-80F annunciators may be connected to the EIA-485 circuit. The annunciators may be powered from the host FACP or a remote UL listed filtered power supply such as the
Reference
Manual
Reference
Manual
FCPS Series. For more detailed information, refer to the LCD-80F manual.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power and control for a maximum of three expander modules. The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions. Refer to the LDM Series Lamp Driver Modules manual for a complete description.
1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS­9200UDLS on-line:
Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page
27)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to "Autoprogram" on page 47)
Resolve Programming Conflicts
Go to Point Program to Enter Specific Data (refer to "Point Program" on page
48). Use the right and left arrow keys to navigate between devices.
MS-9200UDLS PN 52750:A 11/04/05 23
Page 24
Product Description Telephone Requirements and Warnings
1.10 Telephone Requirements and Warnings
1.10.1Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be con­nected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
1.10.2Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equip­ment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-9200UDLS FCC Registration Number: US:1W6AL00B9200UD Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 36 for an illustration of the proper installation of this equipment.
Important! The DACT must not per requirements of UL 864 9th Edition.
24 MS-9200UDLS PN 52750:A 11/04/05
be used to dial a phone number that is call-forwarded
Page 25
Telephone Requirements and Warnings Product Description
1.10.3Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notifica­tion will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream (as first device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or pre­mises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
MS-9200UDLS PN 52750:A 11/04/05 25
Page 26
Product Description Telephone Requirements and Warnings
1.10.4For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTICE: The Industry Canada (IC) label identifies certified equipment. This certifica­tion means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equip­ment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be con­nected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of ser­vice in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed
5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
24 Viceroy Road Concord, Ontario L4K2L9 Phone: (905) 660-7210 FAX: (905) 660-7204
IC Certificate Number: Ringer Equivalence Number (REN): 1.3B Load Number: 2
26 MS-9200UDLS PN 52750:A 11/04/05
Page 27
Mounting Backbox Installation
SECTION 2 Installation
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Mounting Backbox
The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from
!
the body. Use static suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the tow 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
grounding stud
See Page
Mark and predrill hole in the wall for the center top keyhole mounting bolt
using the dimensions illustrated in Figure 2.3 on page 29
Install center top fastener in the wall with the screw head protrudingPlace backbox over the top screw, level and secureMark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Install remaining fasteners and tighten
Main Circuit Board on chassis
mounting studs
mounting slots
92udchassisinbox.cdr
Backbox
Figure 2.1 MS-9200UDLS Chassis Removal
MS-9200UDLS PN 52750:A 11/04/05 27
Page 28
Installation Mounting Transformer
2.2 Mounting Transformer
One XRM-24(E) transformer is supplied standard with the control panel. An optional second XRM-24(E) transformer can be ordered and installed to provide maximum system power. Install the transformers in the locations indicated in the following illustration.
1. When the location is dry and free of construction dust, install the chassis/ transformer/circuit board assembly.
2. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the backbox, then position the two mounting hole tabs over the studs with nuts located in the upper portion of the backbox.
3. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down.
4. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and to ensure proper grounding, use a 3/8” nut driver or socket.
5. If the main circuit board is not already attached to the chassis, install it by positioning the ten mounting holes over the studs on the chassis and secure with the supplied screws.
6. Connect the Standard XRM-24 Transformer plug to Transformer 1 Connector J10 on the FACP main circuit board
7. Connect the Optional XRM-24 Transformer plug to Transformer 2 Connector J11 on the FACP main circuit board.
8. Complete the installation as detailed in the following sections.
Optional XRM-24 Transformer
Standard XRM-24 Transformer
Mounting Studs
Mounting Slot
Figure 2.2 MS-9200UDLS Main Board/Chassis Installation
28 MS-9200UDLS PN 52750:A 11/04/05
Page 29
Mounting Transformer Installation
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
9050udencl.cdr
Figure 2.3 MS-9200UDLS Cabinet Mounting
MS-9200UDLS PN 52750:A 11/04/05 29
Page 30
Installation Mounting Transformer
9050udcab.cdr
Figure 2.4 MS-9200UDLS Cabinet Dimensions
30 MS-9200UDLS PN 52750:A 11/04/05
Page 31
Power Installation
2.3 Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
2.3.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for the MS-9200UDLS or 240 VAC, 50 Hz, 1.5 amps for the MS-9200UDLSE.
TB11
Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00
2
mm
) or larger wire with 600 volt insulation rating.
Make certain that the AC mains circuit breaker is off
HOT NEUT EARTH
before wiring any connections between the mains and the control panel. Connect wiring from the AC mains to TB11 on the FACP, being careful to observe proper connections.
Connect a wire from the grounding stud in the cabinet to a known solid earth ground in the building. Refer to Figure 2.1 on page 27 for location of the stud. This connection is vital for maintaining the control panel’s immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be
applied to the panel before installing the battery interconnect cable (refer to the following section).
LCD DISPLAY
J1
J4
J9
- +
BATTERY
2.3.2 Battery Power
Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not interconnect cable until the system is completely
See Page
installed. Observe polarity when connecting the batteries. Connect the battery cable to J9 on the main circuit board. Refer "Power Supply Calculations" on page 163, for calculation of the correct battery rating.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
2.3.3 Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited and require a ferrite bead per FCC requirements (refer to "UL Power-limited Wiring Requirements" on page 35).
Power-limited Resettable or Nonresettable Power
0.5 amperes max., 24 VDC nominal filtered, resettable or nonresettable power can be drawn from TB1 Terminals 1(+) and 2(-)
JP4 is used to configure TB1, Terminals 1 & 2 for:
• Resettable Power - jumper pins 1 and 2 of JP4 as shown
• Nonresettable Power - jumper pins 2 & 3 of JP4
Figure 2.5 Special Application Power Outputs - 24 VDC
connected. Do not connect the
Power-limited Resettable Power
0.5 amperes max., 24 VDC nominal filtered, resettable power can be drawn from TB1 Terminals 3(+) and 4(-)
+ - + -
JP4
1 2 3
TB1
1 2 3 4
92udtb1.cdr
-
+
+
-
Interconnect Cable
MS-9200UDLS PN 52750:A 11/04/05 31
Page 32
Installation Relays
2.4 Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
Note that relay connections may be power-limited or nonpower-limited, provided that
0.25” spacing is maintained between conductors of power-limited and nonpower­limited circuits. Refer to UL Power-limited wiring requirements.
Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory. The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a fail-safe relay which will transfer on any trouble or total power failure.
TB7
RELAY 3
NO
NC C
Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories
Figure 2.6 Relay Terminals
2.5 Notification Appliance Circuits
The control panel provides four Style Y (Class B) or two Style Z (Class A) NACs
See Page
Reference
Manual
(Notification Appliance Circuits). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to "Calculating the System Current Draw" on page 164). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device Compatibility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be expanded via the FCPS Series field charger/power supplies.
TB5
RELAY 1 RELAY 2
NO
NC C
TB6
NO
NC C
92udreyp.cdr
The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the MS-9200UDLS main circuit board. The NACs are configured for Style Y (Class B) from the factory. Refer to "Configuring NACs" on page 33 for information on changing the NAC configuration to Style Z (Class A).
32 MS-9200UDLS PN 52750:A 11/04/05
Page 33
Notification Appliance Circuits Installation
2.5.1 Configuring NACs
The Notification Appliance Circuits on the main circuit board are configured for Style Y (Class B) or Style Z (Class A) by properly orienting the NACKEY card in JP6 which is located at the top of the main circuit board near the NAC terminal blocks TB3 and TB4. The default configuration is for Style Y (Class B). Refer to Figure 2.7 for information on installing the NACKEY card.
• Style Z (Class A) - install NACKEY into JP6 with Class A pointing down toward circuit board as
NACKEY Card
illustrated to the right.
• Style Y (Class B) - install NACKEY into JP6 with Class B pointing down toward circuit board .
NACKEY must be inserted with text side facing in toward center of main circuit board and key into key­slot as illustrated to the right. It is keyed to prevent
Key
Key-slot
CLASS B
CLASS A
NACKEY -PCA
incorrect insertion.
Top edge of MS-9200UDLS Main Circuit Board
TB3
TB4
NACKEY card slot
JP6
Figure 2.7 NAC Configuration Using NACKEY
2.5.2 Style Y (Class B) NAC Wiring
4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7 kΩ, ½ watt P/N:71252 UL listed
NAC 1
NAC 3
NAC 4
NAC 2
NACKEY -PCA
92nackey.cdr
JP6
Polarized Bells
Polarized Strobes
+
+
+
+
+
+
+
+
+
Polarized Bells
+
Polarized Strobes
+
+
Polarized HornsPolarized Horns
Notification Appliance Circuit polarity shown in alarm state
circuit number
TB3
B+B
B
B
-
-
+
1
33
1
-
B
B+B
-
+ 2244
B
-
Dummy Load all unused circuit
9200nacy.cdr
TB4
Figure 2.8 NAC Style Y (Class B) Wiring
MS-9200UDLS PN 52750:A 11/04/05 33
Page 34
Installation Remote Synchronization Output
A
A
2.5.3 Style Z (Class A) NAC Wiring
Polarized Bell
Polarized Strobe Polarized Strobe
Polarized Horn
NAC 1
Notification Appliance Circuit polarity shown in alarm state
Figure 2.9 NAC Style Z (Class A) Wiring
2 Style Z (Class A) Notification Appliance Circuits,
supervised and power-limited
Polarized Bell
+
+
+
B +
B
A
A
-
-
+
+
+
B
-
-
Polarized Horn
+
B +
+
NAC 2
TB3
TB4
9200nacz.cdr
2.6 Remote Synchronization Output
Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard to individuals. Devices connected directly to the control panel’s NACs can be synchronized as described in "Type" on page 88.
Notification appliances connected to remote power sources may require synchronization with the FACP’s devices. This can be accomplished by connecting the Remote Synchronization Output from TB2 of the MS-9200UDLS to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics, the signal on NAC1. This allows the devices connected to the power supply to be synchronized with the devices connected to NAC1 on the FACP.
The Remote Synchronization Output is power-limited and supervised and requires a ferrite bead (refer to "UL Power-limited Wiring Requirements" on page 35). A 4.7 kΩ ELR resistor must be connected to the end of the wiring at the remote power supply.
Remote Power Supply
Sync Input
4.7 kΩ ELR
FACP main circuit board
Figure 2.10 Remote Sync Output
JP4
Remote Sync Output
TB3
+ 24V -
POWER
+ 24V -
RST
POWER
TB2
REMOTE PWR SUPPLY SYNC
+ -
TB1
1 2
NON-RST
3
TB4
B+ A+ A- B- B+ A+ A- B-
1B+ 3B+ 3B- 1B- 2B+ 4B+ 4B- 2B-
34 MS-9200UDLS PN 52750:A 11/04/05
Page 35
UL Power-limited Wiring Requirements Installation
2.7 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-9200UDLS is shown below.
Figure 2.11 Typical UL Power-limited Wiring Requirements
Power-limited Circuits
Nonpower-limited Circuits
*Ferrite Beads
Power-limited Circuits
Nonpower-limited Circuits
*Ferrite Beads
Power-limited Circuits
maintain minimum 0.25” between power-limited and nonpower-limited circuits wiring
AC Power
Ground Strap
Grounding Stud
To Batteries
Nonpower-limited Circuits
92udulpw.cdr
*Ferrite Bead Installation
Per FCC requirements, ferrite beads are required for the DC Power Outputs, Remote Power Supply Sync, ACS Output and SLC Circuit.
Wrap wire around ferrite bead as shown.
Close ferrite bead.
MS-9200UDLS PN 52750:A 11/04/05 35
Page 36
Installation Digital Communicator
2.8 Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the panel's digital communicator be
located as the first device on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded per requirements of UL 864 9th Edition.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Telephone
Line
Network
Demarcation
Point
RJ31X
Computer
Jack
Unused
RJ-11 Jack
FACP with DACT
Unused
RJ-11 Jack
Telephone
Fax Machine
Answering
System
Telephone
Figure 2.12 DACT Installation
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone lines is required as shown below.
KISSOFF
(Secondary Lines) Incoming Telco Phone Line s
Tip
Ring
Green Wire
Red Wire
123
4
56 8
Ring
To premise phones
Tip
Tip
Ring
123
Telephone
Green Wire
Red Wire
4
56778
(Primary Lines) Incoming Telco Phone Line s
Ring
To premise phones
actadact.cdr
Tip
PRI. ACTIVE
PRI. PHONE LINE
SEC. ACTIVE
J13 J12
SEC. PHONE LINE
Male Plug Connectors
Modular Female Connectors
Note:Shorti ng bars inside RJ31X Jack
removed du ring
male plug insertion
7 foot
Cable MCBL-7 (ordered
separately)
Figure 2.13 Wiring Phone Jacks
36 MS-9200UDLS PN 52750:A 11/04/05
Page 37
Optional Module Installation Installation
2.9 Optional Module Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
MS-9200UDLS Keypad/Display Removal
Removal of the keypad/display is normally not necessary. If, however, it becomes necessary to replace the keypad/display or access jumpers JP5 and JP7 or switch SW1, the Keypad/Display can be removed by inserting a Phillips screwdriver into each of the three holes located in the flexible covering of the Keypad/Display and loosening the three mounting screws. Note that it is not necessary to disconnect the cables between the Keypad/Display and the main circuit board unless the unit itself is being replaced. Carefully lift the Keypad/Display and rest the unit at the bottom of the main circuit board.
Mounting Screw Access Hole
SHIELDSLCSLC
TB1
JP4
1 2 3
TB2 TB3 TB4 TB7
+ 24V -
NON-RST
POWER
+ 24V -
POWER
RST
+ -
REMOTE PWR SUPPLY SYNC
JP6
B+ A+ A- B- B+ A+ A- B-
1B+ 3B+ 3B- 1B- 2B+ 4B+ 4B- 2B-
NAC 1 CLASS A
NAC 1 & 3 CLASS B
NAC 2 CLASS A
NAC 2 & 4 CLASS B
NO NC C
RELAY 3
TB5
NO NC C NO NC C
RELAY 1
TB6
TB8 TB9 TB10
RELAY 2
JP2
OUT+ IN + OUT- I N-
ACS
SLCSLC
B+ A+ B- A- A B
SW1
KEYPAD
I/F
J3
MINI DIN
KEYBOARD CONN.
JP1
1 2 3
PRI. ACTIVE
PRI. PHONE LINE
J6
J5
JP3
CUT TO
MONITOR
4XTMF
SEC. ACTIVE
J13 J12
4XTMF
J7
KISSOFF
SEC. PHONE LINE
REMOVE TO
DISABLE GND. FLT.
JP7
J11
HIGH VOLTAGE
TRANSFOR MER 2
CAUTION!
TRANSFORMER 1
J10
JP5
TB11
HOT NEUT EARTH
LCD DISPLAY
J1
J4
J9
- +
BATTERY
Mounting Screw Access Holes
96dact1.cdr
Figure 2.14 Keypad/Display Removal
MS-9200UDLS PN 52750:A 11/04/05 37
Page 38
Installation Optional Module Installation
2.9.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
Note: 4XTMF Module is not suitable for transmitting reverse polarity supervisory signal.
}Remote Alarm (power-limited)* }Remote Trouble (power-limited)*
No connection
}Municipal Box (nonpower-limited)*
+ - + - + ­1 2 3 4 5 6 7
Polarities are shown for module activation
* Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Box is not connected.
Disconnect LED
4xtmfl.cdr
Disconnect Switch shown in disconnect position
TBL Jumper
Connect to FACP J10 & J11
Figure 2.15 4XTMF Transmitter Module
38 MS-9200UDLS PN 52750:A 11/04/05
Page 39
Optional Module Installation Installation
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (Primary and Secondary) from the FACP before installing 4XTMF
2. Cut jumper JP3 on the main circuit board to allow the control panel to supervise the 4XTMF module
3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the MS-9200UDLS main circuit board, being careful not to bend any pins
4. Secure 4XTMF module to standoffs with supplied screws.
5. Reapply power to the FACP
6. For proper 4XTMF operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3
7. When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left
8. Test system for proper operation
SHIELDSLC
TB5 TB6 TB8 TB9 TB10
NO NC C NO NC C
RELAY 1
Standoff Standoff
RELAY 2
OUT+ IN+ OUT- IN-
JP2
ACS
SLCSLCSLC
B+ A+ B- A- A B
4XTMF
FACP main circuit board
JP1
J5 & J6 Connectors
1 2 3
J5
PRI. ACTIVE
J13 J12
PRI. PHONE LINE
J6
JP3
CUT TO
MONITOR
4XTMF
SEC. ACTIVE
4XTMF
J7
SEC. PHONE LINE
Cut Jumper JP3
KISSOFF
92ud4xtm.cdr
Figure 2.16 4XTMF Connectors to MS-9200UDLS Connectors
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. Relay 3 at TB5 must be programmed as a supervisory relay. Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens
MS-9200UDLS PN 52750:A 11/04/05 39
Page 40
Installation Optional Module Installation
2.9.2 Printer/PC
A serial printer or a PC (personal computer) may be connected to TB8 Terminals 1 - 4 on the FACP. The printer can be used to provide a hard-copy printout of real-time events, history file and walktest data. An IBM compatible PC can be connected to provide local FACP programming capabilities using the PK-CD programming utility. Installation of either device requires panel programming to allow the FACP to communicate with the device.
CAUTION! Do not connect a printer or PC to the MS-9200UDLS FACP if a ground fault (zero impedance to ground) exists on the control panel. Circuit damage may
!
result. Remove all power (Primary and Secondary) before installing or removing any wiring.
Installation
Remote printers and PCs require separate primary power. Also required is the PRT/ PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/ PK-CABLE to TB8 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply power to the FACP and printer or PC. Note that a ground fault (zero impedance to ground) may occur on the FACP, dependent on the printer or PC being used, due to this connection. For this reason, it is important that there be no preexisting ground fault on the panel.
Note that the printer may or may not be supervised as determined by user programming. Refer to "Printer/PC" on page 115.
5 4 3 2 1
9 8 7 6
PRT/PK-CABLE
TX
RCV
DTR
GRND
TB8 TB9 TB10
OUT+ IN+ OUT- IN-
Figure 2.17 Serial Printer and Computer Connections
Red
White
Green
Black
SLC
ACS
SLC
B+ A+ B- A- A B
SHIELDSLCSLC
9600tb7a.cdr
Printer Configuration
Refer to the documentation supplied with the printer for pertinent information about printer setup. Set the printer’s options as listed in the following table:
COMMUNICATION SETUP
BUFFER: LARGE
DATA BITS: 7
PA RI TY: E VE N
STOP BIT: 1 STOP
BAUD RATE: 2400/4800/9600
AUTOMATIC LINE FEED NO
AUTOMATIC CARRIAGE RETURN NO
PC Configuration
The Windows-based PK-CD Programming Utility Kit contains CD-ROM with on-line help file.
40 MS-9200UDLS PN 52750:A 11/04/05
Page 41
Optional Module Installation Installation
2.9.3 Digital Communicator and Annunciators
2.9.3.1 ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps. When installed with an MS-9200UDLS FACP, the ACM-8RF modules provide relay activation for each of the 99 possible FACP zones plus special functions. Options exist to allow for alarm only or alarm and trouble activation per
Reference
Manual
zone. Output activation for general alarm, general trouble, general supervisory, NAC fault, AC fail, walktest start and battery trouble are also available. The ACM­8RF can be mounted remotely in an ABS-8RF annunciator surface-mount backbox. Refer to the ACM-8RF manual for information on setting module switches for addressing and relay functions.
2.9.3.2 ACS and AFM Series Annunciators
ACS and AFM Series Annunciators provide visual indications of FACP status in remote locations. Refer to the appropriate annunciator manual for information on installation, wiring and operation.
Annunciator addressing is specific to the MS-9200UDLS control panel. The following table describes the annunciator addresses and the corresponding addressable devices that will be annunciated at each annunciator address.
ACM Annunciator Address Annunciator Displays the Following Points
1 8 General System Status Points & Zones 1 - 56 2 Zones 57 - 99 & 4 NACs 3 SLC Loop, Module Addresses 1 - 64 4 not used 5 SLC Loop, Module Addresses 65 - 99 6 not used 7 not used 8 SLC Loop, Detector Addresses 1 - 64 9 not used
10 SLC Loop, Detector Addresses 65 - 99
11 not used 12 not used 13 not used 14 not used 15 not used 16 not used 17 not used 18 not used 19 not used 20 8 General System Status Points & Zones 1 - 56 21 Zones 57 - 99 & 4 NACs 22 SLC Loop, Module Addresses 1 - 64 23 not used 24 SLC Loop, Module Addresses 65 - 99 25 not used 26 not used 27 SLC Loop, Detector Addresses 1 - 64 28 not used 29 SLC Loop, Detector Addresses 65 - 99 30 not used 31 not used 32 not used
The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to "Annunciators/UDACT" on page 96 for information on annunciator programming. Make certain to program the annunciator addresses that have been physically installed on the system.
Note: The 8 General System Status Points include the following:
• General Alarm • Alarm Silenced • Battery Fault
• General Trouble • System Off Normal • NAC Fault
• General Supervisory • AC Loss
MS-9200UDLS PN 52750:A 11/04/05 41
Page 42
Programming Programming Data Entry
SECTION 3 Programming
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call Limit N
Permitted in
UL 864? (Y/N)
Possible settings
Refer to "Trouble Call Limit (Dialer Runaway Preven­tion)" on page 102.
Trouble Call Limit = 0 (factory default): unlimited calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble to from 1 to 99 within a 24 hour period
Settings permitted
in UL 864
Trouble Call Limit = 0 for unlimited Central Station trouble calls
3.1 Programming Data Entry
Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the control panel main circuit board.
The information presented in this section refers to programming the MS-9200UDLS via the onboard keypad. If an optional computer keyboard is connected to the MS­9200UDLS main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys.
Keypad Keys Computer Keyboard Keys
1st Event Home CLR Delete ESC Esc RECALL Insert ** ## A - Z A - Z 0 - 9 0 - 9
(on QZ key)
—— //
••
Space bar
   
ENTER Enter ACK/STEP F1 SILENCE F2 DRILL F3 RESET F4
42 MS-9200UDLS PN 52750:A 11/04/05
Page 43
User Programming Programming
3.2 User Programming
The MS-9200UDLS is completely field programmable and requires no special software skills. While programming the MS-9200UDLS, the fire protection capabilities of the
!!!
control panel are
Site-specific programming may be accomplished in three ways:
Autoprogramming Feature - This is a convenient method for quickly bringing
the FACP addressable SLC devices on-line without the necessity of programming each device individually. Refer to "Autoprogram" on page 47 for a detailed description of Autoprogramming
Manual programming or editing, using the FACP keypad or a PC keyboard
Off-line Programming and Editing Feature - allows creation and editing of site­specific custom programs using a Windows-based computer. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming kit can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below:
enabled.
See Page
HONEYWELL LIFE SAFETY SYSTEM ALL NORMAL 10:00A 012102
Programming, Read Status and Manual Dial mode can be entered while the panel is in any
mode of operation. If the panel is in alarm, the alarm condition must be
acknowledged before entering any other mode. To access any of the programming or read status features, the Enter or Mode key must be pressed, which will cause the LCD to display the following:
1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status Mode which allows the user to view the programmed features and status of the control panel The Read Status feature is not password protected. Refer to "Read Status" on page 140 for a detailed description of this feature.
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options.
Pressing 3 will select the Manual Dial Mode which allows the user to enter a troubleshoot mode of operation.
Exit Programming, Read Status and Manual Dial Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Note that the data which is entered
during Programming mode is not repeatedly pressing the ‘ESC’ key. If the Reset key is pressed or power is lost before exiting Programming mode, all data just entered will be lost.
MS-9200UDLS PN 52750:A 11/04/05 43
saved until the programmer exits this mode by
Page 44
Programming Initial Power-up
User Programming Levels
There are two user programming levels:
User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change.
3.3 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If the addressable devices have not yet been programmed into the FACP, their LEDs will not flash and the following trouble message will be displayed.
TROUBL IN SYSTEM NO DEVICES INSTALLED
09:03A 012102
3.4 Programming Screens Description
Three options are available when the Enter key is pressed: Read Status, Programming and Manual Dial Mode. The Read Status and Programming options have multiple functions or features which may be chosen. To view all of the choices, it is necessary that the programmer scroll through a number of additional subscreens. These selections are displayed on multiple screens to make them more readable for the
See Page
programmer. Refer to "Master Programming Level" on page 46, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is followed to view all option choices.
3.5 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From either of the screens, access to specific system and device features or programming may be obtained. All user
See Page
programming entries are stored in nonvolatile memory. The factory set passwords can be changed by the user as described in "Password Change" on page 116. If an invalid password is entered, the blinking cursor will return to the first password character position. To exit Programming, Read Status or Manual Dial mode at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved.
44 MS-9200UDLS PN 52750:A 11/04/05
Page 45
Programming and Passwords Programming
To access user Programming mode, press the Enter or Mode key. The LCD will display the following:
1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING ENTER PASSWORD *****
Entering the Master appear:
If the Maintenance appear:
level password (default 00000) will cause the following screen to
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
level password (default 11111) is entered, the following screen will
PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK
Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key.
MS-9200UDLS PN 52750:A 11/04/05 45
Page 46
Programming Master Programming Level
3.6 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will appear:
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES
Programming Screen #3
PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK
Programming Screen #4
46 MS-9200UDLS PN 52750:A 11/04/05
Page 47
Master Programming Level Programming
3.6.1 Autoprogram
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is powered­up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default values for newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop. While autoprogramming, the panel will display the following:
AUTOPROGRAM AUTOPROGRAMMING! PLEASE WAIT
Autoprogram Progress Screen
When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display:
# OF DET LOOP1 055 # OF MON LOOP1 035 # OF CON LOOP1 030
Autoprogram Result Screen #1
In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
MS-9200UDLS PN 52750:A 11/04/05 47
Page 48
Programming Master Programming Level
3.6.2 Point Program
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
The Point Program option allows the programmer to add a new addressable device to an SLC loop, delete an existing device from a loop or change the programming for an existing device. Pressing 2, while viewing Programming Screen #1, will select the Point Program option and display the following screen:
POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE
Point Program Screen
3.6.2.1 Detector Programming
Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an addressable detector. The following screen will be displayed by the control panel:
DETECTOR 1=ADD 2=DELETE 3=EDIT
Detector Screen
3.6.2.1.1 Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address to programming:
ADD DETECTOR ENTER DETECTOR# ***
Add Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE(ION)
Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector.
48 MS-9200UDLS PN 52750:A 11/04/05
Page 49
Master Programming Level Programming
When the type has been selected, the following screen will be displayed:
ADD DETECTOR DETECTOR# 005 IS ADDED
The programmer can continue adding detectors by pressing the ESC key which will return the display to the Add Detector Screen.
3.6.2.1.2 Delete Detector
DETECTOR 1=ADD 2=DELETE 3=EDIT
Detector Screen
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to delete a specific detector:
DELETE DETECTOR ENTER DETECTOR# ***
Delete Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005. When the last digit is keyed-in, the following screen will be displayed:
DELETE DETECTOR DETECTOR# 005 IS DELETED
The programmer can continue deleting detectors by pressing the ESC key which will return the display to the Delete Detector Screen.
3.6.2.1.3 Edit Detector
The programmer can change a detectors existing or factory default programming by pressing 3 in the Detector Screen. The following screen will be displayed:
EDIT DETECTOR ENTER POINT ADDRESS ***
Edit Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 017.
When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device with the highest that is installed will be displayed.
MS-9200UDLS PN 52750:A 11/04/05 49
address
Page 50
Programming Master Programming Level
If no detectors have been installed on the loop, the following will be displayed:
NO DETECTOR INSTALLED
Edit Detector Screen #1
If the selected address has been added to programming, device summary screens will be displayed. These screens allow the programmer to view all device settings at a single glance. Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at the previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically installed on the SLC or has a communication fault but the address is programmed in the system, the following screen will be displayed:
TROUBL SMOKE(PHOTO) <ADJ><NOUN> ZNNN * 1D017
Edit Detector Screen #1
If the selected address has been added to programming and a detector (such as a photoelectric detector) with the selected address is physically installed on the SLC and is communicating with the control panel, the following will be displayed:
NORMAL SMOKE (PHOTO) <ADJ><NOUN> ZNNN V 1D017
Edit Detector Screen #1
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to view the Edit Detector screens.
In the preceding example:
Normal - indicates that the detector with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the detector is
assigned to (NNN = the three digit zone number from 000 - 099)
V or * - indicates whether or not alarm verification is enabled (V = alarm
verification enabled and * = alarm verification disabled)
1D017 - represents the Loop, Device type and Device address (1 = SLC Loop,
D=Detector and 017 = Detector Address 017)
50 MS-9200UDLS PN 52750:A 11/04/05
Page 51
Master Programming Level Programming
The following examples show the editing of a photoelectric smoke detector with address 017, located on the SLC loop:
EDIT DETECTOR 1D017 1=ENABLED YES 2=TYPE SMOKE(PHOTO) 3=VERIFICATION OFF
Edit Detector Screen #2
EDIT DETECTOR 1D017 1=WALKTEST NO 2=PAS NO 3=PRE-SIGNAL NO
Edit Detector Screen #3
EDIT DETECTOR 1D017 1=ZONE ASSIGNMENT 00 ** ** ** **
EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION
Edit Detector Screen #2
Edit Detector Screen #4
EDIT DETECTOR 1D017 1=NOUN/ADJECTIVE 2=DESCRIPTION ********************
Edit Detector Screen #5
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector will not be polled by the control panel, preventing the detector from reporting alarms and troubles to the panel. The control panel will display the device type and address which has been disabled and will turn on the Trouble LED and Disable LED.
MS-9200UDLS PN 52750:A 11/04/05 51
Page 52
Programming Master Programming Level
Type
EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION
Edit Detector Screen #2
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen #2. This will cause the control panel to display the following Detector Type Screens:
DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE (ION)
Detector Type Screen #1
Pressing the down arrow key will display additional detector types as indicated in the following table.
Detector Type Action When Activated
Smoke Photo Fire Alarm User-Defined-1 same as previous (Smoke Photo) Smoke Ion Fire Alarm User-Defined-2 same as previous (Smoke Ion) Heat Detect Fire Alarm User-Defined-3 same as previous (Heat Detect) Smoke DuctP Fire Alarm User-Defined-4 same as previous (Smoke DuctP) Superv-DuctP Supervisory, latching User-Defined-5 same as previous (Superv DuctP) Future not used Future not used
See Page
EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL
Edit Detector Screen #3
While viewing either Detector Type screen, select the type of detector being programmed by pressing the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and indicate the selection next to the Type option.
Note: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire alarm LED or alarm relay, if the detector senses smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2 so that the display reads Verification On. Each time the
3 key is pressed, the display will toggle between Verification On and Verification Off. For a detailed description, refer to "Alarm Verification (None or One Minute)"
on page 139.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable a device for the Walktest feature, press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Wa l k test No. Refer to "Walktest" on page 139.
52 MS-9200UDLS PN 52750:A 11/04/05
Page 53
Master Programming Level Programming
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation (including alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose). To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the display
See Page
reads PAS Yes . Each press of the 2 key will cause the display to toggle between PA S Ye s and PA S N o. Refer to "Positive Alarm Sequence" on page 137.
For example, if a detector with address 005 is to be configured for PAS operation:
Select PAS Yes when editing the detector set to address 005 Program the desired zone or zones to be activated by this detector, in this
example Z001
Program an output, such as a control module that is to be activated by detector
005 by assigning the same zone to it; in this example Z001
Program an output, such as a control module, for PAS activation by assigning
zone Z97 to it. This control module may be connected to a signaling device used to indicate a PAS condition (do not use a Notification Appliance Circuit
for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay
timer to some value
EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL
Edit Detector Screen #3
See Page
With the preceding program settings, when the detector with address 005 is activated, zone Z97 will cause its associated control module to activate immediately, sounding the connected PAS signaling device. Following the PAS delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time delay of up to three minutes while allowing for visual verification by a person. Note that the alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be programmed to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication (do not use a Notification Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3 while viewing Edit Detector Screen #3 until the display reads Pre-signal Ye s. Each press of the 3 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 136.
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
Select Pre-signal Yes when editing the detector set to address 005 Program the desired zone or zones to be activated by this detector, in this
example Z001
Program an output, such as a control module that is to be activated by detector
005 by assigning the same zone to it; in this example Z001
Program an output, such as a control module, for Pre-signal activation by
assigning zone Z98 to it. This control module may be connected to a signaling device used to indicate a Pre-signal condition (do not use a Notification
Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre-
signal delay timer to some value
MS-9200UDLS PN 52750:A 11/04/05 53
Page 54
Programming Master Programming Level
With the preceding program settings, when the detector with address 005 is activated, zone Z98 will cause its associated control module to activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Zone Assignment
EDIT DETECTOR 1=ZONE ASSIGNMENT 00 ** ** ** **
Edit Detector Screen #4
See Page
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while viewing Edit Detector Screen #4 displays the following screen:
ZONE ASSIGNMENT Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate through the zones and the CLEAR key can be used to quickly clear a zone.
Noun/Adjective
EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION *****************
Edit Detector Screen #5
The Noun/Adjective selection allows the programmer to enter specific descriptors about the detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
54 MS-9200UDLS PN 52750:A 11/04/05
Page 55
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the detector currently being programmed. When an adjective has been selected, it will appear at the top of the display as indicated by the asterisks.
********************** 1=NORTH 2=SOUTH 3=EAST
Adjective Screen #1
********************** 1=WEST 2=FRONT 3=CENTER
********************** 1=3RD 2=4TH 3=5TH
Adjective Screen #5
********************** 1=FLOOR1 2=FLOOR2 3=FLOOR3
Adjective Screen #2
********************** 1=REAR 2=UPPER 3=LOWER
Adjective Screen #3
********************* 1=MAIN 2=FIRST 3=2ND
Adjective Screen #6
********************** 1=FLOOR4 2=FLOOR5 3=ROOM
Adjective Screen #7
Adjective Screen #4
MS-9200UDLS PN 52750:A 11/04/05 55
Page 56
Programming Master Programming Level
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the detector currently being programmed. When a noun has been selected, it will appear at the top of the display as indicated by the asterisks.
********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM
Noun Screen #1
********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
********************** 1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #5
********************** 1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #2
********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #3
********************** 1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #6
********************** 1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #7
********************** 1=ZONE
Noun Screen #4
56 MS-9200UDLS PN 52750:A 11/04/05
Noun Screen #8
Page 57
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION
Edit Detector Screen #5
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit. These descriptors are selected as described in the previous sections.
Description
The Description selection allows the programmer to enter additional information about the detector currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Detector Screen #5 will cause the following screen to be displayed:
DESCRIPTION 1D002 1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 2, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Detector Screen #5, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Description, Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire field is replaced with the field entered for the previous device programmed and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow)
The above increment function may be repeated with each press of the zero key
,
MS-9200UDLS PN 52750:A 11/04/05 57
Page 58
Programming Master Programming Level
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones
3.6.2.2 Module Programming
POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE
Point Program Screen #2
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or change the programming of an addressable module. The following screen will be displayed by the control panel:
MODULES 1=ADD 2=DELETE 3=EDIT
Modules Screen
3.6.2.2.1 Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows the programmer to add a new module address to programming:
ADD MODULE ENTER MODULE# ***
Add Module Screen #1
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
ADD MODULE 1=CONTROL 2=MONITOR
Add Module Screen #2
58 MS-9200UDLS PN 52750:A 11/04/05
Page 59
Master Programming Level Programming
Pressing 1 for Control Module or 2 for Monitor Module will cause the following screen to be displayed:
ADD MODULE MODULE# 005 IS ADDED
Add Module Screen #3
The programmer can continue adding modules by pressing the ESC or left arrow key which will return the display to the Add Module Screen #1.
3.6.2.2.2 Delete Module
Pressing 2 in the Modules Screen will display the Delete Module Screen which
MODULES 1=ADD 2=DELETE 3=EDIT
Modules Screen
allows the programmer to delete a specific module:
DELETE MODULE ENTER MODULE# ***
Delete Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad, key in the module address such as 005. When the last digit is keyed in, the following confirmation that the module has been deleted will be displayed:
DELETE MODULE MODULE# 005 IS DELETED
3.6.2.2.3 Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed:
EDIT MODULE ENTER MODULE ADDRESS ***
Edit Module Screen
MS-9200UDLS PN 52750:A 11/04/05 59
Page 60
Programming Master Programming Level
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 012. When the last digit is keyed-in, if the selected address has not showing information about the highest address that is installed will be displayed. If no modules are installed on the loop, the following screen will be displayed:
been added to programming, a screen
NO MODULE INSTALLED
Edit Module Screen
If the selected address has been added to programming but a module (such as a monitor module) with the selected address is not physically installed on the SLC or has a communication fault, the following screen will be displayed:
TROUBL MONITOR <ADJ><NOUN> ZNNN * 1M012
If the selected address has been added to programming and a module (such as a monitor module) with the selected address is physically installed on the SLC and is communicating with the control panel, the following screen will be displayed:
NORMAL MONITOR <ADJ><NOUN> ZNNN W 1M012
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Monitor screens. In the preceding example:
Normal - indicates that the module with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the module is
assigned to (NNN = the two digit zone number from 000 - 099)
1M012 - represents the Loop, Device type and Device address (1 = SLC Loop
1, M=Module and 012 = Module Address 012)
W or * - indicates whether or not the device is programmed for Walktest (W =
programmed for walktest, * = not programmed for walktest).
60 MS-9200UDLS PN 52750:A 11/04/05
Page 61
Master Programming Level Programming
If the selected address corresponds to a control module, a screen displaying
See Page
information about the control module with the selected address will be displayed as shown in "Edit Module Screen for Control Modules" on page 68.
If the selected address corresponds to a monitor information about the module with the selected address will be displayed as illustrated in the following:
module, a screen displaying
NORMAL MONITOR <ADJ><NOUN> ZNNN 1M012
EDIT MONITOR 1M012 1=ENABLED YES 2=TYPE MONITOR
Edit Monitor Screen #2
EDIT MONITOR 1M012 1=PRE-SIGNAL NO
Edit Monitor Screen #3
EDIT MONITOR 1M012 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR 1M012 1=ADJECTIVE/NOUN 2=DESCRIPTION ********************
Edit Monitor Screen #5
MS-9200UDLS PN 52750:A 11/04/05 61
Page 62
Programming Master Programming Level
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit Module Screen #2. Each press of the key will toggle the screen between Enabled Ye s and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from reporting alarms and troubles to the panel. The control panel will indicate a system trouble condition and the Disable LED with turn on if any devices are disabled.
EDIT MONITOR 1=ENABLED 2=TYPE MONITOR
Edit Monitor Screen #2
Type Monitor
Using the PK-CD Upload/Download utility program, unique user-defined monitor types can be created and loaded into the FACP for later use. The FACP response to the activation of a user-defined type is the same as most previous standard types in the list, thus allowing a variety of user-defined types and responses. To select the type of monitor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2. This will cause the control panel to display the following Monitor Type Screens:
MONITOR TYPE 1=PULL-STATION 2=USER-DEFINED-1 3=WATERFLOW
Monitor Type Screen #1
Pressing the down arrow key will display additional Monitor Type screens. While viewing one of the Monitor Type screens, select the type of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which will show the new type selection.
Table 3.1 on page 63 lists the Monitor Types and their respective functions.
62 MS-9200UDLS PN 52750:A 11/04/05
Page 63
Master Programming Level Programming
Monitor module type selection will affect the function of the point as follows:
Table 3.1 Monitor Types
Monitor Type Action When Activated
Pull-Station Fire Alarm User-Defined-1 same as previous (Pull-Station) Waterflow Fire Alarm Delayed User-Defined-2 same as previous (Waterflow) Monitor Fire Alarm User-Defined-3 same as previous (Monitor) Future not used Future not used Smoke-Conventional Fire Alarm User-Defined-5 same as previous (Smoke-Conventional) Heat-Conventional Fire Alarm User-Defined-6 same as previous (Heat-Detector) Medic-Alert Supervisory, latching User-Defined-7 same as previous (Medic-Alert) Hazard-Alert Supervisory, latching User-Defined-8 same as previous (Hazard-Alert) Tornado-Alert Supervisory, latching User-Defined-9 same as previous (Tornado-Alert) Future not used Future not used Tamper Supervisory, nonlatching (tracking) User-Defined 11 same as previous (Tamper) Supervisory Supervisory, latching User-Defined 12 same as previous (Supervisory) Supervisory-AR Supervisory, nonlatching (tracking) User-Defined 13 same as previous (Supervisory-AR) Power-Monitor Power Fault User-Defined 14 same as previous (Power Monitor) Trouble-Monitor Trouble User-Defined-15 same as previous (Trouble Monitor) Process-Monitor Piezo User-Defined 16 same as previous (Process-Monitor) Process-Monitor-AR Piezo, nonlatching (tracking) User-Defined-17 same as previous (Process-Monitor-AR) Future not used Future not used Ack-Switch Acts like panel Acknowledge Key Sil-Switch Acts like panel Silence Key Reset-Switch Acts like panel Reset Key Drill-Switch Acts like panel Drill Key PAS-Bypass PAS Disable HVAC RESTART Switch HVAC OVRRIDE Switch Drill-Switch-AR Acts like panel Drill Key, nonlatching (tracking)
Note:
1. For the PROCESS-MONITOR-AR selection, AR refers to AutoResettable
2. For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor Module Operation" on page 179
MS-9200UDLS PN 52750:A 11/04/05 63
Page 64
Programming Master Programming Level
EDIT MONITOR 1=PRE-SIGNAL
Edit Monitor Screen #3
See Page
EDIT MONITOR 1=WALKTEST 2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Monitor Screen #4
Pre-signal
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 136 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads Wa lk test Ye s. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 139 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4 displays the following screen:
MON ZONE ASSIGN
Z00 Z** Z** Z** Z**
EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION *****************
Edit Monitor Screen #5
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
64 MS-9200UDLS PN 52750:A 11/04/05
Page 65
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the monitor module currently being programmed.
********************** 1=NORTH 2=SOUTH 3=EAST
Adjective Screen #1
********************** 1=WEST 2=FRONT 3=CENTER
Adjective Screen #2
********************** 1=3RD 2=4TH 3=5TH
Adjective Screen #5
********************** 1=FLOOR 1 2=FLOOR 2 3=FLOOR 3
Adjective Screen #6
********************** 1=REAR 2=UPPER 3=LOWER
Adjective Screen #3
********************** 1=MAIN 2=FIRST 3=2ND
Adjective Screen #4
********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM
Adjective Screen #7
MS-9200UDLS PN 52750:A 11/04/05 65
Page 66
Programming Master Programming Level
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the monitor module currently being programmed.
********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM
Noun Screen #1
********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
Noun Screen #2
********************** 1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #5
********************** 1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #6
********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #3
********************** 1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #4
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit.
********************** 1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #7
********************** 1=ZONE
Noun Screen #8
66 MS-9200UDLS PN 52750:A 11/04/05
Page 67
Master Programming Level Programming
EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION *****************
Edit Monitor Screen #5
Description
The Description selection allows the programmer to enter additional information about the monitor module currently being programmed. This information will be displayed as part of the device label on the LCD display. Pressing 2 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed:
DESCRIPTION 1M012 1=NOUN/ADJECTIVE
********************
Noun/Adjective Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the LCD display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 2, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Monitor Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire Adjective field is replaced with the field entered for the previous device programmed, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by­letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow)
The above increment function may be repeated with each press of the zero key
MS-9200UDLS PN 52750:A 11/04/05 67
Page 68
Programming Master Programming Level
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones
3.6.2.2.4 Edit Module Screen for Control Modules
The programmer can change a module’s existing or factory default programming by
MODULES 1=ADD 2=DELETE 3=EDIT
Modules Screen
pressing 3 in the Modules Screen. The following screen will be displayed:
EDIT MODULE ENTER MODULE ADDRESS ***
Edit Module Screen
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is keyed-in, if the selected address corresponds to a control module, a screen displaying information about the control module with the selected address will be displayed as illustrated in the following:
NORMAL CONTROL <ADJ><NOUN> ZNNN SW 1M002
Edit Control Screen #1
In the preceding example:
Normal - indicates that the module with the selected address is physically
installed on the SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been
programmed, describing the location of the displayed device
Control - indicates that the selected module is a control moduleS or * - represents Silenceable (S) or Nonsilenceable (*)W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay
enabled, * = Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is
assigned to (NNN = the three digit zone number from 000 - 099)
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop,
M=Module and 002 = Module Address 02)
68 MS-9200UDLS PN 52750:A 11/04/05
Page 69
Master Programming Level Programming
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Control screens:
EDIT CONTROL 1=ENABLED YES 2=TYPE CONTROL 3=SILENCEABLE YES
Edit Control Screen #2
EDIT CONTROL 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Control Screen #3
EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION ********************
Edit Control Screen #4
Enable/Disable Module
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2. Each press of the key will toggle the screen between Enabled Ye s and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from activating its output devices. The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled.
MS-9200UDLS PN 52750:A 11/04/05 69
Page 70
Programming Master Programming Level
EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE
Edit Control Screen #2
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit Control Screen #2. This will cause the control panel to display the following Control Type Screens. Press the down arrow key to view additional screens and selections.
CONTROL TYPE 1=BLANK 2=BELL-CIRCUIT 3=HORN-CIRCUIT
Control Type Screen #1
While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Control Screen #2 and indicate the new type selection.
Note: A control module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control module is disabled.
The following table contains control module type codes and their functions which are displayed in the Control Type screens:
Control Type Special Function
Blank None Bell Circuit None Horn Circuit None Sounders None Relay Ignore Open Circuit Strobe Circuit None Control None Resettable Power Relay Type - Ignore Open Circuit HVAC SHUTDN Relay Type - Ignore Open Circuit
Note: For HVAC SHUTDN description, refer to "Control Module Operation" on page 179
70 MS-9200UDLS PN 52750:A 11/04/05
Page 71
Master Programming Level Programming
EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL 1=WALKTEST 2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until the display reads Wa lk tes t Ye s. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 139 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2 while viewing Edit Control Screen #3 displays the following screen:
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION
Edit Control Screen #4
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Control Screen #3.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the control module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
MS-9200UDLS PN 52750:A 11/04/05 71
Page 72
Programming Master Programming Level
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the control module currently being programmed.
********************** 1=NORTH 2=SOUTH 3=EAST
Adjective Screen #1
********************** 1=WEST 2=FRONT 3=CENTER
Adjective Screen #2
********************** 1=3RD 2=4TH 3=5TH
Adjective Screen #5
********************** 1=FLOOR 1 2=FLOOR 2 3=FLOOR 3
Adjective Screen #6
********************** 1=REAR 2=UPPER 3=LOWER
Adjective Screen #3
********************** 1=MAIN 2=FIRST 3=2ND
Adjective Screen #4
********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM
Adjective Screen #7
72 MS-9200UDLS PN 52750:A 11/04/05
Page 73
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the control module currently being programmed.
********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM
Noun Screen #1
********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
Noun Screen #2
********************** 1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #5
********************** 1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #6
********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #3
********************** 1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #4
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit.
********************** 1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #7
********************** 1=ZONE
Noun Screen #8
MS-9200UDLS PN 52750:A 11/04/05 73
Page 74
Programming Master Programming Level
EDIT CONTROL 1=ADJECTIVE/NOUN 2=DESCRIPTION
Edit Control Screen #4
Description
The Description selection allows the programmer to enter additional information about the control module currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Control Screen #4 will cause the following screen to be displayed:
DESCRIPTION 1M002 1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Control Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire Adjective field is replaced with the field entered for the previous device programmed, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by­letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow)
The above increment function may be repeated with each press of the zero key
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01 through Z99 may be selected to link software zones
74 MS-9200UDLS PN 52750:A 11/04/05
Page 75
Master Programming Level Programming
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #2
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated below:
ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99
Zone Setup Screen #1
ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE
ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99
Zone Setup Screen #1
Zone Setup Screen #3
3.6.3.1 Enable
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
ZONE TO ENABLE Z
Enable Screen
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z. Another zone can then be enabled.
MS-9200UDLS PN 52750:A 11/04/05 75
Page 76
Programming Master Programming Level
ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 97 98 99
Zone Setup Screen #1
3.6.3.2 Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
ZONE TO DISABLE Z
Disable Screen
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second digit is entered, the zone will be disabled and the cursor will return to the original position next to the Z. Another zone can then be disabled.
3.6.3.3 Zone 97, 98 and 99
Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following screen:
SPEC PURPOSE ZONE 1=PAS 97 OFF 2=PRESIGNAL 98 OFF 3=TWO STAGE 99 OFF
Zone 97, 98 and 99 Screen
Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the three zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 97 to activate. By assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a PAS condition in the control panel. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning Zone 98 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a Pre-signal condition in the control panel. Do not
assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 90 for a description of this feature.
76 MS-9200UDLS PN 52750:A 11/04/05
Page 77
Master Programming Level Programming
ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED
Zone Setup Screen #2
3.6.3.4 Zones Installed
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the following:
ZONES INSTALLED 00 01 02 03 04 05
Zones Installed Screen
This display will show all of the zones that have been programmed into the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones.
3.6.3.5 Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
ZONES ENABLED 00 01 02 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Zones Enabled Screen
This display will show all of the zones that are enabled in the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones.
3.6.3.6 Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
ZONES DISABLED 03
Zones Disabled Screen
This display will show all of the zones that are disabled in the control panel. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the additional zones.
MS-9200UDLS PN 52750:A 11/04/05 77
Page 78
Programming Master Programming Level
ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE
Zone Setup Screen #3
ZONE TYPE PROG 1=MONITOR 2=SMOKE PHOTO 3=WATERFLOW
3.6.3.7 Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a screen similar to the following:
ZONE TYPE PROG 1=Z00 MONITOR 2=Z01 MONITOR 3=Z02 MONITOR
Zones Installed Screen
This display will show the system zones (default and user programmed) and their associated types. Note that an up and/or down arrow will appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view zones Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each Zones Installed Screen. Available zone types will be displayed in the resultant screens. For example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following screens will be displayed:
ZONE TYPE PROG 1=MEDICAL 2=HAZARD 3=TAMPER
Zone Type Program Screen #1
ZONE TYPE PROG 1=HEAT 2=PULL STATION 3=DUCT
Zone Type Program Screen #2
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow silenceable devices programmed to the same zone can key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable
80.
Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
Zone Type Program Screen #3
ZONE TYPE PROG 1=SUPERVISORY 2=PROC. MON 3=SMOKE ION
Zone Type Program Screen #4
zone type to the selected zone. Any signaling
be silenced by pressing the Alarm Silence
, refer to "System Setup" on page
change how it is reported to the Central Station.
78 MS-9200UDLS PN 52750:A 11/04/05
Page 79
Master Programming Level Programming
ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE
Zone Setup Screen #3
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
3.6.3.8 Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display a screen similar to the following:
ZONES AVAILABLE 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
The display will show all of the zones that are still available for programming. Note that an up and/or down arrow may appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow key to view additional screens.
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the following screen to be displayed:
LOOP SETUP 1=STYLE 4 2=PROTOCOL LITESPEED
Loop Setup Screen
3.6.4.1 Style
To program the SLC Style for the selected loop, press 1 for Style, while viewing Loop Setup Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by the 4 to the right of Style in the display. To change the wiring style, press 1 to toggle the display to read Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and Style 6. Note that,
when programming the Loop Style, the programmer can only select between Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop Setup for Style 6. Style 7 wiring is the same as Style 6 with the added requirement that each addressable device on the loop must have a pair of isolator modules, one on each side.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC trouble.
3.6.4.2 Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. The two Loop Protocols available are CLIP (Classic Loop Interface Protocol) which is used for the older legacy addressable devices such as the M300 Series modules and detectors and LiteSpeed (factory default setting) which is used for the 350 Series or newer addressable devices for quicker response times. Note that the legacy devices can operate only LiteSpeed modes of operation. Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols.
in CLIP mode while the newer devices are compatible with CLIP and
Device Addressing
It is important to note that the MS-9200UDLS addressable device capacity is 99
MS-9200UDLS PN 52750:A 11/04/05 79
Page 80
Programming Master Programming Level
detectors and 99 control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses will not function with the MS-9200UDLS.
Note that It is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are installed.
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or trouble still exists on the FACP after the control panel has been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If the trouble condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the central station if connected.
Banner: This option allows the user to change the top two lines of the LCD display from the factory default readout of HONEYWELL LIFE SAFETY to a user defined readout when the control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the automatic programming of ionization smoke detector sensitivity thresholds to Canadian specifications.
Waterflow Silenceable: This option provides the ability to silence any output
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
circuit activated by a monitor module programmed as a waterflow type.
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be displayed:
SYSTEM SETUP 1=TROUBLE REM OFF 2=BANNER 3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NO
System Setup Screen #3
80 MS-9200UDLS PN 52750:A 11/04/05
Page 81
Master Programming Level Programming
3.6.5.1 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 80, for a detailed description of this feature. Pressing 1 while
See Page
viewing System Setup Screen #1 will cause the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will cause the display to toggle between Trouble Rem On and Trouble Rem Off.
3.6.5.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed:
BANNER 1=FACTORY 2=USER DEFINED
BANNER 1=FACTORY 2=USER DEFINED
Banner Screen
Banner Screen
Pressing 1 while viewing the Banner Screen will select the factory default banner setting and display the following screen:
FACTORY BANNER HONEYWELL LIFE SAFETY
Factory Banner Screen
Pressing the Enter key will store this selection in nonvolatile memory and return the display to the Banner Screen.
Pressing 2 while viewing the Banner Screen will cause the following screens to be displayed:
USER DEFINED BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER - LINE 2 PRESS ENTER IF OK ************
User Defined Banner Screen #2
These screens allow the programmer to enter a two line custom banner. A flashing cursor will appear in the bottom left corner of each display. A maximum of 20 characters (including spaces) can be entered into each screen for a total of two lines with 40 characters. After entering up to 20 characters in the first screen, press Enter
MS-9200UDLS PN 52750:A 11/04/05 81
Page 82
Programming Master Programming Level
to view the second screen. Enter up to 20 characters in the second screen in the same manner or just press Enter if a second banner line is not being entered. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times to place a blank in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Banner Screen.
SYSTEM SETUP 1=TROUBLE REM 2=BANNER 3=TIME-DATE
System Setup Screen #1
3.6.5.3 Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The following screen will be displayed:
TIME AND DATE 1=TIME 10:00 AM 2=DATE 04-07-2002 3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE 1=DAYLIGHT SAVINGS
Time-Date Screen #2
3.6.5.3.1 Time
To change the time, press 1 while viewing the Time-Date Screen. The following screen will be displayed:
ENTER TIME
10:00 AM 1=AM 2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current time. To change the time, enter the two-digit hours followed by the two­digit minutes. The cursor will move one position to the right each time a digit is entered. After the last minutes digit is entered, the cursor will again move one position to the right. At this point enter 1 for AM or 2 for PM. The display will then return to the Time-Date Screen which will show the new time entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again.
82 MS-9200UDLS PN 52750:A 11/04/05
Page 83
Master Programming Level Programming
3.6.5.3.2 Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be displayed:
ENTER DATE
MONTH DAY YEAR 04-07-2002
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current date. To change the date, enter the two-digit month followed by the two­digit day and then the two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right each time a digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen which will show the new date entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again.
3.6.5.3.3 Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
Note: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display purposes only).
TIME AND DATE 1=DAYLIGHT SAVINGS
Time & Date Screen #2
3.6.5.3.4 Daylight Savings Time
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
DAYLIGHT SAVINGS 1=ENABLED YES 2=START MONTH APR 3=START WEEK WEEK-1
Daylight Savings Screen #1
DAYLIGHT SAVINGS 1=END MONTH OCT 2=END WEEK LAST-W
Daylight Savings Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled No. The control panel will automatically update the time for daylight savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April and 3 will select May.
MS-9200UDLS PN 52750:A 11/04/05 83
Page 84
Programming Master Programming Level
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third week, while in the second sub­screen, pressing 1 will select the fourth week and 2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will end. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third week, while in the second sub­screen, pressing 4 will select the fourth week and 5 will select the last week of the selected month.
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
3.6.5.4 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing System Setup Screen #2. The following screen will be displayed:
TIMERS 1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
TIMERS 1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
TIMERS 1=AC LOSS DELAY 000
Timer Screen #2
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear:
PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
84 MS-9200UDLS PN 52750:A 11/04/05
Page 85
Master Programming Level Programming
3.6.5.4.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre­signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
TIMER 1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
Note that the FACP can be programmed for either PAS or Pre-signal operation, not both. For this reason, if the PAS Delay timer is set with a value greater than 000 and then the Pre-Signal Delay timer is set with a value greater than 000, the PAS Delay timer will be automatically reset to 000. Only one of the two timers can have a delay time set for it.
3.6.5.4.3 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
MS-9200UDLS PN 52750:A 11/04/05 85
Page 86
Programming Master Programming Level
TIMER 1=AC LOSS DELAY
Timer Screen #2
3.6.5.4.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY 1=NO DELAY 2=ENTER DELAY
AC Loss Delay Screen #1
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
AC LOSS DELAY
RANGE 00-23
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
AC Loss Delay Screen #2
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1.
Important: For Central Station applications, AC Loss Reporting Delay must be set to a delay value ranging from 06 to 12 hours. For Remote Station applications, AC Loss Reporting Delay must be set to a delay value ranging from 15 to 23 hours.
Note: AC Loss Delay also applies to any programmable output relay programmed for ‘AC Loss.’
3.6.5.5 NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configure by pressing 2 while viewing System Setup Screen #2. The following screens will be displayed:
NACS 1=NAC 1 3=NAC 3 2=NAC 2 4=NAC 4
NAC Selection Screen
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3 or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will be displayed, and can be programmed, regardless of how the NACKEY card is installed. Their programming, however, will have no effect if the NACKEY card is installed for Class A operation.
86 MS-9200UDLS PN 52750:A 11/04/05
Page 87
Master Programming Level Programming
The following screens will be displayed for each selection:
NAC # 1=ENABLED YES 2=TYPE BELL 3=SILENCEABLE YES
NAC Screen #1
NAC # 1=AUTO SILENCE 00 2=CODING TEMPORAL
NAC Screen #2
NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO
NAC Screen #3
NAC # 1=SYNC TYPE S
NAC Screen #4
3.6.5.5.1 Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Note: The programming for NAC 1 will determine the operation of the remote power supply sync.
MS-9200UDLS PN 52750:A 11/04/05 87
Page 88
Programming Master Programming Level
NAC # 1=ENABLED 2=TYPE 3=SILENCEABLE
NAC Screen #1
3.6.5.5.2 Type
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1. The following screen will be displayed. Press the down arrow key to view additional screens:
NAC TYPE 1=BELL 2=HORN 3=STROBE
Type Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
NAC Type Code Special Function
Bell None Horn None Strobe None Synced Strobe Synchronized to manufacturer Strobe Sil Sync Same as Synced Strobe but Silence turns off audible & visual devices Siren Circuit None
3.6.5.5.3 Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This will prevent the selected main circuit board NAC from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the Synced Strobe feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or Autosilence will turn off both audible and visual devices.
88 MS-9200UDLS PN 52750:A 11/04/05
Page 89
Master Programming Level Programming
NAC # 1=AUTO SILENCE 2=CODING TEMPORAL
NAC Screen #2
3.6.5.5.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following screens will be displayed:
AUTO SILENCE 1=NO 2=5 MINUTES 3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE 1=15 MINUTES 2=20 MINUTES 3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE 1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the number corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the display will return to NAC Screen #2.
Note: All silenceable control modules as well as the remote power supply sync will be controlled by the Autosilence timer for NAC 1.
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type)
The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear:
CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA
Coding Screen #1
CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MIN
Coding Screen #2
MS-9200UDLS PN 52750:A 11/04/05 89
Page 90
Programming Master Programming Level
The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selections are:
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
Two Stage - refer to "Two Stage Operation" on page 90 for a description
Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen #2, which will display the new coding choice.
3.6.5.5.5.1 Two Stage Operation
Two Stage operation consists of the following:
1st stage output - 20 ppm (pulse-per-minute) coding
2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events will occur during an alarm.
1. The on-board NACs which are programmed to General Alarm Zone 0 will
activate with a 1st stage output upon activation of any alarm point
2. If the activated alarm point is directly mapped to a zone which is programmed
to an on-board NAC, that NAC will go directly to 2nd stage coding output. All other NACs not directly mapped to the activated alarm point’s zone but assigned to Zone 0 will activate with a 1st stage output
3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has
not
been pressed, all NACs presently in 1st stage activation will go to 2nd
stage activation
4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage
activation will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd stage activation
5. If another alarm point is activated and the countdown timer is counting, the
alarm point will have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the NACs, in which case it will follow the procedure outlined in step 2
6. If another alarm point is activated and the countdown timer has stopped
counting due to the Acknowledge switch being pressed, the countdown timer will restart and the NACs will respond as outlined in step 2. NACs already in 2nd stage activation will not be affected
7. Any control modules assigned to special Zone 99 will be activated either by
direct mapping of an input device programmed to Zone 99 or if the timer counts down to zero
8. Control modules that are programmed to the same zone as the activated input
device will not be delayed for activation
90 MS-9200UDLS PN 52750:A 11/04/05
Page 91
Master Programming Level Programming
NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO
NAC Screen #3
NAC # 1=SYNC TYPE
NAC Screen #4
3.6.5.5.6 Zone
A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while viewing NAC Screen #3 displays the following screen:
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Screen
Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this NAC. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the NAC Screen #3 which will show the zone assignments just entered.
3.6.5.5.7 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for a period of one minute. Resetting the FACP will also be prevented for one minute while the NAC programmed for silence inhibit is activated. Pressing 2 while viewing NAC Screen #3 will cause the display to change from the factory default of Silence Inhibit No to Silence Inhibit Yes. Each press of the 2 key will cause the display to toggle between the two options.
3.6.5.5.8 Sync Type
If synchronized strobes were selected as the Type of device installed, the type of synchronization must be selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following screen to be displayed:
NAC SYNC TYPE 1=SYSTEM SENSOR 2=WHEELOCK 3=GENTEX
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock and 3 will select Gentex.
3.6.5.5.8.1 Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer’s documentation supplied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following is a list of the strobes that have been tested with this FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum current is not exceeded:
System Sensor: 40 StrobesWheelock: 25 StrobesGentex: 23 Strobes
MS-9200UDLS PN 52750:A 11/04/05 91
Page 92
Programming Master Programming Level
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
3.6.5.6 Relays
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two of the three main circuit board Form-C relays. The following screen will be displayed:
RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3
Relays Selection Screen
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed:
RELAY # 1=TYPE ALARM
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed:
RELAY 1=ALARM 2=SUPERVISORY 3=SUPERVISORY AR
Relay Screen #1
RELAY 1=TROUBLE 2=COMM FAIL 3=PROCESS-MON
Relay Screen #2
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Relay Type Screen
RELAY 1=PROCMON AR 2=AC LOSS 3=HAZARD
Relay Screen #3
RELAY 1=MEDICAL
Relay Screen #4
Note: AR in SUPERVISORY AR and PROCMON AR indicates AutoResettable which means that the relay will not latch when either of these conditions occur. If the corresponding condition is cleared, the relay will return to its normal state without the necessity of resetting the control panel.
92 MS-9200UDLS PN 52750:A 11/04/05
Page 93
Master Programming Level Programming
SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NO
System Setup Screen #3
3.6.5.7 Canadian Option
Pressing 1 while viewing System Setup Screen #3 will allow the programmer to configure the system to automatically monitor addressable ionization smoke detector sensitivity using Canadian specifications. The display will change to
Canadian Opt. On. Each press of the 1 key will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NO
Relays Selection Screen
3.6.5.8 Waterflow Silenceable
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the system for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the display between Waterflow Sil. No and Wat er fl ow Sil. Yes. When Waterflow Sil. No is selected, all output devices associated with a waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is selected, all output devices associated with a waterflow type input device, will be silenceable.
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
3.6.6 Verify Loop
Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option. During loop verification, the FACP polls each device on the SLC to determine if the device is communicating and whether or not it responds with the proper type identification. The following screen will be displayed while verification is in progress:
VERIFYING LOOPS PLEASE WAIT
Verification Progress Screen
When Loop verification has been completed, the display will indicate that the system is OK or, if problems have been detected, any device type programming errors. Use the up and down arrow keys to view all detected errors.
MS-9200UDLS PN 52750:A 11/04/05 93
Page 94
Programming Master Programming Level
3.6.7 History
PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES
Programming Screen #3
The History option allows an authorized user to view or erase events which have occurred in the control panel. Pressing 1 while viewing Programming Screen #3 will display the History options as shown in the following display:
HISTORY 1=VIEW EVENTS 2=ERASE HISTORY
History Screen
HISTORY 1=VIEW EVENTS 2=ERASE HISTORY
History Screen
3.6.7.1 View Events
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illustrated in the following:
HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS
View Events Screen
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to view other events. Use the up and down arrow keys to scroll through all of the displayed events.
3.6.7.2 Erase History
The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history file to track future events. Pressing 2 while viewing the History Screen will display the following screen:
ERASE HISTORY PROCEED ? 1=YES 2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as follows:
ERASING HISTORY PLEASE WAIT
Erase History Wait Screen
After the History file has been erased, the display will return to the History Screen.
94 MS-9200UDLS PN 52750:A 11/04/05
Page 95
Master Programming Level Programming
3.6.8 Walktest
PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES
Programming Screen #3
Walktest allows an individual to test the fire alarm system without the necessity to reset the control panel after each device activation. Pressing 2 while viewing the Programming Screen #3 will cause the following Walktest options to be displayed:
WALKTEST 1=SILENT 2=AUDIBLE 3=VIEW RESULT
Walktest Screen
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the following screen will be displayed:
UNIT IN WALKTEST
Walktest Active Screen
The user can now perform a one-person walktest by activating devices throughout the system. As each device is activated, the screen will display the information about the activated device as shown below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the walktest screen from an actual alarm screen.
ALARM PULL STATION <ADJ> <NOUN> Z000 10*00A 010801 1M001
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing the Walktest Screen. The following screen will be displayed:
WALKTEST RESULTS
View Result Screen
Use the up and down arrow keys to view all of the walktest results which will be displayed as illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed.
MS-9200UDLS PN 52750:A 11/04/05 95
Page 96
Programming Master Programming Level
3.6.9 Option Modules
PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES
Programming Screen #3
Options available for the MS-9200UDLS include ACS Series, Graphic and LCD annunciators, printer connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection for uploading and downloading panel data.
Pressing 3 while viewing Programming Screen #3 will display the following screen:
OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ONBOARD DACT 3=PRINTER/PC PR4800
Options Screen
Note that PR4800 in the display indicates that a supervised printer, configured for 4800 baud, has been previously programmed into the system.
3.6.9.1 Annunciators/UDACT
Pressing 1 while viewing the Options Screen will cause the control panel to display the following screens:
ANNUNCIATOR 1=TERM ENABLED YES 2=ACS ENABLED YES 3=UDACT YES
Annunciator Screen #1
ANNUNCIATOR 1=ACS INSTALLED
Annunciator Screen #2
A Terminal Mode annunciator* and ACS Mode annunciator can be installed in the MS-9200UDLS system. To enable any of these devices, press the number corresponding to the selected device shown in Annunciator Screen #1 so that Yes appears in the display to the right of the device. Each press of the corresponding number key will cause the display to toggle between Enabled Yes and Enabled No.
Notes:
1. *The LCD-80F is a Terminal Mode annunciator. To enable the MS-9200UDLS for LCD-80F operation, program Term Enabled to Ye s.
2. The Terminal Mode annunciator (LCD-80F) and the Printer/PC use the same TB8 terminal block on the MS-9200UDLS main circuit board. Only one device can be connected at one time, therefore, programming Term Enabled to Yes will disable any Printer/PC communications.
96 MS-9200UDLS PN 52750:A 11/04/05
Page 97
Master Programming Level Programming
If an ACS annunciator is installed, press 1 while viewing Annunciator Screen #2 to select addresses for the ACS annunciators. The following screen will be displayed:
ANNUNCIATOR 1=ADDRESS 1 YES 2=ADDRESS 2 NO 3=ADDRESS 3 NO
ACS Installed Screen
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1 -31. To select one or more addresses for the installed ACS annunciator(s), press the number key corresponding to the address in each screen. The display for the selected address will change from No to Yes . Each press of the number key will cause the display to toggle between No and Yes.
OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC
Option Module Screen
3.6.9.2 Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a central station. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed:
ON BOARD DACT 1=ENABLED YES 2=PRIMARY PHONE 3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=MANUAL DIAL MODE
On Board DACT Screen #2
3.6.9.2.1 Onboard DACT Enable
To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key.
MS-9200UDLS PN 52750:A 11/04/05 97
Page 98
Programming Master Programming Level
3.6.9.2.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary phone line being connected to the DACT. The following screen will be displayed:
ON BOARD DACT PRIMARY PHONE LINE 1=TYPE TOUCHTONE
Primary Phone Line Screen
To select the type, press 1 while viewing the Primary Phone Line screen. The following screen will be displayed:
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38
ON BOARD DACT 1=ENABLED 2=PRIMARY PHONE 3=SECONDARY PHONE
On Board DACT Screen #1
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
3.6.9.2.3 Secondary Phone
Press 3 while viewing On Board DACT Screen #1 to program the type of secondary phone line being connected to the DACT. The following screen will be displayed:
ON BOARD DACT SECONDARY PHONE LINE 1=TYPE TOUCHTONE
Secondary Phone Line Screen
To select the type, press 1 while viewing the Secondary Phone Line screen. The following screen will be displayed:
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.
98 MS-9200UDLS PN 52750:A 11/04/05
Page 99
Master Programming Level Programming
3.6.9.2.4 Service Terminal
ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=MANUAL DIAL MODE
On Board DACT Screen #2
The MS-9200UDLS can be programmed remotely from a PC using a modem and telephone line. Information can also be retrieved from the FACP using the same method. The Upload/Download option allows an operator to set the necessary parameters to allow the uploading and downloading of data between the FACP and PC. The Service Terminal selection provides the means for entering these parameters.
Pressing 1 while viewing On Board DACT Screen #2 will cause the following screens to appear:
SERVICE TERMINAL 1=PANEL ID 0000 2=TERMINAL 1 3=TERMINAL 2
Service Terminal Screen #1
SERVICE TERMINAL 1=RING COUNT 3
Service Terminal Screen #2
3.6.9.2.4.1 Panel ID
The Panel Identification Number is a 4-digit code (valid digits being 0 - 9 and A - F) that is used to identify the installed FACP. It is important to program this code into the FACP the first time that downloading is performed so that the called Service Terminal can identify the control panel. The factory default is 0000.
To program the Panel ID, press 1 while viewing Service Terminal Screen #1. The following screen will be displayed:
PANEL ID
4 CHARACTER 0-F
Panel ID Screen
A flashing cursor will appear in the lower left corner of the display. Enter a 4-digit code using the digits 0 - 9 and/or the letters A - F by entering the first character. Press the right arrow key to move the cursor to the second position and enter the second character. Follow the same procedure to enter the remaining characters. After entering the fourth character, press the right arrow key and then press the Enter key to store the Panel ID number.
MS-9200UDLS PN 52750:A 11/04/05 99
Page 100
Programming Master Programming Level
3.6.9.2.4.2 Terminal 1 and Terminal 2
SERVICE TERMINAL 1=PANEL ID 2=TERMINAL 1 3=TERMINAL 2
Service Terminal Screen #1
Service Terminal #1 is generally designated as the FACP primary phone line used for receiving phone calls from the service terminal (PC) being used for remote programming. Service Terminal 2 is referred to as the secondary phone line. Pressing 2 for Terminal 1 or 3 for Terminal 2 while viewing Service Terminal Screen #1 will display the following screen:
SERVICE TERMINAL # 1=PHONE NUMBER
Service Terminal # Screen
Phone Number (Service Terminal)
The Service Terminal Phone Number will be used by the control panel to contact the service terminal. Pressing 1 while viewing the Service Terminal # Screen will cause the following screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Printer-PC Screen
A flashing cursor will appear in the lower left corner. Enter the phone number for the service terminal by keying in the first digit, pressing the left arrow key and entering the second digit. Continue this process until all desired numbers have been entered (maximum of 20 characters). Press the Enter key to store the phone number in memory and return the display to the Service Terminal # Screen.
Valid entries are 0 - 9 and A - F with the numeric digits as dialed numbers and letters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = three second pause
E = five second pause
F = end of phone number (F is automatically entered for unused entry positions)
100 MS-9200UDLS PN 52750:A 11/04/05
Loading...